4 Multipoint Temperature Controller E5ZE-8@D1@B-V2
■Input Ranges
Thermocouple
Platinum Resistance Thermometer
Note: 1. A temperature range is factory-set to a range of –200° to
1,300
°C (for K(CA)) or –100.0° to 500.0°C (for Pt 100).
2. Thermocouple W is W/ Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
■Characteristics
Input
(switch
selectable)
K (CA)
Chromel
vs. alumel
(see
note 1)
J (IC)
Iron vs.
constan-
tan
R
Platinum
vs. Plati-
num rhod-
ium 13%
S
Platinum
vs. Plati-
num rhod-
ium 10%
T (CC)/U
Copper
vs. con-
stantan
E (CRC)
Chromel
vs. con-
stantan
B
Platinum
rhodium
30% vs.
platinum
rhodium
6%
N
Nichrosil
vs. nisil
L
Iron vs.
constan-
tan
U
Copper
vs. con-
stantan
W
(see
note 2)
PL-II
(Platinum)
Range
°C –200 to
1,300
–100 to
850
0 to 1,700 0 to 1,700 –200 to
400
0 to 600 100 to
1,800
0 to 1,300 –100 to
850
–200 to
400
0 to 2,300 0 to 1,300
°F –300 to
2,300
–100 to
1500
0 to 3,000 0 to 3,000 –300 to
700
0 to 1100 300 to
3,000
0 to 2,300 –100 to
1,500
–300 to
700
32 to 4,100 0 to 2,300
Setting no. 0123456789AB
Min. setting
unit
1
°C or 0.1°C
Input
(switch selectable)
Pt 100
(see note 1)
JPt 100
Range
°C –100.0 to 500.0 –100.0 to 500.0
°F –100.0 to 900.0 –100.0 to 900.0
Setting no. 01
Min. setting unit 1
°C or 0.1°C
Measurement accuracy (see note) Thermocouple:
(
±0.3% of the process value or ±2°C, whichever greater) ±1 digit max.
(
±0.3% of the process value or ±3.6°F, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(
±0.3% of the process value or ±0.8°C, whichever greater) ±1 digit max.
(
±0.3% of the process value or ±1.5°F, whichever greater) ±1 digit max.
Hysteresis 0.0
° to 99.9°C/°F for ON/OFF control only (in units of 0.1°C/°F)
Cooling coefficient 0.0 to 10.0 (in units of 0.1)
Proportional band 0.0
° to 999.9°C/°F (in units of 0.1°C/°F)
Cooling side: Cooling coefficient
× Proportional band
Integral (reset) time 0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Derivative (rate) time 0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Control period Heating side: 1 to 99 s (in units of 1 s)
Cooling side: 1 to 99 s (in units of 1 s)
Sampling period 200 ms for 8 control points
Dead band/overlap band –999
° to 999°C/°F (in units of 1°C/°F)
Alarm output setting range –999
° to 9999°C/°F, 0 to 9999°C/°F (upper- and lower-limit alarm) (in units of 1°C/°F)
–999.9
° to 9999.9°C/°F, 0.0 to 9999.9°C/°F (upper- and lower-limit alarm) (in units of 0.1°C/°F) (see note
3)
Fuzzy strength 0% to 99% (in units of 1%)
Fuzzy scale 1 0.2
° to 999.9°C/°F (in units of 0.1°C/°F)
Fuzzy scale 2 0.02
° to 99.99°C/s or °F/s (in units of 0.01°C/s or °F/s)
Set value backup Lithium battery
Set value backup period 10 years min. provided that the ambient temperature is within the room temperature
Insulation resistance 20 M
Ω min. between the FG terminal and all analog input terminals (at 500 VDC)
Dielectric strength A leakage current of 1 mA A C max. with 500 VA C for 1 minutes between the FG terminal and all analog
input terminals
Vibration resistance
Malfunction: 10 to 55 Hz, 15 m/s
2
for 8 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
for 8 min each in X, Y, and Z directions
Shock resistance
Malfunction: 150 m/s
2
, 3 times each in 6 directions
Destruction: 200 m/s
2
, 3 times each in 6 directions
Ambient temperature Operating: 0
° to 55°C (with no icing or condensation)
Storage: –25
° to 65°C (with no icing or condensation)
Ambient humidity Operating: 35% to 85%
Storage: 35% to 95%