Omron E5ZE Operation Manual

E5ZE Multipoint Temperature Controller
Operation Manual
Catalog No. H076-E3-1
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or dam­age to property.
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
!
serious injury.
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
!
serious injury.
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
!
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any­thing else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
OMRON, 1997
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis­sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa­tion contained in this publication.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v

TABLE OF CONTENTS

PRECAUTIONS xi. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 General Safety Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Operating Environment Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Application Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Component Names and Functions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 System Configuration 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Main Functions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Preparations 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1 List of Models 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Mounting the Serial Communications Models 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Setting Selectors and Switch 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Installation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Power Supply and Input Wiring 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Wiring CT Inputs and Control/Alarm Outputs 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Connecting Communications 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Functions 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Data Configuration 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 I/O Settings 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Set Point and Process Value 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Alarm Output Settings 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Output Limitations 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6 Ramp 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 Control Adjustments 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8 Control Method Selection 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9 Heating and Cooling Control 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-10 Heater Burnout Detection 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-11 SSR Failure Detection 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Troubleshooting 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Troubleshooting Procedure 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Communications Errors 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Temperature Sensing Errors 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Temperature Control Errors 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Output Errors 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 HB Alarm and HS Alarm Errors 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Specifications 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Current Transformer Specifications 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Manually Setting PID Constants 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Saving Data 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E Hardware Test 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F Available Models 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
vii
About this Manual:
This manual describes the installation and operation of E5ZE Multipoint Temperature Controllers and includes the sections described below.
Refer to the following manuals according to the model being used before operating the E5ZE. Refer to the following manual when using the E5ZE Serial Communications Models: E5ZE Multipoint Temperature Controller Communications Manual (Cat. No. H77) Refer to the following manual when using the DeviceNet Communications Models: E5ZE-8 Multipoint Temperature Controller DeviceNet Communications Manual (Cat. No. H104) DeviceNet Operation Manual (Cat. No. W267) Please read this manual carefully and be sure you understand the information provided before at-
tempting to install or operate an E5ZE Multipoint Temperature Controller. Be sure to read the
Precautions section. Precautions provides precautions for installing and using the E5ZE. Section 1 provides information on the system configuration, component names, and functions. Section 2 describes the installation and wiring procedures necessary before operating the E5ZE. Section 3 describes each of the E5ZE functions. Section 4 describes the troubleshooting procedure for the E5ZE.
The Appendices provide information on specifications, ratings, characteristics, the Current Trans­former, PID constant manual adjustments, saving data, hardware tests, current outputs, and available models.
!
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix

PRECAUTIONS

This section provides general precautions for using the E5ZE Multipoint Temperature Controller and related devices.
The information contained in this section is important for the safe and reliable application of the E5ZE Multipoint Temperature Controller. You must read this section and understand the information contained before attempting to set up or operate an E5ZE Multipoint Temperature Controller.
1 General Safety Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Operating Environment Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Application Precautions xii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xi

1 General Safety Precautions

WARNING Do not attempt to disassemble, apply pressure, distort, subject to temperatures
!
of 100°C or more, or throw the E5ZE into fire. A lithium battery is built into the E5ZE and any attempt to any of the above may result in fire, explosion, or combustion.
WARNING Do not attempt to disassemble, modify, or repair the E5ZE. Any attempt to do so
!
may result in malfunction, fire, or electric shock.
Caution Do not use any terminal that is marked Dont use.
!

2 Operating Environment Precautions

Caution Be sure to check polarity when connecting the terminals.
!
Caution Do not install power lines or high-tension lines alongside lines connected to the
!
E5ZE to prevent the E5ZE from being influenced by inductive noise. Install lines connected to the E5ZE through an independent conduit or use a shielded cable for the lines to protect them from inductive noise.

3Application Precautions

Caution Separate the E5ZE from devices generating a strong high-frequency, such as
!
high-frequency welding machines, or devices that generate surge.
Caution Do not operate the E5ZE in the following locations:
!
Locations subject to exposure to water, oil, or chemicals.
Locations subject to corrosive or flammable gases.
Locations subject to temperatures or humidity outside the range specified in
the specifications.
Locations subject to condensation.
Locations subject to shock or vibration.
Locations subject to severe changes in temperature.
Locations subject to icing.
Caution Do not install the E5ZE in a location with obstructions preventing radiant heat
!
from escaping.
3 Application Precautions
WARNING Make sure that no metal particles or wire chips are accidentally left in the
!
product. Doing so may result in malfunction, fire, or electric shock.
xii
WARNING Install a separate alarm to prevent the temperature from increasing excessively
!
if the E5ZE malfunctions. Insufficient safety precautions may cause serious accidents if the temperature control malfunctions.
Caution Tighten the screws on the terminal block to the torque specified in the manual.
!
Loose screws may result in burning or malfunction.
Caution Do not connect loads to the E5ZE that exceed the specified ratings. Excessively
!
large loads may result in malfunction or burning.
Caution Always use the power supply voltage specified in the manual. An incorrect volt-
!
age may result in malfunction or burning.
Caution Confirm that no adverse effects will occur in the system before attempting to per-
!
form a hardware test. Insufficient confirmation may result in unexpected opera­tions.
Caution Make sure that all the E5ZE set values are suitable for the controlled system.
!
Unsuitable set values may result in unexpected operations causing damage to the product or accidents.
3Application Precautions
xiii
SECTION 1
Introduction
This section describes the components, a standard system configuration, and the functions of the E5ZE. Refer to Section 2 Preparations and later sections for details on functions and their applications.
1-1 Component Names and Functions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 System Configuration 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Main Functions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Component Names and Functions Section 1-1

1-1 Component Names and Functions

The component names and their functions are provided here.
Indicators
Communications connector
Setting selectors and switch
CT INPUT connector
Indicators
Input terminal block
Indicators A: E5ZE-8AB (Standard Models with casing) V: E5ZE-8VB (Heating and Cooling Control Models with casing)
The indicators show the operating status of the E5ZE, as follows:
PWR: Lit when power is ON. RDY: Lit when the E5ZE is ready to operate. ERR: Lit when an error occurs in the E5ZE. RUN: Lit when the E5ZE is operating. AT: Lit when auto-tuning is being executed. RD: Lit when the E5ZE is receiving command data. SD: Lit when the E5ZE is sending response data. CH0 to CH7:
Lit for the control points for which the corresponding control outputs are ON. (Not lit for Current Output Models.)
H0 to H7:
Lit for the control points for which the corresponding heating outputs are ON. (Not lit for Current Output Models.)
C0 to C7:
Lit for the control points for which the corresponding cooling outputs are ON.
AL1: Lit when alarm 1 is ON. AL2: Lit when alarm 2 is ON. HB: Lit when the HB (heater burnout) alarm is ON. HS: Lit when the HS alarm (SSR short circuit) is ON. MB0 to MB2:
Lit when the memory bank designation inputs (bits 2 external contacts.
CONTROL connector
ALARM connector
0
to 22) are turned ON with
2
Component Names and Functions Section 1-1
Setting Selectors and Switch
Input Terminal Block
Communications Connector
The setting selectors and switch are used to select the temperature sensor type, the unit number, and the functions to be used with the E5ZE. Refer to 2-3 Setting Selectors and Switch for details on setting methods.
The input terminal block is connected to a DC power supply, temperature sen­sor, and ground wire. Refer to 2-5 Power Supply and Input Wiring for details on wiring procedures.
The communications connector is connected to the communications cable. Re­fer to the E5ZE Multipoint Temperature Controller Communications Manual
(H77) or the E5ZE-8 Multipoint Temperature Controller DeviceNet Communica­tions Manual (H104) for details on communications functions and their applica-
tions.
CT INPUT Connector
CONTROL Connector
ALARM Connector
E5ZE-8D1B (for DeviceNet
communications)
E53-E01 (for RS-232C
Communications Unit)
E53-E04 (for RS-422/485
Communications Unit)
The CT INPUT connector is connected to the Current Transformer (CT) to detect heater burnout or SSR failure. Use E5ZE-CBL Connecting Cables to con­nect to the Connector Terminal Conversion Unit (XW2B-20G5 for M3.5 terminal screws or XW2B-20G4 for M2.4 terminal screws). Refer to 2-6 Wiring CT Inputs and Control/Alarm Outputs for details on wiring procedures.
The CONTROL connector is used to connect the control output and memory bank designation input contacts. Use E5ZE-CBL Connecting Cables to connect to the Connector Terminal Conversion Unit (XW2B-20G5 for M3.5 ter­minal screws or XW2B-20G4 for M2.4 terminal screws). Refer to 2-6 Wiring CT Inputs and Control/Alarm Outputs for details on wiring procedures.
The ALARM connector for the E5ZE-8A Standard Models is used for an alarm output and that for the E5ZE-8V Heating and Cooling Con­trol Models is used for cooling control output and alarm output. Use E5ZE-CBL­ Connecting Cables to connect to the following devices.
Device Model Specifications and Comments
Connector Terminal Conversion Units
I/O Relay Terminal
I/O Relay Terminal
XW2B-20G4 M2.4 terminal screws XW2B-20G5 M3.5 terminal screws G7TC-OC08 8 relay outputs (no cooling outputs) G7TC-OC16 16 relay outputs G7VC-OC16 16 relay outputs G7VC-OA16 16 SSR AC
outputs
G7VC-OD16 16 SSR DC
outputs
Cooling outputs terminal is not available on the standard model.
3
System Configuration

1-2 System Configuration

The following diagram shows the system configuration of the E5ZE.
Section 1-2
24-VDC power supply
Platinum resistance thermometer or thermocouple
E5ZE
Communications interface: RS-232C, RS-422 or RS-485, or DeviceNet
Host device
Computer
Commu­nications connector
Programmable Controller E5ZD-SDL Setting Display Unit
E5ZE-CBL Connecting Cables
CT INPUT connector
XW2B-20G5/4 Connector Terminal Conversion Unit
Current Trans­former (CT)
Input terminal block
CONTROL connector
ALARM connector
XW2B-20G5/4 Connector Terminal Conversion Unit
XW2B-20G5/4 Connector Terminal Conversion Unit/ I/O Blocks
Control outputs Memory bank desig­nation inputs
Cooling control outputs Alarm outputs
Use the specified cables and wiring devices to prevent malfunctions or acci­dents caused by incorrect wiring.
The connection between the communications connector and the host device differs according to the communications interface used. Refer to the E5ZE
Multipoint Temperature Controller Communications Manual (H77) or the E5ZE-8 Multipoint Temperature Controller DeviceNet Communications Manu­al (H104) for details.
There are restrictions on the items that can be set or displayed from the E5ZD­SDL Setting Display Unit. Refer to the E5ZD-SDL Setting Display Unit Data- sheet (H61) for details.
4
Main Functions
Isolation
Section 1-3
E5ZE
RS-232C RS-422 RS-485
Power supply
Input terminal block
FG
DeviceNet
CT INPUT connector
CONTROL connector
ALARM connector
The components of the E5ZE contained within bold lines in the above diagram are electrically isolated.
Note The covers of the CT INPUT, CONTROL, and ALARM connectors are con-
nected to the frame ground (FG). For the E5ZE-8TC (Thermocouple Input Models), the thermocouple
inputs of the control points are insolated from each other.

1-3 Main Functions

Input Type
CONTROL Outputs
ALARM Outputs
Output Limitations
Ramp
The E5ZE is connected to platinum resistance thermometers or thermocouples, depending on the model used. The type of temperature sensor is specified using the INPUT selector on the front panel of the Unit. The input values can be ad­justed using the input adjustment function.
The control outputs can be either voltage output or current output, depending on the model. The control period and direct/reverse operation can be specified us­ing the set values.
A maximum of 2 alarm outputs are possible. There are 12 alarm modes that can be set for each alarm output according to set values. The outputs are compre­hensive output for all control points.
The output values are limited by the following 2 limiters:
Output limiter
Output change rate limiter
If an output value is outside the upper or lower limit for the output, the output will be limited to the preset upper or lower limit. The output change rate limiter limits the rate at which output values change per unit time.
The ramp function is used to limit the control temperature (set point) from chang­ing rapidly. If the set point changes quicker than the preset rate, the rate of tem­perature change will be limited to the preset rate, and the temperature will gradu­ally change until it reaches the new temperature. The ramp can be set by the user.
5
Main Functions
Section 1-3
Control Adjustment
Heater Burnout and SSR Failure Detection
Control Method Selection
Memory Banks
PID and fuzzy constants can be set by executing auto-tuning (AT). If an offset occurs during P or PD control, manual adjustment is possible using the manual reset function. Temperature turbulence caused by external disturbances can be suppressed and controlled using the fuzzy function.
Output short circuits caused by heater burnout or SSR failure can be detected.
Control can be switched between ON/OFF control and the normal 2-PID control (with 2 degrees of freedom). Manual operation is also possible.
The memory banks store different sets of set values for the control points. There are 8 memory banks for each control point. Memory banks allow the set values for a control point to be changed as a group rather than resetting them individu­ally. Use the external contact inputs or communications to designate the re­quired memory bank.
6
SECTION 2
Preparations
This section provides details on operations that must be performed before starting the E5ZE, such as installation and wiring.
2-1 List of Models 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 Serial Communications Models 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 DeviceNet Communications Models 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Mounting the Serial Communications Models 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Setting Selectors and Switch 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-1 UNIT Selector 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 INPUT Selector 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-3 FUNCTION Switch 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Installation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-1 External and Panel Dimensions 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-2 Mounting 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Power Supply and Input Wiring 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-1 Terminal Block 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-2 Wiring 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-3 Terminal Arrangement 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-4 Power Supply 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-5 Ground 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-6 Thermocouple Input 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-7 Platinum Resistance Thermometer Input 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Wiring CT Inputs and Control/Alarm Outputs 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-1 CT Inputs 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-2 Outputs 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Connecting Communications 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-1 RS-232C 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-2 RS-422 and RS-485 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-3 DeviceNet Interface 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7

2-1 List of Models

2-1-1 Serial Communications Models

2-1SectionList of Models
No. of
control
Casing Control
method
points SSR failure
Control
output
Heater
burnout and
detection
Commu-
nications
Input type
Thermocouple Platinum
resistance
thermometer
8 Yes Standard Option Option Option E5ZE-8AAAMTCB-E E5ZE-8AAAMPB-E
Heating
Option Option Option E5ZE-8VAAMTCB-E E5ZE-8VAAMPB-E and cooling
Model Number Legend:
E5ZE-8AAM-E
1234567
1. Control Point
8: 8
2. Control Method
A: Standard V: Heating and cooling
3. Control Output
A: Option (see note 1)
4. Heater Burnout and SSR Failure Detection (see note 2)
A: Option (see note 3)
5. Communications
M: Option (see note 4)
6. Input Type
TC: Thermocouple P: Platinum resistance thermometer
7. Casing
B: Yes
Note: 1. The E53-E8Q Voltage Output Unit or the E53-E8C
Current Output Unit can be used with the E5ZE. The E53-E8Q Voltage Output Unit and the E53-E8C Current Output Unit are sold separately.
2. The heater burnout and SSR failure detection function of the E5ZE will be invalid if the heating side control output of the E5ZE is current output.
3. The E54-E8CT CT Input Unit is required for the heater burnout and SSR failure detection. The E54-E8CT CT Input Unit is sold separately.
4. The E53-E01 Communications Unit for RS-232C communication or the E53-E04 Communications Unit for RS-422 and RS-485 communication can be used with the E5ZE. The E53-E01 Communications Unit and the E53-E04 Communications Unit are sold separately.
I/O Units (Order Separately)
Units Models RS-232C Communications Unit E53-E01 RS-422/485 Communications Unit E53-E04 CT Input Unit E54-E8CT Voltage Output Unit E53-E8Q Current Output Unit E53-E8C
8

2-1-2 DeviceNet Communications Models

2-1SectionList of Models
No of control
points
Casing Control
method
Control
output
HBA and SSR
failure
Iput type Name
detection
8 Yes Standard Voltage Yes Thermocouple E5ZE-8AQH
D1TCB 24VDC
8 Yes Standard Voltage Yes Platinum
resistance
E5ZE-8AQH D1PB 24VDC
thermometer
8 Yes Standard Current No Thermocouple E5ZE-8ACA
D1TCB 24VDC
8 Yes Standard Current No Platinum
resistance
E5ZE-8ACA D1PB 24VDC
thermometer
8 Yes Heating and
Cooling
Voltage Yes Thermocouple E5ZE-8VQH
D1TCB 24VDC
8 Yes Heating and
Cooling
Voltage Yes Platinum
resistance
E5ZE-8VQH D1PB 24VDC
thermometer
8 Yes Heating and
Cooling
Current No Thermocouple E5ZE-8VCA
D1TCB 24VDC
8 Yes Heating and
Cooling
Current No Platinum
resistance
E5ZE-8VCA D1PB 24VDC
thermometer
Model Number Legend:
E5ZE-8
1234567
1. Control Point
8: 8
2. Control Method
A: Standard control V: Heating and cooling control
3. Control Output
Q: Voltage output C: Current output
4. Heater Burnout and SSR Failure Detection Function (Not available with Current Output Models.)
A: No H: Yes
5. Communications Function
D1: DeviceNet
6. Input Type
TC: Thermocouple P: Platinum resistance thermometer
7. Casing
B: Yes
9

2-2 Mounting the Serial Communications Models

2-2SectionMounting the Serial Communications Models
I/O Units
Communication Unit
CT Input Unit
Output Unit
E53-E01 for RS-232C
E54-E8CT
I/O Units are not mounted on the E5ZE. Mount the appropriate I/O Units according to the specification of the E5ZE. The diagram below is the view from the back of component side.
Type of I/O Units
E53-E04 for
or
Use this CT input unit in combination with the E53-E8Q voltage output unit.
RS-422/RS-485
E53-E8Q for voltage output
or
E53-E8C for current output
Tighten the screws through the holes marked with a black dot () to the fixing studs of the E5ZE.
Mounting Position of I/O Units
Communication Unit
CT Input Unit
Output Unit
Remove this screw when the Unit is mounted on the model with casing.
Connector
Communication Unit
CT Input Unit
Connector
Output Unit
Connector
10
2-2SectionMounting the Serial Communications Models
Mounting the Units
Casing securing
Use appropriate Phillips screwdriver for the screws. Use of an inappropriate screwdriver may damage the screws and cause insufficient tightening.
Mount the Units in an environment where anti-static electricity countermeasures have been taken.
Store the removed screws carefully and use them again when required.
Model With Casing
1, 2, 3... 1. Remove the connector fixing screws (2 screws each for a connector) from
the Units (except for communication unit).
2. Remove the casing fixing screws (6 screws).
3. Remove the casing.
4. Mount the Units in the same manner as the model without casing.
5. Fix the connector to the case using the connector fixing screws with a torque of 0.34 to 0.39 Nm.
6. Replace the casing in its original position using six casing fixing screws.
Casing
Case
Casing securing
Remove the casing after removing the casing fixing screws(6 pcs.)
Identification label for connector
CT INPUT CONTROL ALARM
Fixing studs for the Units Communication Unit : 3 pcs.
CT Input Unit : 3 pcs. Output Unit : 4 pcs.
Communication Unit (sold separately) E53-E01 or E53-E04 (The diagram shows E53-E04)
CT Input Unit (sold separately ) E54-E8CT
Output Unit (sold separately) E53-E8Q or E53-E8C
The Unit fixing screws are mounted on the fixing studs at the factory.
11

2-3 Setting Selectors and Switch

Observe the following precautions when operating the selectors and switch.
Always make sure the power is OFF before changing the selectors and switch.
Use a small flat-blade screwdriver to change the selector and switch settings,
and be sure that the selectors are correctly positioned.

2-3-1 UNIT Selector

When serial communications are being used, the UNIT selector must be set so that the host device can recognize the E5ZE unit number.
When more than one E5ZE Multipoint Temperature Controller is being used with RS-422 or RS-485 communications, set a different unit number for each E5ZE.
The selector settings 0 to F correspond to unit numbers 00 to 0F. The factory setting of 0 corresponds to unit number 00.
2-3SectionSetting Selectors and Switch
UNIT INPUT

2-3-2 INPUT Selector

UNIT INPUT
Set the INPUT selector according to the type of temperature sensor connected to the E5ZE. The selector positions and corresponding temperature sensors are as follows:
Selector
setting
Thermocouple K J R S T E B N L U W PLII Not used. Platinum
resistance thermometer
0 1 2 3 4 5 6 7 8 9 A B C D E F
Pt JPt Not used.
The factory setting is 0.
The platinum resistance thermometer settings Pt and JPt indicate Pt100
and JPt100 respectively.
12

2-3-3 FUNCTION Switch

The FUNCTION switch is used to set the parameters of the E5ZE, such as the baud rate and startup operation.
FUNCTION
2-3SectionSetting Selectors and Switch
Operation mode change Not used. (Always set to OFF.) Temperature unit (°C or °F) Startup operation E5ZD-SDL Setting Display Unit connection Memory bank designation method Baud rate (serial communications)
Baud Rate (Serial Communications)
Baud rate 19,200 bps 9,600 bps 4,800 bps 2,400 bps
Pin 1 Pin 2
Set the baud rate using pins 1 and 2 to the baud rate of the host device con­nected to the EZ5E.
The factory setting is 9,600 bps (pin 1 ON, pin 2 OFF).
Memory Bank Designation Method
Pin 3 is used to set the memory bank designation method.
Memory bank
designation
Pin 3
Communications Contact inputs
The factory setting is for communications (pin 3 OFF). When contact inputs are used to switch memory banks, the specified memory
bank will be used for all control points.
E5ZD-SDL Setting Display Unit Connection
Pin 4 is used to specify when an E5ZD-SDL Setting Display Unit is connected.
E5ZD-SDL connection Not connected Connected
Pin 4
The factory setting is for no connection (pin 4 OFF). Set pin 4 to ON when an E5ZD-SDL Setting Display Unit is to be connected to the E5ZE.
13
2-3SectionSetting Selectors and Switch
Startup Operation
Temperature Unit
Pin 5 is used to set the startup operation.
Startup operation Stop operation control Continue status at
power OFF
Pin 5
The factory setting is for stop operation control (pin 5 OFF). If the power is turned OFF during manual operation and pin 5 is set to ON (con-
tinuous operation), manual operation will automatically begin when the power is turned ON again. The output value will be 0%.
Pin 6 is used to set the unit for measuring temperature.
Temperature unit
Pin 6
C F
1, 2, 3... 1. Initialize the setting data.
Operation Mode Change
The factory setting is for degrees Celsius (pin 6 OFF). When the temperature unit is changed, the temperature data does not automati-
cally change, so make sure to reset the temperature using the following proce­dure.
2. Recalculate the data according to the following conversion formula and re­set the control data within the setting range. (value in F) = 1.8 x (value in C) + 32
3. Store the settings in memory.
Pins 3, 4, 5, and 8 are used to change the operation mode.
E5ZE operation mode Control mode Hardware test mode
Pins 3, 4, 5, and 8
The factory setting is for Control Mode (pins 3, 4, 5, and 8 all OFF).
14
Control Mode: Use for normal temperature control. Hardware Test Mode: Use for testing Peripheral Devices and wiring. Refer to Appendix E for details on how to use Hardware Test Mode. Outputs can
be turned ON and OFF in Hardware Test Mode regardless of the process value.

2-4 Installation

2-4-1 External and Panel Dimensions

2-4SectionInstallation
Serial Communications Model
E5ZE-8D1B (DeviceNet Interface)
Unit: mm Mounting Hole Dimensions
Four, M4
Four, M4
15

2-4-2 Mounting

Precautions
2-4SectionInstallation
Mount the Unit using the methods shown here. The Unit will not operate properly if other methods are used to mount the Unit.
Use the following mounting screws. Make sure the length of the screws is ap­propriate for the mounting panel used.
E5ZE-8B: 4 x M4 screws
Use spring and flat washers and tighten to a torque of 0.43 to 0.58 N  m {4.4 to
5.9 kgf cm}.
Do not mount the terminal block with the connectors facing upwards. Doing so may cause measurement errors.
Mounting Bracket
Mounting Models
Secure the mounting bracket
Secure the mounting bracket using the screws provided according to the ap­propriate mounting method. Tighten to a torque of 0.43 to 0.58 N m {4.4 to
5.9 kgf cm}.
Mounting screws (4 x M4 + spring and flat washers)
Panel
Secure the mounting bracket
Mounting screws (4 x M4 + spring and flat washers)
Panel
16

2-5 Power Supply and Input Wiring

2-5-1 Terminal Block

The input terminal block has been designed with a removable terminal-screw panel. When connecting the power supply or temperature sensor, the terminal­screw panel can be conveniently removed before wiring.
To remove the terminal-screw panel, loosen the two screws alternately indi­cated by A in the above diagram.
To mount the terminal-screw panel, insert it into the terminal block and secure the two screws (A) alternately.
If the terminal block has been removed from the E5ZE Thermocouple Input Model, when reconnecting make sure that the E5ZEs lot number and serial number are the same as those of the terminal block. Accuracy cannot be guar­anteed for a Unit that has been connected to a terminal block with a different lot number and serial number.
2-5SectionPower Supply and Input Wiring

2-5-2 Wiring

Always turn OFF the power supply before performing any wiring.
Be sure to check polarity when connecting the power supply and temperature
sensor.
Wire the power supply cables separately from the temperature sensor cables to prevent noise interference.
Use either crimp terminals or solder the wire ends when wiring terminals.
Tighten the terminal screws.
Wire the power lines close to the terminal block to prevent external force being
exerted on the power lines from torsion or weight.
Do not use the terminals that are marked Dont use.
Do not bend the crimp terminals after they have been connected and the
screws have been tightened.
17
Use the crimp terminals shown in the following diagram.
2-5SectionPower Supply and Input Wiring
Crimp Terminals
End Soldering
Applicable wire size: AWG 22 to 16

2-5-3 Terminal Arrangement

The following diagram shows the arrangement of terminals on the terminal block.
Terminal Block Screw Dimensions
9.5 mm
7.9 mm max.
8.1 mm
7.9 mm max.
Length of exposed wire: 6 to 8 mm
Thermocouple Platinum Resistance Thermometer
24 VDC 24 VDC
8 x M3.5 self-rising screws

2-5-4 Power Supply

ch 0
Dont use
ch 1
Dont use
ch 2
Dont use
ch 3
FG
ch 4
Dont use
ch 5
Dont use
ch 6
Dont use
ch 7
ch 0
ch 1
Dont use
ch 2
ch 3
FG
ch 4
ch 5
Dont use
ch 6
ch 7
The power supply specifications are as follows: 24 VDC (20.4 to 26.4 VDC) 15 W + 20% max.
Use a power supply with a minimum capacity of 2 A. Be sure to consider the in­rush current.

2-5-5 Ground

18
Connect the ground wire to terminal 26. Ground to 100 max.
Loading...
+ 57 hidden pages