Omron E5ER-T, E5AR-T specifications

Programmable Digital Controller
E5AR-T/E5ER-T
A new High-speed, High-precision Digital Controller that is Programmable!
• Create up to 32 programs with up to 256 segments total.
• Coordinated operation for up to four channels with one Dig­ital Controller.
• High-speed sampling at 50 ms.
Refer to “Precautions” on pages 24 and 25.
Features
Up to 32 Programs
You can create up to 32 programs with up to 8 segments each, or you can create up to 8 programs with up to 32 segments each. Either way, you get up to a total of 256 segments of programming. This fea­ture is ideal for testing equipment to make a variety of settings.
Up To
32 Programs
100.0
SP
Segment 1 Segment 2 Segment 3 Segment 4 Segment 6Segment 5
100.0
50.0
70.0
SP
Segment 1 Segment 2 Segment 3 Segment 4
100.0
50.0
5: 00 5: 00 5: 00 5: 00 5: 00
5: 00
50.0
5: 00
SP
5: 00 5: 00 5: 00 5: 00 5: 00
5: 00
5: 008: 00 10: 00
Time (hours and minutes)
Segment 6Segment 5Segment 4Segment 3Segment 2Segment 1
Time (hours and minutes)
Time (hours and minutes)
Coordinated Operation for Up to Four Channels with One Digital Controller
Up to four channels are supported for analog control in a compact­sized body to contribute to downsizing control panels.
High-speed and High-resolution Performance
Sample at the high speed of 50 ms for 4 channels to achieve stable control even for items requiring high-speed response. And, the reso­lution is 0.01
°C for a Pt input. Temperature, humidity, and other fac-
tors for ambient testing equipment can be measured, variations detected, and data logged at a high resolution.
SP
Easy Settings from a Computer Using the CX-Thermo
The CX-Thermo setting software (version 3.1 or higher) lets you set, edit, and transfer parameters all at once.
High-speed sampling
50 ms
High-speed startup in a few seconds
Time
Four
Channels,
One Digital
Controller
Note: Coordinated operation
refers to a slave operating using the same program as the master.
RoHS Compliance for World-wide Application
Available Soon: It will soon be possible to easily setup and monitor
screens online using the SAP Library.
Programmable Digital Controller E5AR-T/E5ER-T 1
Product Lineup
Programmable
E5AR-T
(96 × 96 mm)
Page 4
Basic models
(1 loop)
1 loop for standard control/ 1 loop for heating and cooling control
2-loop models
2 loops for standard control/ 1 loop for heating and cooling control 1 loop for cascade control 1 loop for control with remote SP 1 loop for proportional control
4-loop models
4 loops for standard control 2 loops for heating and cooling control
Control valve
control models
1 loop for position-proportional control
4 auxiliary outputs, 2 event inputs, 2 outputs (control/transfer)
10 auxiliary outputs, 10 event inputs, RS-485 communications, 2/4 outputs (control/transfer)
4 auxiliary outputs, 4 event inputs, RS-485 communications, 2 outputs (control/transfer)
10 auxiliary outputs, 8 event inputs, RS-485 communications, 4 outputs (control/transfer)
10 auxiliary outputs, 8 event inputs, RS-485 communications, 4 outputs (control/transfer)
4 auxiliary outputs, 4 event inputs, 2 relay outputs (open, closed)
10 auxiliary outputs, 8 event inputs, 2 relay outputs (open, closed) RS-485 communications, 1 output (transfer)
Programmable
E5ER-T
(48 × 96 mm)
Page 15
Basic models
(1 loop)
1 loop for standard control/ 1 loop for heating and cooling control
2-loop models
2 loops for standard control/ 1 loop for heating and cooling control 1 loop for cascade control 1 loop for control with remote SP 1 loop for proportional control
Control valve
control models
1 loop for position-proportional control
4 auxiliary outputs, 2 event inputs, 2 outputs (control/transfer)
4 auxiliary outputs, 2 event inputs, RS-485 communications, 2 outputs (control/transfer)
2 auxiliary outputs, 4 event inputs, RS-485 communications, 2 outputs (control/transfer)
2 auxiliary outputs, 4 event inputs, 2 relay outputs (open, closed)
4 auxiliary outputs, no event input, 2 relay outputs (open, closed) RS-485 communications, 1 output (transfer)
2 Programmable Digital Controller E5AR-T/E5ER-T
Peripheral Devices
AGHTURW
Connection Example for E5@R Series, Temperature Sensors, and SSRs
Voltage output terminal (for driving SSR)
Analog values representing temperature,
flowrate, or concentration
Converter, digital panel meter, flowrate meter, non-contact temperature sensor, displacement sensor, etc.
E52
Controller
Direct connection possible
E5AR-T/E5ER-T
E5AR-T
SUB1 SUB2 SUB3 SUB4 WAIT FSP
PV
SV
CMW MANU
OUT2 OUT3 OUT4 RST RSP HOLD
OUT1
PF1
PF2
RUN/RST
PRG. SEG
SSR
INPUT LOAD
Max. No. of SSRs connectable in parallel
5 Units
5 Units
4 Units
5 Units
Load
Heater
Load power
G3PC (SSR with failure detection)
240 VAC (20 A)
Rated input voltage: 12 to 24 VDC
Compact and slim models with a built-in heat sink
G3PB (Single-phase)
240 VAC (15 A, 25 A, 35 A, 45 A)
Rated input voltage: 12 to 24 VDC
Compact and slim models with a built-in heat sink
G3PB (Three-phase)
240 VAC/400 VAC (15 A, 25 A, 35 A, 45 A)
Rated input voltage: 12 to 24 VDC
Simultaneous three­phase control with a built-in heat sink
A G
H
T
A G
H
T
A A
A
G G
G
H
HT
HT
T U
U
R
R
W
W
N
N
AG
BVC
BVC
H
T
D
D
U
S
S
RW
N
BVC
AGHTURW
D
S
NBVC
AGHTURWNBVC
DS DS
AG
HT
U R
W
N
BVC
A
A
G
G
D
H
H
S
T
T
U
U
R
R
W
W
A G
H
T
A G
H T
A
G
A
H
G
T
H
T
A
G
A
H
G
T
H
T
A
G H
A
T
G H
T
A
G H
T
G3PA 240 VAC (10 A, 20 A, 40 A, 60 A) 400 VAC (20 A, 30 A, 50 A)
Rated input voltage: 5 to 24 VDC
Compact and slim models with a built-in heat sink
A A
A
A
G
A A T
O N
O
M
R O N
A
G H
T U
R
A
G
A G H
T U
R W
N B V
C
A G
H T
Calculating the Maximum Number of SSRs Connectable in Parallel
A: The maximum load current of the
voltage output (for SSR drive) of the Digital Controller is 40 mA (E5AR-T). For the E5AR-TQQE3MW-FLK and E5AR-TQQE3MWW-FLK, however, the maximum load current is 21 mA.
B: SSR’s input impedance is 7 mA for
G3NA
In this case, the maximum number of SSRs connectable in parallel would be as follows:
A/B = 5
The maximum load current in the connection example is 40 mA.
E5ER-T
SUB1 SUB2 SUB3 SUB4 WAIT
FSP
CH2 CMW MANU
OUT1
OUT2
RST RSP
HOLD
PF2PF1
RUN/RST
E5ER
PV
SV
PRG. SEG
5 Units
2 Units
240 VAC (5 A, 10 A, 20 A, 40 A) 480 VAC (10 A, 20 A, 40 A)
Rated input voltage: 5 to 24 VDC
Standard models with screw terminals
240 VAC (5 A, 10 A, 20 A)
Rated input voltage: 12 VDC
Compact and low-cost models with tab terminals
G3NA
G3NE
A
A
G
H
T
O
AGHTU
U
M
AGHTURWNBVCD
R
R
W
O
AGHTURWNBVCD
N
N B
AGHTURWNBVCD
V
C
A
A
SIOLHGF
G
H
SIOLHGF
T
U
A
SIOLHGF
R
W
N
B
V
AGHTU
C
A
G3NH
440 VAC (75 A, 150 A)
8 Units
Rated input voltage: 5 to 24 VDC
For controlling high­power heaters
Programmable Digital Controller E5AR-T/E5ER-T 3
Programmable Digital Controller
E5AR-T
A new High-speed, High-precision Digital Controller that is Programmable!
• Create up to 32 programs with up to 256 segments total.
• Coordinated operation for up to four channels with one Digital Controller.
•0.01°C High resolution for Pt input.
• High-speed sampling at 50 ms.
• Settings easily made from a computer using the CX-Thermo.
• RoHS compliance for world-wide application.
Refer to “Precautions” on pages 24 and 25.
Model Number Structure
Model Number Legend
E5AR-T@@@@@@@@-@@@
2345 96781
1. Control method
Blank:Standard or heating/cooling control P: Position proportional control
2. Output 1
R: NO relay output + NO relay output Q: Pulse output/current output + pulse output C: Current output + current output
3. Output 2
R: NO relay output + NO relay output Q: Pulse output/current output + pulse output C: Current output + current output
4. Auxiliary Outputs
Blank:None 4: NO relay output + NO relay output E: 5 transistor outputs + 5 transistor outputs
5. Communications
Blank:None 3: RS-485 communications
6. Optional function
Blank:None D: 4 event inputs M: 4 event inputs + 4 event inputs
7. Input 1
B: Multi-input and 2 event inputs F: Multi-input and FB (Potentiometer input) W: Multi-input and multi-input
8. Input 2
Blank:None W: Multi-input and multi-input
9. Other
FLK: CompoWay/F communications
Note: Be sure to read the precautions for correct use and other precautions in the following user's manual before using the Digital
Controller. E5AR/ER Programmable Digital Controller User's Manual (Cat. No. Z182)
A PDF version of the user's manual can be downloaded from the following web site: OMRON Industrial Web http://www.fa.omron.co.jp/
4 Programmable Digital Controller E5AR-T
Ordering Information
Digital Controllers
Programmable Digital Controllers
Size Control type Control mode Outputs
× 96
96 mm
Basic control (1 loop)
2-loop control 2-loop standard control
4-loop control 4-loop standard control
Control valve control (1 loop)
Standard control Heating and cooling control
Single-loop heating and cooling control Single-loop cascade control Single-loop control with remote SP Single-loop proportional control
2-loop heating and cooling control (See note 4.)
Single-loop position-proportional control Relay outputs
(control/transfer)
2 (pulse + pulse/cur­rent)
2 (current + current) E5AR-TC4B
2 (pulse + pulse/cur­rent)
2 (current + current) E5AR-TC43B-FLK
2 (pulse + pulse/cur­rent)
2 (current + current) E5AR-TCE3MB-FLK
4 (pulse + pulse/cur­rent + 2 current)
2 (pulse + pulse/cur­rent)
2 (current + current) E5AR-TC43DW-FLK
4 (2 pulse + pulse/2 current)
4 (4 current) 10 (See
4 (2 pulse + pulse/2 current)
(1 open, 1 closed)
Relay outputs (1 open, 1 closed) + 1 current
Optional functions Model
Auxiliary
outputs
(SUB)
4 2 None E5AR-TQ4B
10 (See note 3.)
4 4 RS-485 E5AR-TQ43DW-FLK
10 (See note 3.)
note 3.)
4 4 None E5AR-TPR4DF
10 (See note 3.)
Event
inputs
10 E5AR-TQE3MB-FLK
8 E5AR-TQQE3MW-
8 RS-485 E5AR-TCCE3MWW-
8 RS-485 E5AR-TPRQE3MF-
Serial
communi-
cations
RS-485 E5AR-TQ43B-FLK
(See note 2.)
(See note 2.)
(See note 2.)
(See note 2.)
E5AR-TQCE3MB-FLK
(See note 2.)
(See note 2.)
FLK
FLK
E5AR-TQQE3MWW­FLK (See note 2.)
FLK
Note 1: Specify the power supply specifications when ordering. Model numbers for 100 to 240 VAC are different from those for 24 VAC/VDC.
2: These models are for 100 to 240 VAC only. 3: The outputs are transistor output. 4: Only for coordinated operation. (A separate program cannot be set for each channel.)
Inspection Results
If an inspection report is required, it can be ordered at the same time as the Digital Controller using the following model number.
Inspection Report (Order Separately)
Model
E5AR-K
Accessories (Order Separately)
Terminal Cover
Descriptions Model
Terminal Cover for E5AR E53-COV14
Unit Label Sheet
Model
Y92S-L1
Rubber Packing
Model
Y92S-P4
Note: The Rubber Packing is provided with the Digital Controller.
Programmable Digital Controller E5AR-T 5
Specifications
Ratings
Supply voltage
(See note 2.)
CE marking 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz; 24 VDC
UL certification 100 to 120 VAC, 50/60 Hz 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 22 VA max. (with maximum load) 15 VA/10 W max. (with maximum load)
Sensor input (See note 3.) Thermocouple: K, J, T, E, L, U, N, R, S, B, W
Platinum resistance thermometer: Pt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance: 150
for current input, approx. 1 M for voltage input)
Control output Voltage (pulse) output 12 VDC, 40 mA max. with short-circuit protection circuit (E5AR-TQQE3MW-FLK: 21 mA max.)
Current output 0 to 20 mA DC, 4 to 20 mA DC; load: 500
Relay output Position-proportional control type (open, closed)
Auxiliary output Relay Output
Potentiometer input 100
(Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC)
N.O., 250 VAC, 1 A (including inrush current)
N.O., 250 VAC, 1 A (resistive load) Transistor Output
Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage cur­rent: 0.4 mA max.
to 2.5 k
max. (including transfer output)
Event input Contact Input ON: 1 k max.; OFF: 100 k min.
No-contact Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max.
Short-circuit: Approx. 4 mA
Remote SP input Refer to the information on sensor input.
Transfer output Refer to the information on control output.
Control method 2-PID or ON/OFF control
Setting method Digital setting using front panel keys or setting using serial communications
Indication method 7-segment digital display and single-lighting indicator
Character Height PV display: 12.8 mm; SV display: 7.7 mm; MV display: 7.7 mm
Other functions Depends on model.
Ambient operating temperature
10 to 55°C (with no icing or condensation)
For 3 years of assured use:
10 to 50°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Storage temperature
25 to 65°C (with no icing or condensation)
Note 1: Do not use an inverter output as the power supply. (Refer to page 25.)
2: The supply voltage (i.e., 100 to 240 VAC or 24 VAC/VDC) depends on the model. Be sure to specify the required type when ordering. 3: The Controller is equipped with multiple sensor input. Temperature input or analog input can be selected with the input type setting switch. There is basic
insulation between power supply and input terminals, power supply and output terminals, and input and output terminals.
Input Ranges
Platinum Resistance Thermometer, Thermocouple, Current, or Voltage Input
Input type
Name
Tempera­ture range (
°C)
Setting 0 1 2345678910111213141516171819
Minimum setting unit (SP and alarm)
Input type setting switch
Note: The shaded area indicates the setting status at the time of purchase.
6 Programmable Digital Controller E5AR-T
Platinum
resistance
thermometer
Thermocouple Current Voltage
Pt100 K J T E L U N R S B W
2300 1800 1300
850.0 85 0.0 850. 0
900 800 700 600 400 200 100
0
100
200
200.0 150.00 200.0 200.0 200.0 200.0
0.1°C
1300.0 1300.0
500.0 60 0.0
150.00
20.0 100.0 20.0 100.0
0.01
°C
400.0 400. 0 400.0
0.0 0.0 0.0 0.0
0.1
TC.PT
Set to TC.PT. Set to ANALOG
IN1 TYPE
ANALOG
°C
1700.0 1700.0 1800.0
100.0
W/Re
()
5-26
2300.0
mA V
20 to 420 to
0
5 to 1 5 to 0
(Depends on scaling and number
of decimal places.)
TC.PT
IN1 TYPE
ANALOG
10 to
0
Characteristics
Indication accuracy Thermocouple input with cold junction compensation: (±0.1% of PV or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Control mode Standard control (heating or cooling control), heating/cooling control, standard control with remote SP (2-input models only), heating/
Influence of temperature Thermocouple input (R, S, B, W):
Influence of voltage
Control period 0.2 to 99.0 s (in units of 0.1 s) for time-proportioning control output
Proportional band (P) 0.00% to 999.99% FS (in units of 0.01% FS)
Integral time (I) 0.0 to 3,999.9 s (in units of 0.1 s)
Derivative time (D) 0.0 to 3,999.9 s (in units of 0.1 s)
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Manual reset value 0.0% to 100.0% (in units of 0.1% FS)
Alarm setting range 19,999 to 99,999 EU (See note 3.)
Input sampling period 50 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between charged terminals of different polarities)
Vibration resistance (malfunction)
Shock resistance (malfunction)
Inrush current 100 to 240-VAC models: 50 A max.
Weight Controller only: Approx. 450 g; Mounting bracket: Approx. 60 g; Terminal cover: Approx. 30 g
Degree of protection Front panel: NEMA4X for indoor use (equivalent to IP66); Rear case: IP20; Terminals: IP00
Memory protection Non-volatile memory (number of writes: 100,000)
Applicable standards UL 61010C-1, CSA C22.2 No. 1010-1
EMC EMI: EN61326
Note 1: K-, T-, or N-type thermocouple at 100°C max.: ±2°C ±1 digit max.
U- or L-type thermocouple: B-type thermocouple at 400 R- or S-type thermocouple at 200 W-type thermocouple: (
2: U- or L-type thermocouple:
R- or S-type thermocouple at 200
3: “EU” (Engineering Unit) represents the unit after scaling. If a temperature sensor is used, it is either
Thermocouple input without cold junction compensation: (±0.1% FS or ±1°C, whichever is smaller) ±1 digit (See note 2.) Analog input: ±0.1% FS ±1 digit max. Platinum resistance thermometer input: (±0.1% of PV or ±0.5°C, whichever is greater) ±1 digit max. Position-proportional potentiometer input: ±5% FS ±1 digit max.
cooling control with remote SP (2-input models only), cascade standard control (2-input models only), cascade heating/cooling control (2-input models only), proportional control (2-input models only), position-propor tional control (control-valve control models only)
(±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: ( ±1% of PV or ±4°C, whichever is greater) ±1 digit max. *K thermocouple at -100°C max.: ±10°C max. Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max.
(The decimal point position depends on the input type and the decimal point position setting.)
10 to 55 Hz, 20 m/s
2
100 m/s
, 3 times each in X, Y, and Z directions
24 VAC/VDC models: 30 A max.
(Power supply voltage: 100 to 120 VAC): Pollution degree 2/Overvoltage category 2 EN 61010-1 (IEC 61010-1) (Power supply voltage: 100 to 240 VAC): Pollution degree 2/Overvoltage category 2
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1 Class A Noise Terminal Voltage: EN55011 Group 1 Class A
EMS: EN61326
ESD Immunity: EN61000-4-2: 4 kV contact discharge (level 2)
Electromagnetic Immunity: EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3) Burst Noise Immunity: EN61000-4-4: 2 kV power line (level 3)
Conducted Disturbance Immunity: EN61000-4-6: 3 V (0.15 to 80 MHz) (level 3) Surge Immunity: EN61000-4-5: 1 kV line to line (power line, output line (relay output)) (level 2)
Power Frequency Magnetic Field Immunity: EN61000-4-8: 30 A/m (50 Hz) continuous field Voltage Dip/Interrupting Immunity: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
±2°C ±1 digit max.
°C max.: No accuracy specification.
±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
°C max.: ±3°C ±1 digit max.
±1°C ±1 digit
°C max.: ±1.5°C ±1 digit
2
for 10 min each in X, Y, and Z directions
8 kV air discharge (level 3)
2 kV output line (relay output) (level 4) 1 kV measurement line, I/O signal line (level 4) 1 kV communications line (level 3)
2 kV line to ground (power line, output line (relay output)) (level 3)
°C or °F.
Programmable Digital Controller E5AR-T 7
Communications Specifications
Transmission path connection Multiple points
Communications method RS-485 (two-wire, half duplex)
Synchronization method Start-stop synchronization
Baud rate 9,600, 19,200, or 38,400 bps
Transmission code ASCII
Data bit length 7 or 8 bits
Stop bit length 1 or 2 bits
Error detection Vertical parity (none, even, odd)
Flow control None
Interface RS-485
Retry function None
Communications buffer 217 bytes
Communications response send wait time 0 to 99 ms, Default: 20 ms
Block check character (BCC): CompoWay/F CRC-16: Modbus
Program Control Functions
Number of programs (patterns) 32 (with 8 segments/program)
Number of segments (steps) 32 (with 8 programs)
Maximum number of segments 256
Segment setting method Time setting (Segment set with set point and time.)
Segment times 0 h 0 min to 99 h 59 min
Alarm group num­ber specifications
Reset operation Select either stopping control or fixed SP operation.
Startup operation Select continuing, resetting, manual operation, run mode, or ramp back operation.
PID groups Number of groups 8
Alarm SP function Select from ramp SP and target SP.
Program status control
Wait operation Wait method Select from waiting at segment ends and always waiting.
Time signals Number of outputs 6
Segment outputs Number of outputs 10
Program status output Program end output (pulse width can be set)
Program startup operation
Operation end operation Select from resetting, continuing control at final set point, and fixed SP control.
Number of event inputs 10 max.
Number of groups 4
Setting method Set separately for each program.
Setting method Set separately for each program (automatic PID group selection also supported).
Segment operation Advance, hold, and back
Program operation Program repetitions and program links
Wait width setting Wait width upper limit and lower limit set separately for each program.
Setting method ON/OFF setting for each segment
Number of ON/OFF operations
Setting method Set separately for each program.
Setting method ON/OFF set for each segment.
PV start Select from segment 1 set point, slope-priority PV start, and time-priority PV start.
Standby Standby
Gradient setting (Segment set with set point, gradient, and time.)
0 min 0 s to 99 min 59 s 0 min 00.0 s to 99 min 59.9 s
3 each per output
Segment number output
8 Programmable Digital Controller E5AR-T
Wiring Terminals
E5AR-T (Programmable Type)
E5AR-TQ4B E5AR-TC4B
24 VAC/DC 100 to 240 VAC
+
+
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
!
OUT2
Voltage output 12 V 40 mA
OUT1
Voltage output 12 V 40 mA or Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
BEDCA
1
2
3 4
5
6 1
Auxiliary output (Relay output)
B 1
2
3
4
5 6
COM
SUB1
SUB2
COM
SUB3
SUB4
2
3 4
5 6
KJIHGF
1
2
+
3
4
+
5
6 F
Event input
EV1
EV2
COM
+
+
VI
(Voltage)
+
TCPT
(Thermocouple)
(Current) (Resistance temperature input sensor)
1
2
3
4
5 6
K
24 VAC/DC
+
+
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
OUT2
Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
OUT1
Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
100 to 240 VAC
!
BEDCA
1
2
3 4
5
6 1
2
Auxiliary output (Relay output)
B 1
2
3
4
5 6
COM
SUB1
SUB2
COM
SUB3
SUB4
3 4
5 6
KJIHGF
1
2
+
3
4
+
5
6 F
Event input
EV1
EV2
COM
+
+
(Voltage)
+
TCPTVI
(Thermocouple)
(Current) (Resistance temperature input sensor)
1
2
3
4
5 6
K
E5AR-TQ43B-FLK E5AR-TC43B-FLK
B(+)
RS-485
OUT2
Voltage output 12 V 40 mA
OUT1
Voltage output 12 V 40 mA or Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
A(−)
100 to 240 VAC
!
+
1
2
+
3
4
+
5
6 F
Auxiliary output (Relay output)
BEDCA
1
2
3 4
5
6
B
COM
1
SUB1
2
SUB2
3
COM
4
SUB3
5
SUB4
6
1
2
3 4
5 6
KJIHGF
Event input
EV1
EV2
COM
+
++
(Voltage)
(Current)
(Resistance temperature input sensor)
TCPTVI
(Thermocouple)
1
2
3
4
5 6
K
100 to 240 VAC
!
OUT2
Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
OUT1
Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
RS-485
B(+)
A(−)
1
2
3 4
5
6 1
2
3 4
5 6
+
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5AR-T to comply with CE
Note
marking requirements. The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5AR-T to comply with UL requirements.
BEDCA
Auxiliary output (Relay output)
B 1
2
3
4
5 6
COM
SUB1
SUB2
COM
SUB3
SUB4
KJIHGF
1
2
+
3
4
+
5
6 F
Event input
EV1
EV2
COM
+
+
VI
(Voltage)
+
TCPT
(Thermocouple)
(Current) (Resistance temperature input sensor)
1
2
3
4
5 6
K
Programmable Digital Controller E5AR-T 9
Loading...
+ 19 hidden pages