Omron E5ZE-8AQHD1TCB-V2, E5ZE-8ACAD1PB-V2, E5ZE-8AQHD1PB-V2, E5ZE-8ACAD1TCB-V2, E5ZE-8VQHD1TCB-V2 Datasheet

...
Multipoint Temperature Controller E5ZE-8@D1@B-V2 1
Multipoint Temperature Controller
E5ZE-8@D1@B-V2
Multipoint Temperature Controller Connects to the Programmable Controller with Ease
• Conforms to De viceNet req uirements wit h remote I/O and FINS message communications, thus connecting to a CompoBus/D Master without prog rams f or remot e I/O commu nications an d to OMRON’s Programmable Controller with ease for explicit mes­sage communicat ion s .
• High-speed inpu t sampling of only 0.2 s at the maxi mum of eigh t temperature inputs.
Model Number Structure
Model Number Legend
1. Number of Control Points
8: 8 channels
2. Control Method
A: Standard (heating or cooling) V: Heating and cooling
3. Control Output (H e a ting Side)
Q: Voltage output (for driving SSR) C: Current output
4. Heater Burnout and SSR Failure Detection (See note 1.)
H: Available A: Not available
5. Communications Function
D1: DeviceNet
6. Input
TC: Thermocouple P: Platinum resistance thermometer
7. Case
B: Provided (Models with case)
8. Version
V2: Supports explicit messages
Note: 1. Heater burnout and SSR failure detection are not available when the control output on the heating side is current output.
2. Refer to the List of Models for combinations of functions.
1 234
5
6
7
8
E5ZE-8@@@D1@B-V2
2 Multipoint Temperature Controller E5ZE-8@D1@B-V2
Ordering Information
List of Models
Note: 1. Cooling control is possible by making a change in output operation.
2. Models without the heater burnout/SSR failure detection function are also available.
3. Cooling control output is an open collector output (NPN).
Accessories (Order Separately)
Setting Display Unit
Note: Not all the functions of the E5ZE can be set, which should be
taken into consideration when designing the system. For de­tails, refer to the E5ZD-SDL Setting Display Unit Datasheet (H061).
Current Transformers (CT)
Special Cables
Recommended Power Supplies
No. of control
points
Control method Control output Heater burnout and
SSR failure detection
Input type
Thermocouple Platinum resistance
thermometer
8 Standard
(see note 1)
Voltage Available (see note 2) E5ZE-8AQHD1TCB-V2 E5ZE-8AQHD1PB-V2 Current Not available E5ZE-8ACAD1TCB-V2 E5Z E -8ACAD1PB-V2
Heating and cooling Voltage Available (see note 2) E5ZE-8VQHD1TCB-V2 E5ZE-8VQHD1PB-V2
Current (see note 3) Not available E5ZE-8VCAD1TCB-V2 E5ZE-8VCAD1PB-V2
Connecting
model
Connecting
part
Power supply Model
RS-232C Connector 100 to 240 VAC E5ZD-SDL1
24 VDC
Hole diameter 5.8 mm 12.0 mm Model E54-CT1 E54-CT3
Model E5ZE-CBL200 ES100-CT021-202 (25-pin) ES100-CT023-202 (9-pin)
Series S82J S82K
Multipoint Temperature Controller E5ZE-8@D1@B-V2 3
Specifications
Ratings
Supply volt age 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power cons um ption 15 W + 20% max. at rated supply voltage Input Input type Thermocouple: K, J, R, S, T, E, B, N, L, U, W, PL-II
Platinum resistance thermometer: Pt100, JPt100
Input impedance Thermocouple: 1 M
min.
Rated platinum resistance thermometer current
1 mA
Control outputs
Standard (Heating side) Voltage output (with short-circuit protecting function)
ON: 12
± 1.2 VDC
OFF: 0.5 VDC max. Max. load current: 30 mA DC per point
Current output
Rated output range: 4 to 20 mA DC Current output range: 0 to 22 mA DC
With an output value of 0%: 4
+0
/
–0.6
mA DC
With an output value of 100%: 20
+2
/–0 mA DC
Max. load resistance: 600
per point
Cooling side Open collector output (NPN)
Max. applied voltage: 30 VDC Max. load current: 50 mA DC per point ON residual voltage: 2 VDC max. OFF leakage current: 1 mA DC max.
Alarm outputs Temperature alarm: The total output of all control points (alarm 1 NPN open collector output and
alarm 2 NPN open collector output)
HB alarm (heater burnout detection): Total output of all control points (1-point NPN open collector
output)
HS alarm (SSR failure detection): Total output of all control points (1-point NPN open collector
output)
Temperature controller error output (memory, set value, or hardware error):
1-point NPN open collector output Max. applied voltage: 30 VDC Max. load current: 50 mA DC per point
No. of input control points 8 input and 8 control points Setting method Via communication Control modes ON/OFF control
Hybrid of advanced PID control and fuzzy control Manual operation
Memory bank input No. of points: 8 for each control point
Designation method: Through communication or memory bank designation input
Memory bank designation inputs With contact signal input
ON short-circuit resistance: 1 k
max.
OFF open resistance: 100 k
min.
With no-contact signal input
ON residual voltage: 2 VDC max. OFF leakage current: 1 mA DC max.