Omron E5EZ-PRR Series Manual

Page 1
Digital Position-Proportional Controllers
E5EZ-PRR
A position proportional control model for the E5@Z-PRR series
• Just 78mm depth
• All types of input: temperature input type, analog (current, voltage) input type
• Makes use of high-visibility LCD, with three lines of 4-digit display, for simplicity and clarity
• 3 lines of display to observe PV/ SV/ MV (percentage of valve's opening), clearly displaying the state of control (operations)
• Event input enables the selection of multi configurations as well as a start/ stop function
• Alarm delay function
• Communications function
• Able to choose floating control or closed control. In floating control, position proportional control can be realized without a potentiometer
• Equipped with a manual output function (equipped with an automatic/ manual key)
Refer to the "Safety Precautions" on page 52.
Model Number Structure
Model Number Legend
1 2 3 4 5 6
1. Control method
P: Valve control
Control output 1
2.
R: Relay (OPEN)
3. Control output 2
R: Relay (CLOSE)
4. Alarm output
2: 2 alarm outputs
5. Option
Blanks: Not available 01: RS-232C 03: RS-485 B: 2 event inputs
Ordering Information
Power
Size
1/8DIN
×96×78
48 (W
×H×D)
Supply
Vol tage
100 to 240 VAC
Type
Input
Temperature
Input Type
Analog
(Current, Voltage)
Input Type
6. Input Type
T: Temperature L: Analog input (current, voltage)
Control Method
Valve Control 2
Number of
alarm
points
Communication
Function
None
RS-232C
RS-485 E5EZ-PRR203T
None
RS-232C
RS-485 E5EZ-PRR203L
Input Model
Event
None E5EZ-PRR2T
2 points E5EZ-PRR2BT
None
None E5EZ-PRR2L
2 points E5EZ-PRR2BL
None
E5EZ-PRR201T
E5EZ-PRR201L
Accessories (Order Separately)
Unit Label
Model Y92S-L1
Digital Position-Proportional Controllers E5EZ-PRR 29
Page 2
Input Range
• Thermocouples / Platinum Resistance Thermometer
Input Type
Name
Temperature range (˚C)
Setting number
Platinum resistance
thermometer
Pt100 JPt100
1800 1700 1600 1500 1400 1300 1200 1100 1000 900
850
800 700 600 500 400 300 200 100 0
-100
-200
-200
500.0
-199.9
0
1
100.0
0.0
2
500.0
-199.9 3
100.0
0.0
4
KTJELUNRSB
1300
850
-200
500.0
-20.0
6
5
-100
400.0
-20.0
7
The applicable standards for input types are as follows.
K:GB/T2814-98 R:GB/T1598-98
J,L:GB/T4994-98 S:GB/T3772-98
T,U:GB/T2903-98 B:GB/T2902-99
E:GB/T4993-98 JPt100,Pt100:GB/T5977-99
N:GB/T17615-98
settings are the default settings.
Shaded
Thermocouple
1700
1700
ES1B Infrared
temperature sensor
10
60
to
to
70˚C
1800
120˚C
115
to
165˚C
Analog input
140
to
260˚C
0 to 50mV
Usable in the following ranges by scaling:
1300
-1999 to 9999 or -199.9 to
999.9
850
600
400
-200
12
400.0
-199.9
23
-200
13
400
120
70
0
0
14
15
16
60
10
17
18
165
115
19
260
140
20
21
400
400.0
0
-200
-199.9
9
8
22
-100
10
11
• Models with Analog Inputs
[mA] Voltage [V]
Parameters
Setting
number 01234
Minimum
Set Unit (Target Value, Alarm) (Scanning, according to the location of the decimal point)
Current
4
to 20 0 to 20 1 to 50 to 50 to 10
indicates factory settings.
Optional Functions
Type Performance
RS-232C Communications' Baud Rate: 1200/2400/4800/9600/19200bps RS-485 Communications' Baud Rate: 1200/2400/4800/9600/19200bps Event
Input ON: Maximum of 1KOFF: Minimum of 100K
30 Digital Position-Proportional Controllers E5EZ-PRR
Page 3
Specifications
Ratings
Power supply voltage 100 to 240VAC, 50/60Hz Operating voltage range 85% to 110% of the designated source voltage Power consumption 10VA (10W) Sensor input Temperature input type
Thermocouple: K, J, T, E, L, U, N, R, S,B Platinum Resistance Thermometer: Pt100,JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog signal input: 0 to 50mV Analog (current, voltage) input type Current input: 4 to 20mA,0 to 20mA Voltage input: 1 to 5V, 0 to 5V, 0 to 10V
Control
output Relay output
Potentiometer Alarm output SPST-NO,250VAC 2A (resistive load)
Event input Contact input ON: 1k max., OFF: 100 k min.
Control method 2-PID control Setting method Digital setting using front panel keys Indication method 7-segment digital display and individual indicators
Other functions According to controller model Ambient operating temperature -10 to 55°C (with no icing or condensation) Ambient operating humidity 25% to 85% Storage temperature -25 to 65°C (with no icing or condensation)
(OUT1,OUT2)
input 100to 2.5K
Non-contact input
SPST-NO,250VAC 1A (including start-up currents) electrical life: 100,000 operations, minimum applicable load: 5V 10mA
electrical life: 100,000 operations, minimum applicable load: 1V, 1mA.
ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Outflow current: Approx. 7 mA per point
Character height: PV: 9mm; SV: 7mm; MV: 6.8mm
Communications Specifications
Transmission path connection RS-485: Multiple points
RS-232C: Point-to-point
Communications method (see note 1) RS-485 (two-wire, half duplex)/RS-232C Synchronization method Start-stop synchronization Baud rate 1,200/2,400/4,800/9,600/19,200bps Transmission code ASCII Data bit length (see note 2) 7 or 8 bits Stop bit length (see note 2) 1 or 2 bits Error detection Vertical parity (none, even, odd)
Flow control Not available Interface RS-485/RS-232C Retry function Not available
Block check character (BCC)
Digital Position-Proportional Controllers E5EZ-PRR 31
Page 4
Specifications
Characteristics
Indication
Influence of temperature (See note 2.)
Influence of voltage (See note 2.)
Proportional band ( P ) 0.1 to 999.9°C (unit: 0.1 EU) Integral time (I) 0 to 3999 s (in units of 1s) With floating control, 1 to 3999 s Derivative time (D) 0 to 3999 s (in units of 1s) Control period 1 to 99 s (in units of 1s) Manual reset value -10.0% to 110.0% (in units of 0.1%) Alarm settings range -1999 to 9999 (decimal point position depends on input type) Sampling period 500 ms Insulation resistance 20M Dielectric strength 2000VAC,50 or 60Hz for 1min (at different stages of charging) Vibration resistance (Error) 10 to 55Hz, 20m/s Shock resistance (Error) 100m/s Weight Controller : Approx. 260g Memory protection EEPROM (non-volatile memory) (number of writes: 100,000 operations) EMC Emission enclosure: EN55011(GB/T 6113.1,2) 1 group, type A
accuracy Thermocouple:
(displayed value Platinum Resistance Thermometer: (displayed value Analog Input: Potentiometer Input:
R, S, and B thermocouple inputs: (
±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple inputs: (
±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*
±10°C for -100°C or less for K sensors
Platinum resistance thermometer inputs: (
±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog inputs: (
±1% of FS) ±1 digit max.
min, 2 seconds (500 VDC)
2
,3 times each in 3
Emission AC mains: EN55011(GB/T 6113.1,2) 1 group, type A (see note 2) Immunity ESD: IEC61000-4-2(GB/T 17626.2) 4kV contact discharge (series 2)
±0.5 % or ±1°C, whichever is largest) ±1 digit max. (see note 1)
±0.5 % or ±1°C, whichever is largest) ±1 digit max.
±0.5% FS ±1 digit max.
±5% FS ±1 digit max.
2
for 10min each in X,Y, and Z directions
6kV air discharge (series 3)
Immunity RF interference: IEC61000-4-3(GB/T 17626.3): 10V/m, 80MHz-1GHz (series) Immunity-conducted disturbance: EC61000-4-6(GB/T 17626.6): 3V(0.15-80MHz) (series 3) Surges (shocks): IEC61000-4-5(GB/T 17626.5): 2kV power supply line (series 3)
1kV I/O signal line (series 4)
Pending standards UL61010C-1,CSA C22.2 No.1010.1 meets the requirements of EN61326,EN61010-1(IEC61010-1)
Note 1: The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and
U and L thermocouples at any temperature is 400°C max. is not specified. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is
2: For E5EZ-PRR@03-model products, in order to satisfy the conduction and emission specifications of EN61326CLASSA, a magnetic ring
(TDK:ZAT1730-0730) should be added to the communications line between the K3SC unit and the controller.
±2°C ±1 digit maximum. The indication accuracy of the B thermocouple at a temperature of
±3°C ±1 digit max.
32 Digital Position-Proportional Controllers E5EZ-PRR
Page 5
Dimensions
Note:All figures are in mm, unless otherwise stated.
Main Unit
• Dimensions of Panel's Grooves
Independent Installation (Unit: mm)
45
92
above 120
Simultaneous Multiple Installations (Unit: mm)
(48 Number of Units - 2.5)
During installation, please insert a temperature gauge into
During installation, please insert a temperature gauge into the grooves on the panel (thickness of 1 to 8 mm), and
the grooves on the panel (thickness of 1 to 8 mm), and insert the metallic components for installation into the
insert the metallic components for installation into the fixing hooks at the bottom and the top of the rear cover.
fixing hooks at the bottom and the top of the rear cover.
Please ensure that the screws to metallic components are
Please ensure that the screws to metallic components are even and locked.
even and locked.
When doing multiple installations, please ensure that the
When doing multiple installations, please ensure that the temperature gauge remains within the specified
temperature gauge remains within the specified temperature range.
temperature range.
92
• Package Content
1 Temperature Gauge
1 Temperature Gauge 2 Metallic Components For Installation
2 Metallic Components For Installation 1 Operating Manual
1 Operating Manual 1 Quality Certificate
1 Quality Certificate
During removal, please use a screwdriver
During removal, please use a screwdriver to remove the clips on the top and bottom
to remove the clips on the top and bottom of the front covering panel, and then
of the front covering panel, and then remove the temperature gauge's front
remove the temperature gauge's front panel.
panel.
• Unit Labels (Order Separately)
Y92S-L1 Type
11.8
48
Digital Position-Proportional Controllers E5EZ-PRR 33
Page 6
Wiring Terminals
• Standard insulation is applied to the temperature gauge's I/O sections. If reinforced insulation is required, connect the input and output terminals to a device without any exposed current-carrying parts, or to a device with standard insulation suitable for the maximum operation voltage of the power supply I/O section.
• For E5EZ-PRR netic ring (TDK: ZAT1730-0730) should be added to the communications line between the K3SC unit and the controller.
E5EZ-PRR
@03-model products, in order to satisfy the conduction and emission specifications of EN61326CLASSA, a mag-
100 to 240 VAC
Potentiometer
50/60Hz
Control Output 1 (OPEN Output)
Control Output 2 (CLOSE Output)
OPEN
WIPE
CLOSE
DO NOT USE
TC
DO NOT USE
mA
DO NOT USE
Analog Input
V
Event Input
1
2
3
12
13
14
EV1
EV2
Communications
RS232C RS485
SD
12
RD
13
SG
14 14
4
Communications
12
13
B( )
A( )
DO NOT USE
5
6
7
8
A
9
B
10
B
11
Pt
20
21
Alarm Output 1
22
Alarm Output 2
34 Digital Position-Proportional Controllers E5EZ-PRR
Page 7
Nomenclature
E5EZ-PRR
Operation Indicator
1. ALM1 (Alarm 1): Illuminated when Alarm 1 output is on. ALM2 (Alarm 2): Illuminated when Alarm 2 output is on.
2. OUT1, OUT2 Control Output 1(OPEN) and 2(CLOSE) Illuminated when control output 1 and/ or control output 2 are on.
3. STOP (Stop) Illuminated when operations are stopped. Illuminated during controls when time input or the start/ stop function is stopped. Not illuminated in any other cases.
4. CMW (Communications Writing Control) Illuminated when communications writing is enabled. Not illuminated in any other cases.
5. MANU (Manual Control) Illuminated during manual mode. Not illuminated in any other cases.
Mode Key
Press this level key to select parameters.
Temperature Unit
The temperature unit is displayed when the display unit parameter is set to temperature. The value selected for the temperature units parameter determines the unit displayed. When set to ˚C, C is displayed, and when set to ˚F, F is displayed.
MANU
A/M
PV
SV
MV
No. 1 Display
Displays the process value or the designated data type. Fully illuminated for approximately one second upon start-up.
No. 2 Display
Displays setting values, reading values, and input values. Fully illuminated for approximately one second upon start-up.
No. 3 Display
When valve opening display is on, it displays the percentage of the valve’s opening. No display when valve opening display is switched off.
Up Key
Every time that this key is pressed, the figure shown in No. 2 Display will increase. Changes in the displayed value accelerate as the time that the button is pressed decreases. In manual mode, pressing the
U
key will switch on control output 1 (open side
output).
Level Key
Press this key to select the setting level. The sequence of setting level selection is: operation level Adjustment level, Initial input level Communications setting level.
A
M
Down Key
Every time that this key is pressed, the figure shown in No. 2 Display will decrease. Changes in the displayed value accelerate as the time that the key is pressed decreases. In manual mode, pressing the (closed side output).
Automatic/ Manual Key
This automatic/ manual key makes the switch between automatic mode and manual mode. When this key is pressed for at least 1 second (unrelated to the time at which the key is released), the unit will switch modes.
D
key will switch on control output 2
Digital Position-Proportional Controllers E5EZ-PRR 35
Page 8
Operation
L
g
In the past, sensor input types, alarm types, and control time for controllers were set using the DIP switch. Now, these hardware settings can be performed with the parameters in the setting level. The and M keys are used to switch between setting levels, with the level determined
by the amount of time the key is pressed. Two examples of typical setup procedures follow.
• Typical Examples
Changes in Set Values
in-t
0
l.ini
M
intl
onof
l.ini
in-h
100
l.ini
in-l
l.ini
intl
onof
l.ini
M
0
M
• Typical Example 1
Input Type : Control Method : PID Control Alarm 1 Type : Upper limit of 2 (deviation) Alarm Value 1 : 20˚C (deviation) Set value : 100˚
5K thermocouple -200˚C to 1300˚C
C
When there are multi parameters, press down on the mode key until all necessary parameters have been selected.
Changes in Data
c
Changes can be
25
made to data on
0
displays with the
UD key.
0
100.
Setup Steps
Initial setting level
Connect the
power supply
Connect the power supply
Operation level
Initial setting level
c
25
0
Process value/ set value/percentage of
100..0
valve opening
Press the key for at least 3 seconds
L
Control stops
Set the input
alarm type
Operation level
alarm value
type
Set the
Set the
Check input type
Check alarm type
Operation level
Press the DU key, and designate the set value as
˚
C
100
Confirm that control is operating
Press the DU key, and set the alarm value as
˚
C
20
in-t
Input type
5
l.ini
M
alt1
Alarm
2
Alarm
l.ini
M
Press the key for at least 1 second
Control starts
c
Process value/ set value/
25
percentage of valve opening
100
100
100..0
M
While running
r-5
run
While stopped
l.ini
M
c
Alarm value
al-1
20
l.ini
M
5
1
2
L
C
run
stop
1
20
Begin operations
36 Digital Position-Proportional Controllers E5EZ-PRR
Be
in operations
Page 9
• Typical Example 2
prog
Input type : Control method
9T thermocouple -200˚C to 400˚C
: PID control Execute AT (auto-tuning) to calculate the PID constant Alarm 1 type : Upper limit of 2 Set value : 150˚
C
Setup steps
Connect the
power supply
Initial setting level
Set the input
specifications
Set the alarm type
PV/SP After executing AT
Adjustment level
Execute AT
Operation level
Set the alarm value
Begin operations
While executing AT
After AT
While executing AT
25
100
100..0
25
100
100..0
at
off
l. adj
at
on
l. adj
Connect the power supply
Operation level
Initial setting level
Press the DU key, select input type
Check the alarm type
Operation level
DU
Press the key, designate the set value as
˚
150
C
Adjustment level
After AT
(Auto-tuning)
Operation level
Confirm the set value as
C
150˚
Confirm that controls are operating
Press the DU key, and set the alarm value as
C
30˚
c
Process value/ set
25
value/ percentage
0
of valve opening
100..0
Press the key for at least 3 seconds
Control stops
in-t
9
Input type
l.ini
M
alt1
Alarm1
2
Ty pe
l.ini
M
Press the key for at least 1 second
Process value/
c
25
set value/ percentage
150
100..0
of valve
Press the key for less than 1 second
at
Execute AT:
off
Cancel AT:
l. adj
Press the key for less than 1 second
Control starts
c
Process value/
25
set value/
150
percentage of
100..0
valve opening
M
While running
r-5
run
run
While stopped
stop
M
c
al-1
Alarm
30
value 1 30
M
L
9
2
L
150
L
ON
OFF
L
ram execution
Start
Digital Position-Proportional Controllers E5EZ-PRR 37
Page 10
Setting Level Configuration and Panel Key Operations
Parameters are split into groups, which are referred to as levels. Each of the set values (set items) in these levels are referred to as parameters. E5EZ-PRR parameters are categorized into the following 7 levels:
Power ON
Starting in manual mode
Press A key for at least 1 s.
Manual Mode
See note 2.
c
a-m
Press the for at least 1 s; display will flash.
Press the L key for at least 3 s while a-m is displayed.
Operation Level
key
L
Starting in automatic mode
Press for at least 1 s.
Press the
key for
L
at least 1 s.
See note 1.
Adjustment Level
key
L
c
25
100
100.0
Press the L key for at least 1 s; display will flash.
Press the
at least 3 s.
Control stops.
L
key for
Press the
+ M
L
keys for at least 1 s.
L
PV display flashes
c
25
100
100.0
key
L
for at least 3 s
key:
+
M
+
M
See note 2.
Protect Level
The amount of time that a key must
be pressed can be changed under protect level switching time (advanced function setting level).
Manual Control Level
Initial Setting Level
Press
key
L
for at least 1 s.
Advanced Function
Press
key
L
for at least 1 s.
Input password. Set value −169
Communications Setting Level
Setting Level
Control in progress
Control stopped
Not displayed for some models
Level change
Note1:When returning from the initial setting
operation level's initial value will be displayed.
2:When returning from the protect level to the operation level, the
operation level's initial value will be displayed.
Protect level Operation level Adjustment level Manual control level Initial setting level
Advanced function setting level
Communications setting level
: Set the initial/ communications protection parameter in protect level to 0, in order to activate the advanced function setting level.
: Indicates items that can be set. In these cases, the initial setting level, communications setting level, and advanced function setting level can only be used when controls are stopped. Please take note of the fact that when any one of these three levels is selected, the controller's output will be stopped.
With the exception of operation level, the present level will be on display. No. 3 Display will show the following when switching between set values
:
Third Display Level's Name
Manual MV Manual control level l.prt Protect level No display Operation level
l.adj Adjustment level l.ini Initial setting level l.com Communications setting level l.adv Advanced function setting level
lever to the operation level, the
Control operating Control stops
38 Digital Position-Proportional Controllers E5EZ-PRR
Page 11
Descriptions of Each Level
L
L
LLL
L
• Protect Level
• Operation Level
• Adjustment Level
• Manual Control Level
• In order to switch to this level, it is necessary to press the and
M keys simultaneously for at least 3 seconds. This level is used to prevent unnecessary or accidental revisions to the parameters. The protected level is not displayed, so that no changes can be made to parameters within this level.
• Once a power supply is connected, this level is displayed. It is possible to switch from this level to protect level, initial setting lev­el, and adjustment level.
During regular operations, this level is selected. It is possible to
view process value and MV during operations, as well as viewing and revising set values, alarm values, and upper and lower limits.
• In order to switch to this level, press the key for less than 1 second.
Input in this level is used in controlling set values and shifted val-
ues. This level contains parameters used in setting up AT (auto­tuning), communications writing enabling/ disabling, hysteresis, multi-SP, input shift, and PID constants. It is possible to switch from this level to the peak parameters in the initial setting level, protect level, or operation level.
• Pressing the A key for at least 1 second in operations/ adjust­ment level will place you in manual mode and bring you to man­ual control level. During manual operations, nothing besides process value/ set value/ percentage of valve opening (manual MV) can be displayed. In manual control, with process value/ set value/ percentage of valve opening (manual MV) displayed, pressing the A key for at least 1 second will move you into auto­matic mode and switch you to the operation level, displaying op­eration level's initial data. In this mode, it is possible to perform MV manual operations.
• Initial Setting Level
• Advanced Function Setting Level
• Communications Setting Level
• To switch to this level, it is necessary to press the key in op­eration level or adjustment level for at least 3 seconds. One sec­ond later, the PV display will flash. This level is used for designating input types, selecting control methods and control times, as well as setting direct/ reverse operations and alarm types. From this level, it is possible to switch to the advanced function setting level or communications setting level. Press the
key for at least 1 second to return to operation level. Press the key for less than 1 second to switch to the communications
setting level.
• In order to activate the advanced function setting level, set protect level's initial setting/ communications protection to 0, and then in­put the password (-169) in the input initial setting level.
It is possible to switch from this level to the initial setting level. This level is used to set the display mode, event input assign-
• ment, standby sequence, alarm hysteresis, and alarm delay.
• To switch to this level, press the key in the initial setting level for less than 1 second. When using the communications function, the conditions of communication are to be set in this level. Com­munications with a personal computer (host computer) allows set values to be read and written, and manipulated variables to be monitored.
Digital Position-Proportional Controllers E5EZ-PRR 39
Page 12
Setting the Type of Input
Types of input include thermocouple, platinum resistance thermometer, infrared temperature sensor, and analog inputs. Please set your input type in accordance with the sensor to be used. Product spec­ifications also include multi input types, such as thermocouples/ plastic resistance thermometers, and analog input types, resulting in differences between set values. Please confirm the model that you are using.
Table of Input Types
in-t
5
l.ini
Input Types 5
Input Type Name Set value
0 -200 to 850 (°C) / -300 to 1500 (°F)
Platinum Resistance Thermometer
Thermocouple
Infrared temperature sensor,
ES1B
Analog Input 0 to 50 mV 21
Pt100
JPt100
K
J
T
E 10 0 to 600 (°C) / 0 to 1100 (°F) L 11 -100 to 850 (°C) / -100 to 1500 (°F)
U
N 13 -200 to 1300 (°C) / -300 to 2300 (°F) R 14 0 to 1700 (°C) / 0 to 3000 (°F)
S 15 0 to 1700 (°C) / 0 to 3000 (°F) B 16 100 to 1800 (°C) / 300 to 3200 (°F)
10°C to 70°C 17 0 to 90 (°C) / 0 to 190 (°F)
60°C to 120°C 18 0 to 120 (°C) / 0 to 240 (°F)
115°C to
165°C
140°C to
260°C
1 -199.9 to 500.0 (°C) / -199.9 to 900.0 (°F) 2 0.0 to 100.0 (°C) / 0.0 to 210.0 (°F) 3 -199.9 to 500.0 (°C) / -199.9 to 900.0 (°F) 4 0.0 to 100.0 (°C) / 0.0 to 210.0 (°F) 5 -200 to 1300 (°C) / -300 to 2300 (°F) 6 -20.0 to 500.0 (°C) / 0.0 to 900.0 (°F) 7 -100 to 850 (°C) / -100 to 1500 (°F) 8 -20.0 to 400.0 (°C) / 0.0 to 750.0 (°F) 9 -200 to 400 (°C) / -300 to 700 (°F)
22 -199.9 to 500.0 (°C) / -199.9 to 700.0 (°F)
12 -200 to 400 (°C) / -300 to 700 (°F) 23 -199.9 to 500.0 (°C) / -199.9 to 700 (°F)
19 0 to 165 (°C) / 0 to 320 (°F)
20 0 to 260 (°C) / 0 to 500 (°F)
Range of Temperature Input
Set
The scaling usage range is either
-1999 to 9999 or -199.9 to 999.9
Initial value of "5"
Input Type
Current Input
Voltage Input
Analog Input Type
Specifica-
tions
4 to 20mA
0 to 20mA 1
1 to 5V 2
0 to 5V 3
0 to 10V 4
Initial value of "0"
40 Digital Position-Proportional Controllers E5EZ-PRR
Set
value Set Range of Input
0
Use the following scales based on the range of measurements:
-19999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999
Page 13
Alarm Types
• The conditions of alarm output are jointly determined by Alarm Type and Alarm Hysteresis.
Below is an explanation of the alarm type, alarm value, upper alarm limit, and lower alarm limit parameters.
alt1
2
l.ini
Alarm1
Ty pe 2
Set
values
0
1
See note 1.
2
3
4
See note 1.
5
See note 1.
6
7
8
9
10
11
Type
When X is positive When X is negative
Alarm function OFF
Upper-and lower-limits
Upper limits
Lower limits
Upper-and lower-limits
Upper-and lower-limit with standby sequence
Upper-limit with standby sequence
Lower-limit with standby sequence
Absolute-value upper-limits
Absolute-value lower-limits
Absolute-value upper-limit with standby sequence
Absolute-value lower-limit with standby sequence
Alarm output operation
Output OFF
L H
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
L H
X
0
0
0
0
SP
X
SP
SP
SP
L H
SP
X
SP
SP
X
X
X
X
(See note 5)
See note 2.
ON OFF
ON OFF
See note 3.
See note 4.
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Note:1. Upper and lower limits can be set independently for each alarm point, represented by L
and H. The set values are 1, 4, and 5.
2. Set value: 1, Upper-and lower-limit
Case 1 Case 2 Case 3 (Always ON)
L H SP SP L H
H< 0.L >0
|H| < |L|
H> 0.L <0
|H| > |L|
L SP H
H LSP
SP H L
3. Set value: 4, Upper-and lower-limit range
Case 1 Case 2 Case 3 (Always OFF)
L H SP SP L H
H< 0.L >0
|H| < |L|
H> 0.L <0
|H| > |L|
L SP H
H L SP
SP H L
H< 0.L <0
4. Set value: 5, Upper-and lower-limit with standby sequence
*for the upper and lower alarm limits above
- In case 1 and 2, if there are any overlaps in the upper and lower limits for hysteresis, the alarm will always be OFF.
Example of case 1 and case 2: in case 3, the alarm will always be OFF.
5. Set value: 5, Upper-and lower-limit with standby sequence If there are any overlaps in the upper and lower limits for hysteresis, the alarm will always
be OFF.
There are alarm types 1 to 2 (initial setting level), and settings should be made independently for each alarm. The initial value is 2: upper limit.
Digital Position-Proportional Controllers E5EZ-PRR 41
Page 14
Parameters
Parameters related to setting items for each level are marked in boxes in the following flowchart and brief descriptions are given as required. After finishing each setting, press the mode key to return to the beginning of each level.
Power ON
Starting in manual mode
Press A key for at least 1 s.
Manual Mode
See note 2.
c
a-m
Press the for at least 1 s; display will flash.
Press the L key for at least 3 s while a-m is displayed.
Operation Level
key
L
Starting in automatic mode
Press for at least 1 s.
Press the
key for
L
at least 1 s.
See note 1.
Adjustment Level
key
L
c
25
100
100.0
Press the L key for at least 1 s; display will flash.
Press the at least 3 s.
Control stops.
L
key for
Press the
+ M
L
keys for at least 1 s.
L
PV display flashes
c
25
100
100.0
key
L
for at least 3 s
key:
+
M
+
M
Manual Control Level
Initial Setting Level
Press
key
L
for at least 1 s.
Press
key
L
for at least 1 s.
Input password. Set value −169
Advanced Function Setting Level
Note 1: When returning from the initial setting lever to the operation level, the
operation level's initial value will be displayed.
2: When returning from the protect level to the operation level, the oper-
ation level's initial value will be displayed.
Display
c
No. 1 Display
25
0
100
0
No. 2 Display
No. 3 Display
Communications Setting Level
See note 2.
Protect Level
The amount of time that a key must
be pressed can be changed under protect level switching time (advanced function setting level).
Control in progress
Control stopped
Not displayed for some models
Level change
Advanced function
setting level
Press the key for at least 1 s
Initial setting level
Note:
to select the advanced function
Press the key for at least 1 s
Press the key for at least 3 s
setting level, you must input the password (-169) in the initial setting level.
42 Digital Position-Proportional Controllers E5EZ-PRR
Powe r ON
Operation level
Press the key for less than 1 s
Adjustment level
Press the key for less than 1 s
Page 15
Parameters
• In each level, if you press the mode key on the final parameter, you will return to the parameter at the top of the level.
Advanced function setting level
init
Parameter initialization
off
l.
Select the number of
en-m
multi-SP used, with 2
1
or 4 as the designated
l.
value
Event input assignment 1
none
l.
Event input assignment 2
stop
l.
ospu
Multi-SP uses
off
on off
l.
Standby sequence reset
rest
method Conditions for resetting
a
following the cancellation of
l.
a standby sequence
Alarm 1 open in alarm
al1n
n-o
l.
C
alh1
Alarm 1 hysteresis
02
l.
Alarm 2 open in alarm
al2n
n-o
l.
C
alh2
Alarm 2 hysteresis
02
l.
α
alfa
2 PID parameters
0. 65
l.
Input digital filter
inf
Set the time constant,
00
with a unit of s
l.
Multi-value setting and stop/run input
SP alarm output 1 activation status
SP alarm output 2 activation status
a1lt
Alarm 1 latch
off
l.
a2lt
Alarm 2 latch
off
l.
prlt
Move to protect level time
3
l.
sero
Input error output
off
l.
cjc
Cold junction
on
compensation method
l.
MB command logic switching
off
l.
a1on
Alarm 1
0
ON delay
l.
a2on
Alarm 2
0
ON delay
l.
a1of
Alarm 1
0
OFF delay
l.
a2of
Alarm 2
0
OFF delay
l.
Additional MV for stop/error
off
l.
C
p-db
Process value dead band
0
l.
Activate alarm latch
Setting the alarm output’s ON delay/ OFF delay
Initial setting level
in-t
Input type
5
l.ini
in-h
Scaling upper limit
100
l.ini
in-l
Scaling lower limit
0
l.ini
dp
Decimal point
0
l.ini
d-u
Temperature unit ˚C / ˚F
c
is Celsius, and is Fahrenheit
l.ini
C
sl-h
SP upper limit
1300
l.ini
C
sl-l
SP lower limit
-200
l.ini
Direct / reverse operation Direct operation: on-d Reverse operation: or-r
l.ini
alt1
Alarm 1
2
l.ini
alt2
Alarm 2
2
l.ini
Closed / floating
clfl
Floating: flot
flot
Closed: clos
l.ini
Electro-mechanical calibration
calb
Electro-mechanical calibration: on
off
Cancel: off
l.ini
Only used in analog input settings
Limit the set point
Select alarm mode
Additional process value display First display off in operation level
off
l.
Automatic return of display mode
l.
ret
off
Pressing a key on the operation panel automatically returns to operation level
mot
Travel time
Valve opening display
on
l.
Manual MV
oanl
Limits in effect
on
l.
30
l.ini
Switch to advanced function setting level To switch to the advanced function setting level, the initial setting/
0
communications protection parameters must be set to 0.
Digital Position-Proportional Controllers E5EZ-PRR 43
Page 16
Operation level
Adjustment level
C
C
C
C
C
C
C
m-sp
sp-m
al-1
al1h
al1l
al-2
25
Process value
25
Process value/ set point/ valve
0
open percentage
0100.
Multi-SP set point setting
0
SP ramp set point
0
Run/ stop Run: run Stop: stop
Alarm value 1
0
Upper-limit
0
alarm value 1
Lower-limit
0
alarm value 1
Alarm value 2
0
The "add process value display" parameter must be on.
Set either of these parameters
C
C
C
C
C
C
C
l.adj
cmwt
off
l.adj
sp-0
l.adj
sp-1
l.adj
sp-2
l.adj
sp-3
l.adj
in5
l.adj
in5h
l.adj
in5l
l.adj
at
off
0
0
0
0
00
00
00
Execute / cancel AT adjustment AT on: on AT off: off
Communications writing Enabled: on Disabled: off
SP 0
SP 1
SP 2
SP 3
Temperature input shift values
Upper-limit temperature shift (When using a Infrared temperature sensor)
Lower-limit temperature shift (When using a Infrared temperature sensor)
SP used by Multi-SP
1 point shift
2 point shift
Stopped MV Hold: hold Open: open
l.adj
Close: close
PV error MV Hold: hold Open: open
l.adj
Close: close
C
sprt
SP ramp set value
off
l.adj
ol-h
MV upper limit
100.0
l.adj
ol-l
MV lower limit
0. 0
l.adj
db
Position’s proportional dead band
20
l.adj
oc-h
Open/ close hysteresis
0. 8
l.adj
MV limit value
C
C
al2h
al2l
Upper-limit
0
alarm value 2
Lower-limit
0
alarm value 2
Set either these parameters
C
l.adj
233
l.adj
l.adj
p
80
i
d
40
Proportional band
Integral time (Unit: seconds)
Derivative time (Unit: seconds)
PID settings
44 Digital Position-Proportional Controllers E5EZ-PRR
Page 17
Protect level
Operation/ Adjustment Protection
oapt
Operation /
0
adjustment protection
l.prt
Initial setting /
icpt
communications
1
protection
l.prt
wtpt
Setting change protection
off
l.prt
keyp
Automatic/ manual
off
key protection
l.prt
The relationship between the set values and the range of protection is as shown below.
Mode
Set Values
0123
Present value ❍❍❍❍
Set value
: Can be displayed/ changed
: Can be displayed
× : Cannot be displayed/
no changes in level allowed
Others × ×
Adjustment level × × ×
• When the set value is 0, there is no protective function.
• The initial value is 0.
Initial Setting/ Communications Protection
This protect level restricts movement to the initial setting, communications setting, and advanced function setting levels
.
Set Value Initial setting level Communications
0
1
Able to switch (able to switch to the advanced functions setting level)
Able to switch (unable to switch to the advanced functions setting level)
Able to switch
Able to switch
2 Able to switch Unable to switch
• Default setting: 1.
Setting Change Protection
Communications setting level
u-no
Communications
1
Unit No.
l.com
bps
Baud rate
96
l.com
len
Data bits
7
l.com
sbit
Stop bits
2
l.com
Communication parity
l.com
Places restrictions on changes to settings with keys.
: Able to use unit keys to change settings.
off
on: Unable to use unit keys to change settings, but this level can be changed.
Automatic/ Manual Key Protection
Set Value Automatic/ Manual Operations
off Automatic/ Manual Able to switch
on Automatic/ Manual Unable to switch
• Initial value is "off".
Setting Communications Parameters
Configures the E5EZ-PRR's communications specifications, so that its communications with the host computer can be configured properly. In a layout where one point communi­cates with multiple points, in addition to all of the communication unit numbers, all other settings should match. Each unit must have a single communication unit number set for it.
Parameters Character
Communications Unit No.
display
u-no 0 to 99 1 None
Baud rate bps
Data bits len 7,
Stop bits sbit 1,
Communication parity
prty None, even, odd
Set
(monitor) value
1.2,
2.4, 4.8,
9.6,
19.2
Setup Initial
1. 2,
2. 4 ,
9. 6
4. 8,
19. 2
value
9.6 Kbps
8 7 Length
2 2 Bit
none,
even
odd
Even None
Unit
Digital Position-Proportional Controllers E5EZ-PRR 45
Page 18
Trouble shooting
When an error occurs, the main display alternately shows an error signal and the current item for display.
This section explains how to inspect an error signal, as well as corresponding rectification measures.
5.err
Input Error
• Meaning
• Rectification Measures
• Operations with Errors
The figure inputted has exceeded the designated input range (the designated range is between -1999 (-199.9) to 9999 (999.9)).
Check to make sure that the input line has not been connected incorrectly, unplugged, a short-circuit, or is incompatible with this input type.
If there are no problems with the line type or the connection, power off and then restart the unit. If the display remains unchanged, it will be necessary to change the E5EZ-PRR. If the display is recovered, the root of the problem may have been that noise from the energy flow was affecting the control system. Check for any such noise.
The control output will be determined according to the designated value for error MV.
The alarm output function will be the same as it is when the upper limit is crossed.
After setting I/O error (advanced function setting level) on, alarm 1's output will be activated in cases of error.
In process value or process value/ set value/ valve open percentage display mode, error information will be displayed.
Display Range Exceeded
• Meaning
• Operations with Errors
46 Digital Position-Proportional Controllers E5EZ-PRR
Even though this is not really an error, when the range of control exceeds the range of display (-1999 (-199.9) to 9999 (999.9)), and the process value is beyond the range of display, this signal will appear.
Will display [[[[ when the figure is less than -1999 (-199.9).
Will display ]]]] when the figure is more than 9999 (999.9).
Control will continue and operations will remain normal. In process value or pro­cess value/ set value/ valve open percentage display mode, error information will be displayed.
Page 19
S. Err indicator
-1999
(-199.9)
Value display
Input indicator range
Display range
S. Err indicator
9999
(999.9)
cccc indicator
Value display
Input indicator range
-1999
(-199.9)
Display range
S. Err indicator
9999
(999.9)
S. Err indicator
S. Err indicator S. Err indicator
e111
cccc indicator cccc indicator
Value display
-1999
(-199.9)
Input indicator range
Display range
Value display
-1999
(-199.9)
Input indicator range
Display
range
(999.9)
Memory Errors
• Meaning
• Rectification Measures
• Operations with Errors
----
Potentiometer Input Errors
9999
S. Err indicator
9999
(999.9)
There has been an error in the internal memory.
Power off and then restart the unit. If the display remains unchanged, it will be necessary to change the E5EZ-PRR. If the display is recovered, the root of the problem may have been that noise from the energy flow was affecting the control system. Check for any such noise.
Control output and alarm output will be shut off.
• Meaning
• Rectification Measures
• Operations with Errors
err
Electro-Mechanical Calibration Error
• Meaning
• Rectification Measures
• Operations with Errors
Errors appear in potentiometer input. Valve opening has exceeded its regular range of -10% to 110%.
Check to see if there have been any wiring errors, burnouts, or short-circuits in the potentiometer.
If there are no problems with the wiring, you can restart the power supply. If the display remains unchanged, it will be necessary to change the E5EZ-PRR.
If the display, the root of the problem may have been interference, which should be avoided in the future.
The control output will be determined according to the designated value for error MV.
Alarm output will operate as normal.
Electro-mechanical calibration was not properly completed.
After confirming the potentiometer and the wiring of the motor driving valve, per­form electro-mechanical calibration again.
Control output and alarm output are OFF.
Digital Position-Proportional Controllers E5EZ-PRR 47
Page 20
Ceramic Furnace Position Proportional Control
Reading the extent of the valve's opening with a potentiometer, and using open and close tuning control is referred to as position proportional con­trol or on/ off servo control.
Examples of Application
When using position proportional methods to control gas combustion furnace valves, position propor­tional control should be applied. See the following figure for measurement devices:
Temperature Input
Analog Signal Input
Potentiometer
SP
SP SP Ramp
OUT1
PV
PID
MV
OUT2
Set Value
E5EZ-PRR
8888
8888 8888
Ramp
SP ramp's set value
SP ramp as time unit
Time
RUN
PV
SV
MV
MANU
A
M
Temperature Sensor
Burner
The SP ramp function allows limits to be placed on temperature changes
Note:
which control the temperature within a specific range. This is useful for ceramic furnace, in which severe temperature changes may cause dam­age or corruption.
48 Digital Position-Proportional Controllers E5EZ-PRR
Page 21
Wiring
L
L
L
Input should be connected to terminals 9, 10, and 11 depending upon input type. The Out 1 ter­minal links to the position proportional valve's open side and the Out 2 terminal links to its closed side.
Settings
12
13
14
Ceramic kiln (combustion)
Sensor
CWO
CLOSE
OPEN
Valve
1
2
3
4
5
6
7
8
Burner
Position proportional valve
9
10
11
Select a position proportional control model, and perform floating control using a position propor­tional valve with a travel time (time from being totally open to being totally closed) of 45 seconds. Then, use the SP ramp function to make gradual changes to the process value at rates of
10.0°C/ minute. The relevant data and content of the settings are as shown below: Direct/ reverse operation = or-r: Reverse operation (initial value) Closed/ floating = flot: Floating (initial value) Trave l t im e = SP ramp set values = Here, the travel time and SP ramp values are set. Initial values are used for all others.
45 seconds "10"
20
21
22
in-t
5
ini
l.
mot
30
ini
l.
Operation level
25
0
0
100
.
Adjustment level
at
off
adj
l.
sprt
0
adj
l.
Travel time
45
U
Process value/ set value/ percentage of valve opening
0
25
U
SP is the ramp’s set value
0
1
U
1. Press the level.
2. Press the M key multiple times, and select mot: travel time. Press the U key, making the set value 45.
3. Press the value/ percentage of valve opening will be displayed. Press the U key, setting the target value as 250.
4. Press the
5. Press the M key multiple times, and select sprt: SP ramp set value. Press the U key, mak- ing the set value 10.
key for at least 3 seconds to switch from the operation level to the initial setting
key for at least 1 second, returning to the operation level. The process value/ set
key for less than 1 second to switch from operation level to → adjustment level.
Digital Position-Proportional Controllers E5EZ-PRR 49
Page 22
Adjustment
For adjustments to PID, please execute AT.
■ Fixed Settings for Position Proportional Control
• Closed/ Floating
• Electro-Mechanical
Calibration and Travel Time
• Position Proportion Dead
Band Switch and Position Proportional Hysteresis
After selecting position proportional control, it is possible to use closed/ floating, electro-mechanical calibration, travel time, position proportional dead band, switch hysteresis, potentiometer input error, and process value dead band.
• Closed Control Connect the potentiometer to perform valve opening feedback control.
• Floating Control Control in which no feedback is provided by a potentiometer on the valve's opening, so that control can be performed without a potentiometer.
Just like in closed control, or in floating control where a valve's opening is to be monitored, electro-mechanical calibration is to be performed when a potentiom­eter is connected. The valve's travel time, from being completely open to being completely closed, is also set for self-measuring.
In cases of floating control where a potentiometer is not connected, it will be nec­essary to manually set the travel time. Set the time required for the valve to go from complete openness to complete closure under travel time.
The valve output period (the time it takes the OPEN output and CLOSE output switch to go from ON to OFF) is set as the position proportional dead band, and hysteresis is set as switch hysteresis.
Its relationship with the extent of the valve's opening is as shown below:
• PV Dead Band
• Potentiometer Input Error
Switch position proportional hysteresis
Dead Band
ON
OFF
-100%
When the process value is within the PV dead band, control is controlled accord­ing to the logic that the process value = set value. This function is meant to pre­vent unnecessary output in cases where the process value approaches the set value.
When the potentiometer produces an error during closed control, this is a func­tion that chooses to stop control or switch to floating control, allowing control to continue.
0
MV-Extent of Opening
100%
50 Digital Position-Proportional Controllers E5EZ-PRR
Loading...