Omron RX-A2015, RX-A2004, RX-A2007, RX-A2022, RX-A2037 User Manual

...
RX USER’S MANUAL
Cat. No. I560-E2-03-X
RX
Customised to your machine Model: RX 200 V Class Three-Phase Input 0.4 to 55 kW 400 V Class Three-Phase Input 0.4 to 132 kW
USER’S MANUAL
Cat. No. I560-E2-03-X
Introduction
Thank you for choosing the general-purpose Inverter RX Series. This User's Manual (hereinafter called "this manual") describes the parameter setting methods required for installation/wiring and operation of the RX model, as well as troubleshooting and inspection methods.
z This manual should be delivered to the actual end user of the product. z After reading this manual, keep it handy for future reference. z This manual describes the specifications and functions of the product as well as the relations
between them. You should assume that anything not described in this manual is not possible with the product.
z Intended readers
This manual is intended for: Those with knowledge of the workings of electricity (qualified electric engineers or the equivalent), and also in charge of:
• Introducing the control equipment
• Designing the control system
• Installing and/or connecting the control equipment
• Field management
Introduction
1
Read and Understand this Manual
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
2
Read and Understand this Manual
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
3
Read and Understand this Manual
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
4
Safety Precautions
WARNING
CAUTION
WARNING
Safety Precautions
Indications and Meanings of Safety Information
In this user's manual, the following precautions and signal words are used to provide information to ensure the safe use of the RX Inverter. The information provided here is vital to safety. Strictly observe the precautions provided.
Meanings of Signal Words
Indicates an imminently hazardous situation which, if not avoided, is likely to result in serious injury or may result in death. Additionally there may be severe property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage.
Alert Symbols in this Document
Turn off the power supply and implement wiring correctly. Not doing so may result in a serious injury due to an electric shock.
Wiring work must be carried out only by qualified personnel. Not doing so may result in a serious injury due to an electric shock.
Do not change wiring and slide switches (SW1), put on or take off Digital Operator and optional devices, replace cooling fans while the input power is being supplied. Doing so may result in a serious injury due to an electric shock.
Be sure to ground the unit. Not doing so may result in a serious injury due to an electric shock or fire. (200-V class: type-D grounding, 400-V class: type-C grounding)
Do not remove the terminal block cover during the power supply and 10 minutes after the power shutoff. Doing so may result in a serious injury due to an electric shock.
Do not operate the Digital Operator or switches with wet hands. Doing so may result in a serious injury due to an electric shock.
Inspection of the Inverter must be conducted after the power supply has been turned off. Not doing so may result in a serious injury due to an electric shock. The main power supply is not necessarily shut off even if the emergency shutoff function is activated.
5
Safety Precautions
CAUTION
Do not connect resistors to the terminals (PD/+1, P/+, N/-) directly. Doing so might result in a small­scale fire, heat generation or damage to the unit.
Install a stop motion device to ensure safety. Not doing so might result in a minor injury. (A holding brake is not a stop motion device designed to ensure safety.)
Be sure to use a specified type of braking resistor/regenerative braking unit. In case of a braking resistor, install a thermal relay that monitors the temperature of the resistor. Not doing so might result in a moderate burn due to the heat generated in the braking resistor/regenerative braking unit. Configure a sequence that enables the Inverter power to turn off when unusual overheating is detected in the braking resistor/regenerative braking unit.
The Inverter has high voltage parts inside which, if short-circuited, might cause damage to itself or other property. Place covers on the openings or take other precautions to make sure that no metal objects such as cutting bits or lead wire scraps go inside when installing and wiring.
Do not touch the Inverter fins, braking resistors and the motor, which become too hot during the power supply and for some time after the power shutoff. Doing so may result in a burn.
Take safety precautions such as setting up a molded-case circuit breaker (MCCB) that matches the Inverter capacity on the power supply side. Not doing so might result in damage to property due to the short circuit of the load.
Do not dismantle, repair or modify this product. Doing so may result in an injury.
6
Precautions for Safe Use
Precautions for Safe Use
Installation and Storage
Do not store or use the product in the following places.
•Locations subject to direct sunlight.
•Locations subject to ambient temperature exceeding the specifications.
•Locations subject to relative humidity exceeding the specifications.
•Locations subject to condensation due to severe temperature fluctuations.
•Locations subject to corrosive or flammable gases.
•Locations subject to exposure to combustibles.
•Locations subject to dust (especially iron dust) or salts.
•Locations subject to exposure to water, oil, or chemicals.
•Locations subject to shock or vibration.
Transporting, Installation, and Wiring
•Do not drop or apply strong impact on the product. Doing so may result in damaged parts or malfunction.
•Do not hold by the front cover and terminal block cover, but hold by the fins during transportation.
•Do not connect an AC power supply voltage to the control input/output terminals. Doing so may result in damage to the product.
•Be sure to tighten the screws on the terminal block securely. Wiring work must be done after installing the unit body.
•Do not connect any load other than a three-phase inductive motor to the U, V, and W output terminals.
•Take sufficient shielding measures when using the product in the following locations. Not doing so may result in damage to the product.
Locations subject to static electricity or other forms of noise. Locations subject to strong magnetic fields. Locations close to power lines.
Operation and Adjustment
•Be sure to confirm the permissible range of motors and machines before operation because the Inverter speed can be changed easily from low to high.
•Provide a separate holding brake if necessary.
Maintenance and Inspection
•Be sure to confirm safety before conducting maintenance, inspection or parts replacement.
7
Precautions for Correct Use
Precautions for Correct Use
Installation
•Mount the product vertically on a wall with the product's longer sides upright. The material of the wall has to be noninflammable such as a metal plate.
Main Circuit Power Supply
•Confirm that the rated input voltage of the Inverter is the same as AC power supply voltage.
Error Retry Function
•Do not come close to the machine when using the error retry function because the machine may abruptly start when stopped by an alarm.
•Be sure to confirm the RUN signal is turned off before resetting the alarm because the machine may abruptly start.
Non-Stop Function at Momentary Power Interruption
•Do not come close to the machine when selecting restart in the non-stop function at momentary power interruption selection (b050) because the machine may abruptly start after the power is turned on.
Operation Stop Command
•Provide a separate emergency stop switch because the STOP key on the Digital Operator is valid only when function settings are performed.
•When checking a signal during the power supply and the voltage is erroneously applied to the control input terminals, the motor may start abruptly. Be sure to confirm safety before checking a signal.
Product Disposal
•Comply with the local ordinance and regulations when disposing of the product.
8
Warning Labels
Warning labels are located on the Inverter as shown in the following illustration. Be sure to follow the instructions.
Precautions for Correct Use
Warning Description
9
Checking Before Unpacking
RX- A2055-EF
Max. applicable motor capacity
004 007 015 022 037 055 075 110 150 185
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW 11 kW 15 kW
18.5 kW
Voltage class
243-phase 200 V AC (200-V class)
3-phase 400 V AC (400-V class)
Enclosure rating
A
Panel-mounting (IP20 min.) or closed wall-mounting models
220 300 370 450 550 750 900 11K 13K
22 kW 30 kW 37 kW 45 kW 55 kW 75 kW 90 kW 110 kW 132 kW
E: Europe standard
F: Built-in filter
B IP00
Checking Before Unpacking
Checking the Product
On delivery, be sure to check that the delivered product is the Inverter RX model that you ordered. Should you find any problems with the product, immediately contact your nearest local sales representative or OMRON sales office.
zChecking the Nameplate
Inverter model
Input specifications
Output specifications
zChecking the Model
Checking the Accessories
10
Note that this manual is the only accessory included with the RX model. Mounting screws and other necessary parts must be provided by the user.
Revision History
Revision History
A manual revision code appears as a suffix to the catalog number located at the
lower left of the front and back covers.
Cat. No. I560-E2-03
Revision code
Revision code Revision date Changes and revision pages
01 April 2009 First printing
11
About This Manual
About This Manual
This User's Manual is compiled chapter by chapter for user's convenience as follows. Understanding the following configuration ensures more effective use of the product.
Chapter 1 Overview Describes features and names of parts.
Provides external dimensions, installation dimensions, peripheral device
Chapter 2 Design
Chapter 3 Operation
Chapter 4 Functions Describes the functions of the Inverter.
Chapter 5
Chapter 6
Chapter 7 Specifications
Appendix
Maintenance Operations
Inspection and Maintenance
design/selection instructions, and other information necessary for design.
Describes names of parts, the Inverter's operations, including how to use the keys on the Digital Operator, and the monitor function.
Describes the causes and their countermeasures if the Inverter fails, including the solutions to possible troubles (troubleshooting).
Describes items for periodical inspection and/or maintenance for the Inverter.
Provides Inverter specifications, as well as the specifications and dimensions of peripheral devices.
Describes the summarized parameter settings as a reference for users who have used this Inverter and understood the functions.
Overview
13
Contents
Introduction.............................................................................................. 1
Read and Understand this Manual ..........................................................2
Safety Precautions ..................................................................................5
Precautions for Safe Use......................................................................... 7
Precautions for Correct Use ....................................................................8
Checking Before Unpacking .................................................................... 10
Revision History....................................................................................... 11
About This Manual...................................................................................13
Chapter 1 Overview
1-1 Functions .................................................................................................1-1
1-2 Appearance and Names of Parts............................................................. 1-4
Chapter 2 Design
2-1 Installation................................................................................................2-1
2-2 Wiring....................................................................................................... 2-6
Chapter 3 Operation
3-1 Operation Method .................................................................................... 3-3
3-2 Test Run Procedure.................................................................................3-4
3-3 Test Run Operation .................................................................................3-5
3-4 Part Names and Descriptions of the Digital Operator .............................. 3-8
3-5 Keys.........................................................................................................3-11
3-6 Parameter Transition ............................................................................... 3-12
3-7 Parameter List .........................................................................................3-18
Chapter 4 Functions
4-1 Monitor Mode...........................................................................................4-1
4-2 Function Mode ......................................................................................... 4-8
4-3 Functions When PG Option Board (3G3AX-PG01) Is Used....................4-119
4-4 Communication Function ........................................................................4-139
Chapter 5 Maintenance Operations
5-1 Protective Functions and Troubleshooting ..............................................5-1
5-2 Warning Function.....................................................................................5-9
Chapter 6 Inspection and Maintenance
6-1 Inspection and Maintenance.................................................................... 6-1
Chapter 7 Specifications
7-1 Standard Specification List ...................................................................... 7-1
7-2 Dimensional Drawing...............................................................................7-6
7-3 Options ....................................................................................................7-14
15
Contents
Chapter App Appendix
Appendix-1Parameter List ................................................................................. App-1
Appendix-2Product Life Curve........................................................................... App-38
Appendix-3Life Alarm Output............................................................................. App-39
Index
16
Chapter 1
Overview
1-1 Functions .......................................................... 1-1
1-2 Appearance and Names of Parts .................... 1-4
1-1 Functions
1Overview
1
1-1 Functions
RX Inverter Models
Overview
3-phase 200 V AC
3-phase 400 V AC
Rated voltage Enclosure rating Max. applicable motor capacity Model
0.4 kW RX-A2004
0.75 kW RX-A2007
1.5 kW RX-A2015
2.2 kW RX-A2022
3.7 kW RX-A2037
5.5 kW RX-A2055
7.5 kW RX-A2075
11 kW RX-A2110
15 kW RX-A2150
18.5 kW RX-A2185
22 kW RX-A2220
30 kW RX-A2300
37 kW RX-A2370
45 kW RX-A2450
IP20
IP00
55 kW RX-A2550
0.4 kW RX-A4004
0.75 kW RX-A4007
1.5 kW RX-A4015
2.2 kW RX-A4022
4.0 kW RX-A4040
5.5 kW RX-A4055
7.5 kW RX-A4075
11 kW RX-A4110
15 kW RX-A4150
18.5 kW RX-A4185
22 kW RX-A4220
30 kW RX-A4300
37 kW RX-A4370
45 kW RX-A4450
55 kW RX-A4550
75 kW RX-B4750
90 kW RX-B4900
110 kW RX-B411K
132 kW RX-B413K
1-1
1-1 Functions
International Standards Models (EC Directives and UL/cUL Standards)
The RX Inverter meets the EC Directives and UL/cUL standard requirements for worldwide use.
Classification Applicable standard
EC Directives EMC Directive EN61800-3: 2004
Low-voltage Directive EN61800-5-1: 2003
UL/cUL Standards UL508C
Human-/Environment-friendly, High-performance, General-purpose Inverters Suitable for Various Advanced Applications
High Performance
High Starting Torque
With the vector control and auto-tuning functions, the RX Series has achieved high starting torque in excess of 200% at 0.3 Hz.
1
Overview
Trip Suppression
This Inverter features two trip suppression functions: "Overcurrent trip suppression function" to suppress overcurrent trip during acceleration, and "Overvoltage suppression function during deceleration" to suppress overvoltage trip during deceleration. Therefore, the RX Series provides tough operational capabilities regardless of the severe time setting of acceleration and deceleration.
Various Applications
Sensor-less Vector Control at 0 Hz
The RX Series provides sensor-less vector control, which is useful for up/down applications. It can provide a high torque of 150%, even at a speed reference of 0 Hz (150% torque is available when the Inverter capacity is increased by one rank). This function contributes to simplification of control programs and extension of the service life of the brake.
Emergency Shutoff Function
By switching the dedicated switch (SW1) this function enables you to change the multi-function input (input 3) to the emergency shutoff input. You can directly turn off a motor control power module without operating the software. This function simplifies construction of safety applications.
Built-in Braking Circuit (up to 22 kW)
The Inverter models with 22 kW or lower capacity incorporate a braking transistor, enabling space­saving configuration for applications that need rapid acceleration and stop.
Restart Speed Search Function
For a free-running motor (e.g. a fan motor), this function checks the direction of rotation and frequency, enabling smooth restart of the motor.
High-torque Multi-operation
The RX Series enables balanced torque control for the whole system, in proportion to multiple motor loads.
Deceleration Stop During Power Failure
During a power failure or momentary power interruption, the RX Series can decelerate and stop a motor by using the motor braking energy.
1-2
1-1 Functions
Human-/Environment-friendly Features
1
Overview
More Simplified Parameter Settings and View
•Only parameters that have been changed from the default settings can be viewed.
•With the user setting function, only 12 parameters for frequent use can be viewed.
Compliance With Safety Standards
The RX Series meets the requirements of the CE and UL/cUL and complies with various standards.
The RoHS Directive
The standard model meets the requirements of the RoHS Directive.
Easily Meets the Requirements Specified by the Ministry of Land, Infrastructure and Transport of Japan
The RX Series incorporates a zero-phase reactor (radio noise filter) as a standard specification. When an optional DC reactor is added, the RX Series meets the requirements specified by the Min­istry of Land, Infrastructure and Transport of Japan.
1-3
1-2 Appearance and Names of Parts
1-2 Appearance and Names of Parts
When the product is unpacked, it appears as below. (Example of RX-A2150/A4150 to A2220/ A4220)
Front cover
Digital Operator
Spacer cover
Terminal block cover
Open the terminal block cover and you can connect cables to the main circuit terminal block, as well as the control circuit terminal block. Also, open the front cover and you can mount the optional board.
1
Overview
Position for installing optional board 1
Position for installing optional board 2
Control circuit terminal block
Main circuit terminal block
Backing plate
1-4
Chapter 2
Design
2-1 Installation ........................................................ 2-1
2-2 Wiring ................................................................ 2-6
2-1 Installation
WARNING
CAUTION
2Design
2-1 Installation
2
Turn off the power supply and implement wiring correctly. Not doing so may result in a serious injury due to an electric shock.
Design
Wiring work must be carried out only by qualified personnel. Not doing so may result in a serious injury due to an electric shock.
Do not change wiring and slide switches (SW1), put on or take off Digital Operator and optional devices, replace cooling fans while the input power is being supplied. Doing so may result in a serious injury due to an electric shock.
Be sure to ground the unit. Not doing so may result in a serious injury due to an electric shock or fire. (200-V class: type-D grounding, 400-V class: type-C grounding)
Do not connect resistors to the terminals (PD/+1, P/+, N/-) directly. Doing so might result in a small­scale fire, heat generation or damage to the unit.
Install a stop motion device to ensure safety. Not doing so might result in a minor injury. (A holding brake is not a stop motion device designed to ensure safety.)
Be sure to use a specified type of braking resistor/regenerative braking unit. In case of a braking resistor, install a thermal relay that monitors the temperature of the resistor. Not doing so might result in a moderate burn due to the heat generated in the braking resistor/regenerative braking unit. Configure a sequence that enables the Inverter power to turn off when unusual overheating is detected in the braking resistor/regenerative braking unit.
The Inverter has high voltage parts inside which, if short-circuited, might cause damage to itself or other property. Place covers on the openings or take other precautions to make sure that no metal objects such as cutting bits or lead wire scraps go inside when installing and wiring.
2-1
2-1 Installation
Safety Information
Installation and Storage
Do not store or use the product in the following places.
•Locations subject to direct sunlight.
•Locations subject to ambient temperature exceeding the specifications.
•Locations subject to relative humidity exceeding the specifications.
•Locations subject to condensation due to severe temperature fluctuations.
•Locations subject to corrosive or flammable gases.
•Locations subject to exposure to combustibles.
•Locations subject to dust (especially iron dust) or salts.
•Locations subject to exposure to water, oil, or chemicals.
•Locations subject to shock or vibration.
Transporting, Installation, and Wiring
•Do not drop or apply strong impact on the product. Doing so may result in damaged parts or malfunction.
•Do not hold by the front cover and terminal block cover, but hold by the fins during transportation.
•Do not connect an AC power supply voltage to the control input/output terminals. Doing so may result in damage to the product.
•Be sure to tighten the screws on the terminal block securely. Wiring work must be done after installing the unit body.
•Do not connect any load other than a three-phase inductive motor to the U, V, and W output terminals.
•Take sufficient shielding measures when using the product in the following locations. Not doing so may result in damage to the product.
Locations subject to static electricity or other forms of noise. Locations subject to strong magnetic fields. Locations close to power lines.
2
Design
Installation
•Install the Inverter vertically on the wall. Install the Inverter on a nonflammable wall surface material, like metal.
Position for installing a screw
Main Circuit Power Supply
•Confirm that the rated input voltage of the Inverter matches the AC power supply voltage.
Precautions for Use
2-2
2-1 Installation
Ventilation fan
Ventilation fan
Inverter Inverter
(Correct example) (Incorrect example)
Installation Environment
•Increased ambient temperatures will shorten the life of the Inverter.
•Keep the Inverter away from heating elements (such as a braking resistor, DC reactor, etc.). If the Inverter is installed in an enclosure, keep the ambient temperature within the range of the specifications, taking dimensions and ventilation into consideration.
2
Design
*1
Inverter
5 cm min. 5 cm min.
*2
•When several RX models are installed in an enclosure and a ventilation fan is mounted in the enclosure, be careful about the layout of the Inverters and the air intake apertures. Depending on the internal layout of the panel, the Inverter's cooling effect may deteriorate, resulting in an increase in ambient temperature. Also, use thorough caution in making sure that the Inverter's ambient temperature is within the allowable operating temperature range.
Airflow
Inverter
Save enough space to prevent the upper and lower wiring ducts from blocking cooling airflow.
*1 10 cm min. *2 10 cm min.
Note that replacing the smoothing capacitor
Wall
requires 22 cm or more.
•Before installing the Inverter, place a cover over all the ventilation openings to shield them from foreign objects. After completing the installation process, be sure to remove the covers from the Inverter before operation.
•Below is the heat radiation according to the Inverter capacity.
Inverter capacity (kw) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
Load with 70% loss (W) 64 76 102 127 179 242 312 435 575 698
Load with 100% loss (W)
Efficiency at rated output (%) 85.1 89.5 92.3 93.2 94.0 94.4 94.6 94.8 94.9 95.0
Inverter capacity (kw) 22 30 37 45 55 75 90 110 132
Load with 70% loss (W) 820 1100 1345 1625 1975 2675 3375 3900 4670
Load with 100% loss (W)
Efficiency at rated output (%) 95.0 95.0 95.1 95.1 95.1 95.2 95.2 95.2 95.2
2-3
70 88 125 160 235 325 425 600 800 975
1150 1550 1900 2300 2800 3800 4800 5550 6650
2-1 Installation
•To raise the carrier frequency, reduce the output current (or derate the rated current) as shown in the graph below.
Voltage 200-V class 400-V class
Capacity Max. fc (kHz) Derating at fc = 15 kHz Max. fc (kHz) Derating at fc = 15 kHz
0.4 kW 15 100% 15 100%
0.75 kW 15 100% 15 100%
1.5 kW 15 100% 15 100%
2.2 kW 15 100% 15 100%
3.7 kW 15 100% 15 100%
5.5 kW 15 100% 15 100%
7.5 kW 15 100% 15 100%
11 kW 12 90% (41.4 max.) 15 100%
15 kW 12 95% (60.8 A max.) 14 95% (30.4 A max.)
18.5 kW 10 90% (68.4 A max.) 10 90% (34.2 A max.)
22 kW 7 70% (66.5 A max.) 6 75% (36.0 A max.)
30 kW 5 80% (96.8 A max.) 10 75% (43.5 A max.)
37 kW 10 75% (108.7 A max.) 8 80% (60.0 A max.)
45 kW 5 70% (127.4 A max.) 9 75% (68.2 A max.)
55 kW 5 70% (154 A max.) 6 60% (67.2 A max.)
75 kW -- -- 6 85%(126.7 A max.)
90 kW -- -- 4 75% (132.0 A max.)
110 kW -- -- 6 70% (151.9 A max.)
132 kW -- -- 3 60% (156.0 A max.)
2
Design
200-V class 400-V class
100
95 90 85 80 75 70 65 60
Output current derating
55
0.5 2 4 6 8 10 12 1514
45,55 kW
Carrier frequency (kHz)
22 kW
18.5 kW 11 kW
15 kW
30 kW 37 kW
100
95 90 85 80 75 70 65 60
Output current derating
55
0.5 2 4 6 8 10 12 1514
90 kW
132 kW
Carrier frequency (kHz)
75 kW
110 kW
45 kW
30 kW
15 kW
18.5 kW
37 kW
22 kW
55 kW
2-4
2
Connecting points
Unnecessary portion
Design
2-1 Installation
Backing Plate
Inverter with 22 kW or Lower Capacity
When running cables, cut the points between the backing plate and unnecessary portions with nippers or a wire cutter, and remove.
Inverter with 30 kW or Higher Capacity
For Connection Without Cable Conduit
Make a cut in the rubber bushing of the backing plate with nippers or a wire cutter, and insert a ca­ble.
Backing plate
Rubber bushing
For Connection With Cable Conduit
Remove the rubber bushing from the conduit connecting portions, and connect the cable conduit.
* Do not remove the rubber bushing unless you connect a cable conduit.
Otherwise, the cable sheath may be damaged by the inner edge of the backing plate, resulting in short-circuit or ground fault.
2-5
2-2 Wiring
2-2 Wiring
Standard Connection Diagram
DC reactor (optional)
3-phase 200 V AC 3-phase 400 V AC
To wire the control circuit power supply and main circuit power supply separately, be sure to remove the J51 connector wire first.
Multi-function input 1
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
Multi-function input 8
Sequence input common
Thermistor
Frequency setting unit 500 to 2 kΩ
Short-circuit wire
Frequency reference power supply
Frequency reference input (voltage)
Frequency reference auxiliary input (voltage)
Frequency reference input (current)
Frequency reference common
J51
Control circuit power supply
PD/+1 P/+
R/L1
S/L2
T/L3
R
T
Ro
To
P24
CM1
FW
1
2
3
4
5
6
7
8
PLC
TH
H
O
O2
OI
L
Braking resistor (optional)
RBN/-
U/T1
V/T2
W/T3
AL1
Relay output *1
AL2
AL0
Common
11 Multi-function output 1
12 Multi-function output 2
13 Multi-function output 3
14 Multi-function output 4
15 Multi-function output 5
CM2
Multi-function output common
SP
SN
RP
For termination resistors
SN
Analog monitor output
AM
(voltage output)
Analog monitor output
AMI
(current output)
Digital monitor output
FM
(PWM output)
Option 1
Option 1
2
Design
M
RS485 communication
2-6
2
Design
2-2 Wiring
Main Circuit Terminals
Terminal symbol Terminal name Description
R/L1, S/L2,
T/L3
U/T1,V/T2,
W/T3
PD/+1, P/+ External DC reactor
P/+, RB Braking resistor
P/+, N/- Regenerative braking
G Ground terminal Inverter case ground terminal. Connect this terminal to the
Main power supply input terminal
Inverter output terminal Connect to the 3-phase motor.
terminal
connection terminals
unit connection terminal
Control Circuit Terminal
Connect the input power supply.
Remove the short-circuit bar between terminals "PD/+1" and "P/+", and connect the optional power factor improvement DC reactor.
Connect optional external braking resistors. (The RB terminal is provided for the Inverters with 22 kW or lower capacity.)
Connect optional regenerative braking units.
ground. type-D (200-V class), type-C (400-V class)
Analog
Terminal
symbol
H Frequency reference
O Frequency reference
O2 Auxiliary frequency
OI Frequency reference
Frequency reference input
L Frequency reference
Terminal name Description Specifications
power supply output
input (Voltage)
reference input (Voltage)
input (Current)
common
+10 V DC power supply for the O terminal. Allowable load current:
20 mA max.
With a 0 to 10 V DC voltage input, the frequency reaches the maximum at 10 V. Set at A014 if the maximum frequency needs to be achieved at lower than 10 V.
With a 0 to ±10 V DC voltage input, the O2 signal is added to the frequency reference signal of the O or OI terminal. By changing the setting, the frequency reference can be input even with the O2 terminal independently.
With a 4 to 20 mA DC current input, the maximum frequency is set at 20 mA. The OI signal is only active when the AT terminal is ON. Allocate the AT function to the multi­function input terminal.
Common terminal for the frequency setting signals (O, O2 and OI) and the analog output terminals (AM and AMI). Do not connect this terminal to the ground.
Input impedance 10 k Allowable input voltage range:
-0.3 to +12 V DC
Input impedance 10 k Allowable input voltage range: 0 to ±12 V DC
Input impedance 100 Allowable max. current: 24 mA
Continued to the next page
2-7
2-2 Wiring
Terminal
Analog
Monitor output
Monitor output
Digital (contact)
Power supply
symbol
AM Multi-function analog
AMI Multi-function analog
FM Multi-function digital
P24 Internal 24 V DC 24 V DC power supply for contact input
PLC Input common Common terminal for the interface power
Terminal name Description Specifications
This terminal outputs a signal selected from output (Voltage)
output (Current)
output
the "0 to 10 V DC Voltage Output" monitor
items: Output frequency, Output current,
Output torque (with/without sign), Output
voltage, Input power, Electronic thermal load
rate, LAD frequency, Motor temperature,
and Fin temperature.
This terminal outputs a signal selected from
the "4 to 20 mA DC Current Output" monitor
items: Output frequency, Output current,
Output torque (without sign), Output voltage,
Input power, Electronic thermal load rate,
LAD frequency, Motor temperature, and Fin
temperature.
This terminal outputs a signal selected from
the "0 to 10 V DC Voltage Output (PWM)"
monitor items: Output frequency, Output
current, Output torque (without sign), Output
voltage, Input power, Electronic thermal load
rate, LAD frequency, Motor temperature, Fin
temperature, Digital output frequency, and
Digital current monitor.
"Digital output frequency", and "Digital
current monitor" output a digital pulse at 0/10
V DC pulse voltage and 50% duty ratio.
signal.
When the source logic is selected, this
terminal functions as the contact input
common terminal.
supply P24 terminal, thermistor input TH
terminal and digital monitor FM terminal.
When the sink logic is selected, this terminal
functions as the contact input common
terminal. Do not connect this terminal to the
ground.
Allowable max. current: 2 mA
Allowable load impedance: 250 max.
Allowable max. current:
1.2 mA Max. frequency:
3.6 kHz
Allowable max. output current: 100 mA
2
Design
Continued to the next page
2-8
2-2 Wiring
2
Design
Terminal
RUN command
Contact input
Function / Selection
Digital (contact)
Status / Factor
Open collector output
Relay output
Digital (contact)
Status, alarm, etc.
symbol
FW Forward rotation
1 2 3 4 5 6 7 8
CM1 Multi-function input
11 12 13 14 15
CM2 Multi-function output
AL2 AL1
AL0 Relay output
Terminal name Description Specifications
command terminal
Multi-function input Select 8 functions from among the 61 functions
common
Multi-function output Select 5 functions from among 45, and allocate
common
Relay output Select the desired functions from among 45
common
When the FW signal is ON, the motor runs forward. When it is OFF, the motor decelerates and stops.
and allocate them to terminals 1 to 8.
Note: Only terminals 1 and 3 can be used for the
emergency shutoff function. For details, refer to "Emergency Shutoff Function" (page 2-10).
The sink and source logic for contact input can be switched by connecting a short-circuit bar on the control terminal block. Short-circuiting P24 and PLC Sink logic, Short-circuiting PLC and CM1 Source logic To activate contact input via an external power supply, remove the short-circuit bar and connect CM1 terminal to the external interface circuit.
them to terminals 11 through 15. If an alarm code is selected in C062, terminals 11 to 13, or terminals 11 to 14 always output an alarm factor code (e.g. Inverter trip). The signal between each terminal and CM2 always corresponds to the sink or source logic.
Common terminals for multi-function output terminals 11 to 15.
functions, and allocate them. SPDT contact output. By factory default, the relay output (AL2, AL1) contact selection (C036) is set at NC contact between AL2-AL0, and NO contact between AL1-AL0.
Continued to the next page
[Contact input ON condition] Voltage between each input terminal and the CM1 terminal :18 V DC or more
Input impedance between each input terminal and the CM1 terminal: 4.7 k
Allowable max. voltage: Voltage between each input terminal and the CM1 terminal: 27 V DC
Load current at 27 V DC power supply voltage: Approx. 5.6 mA
Between each terminal and CM2 Voltage drop 4 V max. at power-on
Max. allowable voltage: 27 V DC
Max. allowable current: 50 mA
Contact max. capacity AL2-AL0 250 V AC, 2 A (Resistance)
0.2 A (Induction) AL1-AL0 250 V AC, 1 A (Resistance)
0.2 A (Induction) Contact min. capacity 100 V AC, 10 mA 5 V DC, 100 mA
2-9
2-2 Wiring
TH
PLC
Thermistor
8 V DC
10 kΩ
1 kΩ
Analog
Terminal
symbol
TH External thermistor
Sensor
Analog input
Terminal name Description Specifications
Connect an external thermistor to this terminal,
input Terminal
to trip the Inverter when a temperature error occurs. The PLC terminal functions as the common terminal. [Recommended thermistor characteristics] Allowable rated power: 100 mW min. Impedance at temperature error: 3 k Temperature error detection level is adjustable between 0 and 9999 .
Slide Switch (SW1) Settings
The built-in slide switch is used to enable or disable the emergency shutoff function. (Factory Default: Disabled) * For the location of the slide switch, refer to (page 2-12).
Emergency Shutoff Function (Factory Default: Disabled)
•This function is intended to turn off the Inverter output (stop switching the main element) via only the multi-function input terminal of the hardware circuit without going through the CPU software.
* This function stops switching of the main element.The circuit is not electrically turned off. While the
power supply is ON, do not touch the Inverter terminals and power cable (e.g. motor cable). Doing so may result in electric shock, injury or ground fault.
Allowable input voltage range 0 to 8 V DC [Input circuit]
2
Design
•When this function is enabled, the multi-function input terminals 1 and 3 are exclusively used for this function. No other function can be allocated to these terminals. If another function has been allocated, it will automatically be disabled, and terminals 1 and 3 are changed to the emergency shutoff terminals.
Function of multi-function input terminal 1
Reset signal (RS) / NO contact (Fixed) This signal is used to reset the Inverter, and to reset the emergency shutoff trip [ E37.* ].
Function of multi-function input terminal 3
Emergency shutoff signal (EMR) / NC contact (Fixed) This signal is used to turn off the Inverter output without using the built-in CPU. With this signal input, the Inverter activates an emergency shutoff trip [ E37. * ].
* If multi-function input terminal 3 has not been connected or disconnected, or if the signal logic is
not matched, the Inverter activates an emergency shutoff trip [E37. *]. After checking the cable connection and the signal logic, input the reset signal (RS). Emergency shutoff trip [ E37. * ] can be reset only by the reset signal (RS) via multi-function input terminal 1. (It cannot be reset with the Digital Operator.)
•To enable this function, set the slide switch SW1 lever in the Inverter to [ON]. (With the factory default setting, slide switch SW1 is [OFF]. [This function is disabled.])
2-10
2
Design
2-2 Wiring
Slide switch (SW1) setting
SW1 OFF Emergency shutoff: Disabled (factory default)
SW1 ON Emergency shutoff: Enabled
*5
Turning SW1 on, and then off Emergency shutoff: Disabled
*3 *5
* Before operating slide switch SW1, make sure that the input power supply is OFF.
Slide switch SW1 setting and status of multi-function input terminals 1 and 3
Multi-function input terminal 1 Multi-function input terminal 3
Multi-function input 1
selection
[ C001 ]
[Can be selected
randomly]
Factory
*4
01 (RV) Factory
default
Fixed
18 (RS) Fixed function (Cannot
be
changed)
[Can be selected
randomly]
Holds
*4
18 (RS) Holds
setting
while SW1
is ON.
Multi-function input 1
operation selection
*1
[ C011 ]
[Can be selected
randomly]
*4
00 (NO) Factory
default
Multi-function input 3
selection
[ C003 ]
[Can be selected
randomly]
*4
12 (EXT) Factory
default
Automatic allocation to multi-function input terminals 1 and 3,
and the input terminal with 18 (RS) setting
function (Cannot
be
changed)
[Can be selected
randomly]
setting
while SW1
is ON.
00 (NO) Fixed
function (Cannot
be
changed)
*4
00 (NO)
[Can be selected
Emergency
shutoff
function:
Reset
64 (EMR) Fixed
randomly]
*4
(no
allocation)
no
Multi-function input 3
operation selection
[ C013 ]
[Can be selected
randomly]
default
*3
function (Cannot
be
changed)
[Can be selected
randomly]
Holds
setting
while SW1
is ON.
*1 *2
*4
00 (NO)
01 (NC)
*4
01 (NC)
*1. With the terminal with input terminal selection [18 (RS)], NO/NC selection is fixed to [00 (NO)]. *2. When [C003] is [64 (EMR)], [C013] is fixed to [01 (NC)]. *3. If [18 (RS)] has been allocated to a multi-function input terminal (except for 3) other than terminal
1 before switch SW1 is set to "ON", the input terminal selection for the relevant terminal will be automatically changed to "no (no allocation)" by setting SW1 to "ON". This is done in order to prevent duplicated allocation of this function. Then, even if SW1 is reset to [OFF], the initial allocation cannot be restored. The User should Re-allocate the terminal function.
Example) When the multi-function input terminal 2 [C002] is [18 (RS)], setting SW1 to [ON] changes
the [C002] setting to [no (no allocation)]. [18 (RS)] will be allocated to the multi-function input terminal 1 [C001]. Then, even if SW1 is reset to [OFF], the multi-function input terminal 2 [C002] setting is [no (no allocation)], and the multi-function input terminal 1 [C001] setting is [18 (RS)].
*4. Input terminal selection [64 (EMR)] cannot be selected with the Digital Operator. When slide
switch SW1 is set to [ON], this function will be automatically allocated.
2-11
2-2 Wiring
*5. Once slide switch SW1 is set to [ON], allocation of multi-function input terminals 1 and 3 will not
be restored, even if SW1 is reset to [OFF] afterward. Re-allocate the terminal function.
Slide switch SW1
ON
Slide lever (factory default: OFF)
ONOFF
2
Design
Wiring the Main Circuit Terminals
Main Power Supply Input Terminals (R/L1, S/L2, T/L3)
• Use an earth leakage breaker for circuit (wiring) protection between the power supply and the main power supply terminals (R/L1, S/L2, T/L3).
• An earth leakage breaker may malfunction due to the effect of high frequency. Use an earth leakage breaker with a large high-frequency sensitivity current rating.
• If the Inverter protection function is activated, a malfunction or accident may have occurred to your system. Connect a magnetic contactor to turn off the Inverter power supply.
• Do not start or stop the Inverter by switching ON/OFF the magnetic contactor connected on the Inverter power supply input (primary) side and output (secondary) side. To start or stop the Inverter via an external signal, use the operation command (FW or RV) on the control circuit terminal block.
• This Inverter uses a 3-phase power supply. A single-phase power supply cannot be used.
• Do not use this Inverter with a phase loss power input. Doing so may damage the Inverter. By factory default, the phase loss input protection is disabled. If a phase of power supply input is interrupted, the Inverter reverts to the following status:
R/L1-phase or T/L3-phase is inter­rupted:
S/L2-phase is interrupted: The Inverter reverts to single-phase operation, causing a
Even if the power input is under a phase loss condition, the internal capacitor is charged with voltage, causing an electric shock or injury. When changing the cable connections, refer to the instructions on page 2-1.
The Inverter does not operate.
trip (due to undervoltage, overcurrent, etc.) or damage to the Inverter.
2-12
2
Design
2-2 Wiring
• In the following cases, the internal converter module may be damaged. Use caution to avoid them: Imbalance of power supply voltage is 3% or more. Power supply capacity is ten times or more than the Inverter capacity, and also 500 kVA or more. Rapid change in power supply voltage.
Example) When several Inverters are connected with a short bus.
When the phase advance capacitor is turned on/off.
• Do not turn power on/off more than once every 3 minutes. Doing so may damage the Inverter.
Inverter Output Terminals (U/T1, V/T2, W/T3)
• For connection of the output terminal, use the applicable cable or a cable with a larger diameter. Otherwise, the output voltage between the Inverter and the motor may drop. Particularly during low-frequency output, a voltage drop occurs with the cable, resulting in motor torque reduction.
• Do not mount a phase advance capacitor or surge absorber. These devices cause the Inverter to trip, or may cause damage to the capacitor or surge absorber.
• If the cable length exceeds 20 m (particularly, with 400-V class), a surge voltage may be generated at the motor terminal due to stray capacitance or inductance of the cable, causing the motor to burn out.
• To connect several motors, provide a thermal relay for each.
• The RC value of each thermal relay should be 1.1 times of the motor rated current. The relay may trip easily depending on the cable length. In this case, connect an AC reactor to the Inverter output.
DC Reactor Connection Terminal (PD/+1, P/+)
• This terminal is used to connect the optional DC reactor for power factor improvement. By factory default, a short-circuit bar has been connected between the terminals PD/+1 and P/+. Before connecting the DC reactor, remove this short-circuit bar.
• The length of the DC reactor connection cable should be 5 m or less.
If the DC reactor is not used, do not remove the short-circuit bar. If you remove the short-circuit bar without connecting the DC reactor, no power is supplied to the Inverter main circuit, disabling operation.
External Braking Resistor Connection Terminal (P/+, RB)/Regenerative Braking
Unit Connection Terminal (P/+, N/-)
• The Inverters with 22 kW or lower capacity incorporate a regenerative braking circuit. To improve braking capability, mount the optional external braking resistor to this terminal. Do not mount a resistor whose resistance is lower than the specified value. Doing so may damage the regenerative braking circuit.
• The Inverters with 30 kW or higher capacity do not incorporate a regenerative braking circuit. To improve braking capability, the optional regenerative braking unit and braking resistor are required. In this case, connect the regenerative braking unit terminals (+, -) to the Inverter terminals (P/+, N/-).
• The cable length should be 5 m or less. Twist the two wires.
• Do not connect any device other than the optional regenerative braking unit or external braking resistor to this terminal.
2-13
Ground Terminal (G )
• To prevent electric shock, be sure to ground the Inverter and the motor.
• According to the Electric Apparatus Engineering Regulations, the 200-V class Inverter should be connected to the grounding electrodes under type-D grounding conditions (conventional type 3 grounding: ground resistance 100 or less), the 400-V class Inverter should be connected to the grounding electrodes under type-C grounding conditions (conventional special type 3 grounding: ground resistance 10 or less).
• For the ground cable, use the applicable cable or a cable with a larger diameter. Make the cable length as short as possible.
• When several Inverters are connected, the ground cable must not be connected across several Inverters, and must not be looped. Otherwise, the Inverters may malfunction.
2-2 Wiring
2
Design
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Installing Screws in the Main Circuit Terminal Block
• For the main circuit terminal blocks of RX-A2055/-A2075/-A4055/-A4075, be sure to install the terminal block screw washers with their grooved sides aligned vertically, as shown below. Not doing so may result in a contact failure or fire. (Intended terminals: R/L1, S/L2, T/L3, PD/+1, P/+, N/-, U/T1, V/T2, W/T3, RB)
Your ground bolt
Terminal block screw washer
2-14
2
RB
Ro To
G G
CHARGE LED indicator
PD/+1 - P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar attached.
R/L1 S/L2 T/L3
PD/+1
P/+ N/-
U/T1 V/T2 W/T3
Design
2-2 Wiring
Arrangement of Main Circuit Terminals
The terminal arrangement on the Inverter main circuit terminal block is shown below.
Terminal arrangement Applicable model
[EMC filter function switching method]
Dummy plug (green)
Filter enable pin (J61)
Short plug
Filter disable pin (J62)
EMC filter disabled
EMC filter enabled (factory default)
Filter enable pin (J61) Dummy plug (green)
Short plug
In order to enable the EMC filter function, set up the plug inserted into the filter enable pin (J61) and filter disable pin (J62) as shown in the table below. Confirm that electrical power has been disconnected before performing this setup. Not doing so may result in electric shock. Also, use with the plug inserted.
RX-A2004 to A2037 RX-A4004 to A4037
Ro,To: M4 Ground terminal: M4 Others: M4
Filter disable pin (J62)
Short plug
Dummy plug (green)
CHARGE LED indicator
R/L1 S/L2 T/L3 PD/+1
G
Ground terminal with short-circuit bar (shaded area) for EMC filter function switching
P/+ N/- U/T1 V/T2 W/T3
PD/+1 - P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar attached.
[EMC filter function switching method]
EMC filter enabled (factory default) EMC filter disabled
RB
G
Ro To
RX-A2055, A2075 RX-A4055, A4075
Ro,To: M4 Ground terminal: M5 Others: M5
RX-A2110 RX-A4110
Ro,To: M4 Ground terminal: M6 Others: M5
2-15
2-2 Wiring
Ro To
RB
R/L1 S/L2 T/L3 PD/+1
P/+ N/- U/T1 V/T2 W/T3
G
G
Ground terminal with short-circuit bar (shaded area) for EMC filter function switching
PD/+1 - P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar attached.
CHARGE LED indicator
Terminal arrangement Applicable model
RX-A2150 to A2185 RX-A4150 to A4220
2
[EMC filter function switching method]
EMC filter enabled (factory default) EMC filter disabled
CHARGE LED indicator
R/L1 S/L2 T/L3 PD/+1
Ro To
P/+ N/- U/T1 V/T2 W/T3
Ro,To: M4 Ground terminal: M6 Others: M6
RX-A2220
Ro,To: M4 Ground terminal: M6 Others: M8
RX-A2300
Ro, To: M4
GG
Ground terminal: M6 Others: M8
Design
Ground terminal with short-circuit bar (shaded area) for EMC filter function switching
[EMC filter function switching method]
EMC filter enabled (factory default) EMC filter disabled
PD/+1 - P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar attached.
RX-A4300
Ro,To: M4 Ground terminal: M6 Others: M6
RX-A2370 RX-A4370
Ro,To: M4 Ground terminal: M8 Others: M8
2-16
2
Ro To
GG
G
R/L1 S/L2 T/L3 PD/+1
P/+ N/- U/T1 V/T2 W/T3
Ground terminal with short-circuit bar (shaded area) for EMC filter function switching
PD/+1-P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1-P/+ short-circuit bar attached.
CHARGE LED indicator
Ro To
G
G
G
R/L1 S/L2 T/L3 PD/+1
P/+ N/- U/T1 V/T2 W/T3
Ground terminal with short-circuit bar (shaded area) for EMC filter function switching
PD/+1 - P/+ short-circuit bar
When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar attached.
CHARGE LED indicator
Design
2-2 Wiring
Terminal arrangement Applicable model
RX-A2450 RX-A4450 RX-A4550
[EMC filter function switching method]
EMC filter enabled (factory default) EMC filter disabled
Ro,To: M4 Ground terminal: M8 Others: M8
RX-A2550
[EMC filter function switching method]
EMC filter enabled (factory default) EMC filter disabled
2-17
Ro,To: M4 Ground terminal: M8 Others: M10
Recommended Cable Size, Wiring Device and Crimp Terminal
For Inverter wiring, crimp terminal and terminal screw tightening torque, refer to the table below.
2-2 Wiring
Power cable
2
Motor
output
200-V class
Applicable
Inverter
(kW)
0.4 RX-A2004 1.25 1.25 1.25 M4 1.25-4
0.75 RX-A2007 1.25 1.25 1.25 M4 1.25-4
1.5 RX-A2015 2 2 2 M4 2-4
2.2 RX-A2022 2 2 2 M4 2-4
3.7 RX-A2037 3.5 3.5 3.5 M4 3.5-4
5.5 RX-A2055 5.5 5.5 5.5 M5 R5.5-5
7.5 RX-A2075 8 8 8 M5 R8-5
11 RX-A2110 14 14 14 M6 R14-6
15 RX-A2150 22 22 22 M6 22-6
18.5 RX-A2185 30 22 30 M6 38-6
22 RX-A2220 38 30 38 M8 38-8
30 RX-A2300
37 RX-A2370
45 RX-A2450
55 RX-A2550
model
(mm
)
R, S, T, U, V,
W, PD/+1,
P/+, N/-
60
(22 × 2)
100
(38 × 2)
100
(38 × 2)
150
(60 × 2)
Ground
cable
(mm
30 M8 60-8
38 M8
38 M8
60 M10 150-10
External braking resistor between PD/+1
2
)
and RB (mm
2
)
Terminal
screw
size
*1
*1
Crimp
terminal
100-8
100-8
Tightening
torque
N•m
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
2.4
(4.0 max.)
2.4
(4.0 max.)
4.0
(4.4 max.)
4.5
(4.9 max.)
4.5
(4.9 max.)
8.1
(8.8 max.)
8.1
(8.8 max.)
8.1
(20.0 max.)
8.1
(20.0 max.)
20.0
(22.0 max.)
Applicable
device
Earth leakage breaker (ELB)
5 A
10 A
15 A
20 A
30 A
50 A
60 A
75 A
100 A
100 A
150 A
200 A
225 A
225 A
350 A
2
Design
2-18
2-2 Wiring
2
Design
Motor
output
(kW)
Applicable
Inverter
model
Power cable
2
(mm
)
R, S, T, U, V,
W, PD/+1,
P/+, N/-
Ground
cable
(mm
External
braking resistor between PD/+1
2
)
and RB (mm
2
)
Terminal
screw
size
0.4 RX-A4004 1.25 1.25 1.25 M4 1.25-4
0.75 RX-A4007 1.25 1.25 1.25 M4 1.25-4
1.5 RX-A4015 2 2 2 M4 2-4
2.2 RX-A4022 2 2 2 M4 2-4
3.7 RX-A4037 2 2 2 M4 2-4
5.5 RX-A4055 3.5 3.5 3.5 M5 R2-5
7.5 RX-A4075 3.5 3.5 3.5 M5 3.5-5
11 RX-A4110 5.5 5.5 5.5 M6 R5.5-6
15 RX-A4150 8 8 8 M6 8-6
18.5 RX-A4185 14 14 14 M6 14-6
400-V class
22 RX-A4220 14 14 14 M6 14-6
30 RX-A4300 22 22 - M6 22-6
37 RX-A4370 38 22 M8
45 RX-A4450 38 22 M8
55 RX-A4550 60 30 M8
75 RX-B4750
90 RX-B4900
110
132
RX-
B411K
RX-
B413K
100
(38 x 2)
100
(38 x 2)
150
(38 x 2)
80 x 2
38 M10
38 M10
60 M10
80
M10
*1
*1
*1
*1
*1
*1
*1
Crimp
terminal
38-8
38-8
R60-8
100-10
100-10
150-10
80-10
Tightening
torque
N•m
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
1.2
(max.1.8)
2.4
(4.0 max.)
2.4
(4.0 max.)
4.5
(4.4 max.)
4.5
(4.9 max.)
4.5
(4.9 max.)
4.5
(4.9 max.)
4.5
(4.9 max.)
8.1
(20.0 max.)
8.1
(20.0 max.)
8.1
(20.0 max.)
20.0
(22.0 max.)
20.0
(22.0 max.)
20.0
(35.0 max.)
20.0
(35.0 max.)
Applicable
device
Earth leakage breaker (ELB)
5 A
5 A
10 A
10 A
15 A
30 A
30 A
50 A
60 A
60 A
75 A
100 A
100 A
150 A
175 A
225 A
225 A
350 A
350 A
*1. When the cable is connected without using the crimp terminal (bare wires), use the square washer included
with the product.
Note: The cable size is based on the HIV cable (75C heat resistance).
2-19
2-2 Wiring
Connection for Separating Inverter Control Circuit Power Supply from Main Power Supply
If the Inverter protection circuit is activated to turn off the magnetic contactor of the Inverter input power supply, the power to the Inverter control circuit is also turned off, and the alarm signal cannot be kept on. If the alarm signal must be kept on, use control circuit power supply terminals Ro and To. Connect control circuit power supply terminals Ro and To to the primary circuit of the magnetic contactor according to the following procedure.
2
(Connection method) Incoming electricity specifications 200-V class: 200 to 240 V (+10%, -15%) 50, 60 Hz ±5% (282 to 339 V DC) 400-V class: 380 to 480 V (+10%, -15%) 50, 60 Hz ±5% (537 to 678 V DC)
(1) Disconnect the connected wire.
(2) Disconnect the J51 connector.
(3) Connect the control circuit power cable to the control circuit power supply terminal block.
* To separate the control circuit power supply (Ro, To) from the main circuit power supply (R/L1, S/
L2, T/L3), observe the following instructions:
• For wiring between terminals Ro and To (terminal screw size: M4), use a cable of 1.25 mm or more.
• Connect a 3 A fuse to the control circuit power supply cable.
• If the control circuit power supply (Ro, To) is turned on before the main circuit power supply (R/L1, S/L2, T/L3), ground fault detection at power-on is disabled.
• To use a DC power supply for the control circuit power supply (Ro, To), set the multi-function output terminal contact selection (C031 to C036) for the multi-function output terminals (11 to
15) and relay output terminals (AL2, AL1, AL0) to "00". If the multi-function output terminal contact selection is set to "01", the output signal may chatter when the DC power supply is turned off.
• Tightening torque for terminals Ro and To M4: 1.2 N•m (1.4 max.)
Design
2
2-20
2
Design
2-2 Wiring
Wiring Control Circuit Terminals
• Terminals L and PLC are insulated from each other via the input and output signal common terminals. Do not short-circuit or ground these common terminals. Do not ground these common terminals via external equipment. (Check the external equipment ground conditions.)
• For wiring the control circuit terminals, use twisted shielded cables (recommended size: 0.75
2
mm
), and connect the shielded cable to each common terminal.
• The control circuit terminal connection cables should be 20 m or less.
• Separate the control circuit terminal connection cables from the main circuit cable (power cable) and the relay control circuit cable.
• For the connection of the TH (thermistor input) terminal, twist cables with the terminal PLC individually, and separate them from other PLC common cables. Since a weak current flows through the thermistor, the thermistor connection cable must be separated from the main circuit cable (power cable). The thermistor connection cable should be 20 m or less.
TH FW 8 CM1 5
PLC CM1 7
• To use a relay for the multi-function output terminal, connect a surge-absorbing diode in parallel with the coil.
• Do not short-circuit the analog power supply terminals (between H and L) and/or the interface power supply terminals (between P24 and PLC). Doing so may result in failure of the Inverter.
64
Arrangement of the Control Circuit Terminal Block
HO2AMFMTHFW8
L O OI AMI P24 PLC CM1
Terminal screw size M3 Tightening torque 0.7 N·m (0.8 max.)
CM1 5 3 1 14 13 11 AL1
7 6 4 2 15 CM2 12 AL0 AL2
Selecting the Input Control Logic
By factory default the terminal FW and the multi-function input terminal are set to sink logic (NPN). To change the input control logic to source logic (PNP), remove the short-circuit bar between the terminals P24 and CM1 on the control circuit terminal block, and connect it between the terminals CM1 and PLC.
PLC
Thermistor
2-21
Selecting the Sequence Input Method (Sink/Source Logic)
P24+V
CM1
PLC
FW
8
24 V DC
Inverter
COM
DC24V
Output unit etc.
2-2 Wiring
When the Inverter's internal interface power supply is
used
P24+V
Sink logicSource logic
Output unit etc.
Output unit etc.
Short-circuit
bar
COM
COM
Short-circuit
0V
bar
CM1
PLC
FW
8
Inverter
P24
CM1
PLC
FW
8
Inverter
24 V DC
24 V DC
When external power supply is used
(Remove the short-circuit bar from the control
terminal block.)
Output unit etc.
COM
24 V DC
0V
P24 CM1 PLC
FW
8
Inverter
24 V DC
2
Design
Selecting the Sequence Output Method (Sink/Source Logic)
11
12
Sink logic
Inverter
24 V DC
CM2
COM
CM2
24 V DC
11
Source logic
12
Inverter
COM
2-22
2
Design
2-2 Wiring
Wiring the Digital Operator
• The RX Series Inverter can be operated with the optional 3G3AX-OP01/OP05 as well as the
standard Digital Operator.
• To use the Digital Operator apart from the Inverter body, place an order for the optional cable
3G3AX-CAJOP300-EE (3 m).
• The optional cable should be 3 m or less. Using a cable longer than 3 m may cause malfunction.
Conforming to EC Directives
Conforming Standards
•EMC directive EN 61800-3: 2004
•Low-voltage directive EN 61800-5-1: 2003
Concept of Conformity
EMC Directive
OMRON products are the electrical devices incorporated and used in various machines or manufacturing equipment. For this reason, we make efforts to conform our products to their related EMC standards so that the machines or equipment which have incorporated our products should easily conform to the EMC standards. The RX models have conformed to the EMC directive EN 61800-3 by following the installation and wiring method as shown below. Your machines or equipment, however, vary in type, and in addition, EMC performance depends on the configuration, wiring, or location of the devices or control panels which incorporate the EC directive conforming products. This in turn does not allow us to confirm the condition and the conformity in which our products are used. Therefore, we appreciate confirmation of the final EMC conformity for the whole machine or equipment on your own.
Wiring the Power Supply
•Keep the ground cable as short as possible.
•Keep the cable between the Inverter and the noise filter as short as possible.
Connecting a Motor to the Inverter
•When connecting a motor to the Inverter, be sure to use shield braided cables.
•Keep the cables as short as possible.
Low-voltage Directive
The RX models have conformed to the EMC directive EN61800-5-1 by performing the machine in­stallation and wiring as shown below.
•The RX models are an open type device. Be sure to install it inside the control panel.
•The power supply and voltage (SELV) with reinforced or double insulation should be used for
wiring to the control circuit terminals.
•To satisfy requirements of the LVD (low-voltage) directive, the Inverter must be protected with a
molded case circuit breaker (MCCB) in case a short-circuiting accident occurs. Be sure to install a molded case circuit breaker (MCCB) on the power supply side of the Inverter.
•Use one molded case circuit breaker (MCCB) per Inverter.
•Use the crimp-type terminal with an insulation sleeve to connect to the main circuit terminals.
2-23
Chapter 3
Operation
3-1 Operation Method ............................................ 3-3
3-2 Test Run Procedure ......................................... 3-4
3-3 Test Run Operation.......................................... 3-5
3-4 Part Names and Descriptions of the Digital
Operator ............................................................ 3-8
3-5 Keys................................................................... 3-11
3-6 Parameter Transition ....................................... 3-12
3-7 Parameter List .................................................. 3-18
3
WARNING
CAUTION
Operation
3Operation
Do not change wiring and slide switches (SW1), put on or take off Digital Operator and optional devices, replace cooling fans while the input power is being supplied. Doing so may result in a serious injury due to an electric shock.
Do not remove the terminal block cover during the power supply and 10 minutes after the power shutoff. Doing so may result in a serious injury due to an electric shock.
Do not operate the Digital Operator or switches with wet hands. Doing so may result in a serious injury due to an electric shock.
Inspection of the Inverter must be conducted after the power supply has been turned off. Not doing so may result in a serious injury due to an electric shock. The main power supply is not necessarily shut off even if the emergency shutoff function is activated.
Do not touch the Inverter fins, braking resistors and the motor, which become too hot during the power supply and for some time after the power shutoff. Doing so may result in a burn.
Take safety precautions such as setting up a molded-case circuit breaker (MCCB) that matches the Inverter capacity on the power supply side. Not doing so might result in damage to property due to the short circuit of the load.
Safety Information
Operation and Adjustment
•Be sure to confirm the permissible range of motors and machines before operation because the Inverter speed can be changed easily from low to high.
•Provide a separate holding brake if necessary.
3-1
Precautions for Use
Error Retry Function
•Do not come close to the machine when using the error retry function because the machine may abruptly start when stopped by an alarm.
•Be sure to confirm the RUN signal is turned off before resetting the alarm because the machine may abruptly start.
Non-Stop Function at Momentary Power Interruption
•Do not come close to the machine when selecting restart in the non-stop function at momentary power interruption selection (b050) because the machine may abruptly start after the power is turned on.
Operation Stop Command
•Provide a separate emergency stop switch because the STOP key on the Digital Operator is valid only when function settings are performed.
•When checking a signal with the main power supply applied, if a signal voltage is erroneously applied to the control input terminals, the motor may start abruptly. Be sure to confirm safety before checking a signal.
3
Operation
3-2
3-1 Operation Method
3-1 Operation Method
This Inverter has the following operation methods that are selected by the RUN command/ frequency reference settings. The features and the requirements for each operation method are also given below:
3
Operation
To enter the RUN command/frequency reference via the Digital Operator
This action operates the Inverter via a key sequence of the standard or optional Digital Operator. When operating the Inverter only via the Digital Operator, the Inverter does not need to be connected to the control circuit terminal block.
Digital Operator
To enter the RUN command/frequency reference from the control circuit terminal block
This action operates the Inverter by connecting the external signals (from the frequency setting device, starting switch, etc.) to the control circuit terminal block. The operation starts by turning ON the RUN command (FW, RV) while the input power supply is turned ON. Note: that the frequency can be set using a voltage signal or a current signal from the control circuit terminal block, which can be selected according to the system. For details, refer to "Control Circuit Terminal" (page 2-7).
(Requirements for operation)
• RUN command: Switch, Relay etc.
• Frequency reference: External signal (e.g. 0 to 10 V DC, -10 to 10 V DC, 4 to 20 mA)
Frequency reference (FREQ adjuster)
To enter the RUN command/frequency reference in a combination of Sources
from the Digital Operator and the control circuit terminal block
The RUN command/frequency reference sources can be selected individually from the Digital Operator as well as the control circuit terminal block.
3-3
Control circuit terminal block
FW
CM1
RUN command (switch)
LOH
3-2 Test Run Procedure
3-2 Test Run Procedure
Item Description
Installation and Mounting
Wiring and Connection Connect to the power supply and peripheral devices. 2-6
Power On Check the following before turning on the power.
Display Status Check Make sure that there are no faults in the Inverter.
Install the Inverter according to the installation conditions. 2-1
• Make sure that the installation conditions are met.
• Select peripheral devices that meet the specifications, and wire correctly.
• Make sure that an appropriate power supply voltage is supplied and that the power input terminals (R/L1, S/L2, and T/L3) are wired correctly.
• RX-A2: 3-phase 200 to 240 V AC
• RX-A4: 3-phase 380 to 480 V AC
• Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the motor correctly.
• Make sure that the control circuit terminals and the control device are wired correctly and that all control terminals are turned off.
• Set the motor to no-load status (i.e., not connected to the mechanical system).
• After checking the above, turn on the power.
• When the power is turned on normally, the display shows:
• RUN LED indicator : ON ALARM LED indicator : OFF
• POWER LED indicator : ON RUN command LED indicator : ON
• Data LED indicator (frequency) : ON
• Data display : Displays the set value in d001.
• If an error occurs, the error code is displayed on the data display. In this case, refer to "Chapter 5 Maintenance Operations" and make the necessary changes to remedy.
Reference
page
3
Operation
Parameter Initialization Initialize the parameters.
• Set parameter No. b084 to "02", and press the key while holding down the and
keys simultaneously.
Parameter Settings Set the parameters required for a test run.
• Set the motor capacity selection (H003) and the motor pole number selection (H004).
No-load Operation Start the no-load motor via the Digital Operator.
• Display parameter No. F001, set the output frequency using the key and the
key, and press the key. Then, press the key to rotate the motor.
Actual Load Operation Connect the mechanical system and operate via the Digital Operator.
• If there are no difficulties with the no-load operation, connect the mechanical system to the motor and operate via the Digital Operator.
Operation Refer to "Chapter 4 Functions", and set the necessary parameters.
3-4
3
Operation
3-3 Test Run Operation
3-3 Test Run Operation
Power On
Checkpoints Before Turning On the Power
•Make sure that an appropriate power supply voltage is supplied and that the power input terminals (R/L1, S/L2, and T/L3) are wired correctly.
RX- A2: 3-phase 200 to 240 V AC RX- A4: 3-phase 380 to 480 V AC
•Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the motor correctly.
•Make sure that the control circuit terminals and the control device are wired correctly and that all control terminals are turned off.
•Set the motor to no-load status (i.e., not connected to the mechanical system).
Power On
•After checking the above, turn on the power.
Display Status Check
•When the power is turned on normally, the display shows:
[Normal] RUN LED indicator (during RUN) : ON ALARM LED indicator : OFF
POWER LED indicator : ON RUN command LED indicator : ON Data LED indicator (frequency) : ON Data display : Displays the set value in d001
•If an error occurs, refer to "Chapter 5 Maintenance Operations" and make the necessary changes to remedy.
[Fault] RUN LED indicator (during RUN) : ON ALARM LED indicator : ON
POWER LED indicator : ON RUN command LED indicator : ON Data LED indicator (frequency) : ON Data display : An error code, such as "E-01", is displayed. (The display varies depending on the type of error.)
3-5
Parameter Initialization
bk-k-k-
•Initialize the parameters using the following procedure.
•To initialize the parameters, set parameter b084 to "02".
Key sequence Display example Description
3-3 Test Run Operation
k0.0
bk0k0k1
bk0k8k4
0k0
0k2
bk0k8k4
Power On
Press the Mode key once, and then press the Decrement key three times to display "b---".
Press the Mode key. "b001" is displayed.
Use the Increment or Decrement key to display "b084".
Press the Mode key. The set value in "b084" is displayed.
Use the Increment or Decrement key to display "02".
Press the Enter key. The set value is entered and "b084" is displayed.
3
Operation
Press the STOP/RESET key while holding down the Mode and Decrement keys simultaneously. When the display blinks, release the STOP/RESET key first, and then the Mode and Decrement keys.
Displays initialization.
=k.k0k0
(In 1 s) The parameter number is displayed again in approximately 1 s.
dk0k0k1
3-6
3
Operation
3-3 Test Run Operation
No-load Operation
•Start the no-load motor (i.e., not connected to the mechanical system) using the Digital Operator.
Forward/Reverse Rotation via the Digital Operator
Key sequence Display example Description
Press and hold the Mode key for 3 seconds or more to display "d001",
0.0
6.0
•Make sure that no errors have occurred in the Inverter during operation.
•Switch between forward and reverse with the operator rotation direction selection (F004).
Stopping the Motor
•After completing the no-load operation, press the STOP/RESET key. The motor will stop.
and then press again. (Monitors the frequency reference.)
Press the RUN key. The RUN command LED indicator is lit and the monitor value of the frequency reference is displayed. (Factory default: F001 = 6)
Actual Load Operation
•After checking the operation with the motor in the no-load status, connect the mechanical system and operate with an actual load.
Connecting the Mechanical System
•After confirming that the motor has stopped completely, connect the mechanical system.
•Be sure to tighten all the screws when fixing the motor axis and the mechanical system.
Operation via the Digital Operator
•Because a possible error may occur during operation, make sure that the STOP/RESET key on the Digital Operator is easily accessible.
•Use the Digital Operator to operate the Inverter the same way as in no-load operation.
Checking the Operating Status
•After making sure that the operating direction is correct and that the Inverter is operating smoothly at a slow speed, increase the frequency reference.
•By changing the frequency reference or the rotation direction, make sure that there is no vibration or abnormal sound from the motor. Make sure that the output current (output current monitor [d002]) is not excessive.
3-7
3-4 Part Names and Descriptions of the Digital Operator
3-4 Part Names and Descriptions of the
Digital Operator
Part Names and Descriptions
Data display
RUN command LED indicator
Operation keys
3
Operation
8.8.8.8.
Name Function
POWER LED indicator Lit when the power is supplied to the control circuit.
ALARM LED indicator Lit when an Inverter error occurs.
RUN (during RUN) LED indicator
PROGRAM LED indicator
Data display Displays relevant data, such as frequency reference, output
Data LED indicator Lit according to the indication on the data display.
RUN command LED indicator
RUN key Activates the Inverter. Available only when operation via the
STOP/RESET key Decelerates and stops the Inverter. Functions as a reset key if
Mode key Switches between: the monitor mode (d), the basic
Enter key Enters the set value.
Increment key Changes the mode.
Lit when the Inverter is running.
Lit when the set value of each function is indicated on the data display. Blinks during warning (when the set value is incorrect).
current, and set values.
Hz: Frequency V: Voltage A: Current kW: Power %: Ratio
Lit when the RUN command is set to the Digital Operator. (The RUN key on the Digital Operator is available for operation)
Digital Operator is selected. (Check that the RUN command LED indicator is lit.)
an Inverter error occurs.
function mode (F), and the extended function mode (A, b, C, H).
(To change the set value, be sure to press the Enter key.)
Also, increases the set value of each function.
3-8
3
0.00
dk0k0k1
dk0k0k1
0.00
dk0k0k1
Operation
3-4 Part Names and Descriptions of the Digital Operator
Name Function
Decrement key Changes the mode.
Also, decreases the set value of each function.
Display System and Key Sequence of Each Code
• This section explains the examples of typical operation (Basic display, Complete display) and the
extended function mode U as a special operation. This operation can be performed when other display modes are selected.
The display indicates the setting of "b038" when the power is turned on. For details, refer to "Initial Screen Selection (Initial Screen at Power-ON)" (page 4-56). When "b038 = 01" (factory default), for output frequency monitor "d001" is displayed.
Press the Mode key to display .
Note: The Digital Operator display varies depending on the settings of display selection "b037", ini-
tial screen selection "b038", and user parameter automatic setting function selection "b039". For details, refer to "Display Selection" (page 4-53), "Initial Screen Selection (Initial Screen at Power-ON)" (page 4-56), "User Parameter Automatic Setting Function" (page 4-57).
Item Function code Data Description
00 Complete display
01 Individual display of functions
Display selection b037
Initial screen
selection
(Power On)
User parameter
automatic setting
function selection
b038 *
b039
*
02 User setting
03 Data comparison display
04 Basic display (factory default)
00 Screen when the Enter key was pressed last
01 d001 (Output frequency monitor) (factory default)
02 d002 (Output current monitor)
03 d003 (Rotation direction monitor)
04 d007 (Frequency conversion monitor)
05 F001 (Output frequency setting/monitor)
00 Disabled (factory default)
01 Enabled
*Not displayed by factory default.
* To return the display to or
the following procedures.
• Hold down the Mode key for 3 seconds or more to display and
Press the Mode key to display or
* shows the status during stop. Displays the output frequency of the Inverter during
0.00
operation.
3-9
dk0k0k1
*
from any display on the Digital Operator, refer to
0.00
*
0.00
.
*
alternately.
3-4 Part Names and Descriptions of the Digital Operator
Operation Example for Basic Display (factory default: "b037 = 04")
• Displays the limited basic parameters.
Monitor mode : All
Basic function mode : 4 parameters
Extended function mode : 24 parameters
• Other parameters than those mentioned above are not displayed. To display all parameters, select "Complete display 'b037 = 00'".
<Parameters to be Displayed and Arrangement>
3
NO. Display code Item
1 d001 to d104 Monitor display
2 F001 Output frequency setting/monitor
3 F002 Acceleration time 1
4 F003 Deceleration time 1
5 F004 Operator rotation direction selection
6 A001 Frequency reference selection
7 A002 RUN command selection
8 A003 Base frequency
9 A004 Maximum frequency
10 A005 O/OI selection
11 A020 Multi-step speed reference 0
12 A021 Multi-step speed reference 1
13 A022 Multi-step speed reference 2
14 A023 Multi-step speed reference 3
15 A044 V/f characteristics selection
16 A045 Output voltage gain
17 A085 RUN mode selection
18 b001 Retry selection
19 b002 Allowable momentary power interruption time
20 b008 Trip retry selection
21 b011 Trip retry wait time
22 b037 Display selection
23 b083 Carrier frequency
24 b084 Initialization selection
25 b130 Overvoltage protection function during deceleration
26 b131 Overvoltage protection level during deceleration
27 C021 Multi-function output terminal 11 selection
28 C022 Multi-function output terminal 12 selection
29 C036 Relay output (AL2, AL1) contact selection
*
Operation
* If the intended parameter is not displayed, check the setting of display selection "b037".
To display all parameters, set "00" to "b037".
3-10
3-5 Keys
3-5 Keys
Name Description
Switches between the command setting and the data setting, and between the function mode and the extended function mode.
3
With this key, you can always change the display as follows:
[Supplemental Information] To jump to "d001" from any function mode, hold down the Mode key for 3 seconds.
Operation
Mode key
fk0k0k1 fk0k0k1
k5k8.1
or
5k8.0
5k7.9
Note: Always press the Enter key to store any changed data.
Increment key
Changes the set values, parameters, and commands.
Decrement key
RUN key Starts the operation. Forward/Reverse rotation depends on the "F004" setting.
STOP/RESET key Stops the operation. Functions as a reset key if an error occurs.
Enter key
3-11
Enters and stores changed data. Do not press the Enter key if you don't want to store any changes, for example, if you change the data inadvertently.
3-6 Parameter Transition
3-6 Parameter Transition
Operation and sequence of code display
Press the Increment/Decrement key to scroll through codes in the code display and to increase/decrease the number in the data display. Press either key until you see the desired code or data. For fast-forwarding, press and hold either key.
Monitor Mode
Press the Mode key in the code display to display its monitor value.
Operation and sequence of monitor/data display
dk0k0k1
(Monitor display) *1
0.0k0 dk0k0k1
*1 *2
Data setting
Press the Increment/Decrement key to increase/decrease the number.
(Set the desired number.)
Press the Enter key in the data display to fix the data and to return to the code display. Press the Mode key in the data display to return to its code display without changing the data.
dk0k0k2
dk1k0k4
fk0k0k1
fk0k0k4
ak0k0k1
ak0k8k5
bk0k0k1
0.0k0
or
Press the Mode/Enter key in the monitor display to return to its code display.
Note: By factory default, appears at power-on.
Press the Mode key in this status to display .
Function/Extended Function Mode
Press the Mode key in the code display to display its data.
(Data display)
To upper limit
3k0.0k1
3k0.0k0
or
3
Operation
bk1k3k1
ck0k2k1
ck0k2k2
2k9.9k9
To lower limit
*1. The setting displayed varies depending on the parameter. *2. To change the data, be sure to press the Enter key.
3-12
3-6 Parameter Transition
Operation Example for Complete Display (Default: "b037 = 00")
Displays all parameters.
3
Operation
Operation and sequence
of code display
(Monitor/Function modes)
Press the Increment/Decrement key to scroll through codes in the code display and to increase/decrease the number in the data display. Press either key until you see the desired code or data. For fast-forwarding, press and hold either key.
dk0k0k1
dk0k0k2
dk1k0k4
fk0k0k1
fk0k0k4
ak-k-k-
Operation and sequence of
monitor/data display
(Monitor/Function modes)
Monitor
mode
0.0k0
or
Function
mode
3k0.0k1
3k0.0k0
or
2k9.9k9
Operation and sequence of
code display
(Extended function mode)
(Monitor display) *1
*1. The setting displayed varies depending on the parameter. *2. To change the data, be sure to press the Enter key.
(Data display) *1 *2
ak0k0k1
or
ak1k5k3
Operation and sequence of
monitor/data display
(Extended function mode)
Extended
function mode A
or
(Data display)
*1 *2
3
2
1
bk0k0k1
Extended
function
bk-k-k-
or
bk1k3k2
mode B
ck-k-k-
hk-k-k-
pk-k-k-
uk-k-k-
Key sequence and display system of extended function mode U
or
(See the next page.)
ck0k0k1
Extended
function mode C
or
ck1k5k9
hk0k0k1
Extended
function
or
hk0k7k3
mode H
pk0k0k1
Extended
function
mode P
or
pk1k3k1
3-13
3-6 Parameter Transition
Display System and Key Sequence of Extended Function Mode U
The extended function mode U is the parameter to optionally register (or automatically record) other extended function codes, and differs in operation from other extended function modes.
Operation and sequence of
code display
(Monitor/Function modes)
*1. The setting displayed varies depending on the parameter. *2. To change the data, be sure to press the Enter key.
Operation and sequence of
code display
(Extended function mode U)
Operation and sequence of code display
Displaying another mode
from extended function mode U
ak0k0k1
Extended
ak1k5k3
bk0k0k1
Extended
bk1k3k2
ck0k0k1
Extended
ck1k5k9
hk0k0k1
Extended
hk0k7k3
Operation and sequence
of monitor/data display
(Monitor/Function/Extended
function modes)
*1 *2
(Data display)
function mode A
3
2
or
1
function mode B
Press the Enter key to reflect the set value in each parameter. Note that no data can be fixed in parameter "U".
function mode C
function mode H
3
Operation
pk-k-k-
uk-k-k-
dk0k0k1
Pressing the Enter key does not return.
Extended
function mode U
uk0k0k1
uk0k1k2
Press the Enter key to enter the selected code in parameter "U".
pk0k0k1
Extended
function mode P
pk1k3k1
(Factory default)
or
nko
dk0k0k1
Monitor
mode
dk1k0k4
fk0k0k1
Function
mode
fk0k0k4
3-14
3
Press and simultaneously. *1
*2 *3
dk0k0k1
Press (2 times).
("A001" is displayed.)
*3
Operation
3-6 Parameter Transition
Direct Code Specification and Selection
• The codes can be specified or selected by directly entering each digit of the codes or data, as well as by scrolling the codes of the monitor, basic function, and extended function modes.
• Below is an example where monitor mode code "d001" is changed to extended function code "A029".
1. Display the monitor mode code.
("d001" is displayed.)
dk0k0k1
2. Change the extended function mode.
ak0k0k1
• "d" of the 4th digit on the left starts to blink.
• "A" blinks.
• Press the Enter key to fix the blinking digit.
*2
(Continued to the next page)
3-15
Press .
("A" is entered.)
3. Change the 3rd digit of the extended function code.
ak0k0k1
Press .
*2
("0" is entered.)
*2
• "0" of the 3rd digit blinks.
• Press the Enter key to fix "0" of the 3rd digit as you need not change it.
4. Change the 2nd digit of the extended function code.
• "0" of the 2nd digit blinks.
3-6 Parameter Transition
3
Operation
ak0k0k1
Press (2 times).
ak0k2k1
Press .
*2
(Continued to the next page)
("A021" is displayed.)
• "2" of the 2nd digit blinks.
3-16
3-6 Parameter Transition
ak0k2k1
ak0k2k9
*2
Press .
("9" is entered.)
5. Change the 1st digit of the extended function code.
• "1" of the 1st digit blinks.
3
Press or ("A029" is displayed).
(8 times) (2 times)
Operation
6. The extended function code setting is complete.
ak0k2k9
• "9" of the 1st digit blinks.
• The code display "A029" selection is complete.
Note: "A" of the 4th digit on the left starts to blink
again when entering codes which have not been selected for display or codes not on the list.
Refer to
Screen Selection (Initial Screen at Power-ON)" (page 4-56) Setting Function" (page 4-57)
Parameter List" to check the code, and enter again.
"Display Selection" (page 4-53), "Initial
, "User Parameter Automatic
, and "Appendix
7. Press the Mode key to display the data. Use the Increment/Decrement keys to change the data and press the Enter key to set it. The data can be set in the same procedure as 1 to 6.
*1 This operation is available even if code "d001" is not displayed. *2 If pressing the Mode key while each digit is blinking, the display returns the status for the 1-digit
higher entry.
*3 If pressing the Mode key while the 4th digit on the left is blinking, the values under entry are
canceled and the display returns to the status before pressing the Increment and Decrement keys simultaneously in 1.
*4 To change the data, be sure to press the Mode key.
3-17
4
*
4
*3 *
3-7 Parameter List
Monitor Mode (d)
•The default setting displays "d001" at power-on. To select the optional display, change the setting in "b038".
Parameter
No.
d001
d002
d003
d004
Function name Monitor or data range
Output frequency monitor
Output current monitor
Rotation direction monitor
PID feedback value monitor
0.0 to 400.0 Yes Hz 4-1
0.0 to 999.9 1000 to 9999
F: Forward o: Stop r: Reverse
0.00 to 99.99
100.0 to 999.9
1000. to 9999. 1000 to 9999 (10000 to 99990) 100 to 999 (100000 to 999000) (Enabled when the PID function is selected)
3-7 Parameter List
Default setting
Changes
during
operation
 A4-1
4-1
4-1
Unit Page
3
Operation
d005
d006
d007
d008
d009
d010
d012
d013
d014 Input power monitor 0.0 to 999.9 kW 4-4
d015
Multi-function input monitor
Multi-function output monitor
Output frequency monitor (after conversion)
Actual frequency monitor
Torque reference monitor
Torque bias monitor
Output torque monitor
Output voltage monitor
Integrated power monitor
FW
87654321
AL2 15 14 13 12 11
0.00 to 99.99
100.0 to 999.9
1000. to 9999. 1000 to 3996 (10000 to 39960) (Output frequency × Conversion factor of b086)
-400. to -100.
-99.9 to 0.00 to 99.99
100.0 to 400.0
-200. to +200. %4-3
-200. to +200. %4-3
-200. to +200. %4-3
0. to 600.  V4-3
0.0 to 999.9
1000. to 9999. 1000 to 9999 (10000 to 99990) 100 to 999 (100000 to 999000)
(Example) Terminals FW, 7, 2, 1 : ON
Terminals 8, 6, 5, 4, 3: OFF
(Example) Terminals 12, 11 : ON
Terminals AL2, 15, 14, 13: OFF
4-2
4-2
Yes 4-2
Hz 4-3

4-4
3-18
3-7 Parameter List
3
Operation
Parameter
No.
d016 Total RUN time
d017
d018
d019
d022
d023 Not used 
d024 Not used 
d025 Not used 
d026 Not used 
d027 Not used 
d028
d029
d030
d080
d081
d082
d083
d084
d085
d086
d090 Warning monitor Warning code 4-6
d102 DC voltage monitor 0.0 to 999.9  V4-6
d103
d104
Function name Monitor or data range
0. to 9999. 1000 to 9999 (10000 to 99990) 100 to 999 (100000 to 999000)
Power ON time monitor
Fin temperature monitor
Motor temperature monitor
Life assessment monitor
Pulse counter monitor
Position command monitor
Current position monitor
Fault frequency monitor
Fault monitor 1 (Latest)
Fault monitor 2
Fault monitor 3
Fault monitor 4
Fault monitor 5
Fault monitor 6
Regenerative braking load rate monitor
Electronic thermal monitor
0. to 9999. 1000 to 9999 (10000 to 99990) 100 to 999 (100000 to 999000)
-020. to 200.0 C4-4
-020. to 200.0 C4-5
ON
1: Capacitor on the main circuit board
OFF
2
0 to 2147483647 (Displays MSB 4 digits) 4-5
-1073741823 to 1073741823 (Displays MSB 4 digits including "-")
-1073741823 to 1073741823 (Displays MSB 4 digits including "-")
0. to 9999. 1000 to 6553 (10000 to 65530)
Error code (condition of occurrence)
Output frequency [Hz] Output current [A]Internal DC voltage [V] RUN time [h]ON time [h]
0.0 to 100.0 %4-6
0.0 to 100.0 %4-7
2: Cooling fan rotation speed reduced
1
Default
setting
Changes
during
operation
 h4-4
 h4-4
4-5
4-5

Time 4-5

Unit Page
4-5
4-132
4-6
4-6
4-6
4-6
4-6
4-6
3-19
Basic Function Mode (F)
3-7 Parameter List
Parameter
No.
F001
F002 Acceleration time 1
F202
F302
F003 Deceleration time 1
F203
F303
F004
Function name Monitor or data range
Output frequency setting/monitor
* 2nd acceleration time 1
* 3rd acceleration time 1
* 2nd deceleration time 1
* 3rd deceleration time 1
Operator rotation direction selection
0.0/Starting frequency to 1st/2nd/3rd max. frequency
0.0 to 100.0 (PID control enabled)
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
00: (Forward) 01: (Reverse)
Default
setting
30.00 Yes s 4-8
30.00 Yes s 4-8
30.00 Yes s 4-8
30.00 Yes s 4-8
30.00 Yes s 4-8
30.00 Yes s 4-8
Changes
during
operation
Yes Hz 4-8
00 No 4-9
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-20
3-7 Parameter List
Extended Function Mode
3
Operation
Parameter
No.
A001
A002
Basic setting
A003 Base frequency 30. to Maximum frequency [A004] 50.
A203 * 2nd base frequency 30. to 2nd maximum frequency [A204] 50.
A303 * 3rd base frequency 30. to 3rd maximum frequency [A304] 50.
A004 Maximum frequency 30. to 400. 50.
A204
A304
Function name Monitor or data range
00: Digital Operator (FREQ adjuster)
(Enabled when 3G3AX-OP01 is used.) 01: Terminal 02: Digital Operator (F001)
Frequency reference selection
RUN command selection
* 2nd maximum frequency
* 3rd maximum frequency
03: ModBus communication 04: Option 1 05: Option 2 06: Pulse train frequency 07: Not used 10: Operation function result
01: Terminal 02: Digital Operator (F001) 03: ModBus communication 04: Option 1 05: Option 2
30. to 400. 50.
30. to 400. 50.
Default setting
Changes
during
operation
02 No
02 No 4-11
No Hz
No Hz 4-12
Unit Page
4-10
4-138
4-11
4-110
4-11
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-21
3-7 Parameter List
Parameter
No.
A005 O/OI selection
A006 O2 selection
A011 O start frequency
Analog input, Others
A012 O end frequency
A013 O start ratio 0. to O end ratio 0. No %
A014 O end ratio O start ratio to 100. 100. No %
A015 O start selection
A016 O, O2, OI sampling
A017 Not used
Function name Monitor or data range
00: Switches between O/OI via terminal AT 01: Switches between O/O2 via terminal AT 02: Switches between O/FREQ adjuster via
terminal AT (Enabled only when 3G3AX-OP01 is used)
03: Switches between OI/FREQ adjuster via
terminal AT (Enabled only when 3G3AX-OP01 is used)
04: Switches between O2/FREQ adjuster via
terminal AT (Enabled only when 3G3AX-OP01 is used)
00: O2 only 01: O/OI auxiliary frequency reference
(not reversible)
02: O/OI auxiliary frequency reference
(reversible)
03: O2 disabled
0.00 to 99.99
100.0 to 400.0
0.00 to 99.99
100.0 to 400.0
00: External start frequency
(A011 set value)
01: 0 Hz
1. to 30.
31. (with 500 ms filter ± 0.1 Hz hysteresis)
Use "00". * Do not change.
Default setting
Changes
during
operation
00 No 4-12
03 No
0.00 No Hz
0.00 No Hz
01 No
31. No 4-15
00 No 
Unit Page
4-12
4-14
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-22
3-7 Parameter List
3
Operation
Parameter
No.
A019
A020
A220
A320
A021
A022
A023
A024
A025
A026
A027
Multi-step speed, Jogging
A028
A029
A030
A031
A032
A033
A034
A035
Function name Monitor or data range
Multi-step speed selection
Multi-step speed reference 0
* 2nd multi-step speed reference 0
* 3rd multi-step speed reference 0
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
Multi-step speed reference 4
Multi-step speed reference 5
Multi-step speed reference 6
Multi-step speed reference 7
Multi-step speed reference 8
Multi-step speed reference 9
Multi-step speed reference 10
Multi-step speed reference 11
Multi-step speed reference 12
Multi-step speed reference 13
Multi-step speed reference 14
Multi-step speed reference 15
00: Binary: 16-step selection with 4 terminals 01: Bit: 8-step selection with 7 terminals
0.0/Starting frequency to Max. frequency 6.00 Yes Hz
0.0/Starting frequency to 2nd Max. frequency 6.00 Yes Hz
0.0/Starting frequency to 3rd Max. frequency 6.00 Yes Hz
0.0/Starting frequency to Max. frequency
Default setting
Changes
during
operation
00 No 4-16
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Yes Hz 4-16
Unit Page
4-16
4-8
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-23
3-7 Parameter List
Parameter
No.
A038 Jogging frequency 0.00/Starting frequency to 9.99 6.00 Yes Hz
A039
Multi-step speed, Jogging
A041
A241
A042
A342
A043
A343
V/f characteristics
A044
A244
A344
A045 Output voltage gain 20. to 100. 100. Yes % 4-24
Function name Monitor or data range
00: Free running on jogging stop/
Disabled in operation
01: Deceleration stop on jogging stop/
Disabled in operation
02: DC injection braking on jogging stop/ Jogging stop selection
Torque boost selection
* 2nd torque boost selection
Manual torque boost voltage
* 2nd manual torque boost voltage
* 3rd manual torque boost voltage
Manual torque boost frequency
* 2nd manual torque boost frequency
* 3rd manual torque boost frequency
V/f characteristics selection
* 2nd V/f characteristics selection
* 3rd V/f characteristics selection
Disabled in operation
03: Free running on jogging stop/
Enabled in operation
04: Deceleration stop on jogging stop/
Enabled in operation
05: DC injection braking on jogging stop/
Enabled in operation
00: Manual torque boost
01: Automatic torque boost
0.0 to 20.0
0.0 to 50.0
00: Constant torque characteristics (VC)
01: Special reduced torque characteristics
(special VP) 02: Free V/f characteristics 03: Sensorless vector control (SLV) 04: 0-Hz sensorless vector control 05: Sensor vector control (V2)
00: Constant torque characteristics (VC) 01: Special reduced torque characteristics
(special VP) 02: Free V/f characteristics 03: Sensorless vector control (SLV) 04: 0-Hz sensorless vector control
00: Constant torque characteristics (VC) 01: Special reduced torque characteristics
(special VP)
Default setting
Changes
during
operation
00 No
00
No
00
1.0
1.0
1.0
5.0
5.0
5.0
00
00
00
Yes %A242
Yes %A243
No 4-21
Unit Page
4-18
4-19
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-24
3-7 Parameter List
3
Operation
Parameter
No.
A046
A246
A047
V/f characteristics
A247
A051
A052
A053
DC injection braking
A054
A055
A056
A057
DC injection braking
A058
A059
A061 Frequency upper limit 0.00/Frequency lower limit to Max. frequency 0.00
A261
A062 Frequency lower limit
A262
Upper/Lower limiter, Jump
Function name Monitor or data range
Automatic torque boost voltage compensation gain
* 2nd automatic torque boost voltage compensation gain
Automatic torque boost slip compensation gain
* 2nd automatic torque boost slip compensation gain
DC injection braking selection
DC injection braking frequency
DC injection braking delay time
DC injection braking power
DC injection braking time
DC injection braking method selection
Startup DC injection braking power
Startup DC injection braking time
DC injection braking carrier frequency
* 2nd frequency upper limit
* 2nd frequency lower limit
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
00: Disabled 01: Enabled 02: Frequency control [A052 set value]
0.00 to 99.99
100.0 to 400.0
0.0 to 5.0 0.0 No s
0. to 100. (0.4 to 55 kW) 50. No %
0. to 80. (75 to 132 kW) 40. No %
0.0 to 60.0 0.5 No s
00: Edge operation 01: Level operation
0. to 100. (0.4 to 55 kW)
0. to 80. (75 to 132 kW)
0.0 to 60.0 0.0 No s
0.5 to 15.0 (0.4 to 55 kW) 5.0 No kHz
0.5 to 10.0 (75 to 132 kW) 3.0 No kHz
0.00/2nd frequency lower limit to 2nd Max. frequency
0.00/Starting frequency to Frequency upper limit
0.00/Starting frequency to 2nd frequency upper limit
Default setting
Changes
during
operation
Yes
Yes
00 No
0.50 No Hz
01 No
0. No %
No Hz
0.00
0.00
No Hz
0.00
Unit Page
4-19
4-24
4-110
4-24
4-24
4-28
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-25
3-7 Parameter List
Parameter
No.
A063 Jump frequency 1
A064
A065 Jump frequency 2 0.00
A066
A067 Jump frequency 3 0.00
A068
Upper/Lower limit, Jump
A069
A070
A071 PID selection
A072 PID P gain 0.2 to 5.0 1.0 Yes
A073 PID I gain
A074 PID D gain
A075 PID scale 0.01 to 99.99 1.00 No Time
PID control
A076
A077 Reverse PID function
A078
A079
PID control
A081 AVR selection
AVR
A082
Function name Monitor or data range
Jump frequency width 1
Jump frequency width 2
Jump frequency width 3
Acceleration stop frequency
Acceleration stop time
PID feedback selection
PID output limit function
PID feedforward selection
AVR voltage selection
Jump frequency: 0.0 to 400.0 Jump frequency width: 0.0 to 10.0
0.00 to 99.99
100.0 to 400.0
0.0 to 60.0 0.0 No s
00: Disabled 01: Enabled 02: Reverse output enabled
0.0 to 999.9
1000. to 3600.
0.00 to 99.99
100.0
00: OI 01: O 02: RS485 communication 03: Pulse train frequency 10: Operation function output
00: OFF (Deviation = Target value -
Feedback value) 01: ON (Deviation = Feedback value - Target
value)
0.0 to 100.0 0.0 No %
00: Disabled 01: O 02: OI 03: O2
00: Always ON 01: Always OFF 02: OFF during deceleration
200-V class: 200/215/220/230/240 400-V class: 380/400/415/440/460/480
Default setting
Changes
during
operation
0.00
0.50
0.50
0.50
0.00 No Hz
00 No
1.0 Yes s
0.00 Yes s
00 No
00 No
00 No 4-31
02 No
200/
400
No Hz
No V
Unit Page
4-30
4-31
4-35
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-26
3-7 Parameter List
3
Operation
Parameter
No.
A085 RUN mode selection
A086
A092 Acceleration time 2
A292
A392
A093 Deceleration time 2 15.00
A293
A393
A094
A294
A095
RUN mode, Acceleration/Deceleration functions
A295
A096
A296
A097
A098
Function name Monitor or data range
00: Normal operation 01: Energy-saving operation 02: Automatic operation
Energy-saving response/accuracy adjustment
* 2nd acceleration time 2
* 3rd acceleration time 2
* 2nd deceleration time 2
* 3rd deceleration time 2
2-step acceleration/ deceleration selection
* 2nd 2-step acceleration/ deceleration selection
2-step acceleration frequency
* 2nd 2-step acceleration frequency
2-step deceleration frequency
* 2nd 2-step deceleration frequency
Acceleration pattern selection
Deceleration pattern selection
0.0 to 100.0 50.0 Yes
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
00: Switched via multi-function input 09 (2CH) 01: Switched by setting 02: Enabled only when switching forward/
reverse
0.00 to 99.99
100.0 to 400.0
00: Line 01: S-shape curve 02: U-shape curve 03: Inverted U-shape curve 04: EL-S-shape curve
Default setting
15.00
15.00
15.00
15.00
15.00
Changes
during
operation
00 No
Yes s
00
No
00
0.00
No Hz
0.00
0.00
No Hz
0.00
00 No
00 No
Unit Page
4-36
4-37
4-38
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-27
3-7 Parameter List
Parameter
No.
A101 OI start frequency
A102 OI end frequency 0.00 No Hz
A103 OI start ratio 0. to OI end ratio 20. No %
A104 OI end ratio OI start ratio to 100. 100. No %
A105 OI start selection
A111 O2 start frequency -400. to -100.
A112 O2 end frequency 0.00 No Hz
External frequency adjustment
A113 O2 start ratio -100. to O2 end ratio -100. No %
A114 O2 end ratio O2 start ratio to 100. 100. No %
External frequency adjustment
A131
Function name Monitor or data range
0.00 to 99.99
100.0 to 400.0
00: Use OI start frequency [A101] 01: 0 Hz
-99.9 to 0.00 to 99.99
100.0 to 400.0
Acceleration curve parameter
Default setting
Changes
during
operation
0.00 No Hz
00 No
0.00 No Hz
02 No
Unit Page
4-14
3
Operation
4-15
A132
Acceleration/Deceleration
A141
A142
A143 Operator selection
Operation frequency
A145
A146
Deceleration curve parameter
Operation frequency input A setting
Operation frequency input B setting
Frequency addition amount
Frequency addition direction
01 (small curve) to 10 (large curve)
00: Digital Operator (F001) 01: Digital Operator (FREQ adjuster)
(Enabled when 3G3AX-OP01 is used.) 02: Input O 03: Input OI 04: RS485 communication 05: Option 1 06: Option 2 07: Pulse train frequency
00: Addition (A + B) 01: Subtraction (A - B) 02: Multiplication (A × B)
0.00 to 99.99
100.0 to 400.0
00: Add A145 value to output frequency 01: Subtract A145 value from output
frequency
02 No
02 No
03 No
00 No
0.00 No Hz
00 No
4-38
4-41
4-41
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-28
3-7 Parameter List
3
Operation
Parameter
No.
A150
A151
A152
A153
Acceleration/Deceleration
b001 Retry selection
b002
b003 Retry wait time 0.3 to 100.0 1.0 No s 4-85
b004
Momentary power interruption/Trip restart
b005
b006
b007
b008 Trip retry selection
b009
b010
Momentary power interruption/Trip restart
b011 Trip retry wait time 0.3 to 100.0 1.0 No s
Function name Monitor or data range
EL-S-curve ratio 1 during acceleration
EL-S-curve ratio 2 during acceleration
EL-S-curve ratio 1 during deceleration
EL-S-curve ratio 2 during deceleration
Allowable momentary power interruption time
Momentary power interruption/ undervoltage trip during stop selection
Momentary power interruption retry time selection
Input phase loss protection selection
Frequency matching lower limit frequency setting
Undervoltage retry time selection
Overvoltage/ overcurrent retry time selection
0. to 50. 25. No %
0. to 50. 25. No %
0. to 50. 25. No %
0. to 50. 25. No %
00: Alarm 01: 0 Hz start 02: Frequency matching start 03: Trip after frequency matching
deceleration stop
04: Active Frequency Matching restart
0.3 to 25.0 1.0 No s
00: Disabled 01: Enabled 02: Disabled during stop and deceleration
stop
00: 16 times 01: No limit
00: Disabled 01: Enabled
0.00 to 99.99
100.0 to 400.0
00: Trip 01: 0 Hz start 02: Frequency matching start 03: Trip after frequency matching
deceleration stop
04: Active Frequency Matching restart
00: 16 times 01: No limit
1 to 3 3 No Time
Default setting
Changes
during
operation
00 No
00 No
00 No
00 No 4-46
0.00 No Hz
00 No
00 No
Unit Page
4-39
4-42
4-42
4-42 4-68 4-85
4-42
4-42
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-29
3-7 Parameter List
Parameter
No.
b012
b212
b312
b013
b213
b313
b015
Electronic Thermal
b017
b019
b016
b020
Function name Monitor or data range
Electronic thermal level
* 2nd electronic thermal level
* 3rd electronic thermal level
Electronic thermal characteristics selection
* 2nd electronic thermal characteristics selection
* 3rd electronic thermal characteristics selection
Free setting, electronic thermal frequency 1
Free setting, electronic thermal frequency 2
Free setting, electronic thermal frequency 3
Free setting, electronic thermal current 1
Free setting, electronic thermal current 2
Free setting, electronic thermal current 3
0.20 × Rated current to 1.00 × Rated current
00: Reduced torque characteristics 01: Constant torque characteristics 02: Free setting
0. to 400. 0. No Hz
0.0 to Rated current 0.0 No Ab018
Default setting
Rated
current
Changes
during
operation
No A
00 No
Unit Page
4-46
4-46
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-30
3-7 Parameter List
3
Operation
Parameter
No.
b021
b022 Overload limit level
b023
b024
b025 Overload limit level 2
b026
Overload limit, Overcurrent Protection
b027
b028
b030
b031 Soft lock selection
Lock
Function name Monitor or data range
Overload limit selection
Overload limit parameter
Overload limit selection 2
Overload limit parameter 2
Overcurrent suppression function
Active Frequency Matching restart level
Active Frequency Matching restart parameter
Starting frequency at Active Frequency Matching restart
Default setting
00: Disabled 01: Enabled in acceleration/constant speed
operation 02: Enabled in constant speed operation 03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current (0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current (75 to 132 kW)
0.10 to 30.00 1.00 No s
00: Disabled 01: Enabled in acceleration/constant speed
operation 02: Enabled in constant speed operation 03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current (0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current (75 to 132 kW)
0.10 to 30.00 1.00 No s
00: Disabled 01: Enabled
0.20 × Rated current to 2.00 × Rated current (0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current (75 to 132 kW)
0.10 to 30.00 0.50 No s
00: Frequency at interruption 01: Max. frequency 02: Set frequency
00: Data other than b031 cannot be changed
when terminal SFT is ON. 01: Data other than b031 and the specified
frequency parameter cannot be changed
when terminal SFT is ON. 02: Data other than b031 cannot be changed. 03: Data other than b031 and the specified
frequency parameter cannot be changed. 10: Data other than parameters changeable
during operation cannot be changed.
Rated
current
Rated
current
Rated
current
Changes
during
operation
01 No
1.50 ×
No A
01 No
1.50 ×
No A
01 No 4-51
No A
00 No
01 No 4-51
Unit Page
4-49
4-43 4-69b029
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-31
3-7 Parameter List
Parameter
No.
b034
b035
Others
b036
b037 Display selection
b038
Others
b039
b040 Torque limit selection
b041
b042
Torque limit
b043
b044
b045
Function name Monitor or data range
RUN time/Power ON time setting
Rotation direction limit selection
Reduced voltage startup selection
Initial screen selection
User parameter automatic setting function selection
Torque limit 1 (Four-quadrant mode forward power running)
Torque limit 2 (Four-quadrant mode reverse regeneration)
Torque limit 3 (Four-quadrant mode reverse power running)
Torque limit 4 (Four-quadrant mode forward regeneration)
Torque LADSTOP selection
Default setting
0. to 9999. (0 to 99990) 1000 to 6553 (10000 to 655300)
00: Forward and Reverse are enabled 01: Only Forward is enabled. 02: Only Reverse is enabled.
0 (Reduced voltage startup time: small) to 255 (Reduced voltage startup time: large)
00: Complete display 01: Individual display of functions 02: User setting 03: Data comparison display 04: Basic display
00: Screen when the Enter key was pressed
last 01: d001 02: d002 03: d003 04: d007 05: F001
00: Disabled 01: Enabled
00: Four-quadrant separate setting 01: Terminal switch 02: Analog input 03: Option 1 04: Option 2
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW) no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW) no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW) no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW) no (Torque limit disabled)
00: Disabled 01: Enabled
Changes
during
operation
0. No h 4-52
00 No 4-52
6No 4-53
04 No 4-53
01 No 4-56
00 No 4-57
00 No -
150. No %
150. No %
150. No %
150. No %
00 No 4-59
Unit Page
4-57 4-59
4-57 4-59
4-57 4-59
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-32
3-7 Parameter List
3
Operation
Parameter
No.
b046
b050
b051
b052
b053
Others
b054
b055
b056
Function name Monitor or data range
Reverse rotation prevention selection
Selection of non-stop function at momentary power interruption
Starting voltage of non-stop function at momentary power interruption
Stop deceleration level of non-stop function at momentary power interruption
Deceleration time of non-stop function at momentary power interruption
Deceleration starting width of non-stop function at momentary power interruption
Proportional gain setting of non-stop function at momentary power interruption
Integral time setting of non-stop function at momentary power interruption
00: Disabled 01: Enabled
00: Disabled 01: Enabled (deceleration stop) 02: Enabled (without recovery) 03: Enabled (with recovery)
0.0 to 999.9
1000.
0.0 to 999.9
1000.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.00 to 10.00 0.00 No Hz
0.00 to 2.55 0.20 Yes
0.000 to 9.999/10.00 to 65.53
Default setting
0.100
Changes
during
operation
00 No 4-59
00 No
220/
440
360/
720
1.00 No s
No V
No V
Yes s 4-60
Unit Page
4-60
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-33
3-7 Parameter List
Parameter
No.
b060
b061
b062
b063
b064
b065
Others
b066
b067
b068
b070
b071
b072
Function name Monitor or data range
Set an upper limit level.
Window comparator O upper limit level
Window comparator O lower limit level
Window comparator O hysteresis width
Window comparator OI upper limit level
Window comparator OI lower limit level
Window comparator OI hysteresis width
Window comparator O2 upper limit level
Window comparator O2 lower limit level
Window comparator O2 hysteresis width
Analog operation level at O disconnection
Analog operation level at OI disconnection
Analog operation level at O2 disconnection
Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2
Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2
Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2
Set an upper limit level. Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2
Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2
Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2
Set an upper limit level. Setting range: -100 to 100 Lower limit: Lower limit level + Hysteresis width × 2
Set a lower limit level. Setting range: -100 to 100 Upper limit: Upper limit level - Hysteresis width × 2
Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2
0. to 100./no (ignored) no No
0. to 100./no (ignored) no No
-100. to 100./no (ignored) no No
Default setting
Changes
during
operation
100. Yes %
0. Yes %
0. Yes %
100. Yes %
0. Yes %
0. Yes %
100. Yes %
-100. Yes %
0. Yes %
Unit Page
4-63
4-63
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-34
3-7 Parameter List
3
Operation
Parameter
No.
b078
b079
b082 Starting frequency 0.10 to 9.99 0.50 No Hz 4-65
b083 Carrier frequency
b084 Initialization selection
b085
b086
b087 STOP key selection
b088
Others
b089
b090
b091 Stop selection
b092 Cooling fan control
b096
b098 Thermistor selection
b099 Thermistor error level 0. to 9999.
Function name Monitor or data range
Integrated power clear
Integrated power display gain
Initialization parameter selection00*Do not change.
Frequency conversion coefficient
Free-run stop selection
Automatic carrier reduction
Usage rate of regenerative braking function
Regenerative braking function operation selection
Regenerative braking function ON level
Cleared with the Enter key after changing to 01
1. to 1000. 1. No
0.5 to 15.0 (0.4 to 55 kW) *Derating enabled
0.5 to 10.0 (75 to 132 kW) *Derating enabled
00: Clears the trip monitor 01: Initializes data 02: Clears the trip monitor and initializes data
0.1 to 99.0 1.0 Yes 4-2
00: Enabled 01: Disabled 02: Disabled only during stop
00: 0 Hz start 01: Frequency matching start 02: Active Frequency Matching restart
00: Disabled 01: Enabled
0.0 to 100.0 0.0 No % 4-72
00: Deceleration Stop 01: Free-run stop
00: Always ON 01: ON during RUN
00: Disabled 01: Enabled (Disabled during stop) 02: Enabled (Enabled during stop)
330 to 380 660 to 760
00: Disabled 01: PTC enabled 02: NTC enabled
Default setting
3000.
Changes
during
operation
00 Yes
5.0 No kHz
3.0 No kHz
00 No
00 No
00 No 4-68
00 No 4-69
00 No 4-71
00 No 4-68
01 No
00 No
360/
720
00 No
No V
No
Unit Page
4-65
4-118
4-66
4-72b095
4-73
4-4
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-35
3-7 Parameter List
Parameter
No.
b100 Free V/f frequency 1 0. to Free V/f frequency 2 0. No Hz
b101 Free V/f voltage 1 0.0 to 800.0 0.0 No V
b102 Free V/f frequency 2 0. to Free V/f frequency 3 0. No Hz
b103 Free V/f voltage 2 0.0 to 800.0 0.0 No V
b104 Free V/f frequency 3 0. to Free V/f frequency 4 0. No Hz
b105 Free V/f voltage 3 0.0 to 800.0 0.0 No V
b106 Free V/f frequency 4 0. to Free V/f frequency 5 0. No Hz
b107 Free V/f voltage 4 0.0 to 800.0 0.0 No V
b108 Free V/f frequency 5 0. to Free V/f frequency 6 0. No Hz
Vf free setting
b109 Free V/f voltage 5 0.0 to 800.0 0.0 No V
b110 Free V/f frequency 6 0. to Free V/f frequency 7 0. No Hz
b111 Free V/f voltage 6 0.0 to 800.0 0.0 No V
b112 Free V/f frequency 7 0. to 400. 0. No Hz
b113 Free V/f voltage 7 0.0 to 800.0 0.0 No V
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Function name Monitor or data range
Default setting
Changes
during
operation
Unit Page
4-22
3
Operation
3-36
3-7 Parameter List
3
Operation
Parameter
No.
b120
b121
b122
b123
b124
b125
b126 Brake release current
b127
Others
b130
b131
b132
b133
b134
Function name Monitor or data range
Brake control selection
Brake wait time for release
Brake wait time for acceleration
Brake wait time for stopping
Brake wait time for confirmation
Brake release frequency
Brake input frequency
Overvoltage protection function selection during deceleration
Overvoltage protection level during deceleration
Overvoltage protection parameter
Overvoltage protection proportional gain setting
Overvoltage protection integral time setting
Default setting
00: Disabled 01: Enabled
0.00 to 5.00 0.00 No s
0.00 to 5.00 0.00 No s
0.00 to 5.00 0.00 No s
0.00 to 5.00 0.00 No s
0.00 to 99.99
100.0 to 400.0
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
0.00 to 99.99
100.0 to 400.0
00: Disabled 01: DC voltage kept constant 02: Acceleration enabled
200-V class: 330 to 390 400-V class: 660 to 780
0.10 to 30.00 1.00 No s
0.00 to 2.55 0.50 Yes
0.000 to 9.999
10.000 to 65.53
Rated
current
0.060 Yes s
Changes
during
operation
00 No
0.00 No Hz
No
0.00 No Hz
00 No
380/
760
No V
Unit Page
4-75
4-76
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-37
3-7 Parameter List
01
12
18
02
03
04
05
06
Changes
during
operation
*1
*1
No 4-77
Unit Page
Parameter
No.
C001
C002
C003
C004
C005
Multi-function input terminals
C006
C007
C008
*1.
C001 and C003 are forcibly rewritten into 18 (RS) and 64 (EMR), respectively, when the emergency shutoff
function is enabled (SW1 = ON).
Function name Monitor or data range
01: RV (reverse) 02: CF1 (multi-step speed setting binary 1)
Multi-function input 1 selection
*1
Multi-function input 2 selection
Multi-function input 3 selection
*1
Multi-function input 4 selection
Multi-function input 5 selection
Multi-function input 6 selection
Multi-function input 7 selection
Multi-function input 8 selection
03: CF2 (multi-step speed setting binary 2) 04: CF3 (multi-step speed setting binary 3) 05: CF4 (multi-step speed setting binary 4) 06: JG (jogging) 07: DB (external DC injection braking) 08: SET (2nd control) 09: 2CH (2-step acceleration/deceleration) 11: FRS (free-run stop) 12: EXT (external trip) 13: USP (USP function) 14: CS (commercial switch) 15: SFT (soft lock) 16: AT (analog input switching) 17: SET3 (3rd control) 18: RS (reset) 20: STA (3-wire start) 21: STP (3-wire stop) 22: F/R (3-wire forward/reverse) 23: PID (PID enabled/disabled) 24: PIDC (PID integral reset) 26: CAS (control gain switching) 27: UP (UP/DWN function accelerated) 28: DWN (UP/DWN function decelerated) 29: UDC (UP/DWN function data clear) 31: OPE (forced operator) 32: SF1 (multi-step speed setting bit 1) 33: SF2 (multi-step speed setting bit 2) 34: SF3 (multi-step speed setting bit 3) 35: SF4 (multi-step speed setting bit 4) 36: SF5 (multi-step speed setting bit 5) 37: SF6 (multi-step speed setting bit 6) 38: SF7 (multi-step speed setting bit 7) 39: OLR (overload limit switching) 40: TL (torque limit enabled) 41: TRQ1 (torque limit switching 1) 42: TRQ2 (torque limit switching 2) 43: PPI (P/PI switching) 44: BOK (Brake confirmation) 45: ORT (orientation) 46: LAC (LAD cancel) 47: PCLR (position deviation clear) 48: STAT ( 50: ADD (frequency addition) 51: F-TM (forced terminal block) 52: ATR (torque command input permission) 53: KHC (integrated power clear) 54: SON (servo ON) 55: FOC (preliminary excitation) 56: Not used 57: Not used 58: Not used 59: Not used 60: Not used 61: Not used 62: Not used 63: Not used 65: AHD (analog command held) 66: CP1 (position command selection 1) 67: CP2 (position command selection 2) 68: CP3 (position command selection 3) 69: ORL (zero return limit signal) 70: ORG (zero return startup signal) 71: FOT (forward driving stop) 72: ROT (reverse driving stop) 73: SPD (speed/position switching) 74: PCNT (pulse counter) 75: PCC (pulse counter clear) no: NO (no allocation)
pulse train position command input permission
(64 cannot be set optionally.)
Default setting
)
When SW1 is turned ON once and then OFF, C003 has no allocations ("no").
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-38
3-7 Parameter List
3
Operation
00
00
00
00
00
00
00
00
00
Changes
during
operation
No 4-79
Unit Page
Parameter
No.
C011
C012
C013
C014
C015
C016
Multi-function input terminals
C017
C018
C019
Function name Monitor or data range
Multi-function input 1 operation selection
Multi-function input 2 operation selection
Multi-function input 3 operation selection
Multi-function input 4 operation selection
Multi-function input 5 operation selection
Multi-function input 6 operation selection
Multi-function input 7 operation selection
Multi-function input 8 operation selection
FW terminal operation selection
00: NO 01: NC
Default setting
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-39
3-7 Parameter List
00
01
03
07
40
05
Changes
during
Unit Page
operation
No 4-93
Parameter
No.
C021
C022
C023
C024
Multi-function output terminal
C025
C026
Function name Monitor or data range
00: RUN (signal during RUN) 01: FA1 (constant speed arrival signal)
Multi-function output terminal 11 selection
Multi-function output terminal 12 selection
Multi-function output terminal 13 selection
Multi-function output terminal 14 selection
Multi-function output terminal 15 selection
Relay output (AL2, AL1) function selection
02: FA2 (over set frequency arrival signal) 03: OL (overload warning) 04: OD (excessive PID deviation) 05: AL (alarm output) 06: FA3 (set-frequency-only arrival signal) 07: OTQ (overtorque)
signal during momentary power interruption
08: IP ( 09: UV (signal during undervoltage) 10: TRQ (torque limit) 11: RNT (RUN time over) 12: ONT (Power ON time over) 13: THM (thermal warning) 19: BRK (brake release) 20: BER (brake error) 21: ZS (0 Hz signal) 22: DSE (excessive speed deviation) 23: POK (position ready) 24: FA4 (set frequency exceeded 2) 25: FA5 (set frequency only 2) 26: OL2 (overload warning 2) 27: ODc (analog O disconnection detection) 28: OIDc (analog OI disconnection detection) 29: O2Dc ( 31: FBV (PID FB status output) 32: NDc (network error) 33: LOG1 (logic operation output 1) 34: LOG2 (logic operation output 2) 35: LOG3 (logic operation output 3) 36: LOG4 (logic operation output 4) 37: LOG5 (logic operation output 5) 38: LOG6 (logic operation output 6) 39: WAC (capacitor life warning signal) 40: WAF (cooling fan life warning signal) 41: FR (starting contact signal) 42: OHF (fin overheat warning) 43: LOC (light load detection signal) 44: Not used 45: Not used 46: Not used 47: Not used 48: Not used 49: Not used 50: IRDY (operation ready signal) 51: FWR (forward run signal) 52: RVR (reverse run signal) 53: MJA (fatal fault signal) 54: WCO (window comparator O) 55: WCOI (window comparator OI) 56: WCO2 (window comparator O2) (When C062 is used to select the alarm code output, the multi-function output terminals 11 to 13, or 11 to 14 are forcibly changed to AC0 to AC2 or AC0 to AC3 [Acn 'Alarm code output'], respectively.)
analog O2 disconnection detection
Default setting
)
)
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-40
3-7 Parameter List
3
Operation
Parameter
No.
C027 FM selection
C028 AM selection
Analog monitor
C029 AMI selection
Digital current
C030
monitor reference value
Function name Monitor or data range
00: Output frequency 01: Output current 02: Output torque 03: Digital output frequency 04: Output voltage 05: Input voltage 06: Thermal load rate 07: LAD frequency 08: Digital current monitor 09: Motor temperature 10: Fin temperature 12: Not used
00: Output frequency 01: Output current 02: Output torque 04: Output voltage 05: Input voltage 06: Thermal load rate 07: LAD frequency 09: Motor temperature 10: Fin temperature 11: Output torque <signed> 13: Not used
00: Output frequency 01: Output current 02: Output torque 04: Output voltage 05: Input voltage 06: Thermal load rate 07: LAD frequency 09: Motor temperature 10: Fin temperature 14: Not used
0.20 × Rated current to 2.00 × Rated current (Current value at the digital current monitor output 1440 Hz)
Default setting
Rated
current
Changes
during
operation
00 No
00 No
00 No
Yes A 4-107
Unit Page
4-107 4-116
4-108 4-116
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-41
3-7 Parameter List
Parameter
No.
C031
C032
C033
C034
Multi-function output terminal
C035
C036
C038
C039
C040
C041
C042
C043
Level and output terminal status
C044
C045
C046
C052
C053
Function name Monitor or data range
Multi-function output terminal 11 contact selection
Multi-function output terminal 12 contact selection
Multi-function output terminal 13 contact selection
Multi-function output terminal 14 contact selection
Multi-function output terminal 15 contact selection
Relay output (AL2, AL1) contact selection
Light load signal output mode
Light load detection level
Overload warning signal output mode
Overload warning level
Arrival frequency during acceleration
Arrival frequency during deceleration
PID deviation excessive level
Arrival frequency during acceleration 2
Arrival frequency during deceleration 2
PID FB upper limit
PID FB lower limit
00: NO contact at AL2; NC contact at AL1 01: NC contact at AL2; NO contact at AL1
00: Enabled during acceleration/deceleration/
constant speed 01: Enabled only during constant speed
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
00: Enabled during acceleration/deceleration/
constant speed 01: Enabled only during constant speed
0.0: Does not operate.
0.1 × Rated current to 2.00 × Rated current (0.4 to 55 kW)
0.1 × Rated current to 1.80 × Rated current (75 to 132 kW)
0.00 to 99.99
100.0 to 400.0
0.00 to 99.99
100.0 to 400.0
0.0 to 100.0 3.0 No % 4-31
0.00 to 99.99
100.0 to 400.0
0.00 to 99.99
100.0 to 400.0
0.0 to 100.0
0.0 to 100.0 0.0 No %
Default setting
Rated
current
Rated
current
100.0
Changes
during
operation
00
No 4-94
01
01 No
No A
01 No
No A
0.00 No Hz
0.00 No Hz
0.00 No Hz
0.00 No Hz
No %
Unit Page
4-104
4-49
4-96
4-96
4-31
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-42
3-7 Parameter List
3
Operation
Parameter
No.
C055
C056
C057
C058
C061
Level and output terminal status
C062 Alarm code selection
C063 0 Hz detection level
C064
C071
C072
C073
C074
C075
Communication function
C076
C077
C078
C079
Function name Monitor or data range
Overtorque level (Forward power running)
Overtorque level (Reverse regeneration)
Overtorque level (Reverse power running)
Overtorque level (Forward regeneration)
Thermal warning level
Fin overheat warning level
Communication speed selection (Baud rate selection)
Communication station No. selection
Communication bit length selection
Communication parity selection
Communication stop bit selection
Communication error selection
Communication error timeout
Communication wait time
Communication method selection
Default setting
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
0. to 100. 80. No % 4-46
00: Disabled 01: 3-bit 02: 4-bit
0.00 to 99.99
100.0
0. to 200. 120. No C4-103
02: Loop-back test 03: 2400 bps 04: 4800 bps 05: 9600 bps 06: 19200 bps
1. to 32. 1. No
7: 7-bit 8: 8-bit
00: No parity 01: Even 02: Odd
1: 1-bit 2: 2-bit
00: Trip 01: Trip after deceleration stop 02: Ignore 03: Free-run stop 04: Deceleration stop
0.00 to 99.99 0.00 No s
0. to 1000. 0. No ms
00: ASCII 01: ModBus-RTU
Changes
during
operation
100. No %
100. No %
100. No %
100. No %
00 No 4-99
0.00 No Hz 4-99
04 No
7No
00 No
1No
02 No
01 No
Unit Page
4-98
4-140
4-102 4-140
4-140
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-43
3-7 Parameter List
Parameter
No.
C081 O adjustment
C082 OI adjustment
C083 O2 adjustment
Adjustment
C085
C091 Not used
C101 UP/DWN selection
C102 Reset selection
Others
C103
C105 FM gain setting 50. to 200. 100. Yes % 4-108
C106 AM gain setting 50. to 200. 100. Yes %
C107 AMI gain setting 50. to 200. 100. Yes %
C109 AM bias setting 0. to 100. 0. Yes %
Meter adjustment
C110 AMI bias setting 0. to 100. 20. Yes %
Function name Monitor or data range
0. to 9999. 1000 to 6553 (10000 to 65530)
0. to 9999. 1000 to 6553 (10000 to 65530)
0. to 9999. 1000 to 6553 (10000 to 65530)
Thermistor adjustment
Reset frequency matching selection
0.0 to 999.9
1000.
Use "00". * Do not change.
00: Do not store the frequency data 01: Store the frequency data
00: Trip reset at power-on 01: Trip reset when the power is OFF 02: Enabled only during trip (Reset when the
power is ON) 03: Trip reset only
00: 0 Hz start 01: Frequency matching start 02: Active Frequency Matching restart
Default setting
Factory
default
Factory
default
Factory
default
Factory
default
Changes
during
operation
Yes 
Yes 
Yes 
Yes 4-73
00 No 
00 No 4-88
00 Yes
00 No 4-85
Unit Page
3
Operation
4-85
4-132
4-109
C111
Terminal
C121 O zero adjustment
Adjustment
C123 O2 zero adjustment
Overload warning level 2
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
0. to 9999. 1000 to 6553 (10000 to 65530)
0. to 9999. 1000 to 6553 (10000 to 65530)
0. to 9999. 1000 to 6553 (10000 to 65530)
Rated
current
Factory
default
Factory
default
Factory
default
No A 4-49
Yes
Yes
Yes
C122 OI zero adjustment
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-44
3-7 Parameter List
3
Operation
00
00
00
00
00
00
00
00
00
00
Changes
during
operation
No s 4-106
No 4-100
Unit Page
Parameter
No.
C130 Output 11 ON delay 0.0 to 100.0 0.0
C131 Output 11 OFF delay 0.0 to 100.0 0.0
C132 Output 12 ON delay 0.0 to 100.0 0.0
C133 Output 12 OFF delay 0.0 to 100.0 0.0
C134 Output 13 ON delay 0.0 to 100.0 0.0
C135 Output 13 OFF delay 0.0 to 100.0 0.0
C136 Output 14 ON delay 0.0 to 100.0 0.0
C137 Output 14 OFF delay 0.0 to 100.0 0.0
C138 Output 15 ON delay 0.0 to 100.0 0.0
C139 Output 15 OFF delay 0.0 to 100.0 0.0
C140
C141
Output terminal operation function
C142
C143
C144
C145
C146
C147
C148
C149
Output terminal operation function
C150
C151
Function name Monitor or data range
Relay output ON delay
Relay output OFF delay
Logic output signal 1 selection 1
Logic output signal 1 selection 2
Logic output signal 1 operator selection
Logic output signal 2 selection 1
Logic output signal 2 selection 2
Logic output signal 2 operator selection
Logic output signal 3 selection 1
Logic output signal 3 selection 2
Logic output signal 3 operator selection
Logic output signal 4 selection 1
0.0 to 100.0 0.0
0.0 to 100.0 0.0
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Default setting
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-45
3-7 Parameter List
00
00
00
00
00
00
00
00
Changes
during
operation
No 4-100
No ms 4-106
Unit Page
4-16
4-132
Parameter
No.
C152
C153
C154
C155
C156
C157
Output terminal operation function
C158
C159
C160
C161
C162
C163
C164
C165
Input terminal response
C166
C167
C168
C169
Others
Function name Monitor or data range
Logic output signal 4 selection 2
Logic output signal 4 operator selection
Logic output signal 5 selection 1
Logic output signal 5 selection 2
Logic output signal 5 operator selection
Logic output signal 6 selection 1
Logic output signal 6 selection 2
Logic output signal 6 operator selection
Input terminal response time 1
Input terminal response time 2
Input terminal response time 3
Input terminal response time 4
Input terminal response time 5
Input terminal response time 6
Input terminal response time 7
Input terminal response time 8
FW terminal response time
Multi-step speed/ position determination time
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
Same as options for C021 to C026 (excluding LOG1 to LOG6)
Same as options for C021 to C026 (excluding LOG1 to LOG6)
00: AND 01: OR 02: XOR
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 2 ms) 1
0. to 200. (× 10 ms) 0 No ms
Default setting
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-46
3-7 Parameter List
3
Operation
Parameter
No.
H001 Auto-tuning selection
H002
H202
H003
H203
Control parameter
H004
H204
H005 Speed response
H205 * 2nd speed response 1.590
Function name Monitor or data range
00: Disabled 01: Not rotate 02: Rotate
Motor parameter selection
* 2nd motor parameter selection
Motor capacity selection
* 2nd motor capacity selection
Motor pole number selection
* 2nd motor pole number selection
00: Standard motor parameter 01: Auto-tuning parameter 02: Auto-tuning parameter
(online auto-tuning enabled)
0.20 to 160.0
2/4/6/8/10
0.001 to 9.999/10.00 to 80.00 (10.000 to 80.000)
Default setting
Factory
default
Factory
default
1.590
Changes
during
operation
00 No 4-109
00
No
00
No kW
4
No Pole
4
Yes
Unit Page
4-109 4-111 4-113
4-19 4-109 4-113 4-116
4-87
4-90
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-47
3-7 Parameter List
100.
100.
100.
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
on the
motor
Changes
during
operation
Yes 4-118H206
No
No
No mH
No A
No kgm
Unit Page
4-113
4-113
2
Parameter
No.
H006
H306
H020 Motor parameter R1
H220
H021 Motor parameter R2
H221
H022 Motor parameter L
Control parameter
H222
H023 Motor parameter Io
H223
H024 Motor parameter J
H224
Function name Monitor or data range
Stabilization parameter
* 2nd stabilization parameter
* 3rd stabilization parameter
* 2nd motor parameter R1
* 2nd motor parameter R2
* 2nd motor parameter L
* 2nd motor parameter Io
* 2nd motor parameter J
0. to 255.
0.001 to 9.999
10.00 to 65.53
0.001 to 9.999
10.00 to 65.53
0.01 to 99.99
100.0 to 655.3
0.01 to 99.99
100.0 to 655.3
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Default setting
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-48
3-7 Parameter List
3
Operation
on the motor
on the motor
on the motor
on the motor
on the motor
on the motor
on the motor
on the motor
on the motor
on the motor
Changes
during
operation
No
No
No mH
No A
No kgm
Unit Page
4-109 4-113
2
Parameter
No.
H030
H230
H031
H231
H032
H232
Control parameter
H033
H233
H034
H234
Motor parameter R1 (auto-tuning data)
* 2nd motor parameter R1 (auto-tuning data)
Motor parameter R2 (auto-tuning data)
* 2nd motor parameter R2 (auto-tuning data)
Motor parameter L (auto-tuning data)
* 2nd motor parameter L (auto-tuning data)
Motor parameter Io (auto-tuning data)
* 2nd motor parameter Io (auto-tuning data)
Motor parameter J (auto-tuning data)
* 2nd motor parameter J (auto-tuning data)
Function name Monitor or data range
0.001 to 9.999
10.00 to 65.53
0.001 to 9.999
10.00 to 65.53
0.01 to 99.99
100.0 to 655.3
0.01 to 99.99
100.0 to 655.3
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Default setting
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
Depends
capacity.
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-49
3-7 Parameter List
Parameter
No.
H050 PI proportional gain
H250
H051 PI integral gain
H251 *2nd PI integral gain 100.0
H052 P proportional gain
H252
H060 Limit at 0 Hz
H260 * 2nd limit at 0 Hz 100.0
H061
Control parameter
H261
H070
H071
H072
H073 Gain switching time 0. to 9999. 100. Yes ms
P001
P002
P011 Encoder pulses
P012
Options
P013
P014
P016
Function name Monitor or data range
* 2nd PI proportional gain
*2nd P proportional gain
Boost amount at SLV startup, 0 Hz
* 2nd boost amount at SLV startup, 0 Hz
For PI proportional gain switching
For PI integral gain switching
For P proportional gain switching
Operation selection at option 1 error
Operation selection at option 2 error
V2 control mode selection
Pulse train mode selection
Orientation stop position
Orientation speed setting
Orientation direction setting
0.0 to 999.9
1000.
0.0 to 999.9
1000.
0.01 to 10.00
0.0 to 100.0
0. to 50.
0.0 to 999.9
1000.
0.0 to 999.9
1000.
0.00 to 10.00 1.00 Yes
00: Trip 01: Continues operation
00: Trip 01: Continues operation
128. to 9999. 1000 to 6500 (10000 to 65000)
00: ASR (speed control mode) 01: APR (pulse train position control mode) 02: APR2 (absolute position control mode) 03: HAPR (High resolution absolute position
control mode)
00: Mode 0 01: Mode 1 02: Mode 2
0. to 4095. 0. No
Starting frequency to Max. frequency (upper limit: 120.0)
00: Forward side 01: Reverse side
Default setting
100.0
100.0
100.0
100.0
100.0 Yes
100.0 Yes
1024.
Changes
during
operation
Yes
Yes
1.00
Yes
1.00
Yes %
50.
Yes %
50.
00 No
00 No
No Pulse
00 No
00 No 4-123
5.00 No Hz
00 No
Unit Page
4-87 4-90
4-115
4-87
4-109
4-120 4-128 4-129
4-120 4-131
4-129P015
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3
Operation
3-50
3-7 Parameter List
3
Operation
Parameter
No.
P017
P018
P019
P020
P021
P022
P023 Position loop gain
P024 Position bias amount -204(-2048.)/-999. to 2048. 0. Yes 4-124
P025
Options
P026
P027
P028
P029
P031
P032
P033
P034
P035
Function name Monitor or data range
Position ready range setting
Position ready delay time setting
Electronic gear setting position selection
Electronic gear ratio numerator
Electronic gear ratio denominator
Position control feedforward gain
Secondary resistance compensation enable/disable selection
Overspeed error detection level
Speed deviation error detection level
Motor gear ratio numerator
Motor gear ratio denominator
Acceleration/ deceleration time input type
Orientation stop position input type
Torque reference input selection
Torque reference setting
Polarity selection at torque reference via O2
0. to 9999. 1000(10000)
0.00 to 9.99 0.00 No s
00: Position feedback side (FB) 01: Position command side (REF)
0. to 9999. 1. No
0. to 9999. 1. No
0.00 to 99.99
100.0 to 655.3
0.00 to 99.99
100.0
00: Disabled 01: Enabled
0.0 to 150.0 135.0 No % 5-6
0.00 to 99.99
100.0 to 120.0
1. to 9999. 1. No
1. to 9999. 1. No
00: Digital Operator 01: Option 1 02: Option 2
00: Digital Operator 01: Option 1 02: Option 2
00: Terminal O 01: Terminal OI 02: Terminal O2 03: Digital Operator
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
00: Signed 01: Depends on the RUN direction
Default setting
Changes
during
operation
5. No Pulse
00 No
0.00 No
0.50 No rad/s
00 No 4-112
7.50 No Hz 4-120
00 No 4-8
00 No 
00 No
0. Yes %
00 No
Unit Page
4-123 4-129
4-123 4-129
4-123 4-125
4-120 4-124 4-125 4-129 4-131
4-128
4-122
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-51
Loading...