Omron E5EK PROGRAMMABLE TYPE, E5EK-T, E5EK User Manual

Page 1
User's Manual
Cat. No. H089-E1-02
Digital Controller
(Programmable Type)
Page 2
Preface
Set program patterns to each step by time or ramp rise rate
Execute advance, hold and reset step operations
Execute continuous operation of all patterns and repeated operation of same pat-
terns
Check the start of each step or program end time by signals.
Count time from the beginning of each step (time signal)
Select from many types of temperature and analog input (multi-input)
Support position-proportional control (position-proportional type controllers only)
Select output functions such as control output or alarm output (output assign-
ment)
Use the HBA (heater burnout alarm) function (standard type controllers only)
Monitor the control loop by LBA (Loop Break Alarm)
Use the communications function
Calibrate input or transfer output
The E5EK-T also features a watertight construction (NEMA4: equivalent to
IP66).
This User’s Manual describes how to use the E5EK-T. Before using your E5EK-T thoroughly read and understand this manual in order to ensure correct use. Also, store this manual in a safe place so that it can be retrieved whenever neces­sary.
PRECAUTIONS IN USING THE PRODUCT
When the product is used under the circumstances or environment below, ensure adherence to limitations of the ratings and functions. Also, take countermeasures for safety precautions such as fail-safe installations.
(1) Use under circumstances or environments which are not described in this user’s manual. (2) Use for nuclear power control, railway, air craft, vehicle, incinerator, medical equipment, enter-
tainment equipment, safety device, etc.
(3) Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
About this manual
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, with­out the prior written permission of OMRON.
(2) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice.
(3) Every precaution has been taken in the preparation of this manual. Nevertheless, if you find any errors or
omissions, please contact the branch of OMRON or sales office listed at the end of this manual, and inform them of the catalog No. on the front cover.
I
Page 3
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text ex­planations. These abbreviations mean the following:
Symbol Term
PV Process value
SP (Present) set point *1
LBA Loop break alarm
HB Heater burnout
AT Auto-tuning
EU Engineering unit *2
*1 In program pattern diagrams, the present SP is indicated.
*2 _C, m, g and other units are indicated for scaled data. However, “EU” is used as the mini -
mum unit for the data. For example, for “50.02 (m)”, 1EU is taken as the minimum unit
0.01 (m).
JHow to Read Display Symbols
The following tables show the correspondence b etween the symbols displayed on the displays and alphabet characters.
ABCDEF GHI J KL M
NOPQRST UVWXYZ
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explana­tions and how to apply functions.
II
Page 4
JHow This Manual is Organized
Purpose Title Description
D Learning about the gener-
al features of the E5EK-T
Chapter 1 INTRODUC­TION
This chapter describes the fea­tures of the E5EK-T, n ames of parts, and typical functions.
D Setting up
D Basic E5EK-T operations
D Applied E5EK-T opera-
tions
D Using a Position-propor-
tional type controller
D Communications with a
host computer
Chapter 2 PREPARA­TIONS
Chapter 3 BASIC OPERA­TION Chapter 5 PARAMETERS
Chapter 4 APPLIED OP­ERATION Chapter 5 PARAMETERS
Chapter 4 APPLIED OP­ERATION /4.1 Selecting the Control Method
Chapter 6 USING THE COMMUNICATIONS FUNCTION
This chapter describes the op­erations that you must carry out (e.g. installation, wiring and switch settings) before you can use the E5EK-T.
These chapters describe using basic control examples how to use the front panel keys and how to view the display when setting the parameters of the major functions for the E5EK-T.
These chapters describes the important functions of the E5EK-T an d how to use the pa­rameters for making full use of the E5EK-T.
This chapter describes how to use the functions related specifi­cally to position-proportional type controllers.
This chapter mai nly describes how to use the communications commands, and gives program examples.
D Calibration
D Troubleshooting
Chapter 7 CALIBRATION This chapter describes how the
user should calibrate the E5EK­T.
Chapter 8 TROUBLE­SHOOTING
This chapter describes what to do if any problems o ccur.
III
Page 5
PRECAUTIONS ON SAFETY
F Marks For Ensuring Safe Use and Their Meanings
This manual uses the following marks to indicate precautions for ensuring that the E5EK-T is used safely. The precautions indicated below describe important information regarding safety. Be sure to follow the instructions described in these precautions.
WARNING
Incorrect handling may cause death or injury.
WARNING
Do not touch the terminals while the power is ON. This may cause an electric shock.
IV
Page 6
NOTICE
Be sure to observe these precautions to ensure safe use.
F Do not use the product in places where explosive or flammable gases may be present.
F Never disassemble, repair or modify the product.
F Tighten the terminal screws properly.
F Use the specified size of solderless terminals for wiring.
F Use the product within the rated supply voltage.
F Use the product within the rated load.
F The life expectancy of the output relay varies considerably according to its switching capacity
and operating conditions. Be sure to use the output relay within its rated load and electrical life expectancy. If the output relay is used beyond its life expectancy, its contacts may become fused or burned.
F If you remove the controller from its case, never touch nor apply shock to the electronic parts
inside.
F Do not cover the E5EK-T. (Ensure sufficient space around the controller to allow heat radiation.)
F Do not use the controller in the following places:
Places subject to icing, condensation, dust, corrosive gas (especially sulfide gas or ammonia gas).
Places subject vibration and large shocks.
Places subject to splashing liquid or oil atmosphere.
Places subject to intense temperature changes.
Places subject to heat radiation from a furnace.
F Be sure to wire properly with correct polarity of terminals.
F When wiring input or output lines to your controller, keep the following points in mind to reduce
the influence from inductive noise:
Allow adequate space between the high voltage/current power lines and the input/output lines.
Avoid parallel or common wiring with high voltage sources and power lines carrying large cur-
rents.
Using separating pipes, ducts, and shielded line is also useful in protecting the controller, and its lines from inductive noise.
F Cleaning: Do not use paint thinner or organic solvents. Use standard grade alcohol to clean the
product.
F Use a voltage (100 to 240 VAC at 50 to 60 Hz). At power ON, the prescribed voltage level must be
attained within two seconds.
F Allow as much space as possible between the controller and devices that generate a powerful high
frequency (high-frequency welders, high-frequency sewing machines, etc.) or surge. These devices may cause malfunctions.
F If there is a large power-generating peripheral device and any of its lines near the controller, at-
tach a surge suppressor or noise filter to the device to stop the noise affecting the controller sys­tem. In particular, motors, transformers, solenoids and magnetic coils have an inductance compo­nent, and therefore can generate very strong noise.
F When mounting a noise filter on the power supply to the controller, be sure to first check the fil-
ter’s voltage and current capacity, and then mount the filter as close as possible to the controller.
V
Page 7
F Use within the following temperature and humidity ranges:
Temperature: -10_Cto55_C, humidity: 35%RH to 85%RH (with no icing or condensation) If the controller is installed inside a control board, the ambient temperature must be kept to un ­der 55_C, including the temperature around the controller. If the controller is subjected to heat radiation, use a fan to cool the surface of the controller to under 55_C.
F Store within the following temperature and humidity ranges:
Temperature: -25_Cto65_C, humidity: 35%RH to 85%RH (with no icing or condensation)
F Never place heavy objects on, or apply pressure to the controller that may cause it to deform and
deteriorate during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installation. These
devices can cause radio disturbances which adversely affect the performance of the controller.
VI
Page 8
Table of Contents
Preface I......................................
Conventions Used in This Manual II...............
Precautions on Safety IV.........................
CHAPTER 1 INTRODUCTION 1--1...........................
This chapter introduces the names of parts on the E5EK-T and their functions. For details on how to use the controller and parameter settings, see Chapter 2 onwards.
1.1 Names of parts 1--2..........................................
1.2 Input and Output 1--5.........................................
1.3 Program 1--8................................................
1.4 Parameters and Menus 1--9...................................
1.5 About the Communications Function 1--12.......................
1.6 About Calibration 1--13........................................
CHAPTER 2 PREPARATIONS 2--1...........................
This chapter describes the operations (e.g. setup, installation and wiring) you should carry out before turning the E5EK-T ON.
2.1 Setup 2--2..................................................
2.2 Installation 2--5..............................................
2.3 Wiring Terminals 2--8.........................................
CHAPTER 3 BASIC OPERATION 3--1........................
This chapter describes actual examples for understanding the basic operation of the E5EK-T
3.1 Convention Used in this Chapter 3--2...........................
3.2 Setting Input Specifications 3--4...............................
3.3 Setting Output Specifications 3--7..............................
3.4 Setting Alarm Type 3--10.......................................
3.5 Setting Patterns 3--14.........................................
3.6 Protect Mode 3--19............................................
3.7 Starting and Stopping Operation 3--21...........................
3.8 Adjusting Control Operation 3--22...............................
CHAPTER 4 APPLIED OPERATION 4--1......................
This chapter describes each of the parameters required for making full use of the features of the E5EK-T. Read this chapter while referring to the parameter descriptions in chapter 5
4.1 Selecting the Control Method 4--2..............................
4.2 Operating Condition Restrictions 4--7...........................
4.3 Ramp Rise Rate Setup Program 4--9...........................
4.4 Program Operation 4--13......................................
Page 9
4.5 Wait Operation 4--16..........................................
4.6 Program output 4--17..........................................
4.7 Setting Running Conditions 4--19...............................
4.8 How to Use Event Input 4--21..................................
4.9 How to Use the Heater Burnout Alarm 4--23......................
4.10 LBA 4--26....................................................
4.11 How to Use Transfer Output 4--28...............................
CHAPTER 5 PARAMETERS 5--1.............................
This chapter describes the parameters of the E5EK-T. Use this chapter as a reference guide.
Conventions Used in this Chapter 5--2..............................
Protect Mode 5--3................................................
Manual Mode 5--5................................................
Level 0 Mode 5--6................................................
Program Mode 5--11...............................................
Level 1 Mode 5--17................................................
Level 2 Mode 5--24................................................
Setup Mode 5--30.................................................
Expansion Mode 5--38.............................................
Option Mode 5--46.................................................
Calibration Mode 5--52.............................................
CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6--1..
This chapter mainly describes communications with a host computer and com­munications commands
6.1 Outline of the Communications Function 6--2....................
6.2 Preparing for Communications 6--3............................
6.3 Command Structure 6--5......................................
6.4 Commands and Responses 6--7...............................
6.5 How to Read Communications Error Information 6--15.............
6.6 Program Example 6--17.......................................
CHAPTER 7 CALIBRATION 7--1.............................
This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated.
7.1 Parameter Structure 7--2.....................................
7.2 Calibrating Thermocouples 7--4................................
7.3 Calibrating Platinum Resistance Thermometers 7--7.............
7.4 Calibrating Current Input 7--9..................................
7.5 Calibrating Voltage Input 7--10..................................
Page 10
7.6 Checking Indication Accuracy 7--12.............................
CHAPTER 8 TROUBLESHOOTING 8--1......................
This chapter describes how to find out and remedy the cause if the E5EK-T does not function properly. Remedy E5EK-T trouble in the order of the descriptions in this chapter
8.1 Initial Checks 8--2............................................
8.2 How to Use the Error Display 8-- 3..............................
8.3 How to Use the Error Output 8--5..............................
8.4 Checking Operation Restrictions 8--6...........................
APPENDIX
SPECIFICATIONS A--2........................
ABOUT CURRENT TRANSFORMER (CT) A--5...
CONTROL BLOCK DIAGRAM A--6..............
SETTING LIST A--8...........................
MODEL LIST A--12.............................
PARAMETER OPERATIONS LIST A--13..........
ASCII CODE LIST A--15........................
INDEX
REVISION HISTORY
Page 11
CHAPTER1
CHAPTER 1
INTRODUCTION
This chapter introduces the names of parts on the E5EK- T and their functions. For details on how to use the controller and parameter settings, see Chapter 2 onwards.
CHAPTER 1 INTRODUCTION
1.1 Names of parts 1-2........................
Main parts 1-2............................
Front panel 1-2...........................
About the displays 1-3.....................
How to use keys 1-4.......................
1.2 Input and Output 1-5......................
Input 1-5.................................
Output 1-6................................
1.3 Program 1-8..............................
How programs are structured 1-8...........
Program operation 1-8.....................
Alarm output 1-8..........................
Program output 1-8........................
1.4 P arameters and Menus 1-9.................
Parameter types 1-9.......................
Selecting modes 1-10........................
Selecting parameters 1-11...................
Fixing settings 1-11.........................
1.5 About the Communications Function 1-12....
1.6 About Calibration 1-13......................
1--1
Page 12
CHAPTER 1 INTRODUCTION
1.1 Names of parts
JMain parts
Terminals
P2-6
Rear case
Front panel
This page
JFront panel
Pattern No.
Operation indicators
OUT1 SUB1 MANU HOLD WAIT
Display key
Run/Reset key
RUN/RST
1--2
OUT2 SUB2 RMT RST AT
PTN
RMT
OUT1 OUT2
RUN
RST
PV
SV
MANU
RSP SUB1
STOP
No.1 display
No.2 display
SUB2
AT
WAIT
Up k ey
Down ke y
E5EK
Page 13
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Pattern No.
F Program status
indicators
F Op eration statu s
indicators
Displays the process value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
Displays pattern No..
Indicate how the present-SP of the operating step changes.
OUT1 Lights when the pulse output function assigned to “control output 1” is ON.
OUT2 Lights when the pulse output function assigned to “control output 2” is ON.
SUB1 Lights when the pulse output function assigned to “auxiliary output 1” is ON.
SUB2 Lights when the pulse output function assigned to “auxiliary output 2” is ON.
MANU Lights in the manual operation mode.
RST Lights when the control is in reset status.
RMT Lights during remote operation.
HOLD Lights when the program is in hold status.
WAIT Lights when the program is in wait status.
AT Flashes during auto-tuning.
1--3
Page 14
CHAPTER 1 INTRODUCTION
JHow to use keys
RUN/RST
F key
F key
F key
The following describes basic key operations.
To change to run operation from the reset status, press this key for one
second minimum. To change to the reset status from run operation, press this key for two seconds minimum.
The functions of this key change according to how long it is pressed. If the key is pressed for less than one second, the parameters are switched.
If the key is pressed for one second minimum, the menu display ap­pears. In key operations from here on, “press the key” refers to pressing the key for less than one second. For details on switching of parameters and menu display items, see
page 1-10.
Each press of
the No.2 display, while each press of the key decrements or returns the values or settings on the No.2 display.
Functions vary, for example, when the
key increments or advances the values or settings on
RUN/RST
key is held down simul-
taneously with the
tails, see page 1-10. Also, chapters 3 and 4 describe examples using vari­ous key combinations.
key, or a key is held down continuously. For de-
1--4
Page 15
1.2 Input and Output
1.2 Input and Output
T emperature input
Voltage input
Current input
CT input Potentiometer
Event input
Controller
Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Time signal 1
Time signal 2
Program end
Stage output
Error 1
Error 2
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
JInput
The E5EK-T supports the following inputs:
Temperature input, Current input, Voltage input, CT input/potentiom­eter, and Event input.
F Temperature input/Voltage input/Current input
Only one of temperature input, current input and voltage input can be selected and connected to the controller.
The following input sensors can be connected for temperature input:
Thermocouple:K,J,T,E,L,U,N,R,S,B,W,PLII Platinum resistance thermometer: JPt100, Pt100
The following currents can be connected for current input:
4to20mA,0to20mA
The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input/Poten -
tiometer
Connect CT input when using the HBA (heater b urnout alarm) func­tion on a standard type controller (E5EK-TAA2). Note that CT input cannot be used when the linear output unit is mounted.
Connect the potentiometer when monitoring the valve opening on a position-proportional type controller (E5EK-TPRR2).
1--5
Page 16
CHAPTER 1 INTRODUCTION
F Event input
JOutput
F Ou tput assign-
ments
Add on the input unit (E53-CKB) when using event input. You can se­lect from the following five event inputs:
Run/Reset, Auto/Manual, Hold/Hold Cancel, Advance, Pattern
The output functions of the E5EK-T do not operate for five seconds after the E5EK-T is turned ON.
The E5EK-T supports the following five outputs:
Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2 Transfer output
When using control output 1 and 2, set the output unit (sold sepa­rately). Nine output units are available to suit the output circuit config­uration.
When using transfer output, add on the communication unit (E53-AKF).
The E5EK-T supports the following thirteen output functions:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, LBA, Time Signals 1 and 2, Program End, Stage Output, Error 1 (input error), Error 2 (A/D converter error)
Assign these output functions to control output 1, control output 2, auxiliary output 1, and auxiliary output 2. However, note that as control output 1 is used as the open output and control output 2 is used as close output on a position-proportional type controller (E5EK-TPRR2), control outputs 1 and 2 cannot be used as assignment destinations. Also, of the output functions, control output (heat), control output (cool), HBA and LBA are disabled.
On a standard type controller, there are restrictions on how assign­ment destinations (control output 1, control output 2, auxiliary out­put 1, and auxiliary output 2) can be used. For details, see Chapter 3 Basic Operation/3.3 Setting Output Specifications (page 3-7).
In the example on the previous page, “control output (heat)” is as­signed to “control output 1”, “alarm 1” is assigned to “control output 2”, and “alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configuration is such that heating control output is connected to con­trol output 1, and alarm output is connected to control output 2 and auxiliary output 1.
Control outputs 1 and 2 are used depending on the differences in con­trol method as follows:
1--6
Page 17
1.2 Input and Output
F Transfer ou t pu t
Control Method
Standard control E5EK-TAA2 AC100-240
E5EK-TAA2 AC/DC24
Heating and cooling control
Position-propor­tional control
The E5EK-T supports the following five transfer outputs:
Set point, Process value, Heating side manipulated variable,
Cooling side manipulated variable, Valve opening However, note that heating/cooling side manipulated variables can be output only on standard type controllers, and valve opening can be out­put only on position-proportional type controllers.
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so re­verse scaling can also be carried out.
E5EK-TAA2 AC100-240 E5EK-TAA2 AC/DC24
E5EK-TPRR2 AC100-240 E5EK-TPRR2 AC/DC24
Model
Control Output 1/
Control Output 2
Control output (heat) / Alarm, etc.
Control output (heat) / Control output (cool)
Open/Close
1--7
Page 18
CHAPTER 1 INTRODUCTION
1.3 Program
JHow programs
are structured
E5EK-T allows you to configure programs made up of a maximum of four patterns (pattern 0 to 3). The number of steps (16 maximum) in each pattern can be specified in
parameters.
Pattern 3
Pattern 1
Pattern 0
Step 0 Step 1 Step 2 Step 15
Generally, the “time setup method” is used to configure programs. By
this method, set points at each step and time are used as program ele­ments. However, the “ramp rise rate setup method” can also be used. By this method, the set point, ramp time and soak times are used as program elements.
JProgram opera-
tion
F Step operation
F Wait operation
JAlarm output
JProgram output
1--8
Generally, the target patterns are specified before the program is
executed.
In parameter setup, you can specify repeated execution of the same
pattern (Repeat) or consecutive execution of all patterns 0 to 3 (Run all).
During program operation, steps can be skipped (Advance) and the
control monitoring can be paused (Hold).
When the wait width is specified in parameter setup, the program
does not go to the next step and waits until the PV reaches the speci­fied time (wait width) at the end of each step.
Alarms that are assigned as outputs operate referenced to the alarm
values preset to each pattern.
Time signals, program end and stage output can be output accor din g
to output assignment.
ON/OFF signals are output as time signals according to the timer
that takes a specified step as its start point.
Page 19
1.4 Parameters and Menus
1.4 Parameters and Menus
JParameter types
F Protect mode
F Manual mode
F L evel 0 mode
E5EK-T parameters are distributed between the following ten modes:
Protect mode
Manual mode
Level 0 mode
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of eight modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the menu display.
The protect function is for preventing unwanted modification of param-
eters, and switching between run and reset operation or auto and manual operation.
In this mode, the controller can be switched to manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you can change the set p oint and pattern during operation, and execute
step operation (e.g. advance). You can only monitor (not change) the process value, step No., standby time, pattern elapsing time, pattern execution count and manipulated variable.
F Program mode
F L evel 1 mode
F L evel 2 mode
F Setup mode
This is the programming mode. In this mode, you can set the number of steps used in each pattern, pattern execution count, alarm values, set points for each step, step time, and time signals for two steps.
This is the main mode for adjusting control. In this mode, you can execute AT (auto-tuning), and set up the control period, PID parame­ters and heater burnout alarm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can set the parameters for limiting the manipulated variable, switch be­tween the remote and local modes, and set the loop break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse opera­tion.
1--9
Page 20
CHAPTER 1 INTRODUCTION
F Expansion mode
F Option mode
F Calibration mode
JSelecting modes
This is the mode for setting expanded functions. In this mode, you can set SP setting limitter, switching between advanced PID control or ON/ OFF control, program time unit, selection of step time/rate of rise p ro­gramming, time unit of ramp rise rate, and the time for automatic re­turn to the monitoring display.
This is the mode for setting optional functions. You can select this mode only when an option unit is mounted in the controller. In this mode, you can set the communications conditions, transfer output and event input parameters to match the type of option unit mount in the control-
ler. Heater burnout alarm function and position-proportional travel time are also located in this mode.
This mode is provided so that the user can calibrate inputs and output.
When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when the communication unit (E53-AKF) is set in the controller.
The following diagram shows the order in which modes are selected.
Power ON
+
1 second min.
Level 0 mode
1secondmin.
Manual mode
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
RUN/RST
1 second min.
RUN/RST
1 second min.
+
Protect mode
+
+
1 second min.
RUN/RST
1secondmin.
+
To select the menu display in any of the above modes (excluding the
protect mode and manual mode), press the
key for 1 second mini­mum. When you have selected the menu display, the previous mode is selected. For example, if you selected the menu display while in the level 0 mode, the No.2 display changes to [
] as shown on the left.
To move to the desired mode after you have entered the menu display, select the desired mode using the
keys and hold down the
key for one second minimum. The display switches to the first
parameter of the mode that you specified.
1--10
Page 21
1.4 Parameters and Menus
Protected modes cannot be selected. Also, the menu display does not appear when modes are protected up to the program mode.
If you select [ the level 0, program, level 1 and level 2 modes, respectively, are se­lected. These modes are selected with control still continuing.
If you select[ setup, expansion, option and calibration modes, respectively, are se­lected. When these modes are selected, the control is reset. So, control out­puts and auxiliary output are turned OFF. When another mode is se­lected while in these modes control, reset is canceled.
To set the controller to the protect mode or to return to the level 0
mode from the protect mode, press the
simultaneously for 1 second minimum.
To set the controller to the manual mode, press the second minimum with the modes. To return to the level 0 mode in the manual mode, press the
key for one second minimum with the key pressed. Be sure
to press the
], [ ], [ ]or[ ]inthe menudisplay,
][ ][ ]or[ ]inthe menudisplay,the
RUN/RST
keyhelddowninthelevel0to2
key first in this operation.
key and the key
key for one
JSelecting
parameters
JFixing settings
When the controller is not in the manual mode, each press of the key switches the parameter in the respective mode.
Parameter
1
If you press the key when at the final parameter, the display re- turns to the top parameter for the current mode.
When you change parameter settings or contents, specify the parame­ter using the two seconds or press the
When another mode is selected, the content of the parameters before the mode was selected is fixed.
When you turn the power OFF, you must first fix the settings and pa­rameter contents (by pressing the mode). The settings and parameter contents are sometimes not changed by merely pressing the
Parameter
2
or keys, and either leave the setting for at least
Parameter
Parameter
3
key. This fixes the setting.
key or selecting another
or keys.
n
1--11
Page 22
CHAPTER 1 INTRODUCTION
1.5 About the Communications Function
The E5EK-T can be provided with a communications function that al­lows you to check and set controller parameters from a host computer.
If the communications function is required, add on the communications unit. For details on the communications function, refer to Chapter 6.
F RS-232C
F RS-422
F RS-485
When using the communications function on the RS -232C interface, add on the communications unit (E53-AK01).
When using the communications function on the RS-422 interface, add on the communications unit (E53-AK02).
When using the communications function on the RS-485 interface, add on the communications unit (E53-AK03).
1--12
Page 23
1.6 About Calibration
The E5EK-T controller is calibrated before shipment from the factory. So, the user need not calibrate the E5EK-T controller during regular
use.
However, if the E5EK-T controller must be calibrated by the user, use the parameters provided for the user to calibrate temperature input, analog input (voltage, current) and transfer output. In this case, note
that the results of calibration will not be assured. Also, note that calibration data is updated to the latest value each time that the E5EK-T controller is calibrated. Calibration data set before shipment from the factory cannot be returned to after calibration by
the user.
1.6 About Calibration
F Calibrating
inputs
F Calibrating trans -
fer output
F Registering cal-
ibration data
The input type selected in parameters is the item to be calibrated. The E5EK-T is provided with the following four calibration parameters:
Thermocouple
Platinum resistance thermometer
Current input
Voltage input
Two parameters are provided for thermocouple and voltage input.
Transfer output also can be calibrated when the communications unit (E53-AKF) is added on.
When calibrating each item, the calibration data is temporarily regis­tered. This data can be registered as final calibration data only when all items have been newly calibrated. So, all items must be temporarily registered when the E5EK-T controller is calibrated.
When registering data, information regarding whether or not calibra­tion has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring de­vices and equipment. For details on handling these measuring devices
and equipment, refer to the respective manuals.
For details, see Chapter 7 Calibration.
1--13
Page 24
CHAPTER 1 INTRODUCTION
1--14
Page 25
CHAPTER2
CHAPTER 2
PREPARATIONS
This chapter describes the operations (e.g. setup, installation and wiring) you should carry out before turning the E5EK-T ON.
CHAPTER 2 PREPARATIONS
2.1 Setup 2-2.................................
Draw-out 2-2..............................
Setting up the output unit 2-3..............
Setting up the option unit 2-4...............
2.2 Installation 2-5............................
Dimensions 2-5............................
Panel cutout 2-5...........................
Mounting 2-6.............................
2.3 Wiring Terminals 2-8......................
Terminal arrangement 2-8.................
Precautions when wiring 2-8...............
Wiring 2-8................................
2--1
Page 26
CHAPTER 2 PREPARATIONS
2.1 Setup
On a standard type controller, set up the output units for control out­puts 1 and 2 before mounting the controller.
On a position-proportional type controller, the relay output unit is already mounted. So, this setup operation is unnecessary. (That is, do not replace the currently mounted unit with other output units.)
When setting up the output units, draw out the internal mechanism from the housing, and insert the output units into the sockets for con­trol outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, prepare a
Phillips screwdriver matched to the size of the screw on the lower part of the front panel.
(1) Press down on the hook on the top of the front panel, and turn the
Phillips screwdriver to the left to loosen the screw on the lower
part of the front panel.
Fixing Screw for Front Panel
2--2
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 Nm (approx. 3 to 5 kgfcm).
Page 27
JSetting up the output unit
2.1 Setup
F Before setup
F Procedure
Check the type of the output unit you are about to set up.
For details on types of output unit and main specifications, see page
2-7.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) R emove the power board in the direction of the arrow in the figure
below. The power board is connected to the control board by a con­nector at the center of the board.
Control board
Power board
(3) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(4) Fasten the output units with the bracket (accessory).
(5) Mount the power board at its original position.
2--3
Page 28
CHAPTER 2 PREPARATIONS
JSetting up the option unit
F Before setup
F Procedure
Check the type of the option unit you are about to set up.
For details on types of option unit and main specifications, see Appen-
dix, Model List (page A-11) and Appendix, Option Unit Ratings and Characteristics (page A-4).
For details on the relationship between units and terminals, see page 2-8.
(1) R emove the power board and option boards in the order shown in
the following diagram.
2
1
(2) Insert the option unit into the socket for option 1. The following
diagram shows the relationship between option unit and mounting position.
Option 1 E53--AKB: Event inputs 1/2 E53-- AK01: RS--232C E53-- AK02: RS--422 E53-- AK03: RS--485 E53-- AKF: Transfer output
(3) Mount the option board and the power board in the order shown.
2--4
Page 29
2.2 Installation
JDimensions
48
PV
2.2 Installation
13.5 100
PTN
MANU
RMT
OUT1 OUT2
STOP
RUN
RST
JPanel cutout
Unit (mm)
SV
91
SUB2RSP SUB1
AT
WAIT
E5EK
96
112
60 mm min
120 mm min
45
+0.6
0
92
+0.8
0
Recommended panel thickness is 1 to 8 mm.
Maintain the specified vertical and hori­zontal mounting space between each con­troller. Controllers must not be closely mounted vertically or horizontally.
2--5
Page 30
CHAPTER 2 PREPARATIONS
JMounting
(1) Insert the E5EK-T controller into the mounting hole in the panel.
(2) Fit the mounting b racket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the two mounting bracket screws alternately a little at a
time until the ratchet starts to slide.
2--6
Page 31
F Setting up the terminal covers
Fasten the terminal covers (E53-COV0809) to protect terminals.
E5EK-VV2-500 controller is provided with terminal covers.
Use E53-COV09 for terminals 1 to 10, and E53-COV08 for terminals
11 to 33.
Fasten the terminal covers as follows by using the snap pins.
2.2 Installation
E5EK-- T
E53-COV08
To remove the terminal covers, pull the edges of the snap pins.
2--7
Page 32
CHAPTER 2 PREPARATIONS
2.3 Wiring Terminals
JTerminal arrangement
SOURCE
OUT1
OUT2
SUB1
SUB2
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
EV1/2
TRSF
RS232C
RS422 RS485
CT
PTMR
TC
Pt
I
V
JPrecautions
when wiring
JWiring
F Power supply
10
21 22
9
8 7 6 5 4 3 2
23
2--8
1
20 19 18 17 16 15 14 13 12
11
TRSF : Transfer output EV1/2 : Event inputs PTMR : Potentiometer SOURCE : 100 to 240 VAC, 50/60 Hz 15VA or 24VAC/DC, 50/60 Hz, 12VA 8W
On some models, terminals are not used and are left free. Do not wire these terminals.
Separate input leads and power lines in order to protect the controller and its lines from external noise.
We recommend using solderless terminals when wiring the controller.
Tighten the terminal screws using a torque no greater than 0.78 N¡m
(8kgf¡cm).
Use the following type of solderless terminals for M3.5 screws.
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indi­cates the inside of the controller.
Input power to terminals Nos. 9 and 10. Powe r specifications are as fol­lows:
100 to 240 VAC, 50/60 Hz, approx. 15 VA or 24 VAC, 50/60 Hz, approx. 12 VA 24 VDC, 8W
Page 33
2.3 Wiring Terminals
F Sensor input
21 22
23
20 19
18 17 16 15
14 13 12 11
10
9 8
7 6 5 4 3
2 1
F Control output
10
9
8
7 6 5
4 3
2 1
21 22
23
20 19
18
17 16 15 14 13
12
11
Connect the sensor input to terminal Nos. 11 to 14 and 23 as follows according to the input type.
14
13
12
11
23
Thermocouple Platinum
-
+
resistance
thermometer
14
13
12
11
23
+
14
V
13
12
-
11
23
Voltage input Current input
14
13
12
11
23
-
mA
+
Term inal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos. 5 and 6 are for control output 2 (OUT2). The following diagrams show the available output units and their internal equalizing circuits.
86
75
NPN
E53-Q E53-Q3
+
L
GND
-
86
75
Relay
E53-R E53-S E53-Q4
+
86
mA V
4to20mA/0to20mA
E53-C3 E53-C3D
LL
75
-
86
75
SSR PNP
86
75
0 to 10V/0 to 5V
E53-V34 E53-V35
+v
GND
+
-
+v
86
75
+
L
-
With E53-Vjj output units, about 2 V is output for one second after the power is interrupted.
The following table shows the specifications for each output unit.
Model Output Type Output Mode Specifications
E53-R Relay Pulse 250 VAC, 5 A
E53-S SSR Pulse 75 to 250 VAC, 1 A
E53-Q E53-Q3 E53-Q4
E53-C3 E53-C3D
E53-V34 E53-V35
Voltage (NPN) Voltage (NPN) Voltage (PNP)
4to20mA 0to20mA
0to10V 0to5V
Pulse Pulse Pulse
Linear Linear
Linear Linear
NPN : 12 VDC, 40 mA (with short-circuit protection) NPN : 24 VDC, 20 mA (with short-circuit protection) PNP : 24 VDC, 20 mA (with short-circuit protection)
4 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600
0 to 10 VDC, Permissible load impedance: 1 k min., Resolution: Approx. 2600 0 to 5 VDC, Permissible load impedance: 1 k min., Resolution: Approx. 2600
With E5EK-T PRR2 controllers, relay output (250 VAC, 1A) is fixed. When the output unit is replaced, use the E53-R. The following dia­grams show the relationship between terminals and open/close relay terminal settings.
8
7
Open
6
5
Close
2--9
Page 34
CHAPTER 2 PREPARATIONS
F Auxiliary output
10
9 8
7 6 5
4 3 2 1
21 22
23
20 19
18 17 16 15 14 13 12
11
F CT input/
Potentiometer
21 22
23
20 19 18
17 16 15
14
13 12
11
10
9 8 7 6 5 4
3 2
1
Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal Nos.1 and 2 are for auxiliary output 2 (SUB2).
The internal equalizing circuits for the auxiliary outputs are as fol­lows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
Output specifications are as follows:
SPST- NO, 250 VAC, 3 A
When the HBA function on an E5EK-TAA2 controller is used, connect CT input (CT) to terminal Nos.15 and 17. When monitoring the valve opening on an E5EK-TPRR2 controller, connect the potentiometer (PTMR) to terminal Nos.15 to 17. Connect each of these inputs as fol­lows:
17
16
15
CT input Potentiometer
CT
17
16
15
O
W
C
For details on CT inputs, see Appendix, About Current Transformer (CT) Input (page A-5).
For details on the p otentiometer, see the Instruction Manual for the valve connected to the controller. The meaning of terminal symbols is as follows:
O: OPEN, W: WIPE, C: CLOSE
Thevariableresistancerangeis100to 2.5 kΩ.
About Isolation
2--10
The E5EK-T has independent power supplies for each of the terminal blocks shown on the right.
AB/CC
21 22
23
20 19 18 17 16 15 14 13 12 11
10
9 8 7
B
6 5 4
E
3 2 1
FD
Page 35
2.3 Wiring Terminals
F Event input
21 22
23
20 19
18
17 16 15 14 13 12 11
10
9
8 7 6 5 4 3 2 1
Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20. How ­ever, note that terminal Nos.18 to 20 cannot be used on controllers supporting the communications function.
Connect the event inputs as follows:
EV1
EV2
COM
Event input 1 and 2
19
18
+
-
+
20
Use event inputs under the following conditions:
Contact input
ON: 1 kmax., OFF: 100 kmin.
No-contact input ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Polarities during no-contact input are as follows:
+
20
EV1
19
18
+
-
EV2
COM
Event input 1 and 2
F Transfer ou t pu t
21 22
23
20 19
18 17 16 15 14 13 12 11
10
9
8 7 6 5 4 3 2 1
F Communications
Connect transfer output (TRSF) to terminal Nos. 21 and 22.
The internal equalizing circuit for transfer output is as follows:
+
21
4to20mA L
22
-
Transfer output specifications are as follows:
4to20mADC,Permissibleloadimpedance:600max., R esolution:
Approx. 2600
Terminal Nos.18 to 20, 21 and 22 can be used only on controllers that support the communications units (E53-AK01/02/03).
For details on wiring, see Chapter 6, Using the Communications Function.
2--11
Page 36
CHAPTER 2 PREPARATIONS
2--12
Page 37
CHAPTER3
CHAPTER 3
BASIC OPERATION
This chapter describes actual examples for understanding the basic operation of the E5EK-T.
3.1 ConventionUsedinthisChapter 3-2........
3.2 Setting Input Specifications 3-4.............
Input type 3-4.............................
CHAPTER 3 BASIC OPERATION
Temperature input 3-5.....................
Analog input 3-5..........................
3.3 Setting Output Specifications 3-7...........
Output assignments 3-7....................
Direct/reverse operation 3-8................
Control period 3-8.........................
3.4 Setting Alarm Type 3-10....................
Alarm type 3-10............................
Alarm value 3-10...........................
Alarm hysteresis 3-11.......................
Closeinalarm/openinalarm 3-11............
3.5 Setting Patterns 3-14.......................
Pattern No. 3-15............................
Number of steps 3-15.......................
Step SP/Step time 3-15......................
Alarm value 3-16...........................
3.6 Protect Mode 3-19..........................
Security 3-19...............................
Key protect 3-19............................
3.7 Starting and Stopping Operation 3-21........
3.8 Adjusting Control Operation 3-22............
Changing programs 3-22....................
Manual operation 3-24......................
Auto-tuning (A.T.) 3-25.....................
3--1
Page 38
CHAPTER 3 BASIC OPERATION
3.1 Convention Used in this Chapter
This chapter describes basic E5EK-T operations such as how to set up parameters, start and stop operation, and adjust control operation.
For more complex control examples, refer to Chapter 4 Applied Opera­tion and Chapter 5 Parameters.
F Basic Operation
Flow
The following diagram shows the basic flow of operation.
Power ON
Setup
Setting input specifications
Setting output specifications
Setting alarm output
Setting patterns
Protecting parameters
Operation
Start
Adjustment
3--2
Stop
Power OFF
The descriptions in this chapter follow the order of basic operations shown in the flow above. Examples of operation of each of the items are described up to completion of parameter setup. However, you must move to the top parameter of the following Setting. For example, when
you have finished “setting input specifications” and you want to “set output specifications,” move to the top parameter of “setting output specifications” from the bottom parameter of “setting input specifica-
tions.” For details on moving to parameters between items, refer Chapter, Se­lecting modes and Selecting parameters (page 1-10).
Page 39
3.1 Convention Used in this Chapter
F Setup examples
This description assumes that the controller is operated under the fol­lowing conditions.
A K thermocouple is used as the input.
Control output (heat), alarm 1 and alarm 2 functions are assigned to
“control output 1,” “control output 2” and auxiliary output 1, respec­tively. Of these, only control output 1 and auxiliary output 1 are used.
The relay output unit is mounted at control output 1.
The upper-limit alarm is set as alarm 2. The alarm is output when the
temperature exceeds 10_C with respect to the PV.
The program is made up of one pattern comprising four steps.
The following figures show terminal wiring and the program used in
the setting examples.
Temperature sensor: K thermocouple
Control target
20
19
18
17
16
15
14
13
12
11
--
+
Alarm 2 (upper limit) (alarm value=10_C)
10
SOURCE
OUT1
SUB1
E5EK-- TAAjj (Control output 1: E53--R)
9
8
7
6
5
4
3
2 1
21 22
23
SP
Step 1 Step 2 Step 3
100
Pattern 0
50
0.20 0.40 0.20
Time: hr, min
3--3
Page 40
CHAPTER 3 BASIC OPERATION
3.2 Setting Input Specifications
Setting input specifications
Input type
N
Temperature input?
Y
Temperature unit
Decimal point
Temperature input shift
End of setup
Setup mode
Scaling
Level 2 mode
With temperature input, scaling and decimal point parameters need not b e set as this information is determined by the input (sensor) type. (These parameters are not displayed.) Note that temperature unit and temperature input shift parameters need to be set.
With analog input, the “scaling upper limit”, “scaling lower limit” and “decimal point” parameters need to be set.
JInput type
3--4
Set the type No. (0 to 21) in the “input type” parameter (Set up mode). The factory setting is “2: K1 (thermocouple).”
For details on input types and setting ranges, see page 5-31.
Page 41
JTemperature input
F Temperature unit
3.2 Setting Input Specifications
To switch the temperature unit from “_C” to“_F” when input is tem- perature, switch the “_C/_F selection” parameter (setup mode) from
”to“ ”.
F Temperature
input shift
JAnalog input
When input is temperature input, the upper and lower limit values of the sensor can be shifted linearly. For example, if both the upper and lower limit values are shifted by 1.2_C,theprocessvalue(beforeshift) is regarded as 201.2_C after shift when input is 200_Cbeforeshift.
To set input shift, set shift values in the “input shift upper limit” and “input shift lower limit” parameters (level 2 mode).
Temperature
Input shift upper limit value
Upper limit value
After shift
Before shift
Input shift lower
Lower limit value
0
limit value
Input (%FS)
100
When the analog input (the voltage input and current input) is se­lected, scaling matched to the control is required.
The “scaling upper limit”, “scaling lower limit” and “decimal point” parameters (setup mode) are used for scaling. These parameters can­not be used when the temperature input type is selected.
The “scaling upper limit” parameter sets the physical quantity to be expressed by the upper limit value of input, and the “scaling lower limit” parameter sets the physical quantity to be expressed by the lower limit value of input. The “decimal point” parameter sets the number of digits past the decimal point.
The following figure shows a scaling example of 4 to 20 mA input. Af­ter scaling, the humidity can be directly read. In this case, the “deci­mal point” parameter is set to “1”.
Readout (humidity)
Scaling upper limit value (95.0%)
Scaling lower limit
value (10.0%)
0
100%FS
Input (4 to 20 mA)
3--5
Page 42
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
1 second min.
In this example, let’s check the input type and temperature units, and shift the lower limit by 1_C and the upper limit by 3_C.
“input type” = “2: K1” “temperature unit” = “_C”
“input shift upper limit”= “3.0” “input shift lower limit” = “1.0”
(1) Select the menu display, and select “ :setup mode”usingthe
or keys. For details on selecting the menu display, see page
1-10.
(2) Press the
mode. The top parameter in the setup mode “
key for one second minimum to enter the setup
:inputtype”is
displayed. This parameter is factory-set to “2: K1”.
(3) Press the
: _C”.
to “
(4) Select the menu display, and select “
key to fix the set value. The display changes to
: _C/_F selection” parameter. This parameter is factory-set
: level 2 mode” using the
or keys.
(5) Press the
key for one second minimum to enter the level 2
mode. The top parameter in the level 2 mode [ ] (“local/re­mote” parameter) is displayed.
(6) Press the
key until [ ] (“input shift upper limit” parame-
ter) is selected. This parameter is factory-set to “0.0”.
(7) Press the
(8) Press the
key until “3.0” is displayed.
key until [ ] (“input shift lower limit” parame-
ter) is selected. This parameter is factory-set to “0.0”.
(9) Press the
keyuntil“1.0”isdisplayed.Thissetsthe“inputshift
upper limit” and “input shift lower limit” values.
3--6
Page 43
3.3 Setting Output Specifications
Dest
inat
i
Some output specifications are different according to controller type,
standard or position-proportional. The following table summarizes which output-related parameter settings are supported.
3.3 Setting Output Specifications
JOutput assignments
F Standard type
Parameter
Control output 1 assignment F
Control output 2 assignment F
Auxiliary output 1 assignment F F
Auxiliary output 2 assignment F F
Direct/reverse operation F F
Control period (heat) F
Control period (cool) F
(F Indicates that an output specification is supported.)
Standard
Typ e
Position-
proportional
Typ e
Output assignments are described according to controller type.
Thirteen outputs are supported. These functions are assigned to con­trol outputs 1 and 2, and auxiliary outputs 1 and 2.
Restrictions on assignment destination are placed on some of the out­puts.
The following table shows where outputs may be assigned to.
Assignment
Control Output Auxiliary Output
on
Output Function
Control output (heat) F F Control output (cool) F F Alarm 1 F F F F Alarm 2 F F F F Alarm 3 F F F F HBA F F F F LBA F F F F Time signal 1 F F F F Time signal 2 F F F F Program end F F F F Stage output F F F F Error 1 : Input error F F Error 2 : A/D convertor error F F
1 2 1 2
With control output (cool), the conditions for switching from standard control to heating and cooling control are reached when the output function is assigned at the cooling side during heating and cooling control.
In other words, heating and cooling control is carried out when con­trol output (cool) is assigned, and standard control is carried out when output is not assigned. For details on heating and cooling con­trol, see Chapter 4 Applied Operation/4.1 Selecting the Control Meth­od (page 4-2).
3--7
Page 44
CHAPTER 3 BASIC OPERATION
Dest
inat
i
Factory settings are as follows:
control output 1 = Control output (heat) control output 2 = Alarm 1 auxiliary output 1 = Alarm 2 auxiliary output 2 = Alarm 3
Output assignments are set in the “control output 1 assignment”, “control output 2 assignment”, “ auxiliary output 1 assignment” and “ auxiliary output 2 assignment” parameters (setup mode).
F Position -propor-
tional type
JDirect/reverse
operation
Position-proportional type controllers support nine output functions. These are assigned to auxiliary outputs 1 and 2.
Restrictions on assignment destinations are placed on some of the outputs. The following table shows where outputs may be assigned to.
Assignment
Output Function
Alarm 1 F F Alarm 2 F F Alarm 3 F F Time signal 1 F F Time signal 2 F F Stage output F F Program end output F F Error 1 : Input error F F Error 2 : A/D converter error F F
“Direct operation” (or normal operation) refers to control where the ma­nipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the ma­nipulated variable is decreased according to the decrease in the process value. For example, when the process value (PV) (temperature), is lower than the set point (SP) (temperature), in a heating control system, the manipulatedvariableincreasesbythedifferencebetweenthePVand SP values. Accordingly, this becomes “reverse operation” in a heating control system, or alternatively, “direct operation” in a cooling control sys­tem.
Direct/reverse operation is set in the “direct/reverse operation” pa­rameter (setup mode). Default is “
Control Output Auxiliary Output
on
1 2 1 2
: reverse operation”.
JControl period
3--8
On position-proportional type controllers, this item cannot be set.
On a standard type controller, when the output unit is for pulse out-
put such as relay output, set the pulse output cycle (control period). Though a shorter control period provides better control performance, the control period should be set to 20 seconds minimum taking the life expectancy of the output unit into consideration when the output unit is for relay output.
The control period is set in the “control period (heat)” parameter (level 1 mode). Default of the “control period” parameter is “20:20 seconds.” Default of the “control period (cool)” output function is not assigned. So, the “control period (cool)” parameter cannot be set.
Page 45
3.3 Setting Output Specifications
Setting Example
1 second min.
1 second min.
1 second min.
All of the above settings in this example are factory settings. In this ex­ample, let’s check the parameter settings. In this example, the parameters are set as follows:
“control output 1 assignment” = “control output (heat)”
“auxiliary output 1 assignment” = “alarm output 2” “direct/reverse operation” = “reverse operation” “control period” = “20 secs”
(1) Select the menu display, and select “ :setupmode”usingthe
or keys. For details on selecting the menu display, see page
1-10.
(2) Press the
mode. The top parameter in the setup mode “
key for one second minimum to enter the setup
:inputtype”is
displayed.
(3) Press the
parameter) is displayed. Default is [
(4) Asthesettinginthisexampleistobeleftasitis,pressthe
twice. The display changes to [ ment” parameter). Default is [
(5) Asthesettinginthisexampleistobeleftasitis,pressthe
until [ Default is [
(6) Asthesettinginthisexampleistobeleftasitis,pressthe
key until [ ] (“control output 1 assignment”
].
key
] (“auxiliary output 1 assign-
].
key
] (“direct/reverse operation” parameter) is displayed.
].
or
keys to select “ : l evel 1 mode”. For details on selecting
the menu display, see page 1 -10.
(7) Press the
key for one second minimum to enter the level 1
mode. The top parameter in the level 1 mode “ : Proportional band” is displayed.
(8) Press the
key until [ ] (“control period (heat)” parameter) is displayed. Default is “20”. As the setting in this example is to be
left as its is, quit key operation.
3--9
Page 46
CHAPTER 3 BASIC OPERATION
A
l
3.4 Setting Alarm Type
Three alarm outputs are supported: alarms 1 to 3. Of these, only the alarm assigned as the output can be used.
Alarm output conditions are determined according to the combina­tion of the “alarm type”, “alarm value” and “alarm hysteresis” pa­rameter settings.
The contact conditions for when alarm output is ON can be set to “open” or “closed” in the “close in alarm/open in alarm” parameter.
JAlarm type
The following table shows the alarm types supported by the E5EK-T controller and their respective operations.
armType
Upper-and lower-limit alarm
1
(deviation)
Upper-limit alarm
2
(deviation)
Lower-limit alarm
3
(deviation)
Upper-and-lower-limit range alarm
4
(deviation)
Upper-and-lower-limit alarm with standby sequence
5
(deviation)
Upper-limit alarm with stand­by sequence
6
(deviation)
Lower-limit alarm with stand­by sequence
7
(deviation)
Absolute-value upper-limit
8
alarm
Absolute-value lower-limit
9
alarm
Absolute-value upper-limit
10
alarm with standby sequence
Absolute-value lower-limit
11
alarm with standby sequence
When X is positive When X is negative
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
Alarm Output Operation
XX
SP
X
SP
X
SP
XX
SP
XX
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Always ON
ON OFF
ON OFF
Always OFF
Always OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Alarm types are set independently for each alarm in the “alarm 1 to 3” parameters (setup mode). Default is “2: Upper-limit alarm (devi­ation)”.
JAlarm value
3--10
Alarm values are indicated by “X” in the tabl e above. Alarm output operation differs according to whether the value of the alarm is posi­tive or negative.
Alarm values are built into the program and are set for each pattern. For details, see 3.5 Setting Patterns” (page 3-14).
Page 47
3.4 Setting Alarm Type
C
l
O
JAlarm hysteresis
F Standby
sequence
The hysteresis of alarm outputs when alarms are switched ON/OFF can be set as follows:
Upper limit alarm Lower limit alarm
ON
OFF
Alarm hysteresis
Alarm value
ON
OFF
Alarm value
Alarm hysteresis
Alarm hysteresis is set independently for each alarm in the “alarm 1 to 3 hysteresis” parameters (level 2 mode). Default is “0.02:
0.02%FS”.
“Standby sequence” is a function for unconditionally turning alarm output OFF when the process value has left the alarm range once and it next enters the alarm range.
For example, when the alarm type is set to “ lower-limit alarm,” gen­erally the process value is within the alarm range, and alarm output smaller than the set point, and alarm output becomes ON when this state continues. However, if the alarm type is set to “ lower-limit alarm with standby sequence”, alarm output first becomes ON when theprocessvalueexceedsthe alarm settingvaluetoleavethealarm range and once again falls below the alarm value.
The standby sequence is canceled when an alarm is output. It is, how­ever, restarted later by one of the following conditions:
Operation is started or power is turned ON. A pattern is started. The program advances to the next step.
The SP of the current step is changed. The currently running alarm value is changed. The input shift value is changed. Advance is executed.
JCloseinalarm/openinalarm
When the controller is set to “close in alarm,” the status of the alarm output function is output as it is. When set to “open in alarm,” the status of the alarm output function is output inverted.
Output Output LED
oseinalarm
peninalarm
Alarm
ON ON Lit
OFF OFF Not lit
ON OFF Lit
OFF ON Not lit
Alarm type and close in alarm (normally open)/open in alarm (nor­mally close) can be set independently for each alarm.
Close in alarm/open in alarm is set in the “alarm 1 to 3 open in alarm” parameters (setup mode). Default is “
: close in alarm”.
3--11
Page 48
CHAPTER 3 BASIC OPERATION
F Summary of
alarm operations
The figure below visually summarizes the above descriptions of alarm operations (when alarm type is set to “lower-limit alarm with standby sequence”):
Alarm type: lower limit alarm with standby sequence
PV
Alarm value
Alarm hysteresis
Time
Standby sequence canceled
Alarm
output
ON
OFF
ON (closed) OFF (open)
3--12
Page 49
3.4 Setting Alarm Type
Setting Example
1 second min.
1 second min.
Alarm 2 is output when the temperature exceeds alarm value 2 pro­grammed to the SP. Parameter factory settings for “alarm type 2,” “alarm hysteresis” and “close in alarm/open in alarm” are used. In this example, the related parameters are set as follows:
“alarm type 2” = “2: upper-limit” “alarm value 2” = (set in program setting) “alarm hysteresis: = “0.02” “close in alarm/open in alarm” = “
: close in alarm”
In this example, let’s check the alarm type.
(1) Select the menu display, and select “ : setup mode” pressing
the or keys. For details on selecting the menu display, see page 1-9.
(2) Press the
the setup mode “
(3) Press the
key to enter the setup mode. The top parameter in
: input type” is displayed.
key until [ ] (“alarm type 2” parameter) is dis-
played. Default is “2: upper limit”.
1 second min.
3--13
Page 50
CHAPTER 3 BASIC OPERATION
3.5 Setting Patterns
If you want to set parameters in the program mode during controller operation, you must first stop op­eration. Operation may continue only in special instances, for example, to change SP during controller operation.
Parameters that you use frequently for programming can be set in the “program mode.” The flow below shows the parameters that are available in the program mode and the order in which they are set.
Select the program mode.
Select pattern No.
Set number of steps
Step time/Rate of rise
programming
Step time setting
Set step SP/step time
Set pattern execution count
Set alarm value
Set time signal 1, 2
Step/ON time/OFF time
n
All patterns completed?
Rate of rise setting
Set SP/Ramp time
/Soak time of each step
y
3--14
End of program
This chapter describes the basic operation of programming. For details on the following parameters, refer to Chapter 4 Applied Operation:
“Step time/Rate of rise programming”, “Pattern execution count”, “Time signal 1, 2”
Page 51
3.5 Setting Patterns
JPattern No.
JNumber of steps
JStep SP/Step
time
:
:
: :0to15
This parameter cannot be changed during controller operation.
Set the desired pattern No. Step SP, step time, alarms and other pa-
rameters that follow this parameter are set for the pattern that is set in this parameter.
Set within the range 0 to 3 (pattern 0 to 3). Default is “0”.
Set the number of steps for the pattern that you specified in the “pat-
tern No.” parameter.
Set within the range 1 to 16 (step). Default is “8”.
Set only the number of steps used in the program in order from step
0, as “step 0 SP”, “step 0 time”, “step 1 SP”, “step 1 time” and so forth.
Set within the range from set point lower limit to set point upper limit for step SP. Default is “0”.
Set within the range 0.00 to 99.59 (hours:minutes or minutes:se­conds). Default is “0.00”.
SP
Step 0 Step 1 Step 2 Step 3
Step 0 hour
A: SP of steps 0 and 3 B: SP of steps 1 and 2
As shown in the above figure, step 0 is a fixed value, so when ramp operation is started, set the “step 0 time” parameter to “0.00” to con­figure the program so that ramp operation starts from step 1.
Step 1 hour Step 2 hours Step 3 hours
Time
3--15
Page 52
CHAPTER 3 BASIC OPERATION
JAlarm value
:
: :0to3
Alarm values can be set onl y for alarms that have been assigned as output.
When a deviation alarm i s assigned as output, the alarm value is set with respect to SP. The following example shows the relationship be­tween the SP and alarm value when the alarm type is set to “upper limit.”
SP
Step 0 Step 1 Step 2
Step1SP
Step0SP
Alarm type: upper-limit alarm
Alarm value
Time
Time
About the Alarm Value Decimal Point
3--16
The decimal point of the alarm value conforms to the setting of the “decimal point” parameter.
Page 53
3.5 Setting Patterns
Setting Example
1 second min.
In this example, let’s set the next program to pattern 0.
SP
100
50
Step 0 50 0.00 10 Step 1 100 0.20 10 Step 2 100 0.40 10 Step 3 50 0.20 10
Step 1 Step 2 Step 3
0.20 0.40 0.20
SP
Time
(hr, min.)
Alarm
value 2
Pattern execution count “1”
Time signals are not used.
Time: hr, min
(1) Select the menu display, and select “ : program” pressing the
or keys. For details on selecting the menu display, see page
1-10.
(2) Press the
in the program mode “
key to enter the program mode. The top parameter
: pattern” is displayed. Default is “0 :
pattern 0”.
(3) As the setting “0: pattern 0” in this example is to be left as it is,
press the
key. The display changes to the [ ](“numberof
steps” parameter). Default is “8”.
(4) Set the parameter to “4” pressing the
(5) When you press the
, the display changes to the [ ](“step0
or keys.
SP” parameter). Default is “0”.
(6) Set the parameter to “50” pressing the
(7) When you press the
, the display changes to the [ ](“step0
or keys.
time” parameter). Default is “0.00”.
(8) As the setting “0.00: 0 minutes” in this example is to be left as it is,
press the
key. The display changes to the [ ](“step1SP”
parameter). Default is “0”.
(9) Set the parameter to “100” pressing the
(10)Inthesameway,setthe“
: step 1 time”, “ :step2SP”,
or keys.
: step 2 time”, “ :step3SP”,“ : step 3 time” parame­ters, in that order.
(11) When you have finished setting the step SPs and times press the
key. The [ ] (“pattern execution count” parameter, is dis-
played. Default is “1”.)
3--17
Page 54
CHAPTER 3 BASIC OPERATION
(12) As the setting in this example is to be left as it is, set the alarm val-
(13) Set the parameter to “10: 10 seconds” pressing the
ue. Press the
key until [ ] (“alarm 2” parameter) is dis-
played. Default is “0”.
keys.
or
3--18
Page 55
3.6 Protect Mode
Mod
3.6 Protect Mode
JSecurity
This parameter allows you to protect until start of operation parame­ters that do not change during operation to prevent unwanted modifi­cation.
The set value of the “security” parameter (protect mode) limits the range of protectable parameters. The following table shows the rela­tionship between set values and the range of protection. (Only modes marked by F can be operated.)
Set value
e
Calibration F F Option F F Expansion F F Setup F F Level 2 F F F Level 1 F F F F Program F F F F F Level 0 F F F F F F *1
*1 Only the PV/Present SP” parameter can be displayed.
0 1 2 3 4 5 6
When this parameter is set to “0”, parameters are not protected.
When this parameter is set to “5”, operations in only the level 0 mode
can be selected, and the mode is not displayed on the menu display.
When this parameter is set to “6”, the “PV/Present SP” parameter can only be monitored.
Default is “1”.
JKey protect
This parameter disables key operation for switching run/reset or auto/manual. For example, if you protect the key operation for switch­ing auto/manual by the “key protect” parameter (protect mode) dur­ing automatic operation, the controller cannot be set to the manual mode, preventing manual operation of the controller during opera­tion.
The following table shows the relationship between set values and keys that are protected.
Set value
0
1
2
3
Key protection OFF A/M cannot be selected. RUN/RST cannot be selected. Both A/M and RUN/RST cannot be selected.
Description
Default is “0 : All keys can be operated.”
3--19
Page 56
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
RUN/RST
RUN/RST
In this example, let’s set the parameters as follows: “Security” “2” (all parameters in modes other than the setup
mode are protected)
“Key protect” “1” (Auto/manual key operation cannot be
switched)
(1) Press the
RUN/RST
and keys simultaneously for 1 second mini-
mum. The controller enters the protect mode. In the protect mode, the top parameter in the protect mode “security” is displayed. Default is “1”.
(2) Press the
(3) Press the
(4) Press the
(5) Press the
key to change the parameter setting to “2”.
key to switch to the “key protect” parameter.
key to change the parameter setting to “1”.
RUN/RST
and
keys simultaneously for 1 second mini-
mum. The display changes to the “PV/Present SP mon itor” param-
eter (level 0 mode).
3--20
Page 57
3.7 Starting and Stopping Operation
3.7 Starting and Stopping Operation
To start program operation (that is, switch from the reset state to run
RUN/RST
operation), press the
To stop program operation (that is, switch from run operation to the
reset state), press the
the controller has stopped operating (reset state), the RST LED lights.
The controller cannot be reset during auto-tuning (A.T.).
RUN/RST
RUN/RST
key for one second minimum.
key from two seconds minimum. When
F Man ip ulated vari-
able at reset
On a standard type controller, specify the manipulated variable ( -5.0 to 105.0%) in the “MV at reset” parameter (level 2 mode) to output the manipulated variable during reset. Default is “0.0:0.0%”.
When the controller is reset in the manual mode, the manual MV takes precedence.
Both the MV limitter and MV change rate limitter are ineffective against the manipulated value at reset.
On a position-proportional type controller, you can select either of the open, closed or hold state. In an open state, only control output 1 is ON. In a closed state, only control output 2 is ON. In a hold state, both control outputs 1 and 2 are OFF. Default is “
”.
Using Event Input
On the E53-AKB, run/reset can be selected by event input. For details on how to use event input, see 4.8 How to Use Event Input, page 4-21.
3--21
Page 58
CHAPTER 3 BASIC OPERATION
3.8 Adjusting Control Operation
JChanging
programs
F Changing the SP
Before change
Programs are changed in the pr ogram mode. Note that pattern Nos. cannot be changed during program operation. So, only the pattern that is currently running can be changed.
You cannot change the program when the “security” parameter (pro­tect mode) is set to “5” or “6”.
ChangetheSPofsteps0to15in“step0to15SP”parameters(pro­gram mode).
When the SP is changed midway through a step, the Present SP is shifted on a line obtained by taking the new SP as the target point.
SP
After change
Changing point
Time
Step N Step N+1
F Changing the
time value
Before change
After change
About Changing the Number of Steps
Change the time value of steps 0 to 15 in “step 0 to 15 time” parame­ters (program mode).
When the time value is changed midway through a step, the step time changes. The gradient of the line by which SP shifts also changes.
SP
Changing point
Time
Step N Step N+1
Step N Step N+1
If you set the “number of steps” parameter (program mode) to a value smaller than the current number of steps during program operation, program operation is immediately exited.
3--22
Page 59
3.8 Adjusting Control Operation
Setting Example
1 second min.
1 second min.
In the following example, let’s change the temperature set point to “60_C” from “50_C”.
(1) Press the key for 1 second minimum at the currently executing
“PV/Present SP” display.
(2) The display changes to the menu display.
(3) Set the parameter to “
(4) Press the
key to enter the program mode. The top parameter in
: program” pressing the or keys.
the program mode “ : pattern” is displayed.
(5) Press the
key to display the [ ] (“number of steps” parame-
ter).
(6) Press the
key. [ ] (“step 0 SP” parameter) is displayed, and the
No.2 display indicates “50.0”.
(7) Press the
(8) Press the
key to set the parameter to ”60.0”.
key for 1 second minimum. The menu display (“
: program” parameter) is redisplayed.
(9) Select “
the
: level 0 mode” pressing the or keys, and press
key for 1 second minimum. The “PV/Present SP” display is
redisplayed.
1 second min.
1 second min.
3--23
Page 60
CHAPTER 3 BASIC OPERATION
JManual operation
F Standard type
On a standard type controller, the manipulated variable is controlled, and on a position-proportional type controller, the valve opening is controlled.
To set manual operation and manually set the manipulated variable or the valve opening, press the
key and key simultaneously for 1 second minimum. Then the controllers enters the manual mode. To quit the manual mode, press the
key and key again simul­taneously for 1 second minimum. The controller enters the level 0 mode without entering the menu display.
Though the control shifts to manual operation if the controller is set to the manual mode during program operation, the program ad­vances. When program operation is started in the manual mode, pro­gram also advances.
In the manual mode, the automatic return of display mode does not work.
The process value is displayed on the No.1 display, and the manipu­lated variable is displayed on the No.2 display.
To change the manipulated variable, press the
or keys. After
two seconds, the manipulated variable is updated to the new setting.
When switching between manual and auto operation, the manipu­lated variable is subject to balance-less, bump-less operation.
If the power is interrupted during manual operation, manual opera­tion is resumed at the manipulated variable that was active at power interruption when the power is reset.
Manipulated variable (%)
Manual
Auto
F Position -propor-
tional type
Balance-less, Bump-less Opera­tion
Balance-less,
bump-less points
0
Manipulated vari­able switched
++
OFF ON
Power inter­ruption
When a potentiometer is connected to the controller, the process value is displayed on the No.1 display, and the valve opening is displayed on the No.2 display.
When you press the press the
To prevent sudden changes in the manipulated variable when switching between manual and auto operation, operation is resumed using the value that was active immediately before operation was switched, and the value is brought gradually closer to the value immediately after operation was switched.
key, the close side becomes ON.
key, the open side becomes ON. When you
Time
3--24
Page 61
3.8 Adjusting Control Operation
JAuto-tuning
(A.T.)
F 40%AT
Deviation at start of AT execution 10% FS
AT (auto-tuning) cannot be executed while operation is reset or dur­ing ON/OFF control.
When you execute auto-tuning, the optimum PID parameters are au­tomatically set by forcibly changing the manipulated variable to cal­culate the characteristics (called the “limit cycle method”) of the con ­trol target. During auto-tuning, time counting is stopped and the “AT ” L E D f la sh e s.
40%AT or 100%AT can be selected by the limit cycle o f MV change width. Specify [
]or[ ], respectively, in the “A T execute/
cancel” parameter (level 1 mode).
During heating and cooling control on a standard type controller, and on a position-proportional type controller, only 100%AT can be executed. (So, “
To cancel AT execution, specify “
: 40%AT” is not displayed.)
:ATcancel”.
In order to set the limit cycle of MV change width to 40%, select 40%AT to execute auto-tuning with fluctuations in the process value kept to a minimum. However, note that auto-tuning takes longer to execute compared with 100%AT. The timing by which limit cycles are generate d varies according to wheth­er or not the deviation (DV) at the start of AT execut ion is 10% full-scale or less.
Deviation at start of AT execution < 10% full-scale
Limit cycle of MV change width 40%
Limit cycle of MV change width 40%
Set point Set point
Deviation 10% full-scale
StartofAT execution
F 100%AT
End of AT execution
In order to set the li mi t cycle of MV change width to 100%, select
Time Time
100%AT to shorten the AT execution time without worrying about fluc­tuations in the process value.
Limit cycle of MV change width 100%
Set point
StartofAT execution
StartofAT execution
End of AT
Deviation 10% full-scale
End of AT execution
Time
3--25
Page 62
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
AT execute
End of AT execution
In this example, let’s execute 40%AT.
(1) Select the menu display, and select “ : level 1 mode” using the
or keys. For details on selecting the menu display, see page
1-10.
(2) Press the
the setup mode “ example, the parameter setting is “
(3) Press the
key to enter the level 1 mode. The top parameter in
: AT execute/cancel” is displayed. In this
:ATcancel”.
key to specify [ ].
(4) The AT LED flashes, and AT execution starts. When the AT LED
goes out (end of AT execution), the parameter automatically re­turns to “
:ATcancel”.
3--26
About PID Param­eters
AT Execution T im­ing
When control characteristics are already known, the PID parameters can be set directly to adjust control. PID parameters are set in the “proportional band” (P), “integrated time” (I) and “derivative time” (D) parameters (level 1 mode). For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode (page 5-18).
The E5EK-T differs from fixed-value type controllers in that the SP changes au­tomatically. So, the timing of AT execution is the most important factor in con­trol. To obtain PID parameters for a specific SP, make a fixed-value program as follows and execute AT.
10 minutes
100
Step 0
Set value
SP Time
Step 0 100 0.10
Page 63
CHAPTER4
CHAPTER 4
APPLIED OPERATION
This chapter describes each of the parameters required for making full use of the features of the E5EK-T. Read this chapter while referring to the parameter descriptions in chapter 5.
CHAPTER 4 APPLIED OPERATION
4.1 Selecting the Control Method 4-2............
Heating and cooling control 4 -2.............
Position-proportional control 4-4............
ON/OFF control 4-5.......................
4.2 Operating Condition Restrictions 4-7........
Manipulated variable restrictions 4-7........
Set point limiter 4-8.......................
4.3 Ramp Rise Rate Setup Program 4-9.........
Runningtherampriseratesetupprogram 4-11
Program example 4-12......................
4.4 Program Operation 4-13....................
Hold/Advance 4-13..........................
Pattern operation 4-14......................
4.5 W ait Operation 4-16........................
4.6 Program output 4-17........................
Time signal 4-17............................
Program output 4-18........................
4.7 Setting Running Conditions 4-19.............
Operation at power ON 4-19.................
Starting the program run 4-19...............
End condition 4-20.........................
4.8 How to Use Event Input 4-21................
Input assignments 4-21.....................
Detailed description of input functions 4-22...
4.9 How to Use the Heater Burnout Alarm 4-23...
Heater burnout detection 4-23...............
Operating conditions 4-23...................
How to calculate the heater burnout
set value 4-24..............................
4.10 LBA 4-26..................................
4.11 How to Use Transfer Output 4-28............
4--1
Page 64
CHAPTER 4 APPLIED OPERATION
4.1 Selecting the Control Method
JHeating and
cooling control
When selecting the control method, set the parameters according to the following table. (Parameters are factory-set to heating control.)
Parameter
Control Method
Heating control
(Standard)
Cooling control
(Standard)
Heating and cooling
control
(Parameters are factory-set to heating control.)
For details on how to assign outputs, see 3.3 Setting Output Specifica­tions (page 3-7).
When heating and cooling control is selected, the “dead band” and “cooling coefficient” parameters can be used.
F Dead band
The dead band is set with the set point as its center. The dead band width is the set value of the “dead band” parameter (level 1 mode). Set­ting a p ositive value produces a dead band, while setting a negative val­ue produces an overlap band. The dead band is factory-set to “0.00:0.00%FS.”
Output Output
Dead band: dead band width = positive
Control Output 1
Assignment
Control output (heat)
Control output (heat)
Control output (heat) Control output (cool) Reverse operation
Control Output 2
Assignment
-
-
Overlap band: dead band width = negative
Direct/Reverse
operations
Reverse operation
Direct operation
Heating side
0
F Cooling
coefficient
Cooling side
PV
Set point Set point
Heating side
0
If the heating and cooling characteristics of the control target greatly differ, preventing satisfactory control characteristics from being ob­tained by the same PID parameters, adjust the proportional band (P at cooling side) using the cooling coefficient to balance control between the heating and cooling sides. In heating and cooling control, P at the heating or cooling side is calculated by the following formula:
Heating side P = P; Cooling side P = cooling coefficient ¢ P
Cooling side
PV
4--2
Page 65
4.1 Selecting the Control Method
F Man ip ulated vari-
able at reset
In heating and cooling control, the manipulated variable output that is output when controller operation is stopped is dependent on the set value of the “MV at reset” parameter (level 2 mode) in the same way as for standard control.
However, note that in heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. When the manipulated variable at reset is a negative value, the manipulated variable is output to only the cooling side, and when a positive value, the manipulated variable is output to only the heating side. Default is “0”. If the controller is operated with default, the manipu­lated variable is not output to both the heating and cooling sides.
Switching with Manual Operation
When the overlap band is set, the bumpless function that operates when switch­ing between manual and automatic operation may not work.
4--3
Page 66
CHAPTER 4 APPLIED OPERATION
JPosition-propor-
tional control
8
Open
7
6
Close
5
O
17
W
16
C
15
Potentiometer
F Travel time
F Valve opening
monitor
Use the position-proportional type controller for position-proportion­al control.
On a position-proportional type controller, control output 1 is used for open output, and control output 2 is used for closed output. Ac­cordingly, control outputs 1 and 2 cannot be used as output assign­ments. Special output units are already set on position-proportional type controllers.
On a position-proportional type controller, the following functions are disabled:
MV limitter P and PD control 40% AT LBA HBA ON/OFF control
To change the travel time, either set in the “travel time” parameter (option mode), or execute motor calibration in the “motor calibra­tion” parameter (option mode).
Default is “30:30 seconds.”
The valve opening can be monitored when a potentiometer is con-
nected to the controller. However, be sure to execute motor calibra­tion after connecting the potentiometer.
F Man ip ulated vari-
able at reset/PV error
F Other functions
Open, closed or hold can be selected as output at reset or PV error. Set these outputs in the “MV at reset” or “MV at PV error” parameters (level 2 mode).
Set the dead band in the “position-proportional dead band” parame­ter (level 1 mode). Default is “2.0:2.0%”.
Set the open/close hysteresis in the “open/close hysteresis” parameter (level 2 mode).
Open/close hysteresis
Dead band
ON
OFF
MV-Valve opening
100%0-100%
4--4
Page 67
4.1 Selecting the Control Method
JON/OFF control
F Hysteresis
ON/OFF control is selected by the “PID/ON/OFF” parameter (expan­sion mode). When this parameter is set to [ trol is selected, and when set to [
], ON/OFF control is selected.
The “ON/OFF control” parameter is factory-set to [
], advanced PI D con-
].
During position-proportional control, ON/OFF control cannot be se­lected.
In ON/OFF control, hysteresis is provided in the p rogram when switching between ON and OFF to stabilize operation. The hysteresis width provided during ON/OFF control is simply referred to as “hys­teresis.” Control output (heat) and control output (cool) functions are set in the “hysteresis (heat)” and “hysteresis (cool)” parameters, re­spectively.
In standard control (heating or cooling control), hysteresis can be set only for the heating side.
Hysteresis (heat)
ON
OFF
Set point
PV
In heating and cooling control, a dead band can be set. So, 3-position control is made possible.
Dead band
Hysteresis (heat)
ON
Heating side
OFF
Hysteresis (cool)
Cooling side
PV
Set point
4--5
Page 68
CHAPTER 4 APPLIED OPERATION
Parameters
Symbol Parameter Name: Mode Description
Control output 1
assignment : Setup
Control output 2
assignment : Setup
Direct/reverse
operation : Setup
Dead band : Level 1 Heating and cooling control
Cooling coefficient : Level 1 Heating and cooling control
MV at reset : Level 2 Manipulated variable when control
MV at PV error : Level 2 Manipulated variable when control
Travel time : Option Position-proportional control
Motor calibration : Option Position-proportional control
Positional-proportional
dead band : Level 1
Open/close
hysteresis : Level 2
Hysteresis (heat) : Level 1 ON/OFF control
Hysteresis (cool) : Level 1 ON/OFF control
PID / ON/OFF : Expansion ON/OFF control
For specifying control method
For specifying control method
For specifying control method
operation is stopped
operation is PV error
Position-proportional control
Position-proportional control
4--6
Page 69
4.2 Operating Condition Restrictions
4.2 Operating Condition Restrictions
JManipulated vari-
able restrictions
F MV limiter
The upper- and lower-limit values of the manipulated variable can be restricted by the MV limitter, and the change rate of manipulated vari­able can be restricted by the MV change rate limitter.
The upper- and lower-limit values of the manipulated variable are set in the “MV upper limit” and “MV lower limit” parameters (level 2 mode). When the manipulated variable calculated by the E5EK-T is out­side of the range of the MV limitter, actual outputs are dependent on thesetvalueoftheseparameters.
Output (%)
100
0
MV upper limit value
MV lower limit value
PV
In heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. The up­per limit is set for the heating side (positive value), and the lower limit is set for the cooling side (negative value) as shown in the following fig­ure.
F MV change rate
limiter
Output (%)
100
MV lower limit value
MV upper limit value
Heating side
0
Set point
Cooling side
PV
The “MV change rate limitter” parameter (level 2 mode) sets the maxi­mum permissible change width per second of the manipulated variable. If a change in the manipulated variable exceeds this parameter setting, the value calculated by the E5EK-T is reached while changing the value by the per-second value set in this parameter.
Output (%)
100
MV change rate limit value
1 second
0
Switching point
Time
4--7
Page 70
CHAPTER 4 APPLIED OPERATION
F Limiter operation
conditions
JSet point limiter
Set point Upper-and lower-limit values of the limitter
Scaling (sensor) upper-and lower-limitter values
The limitters are disabled or cannot be set when any of the following conditions occurs:
During ON/OFF control
During AT execution (only by MV change rate limitter)
During manual operation
When operation is stopped
When an error has occurred
During position-proportional control (manipulated variable limitter
only)
The setting range of the set point is limited by the set point limitter. The upper- and lower-limit values of this set point limitter are set in the “set point upper limit” and “set point lower limit” parameters (ex-
pansion mode), respectively. However, note that when the set p oint li­mitter is reset, the set point is forcibly changed to the upper- or lower­limit value of the set point limitter if the set point is out of the limitter range. Also, when the input type, temperature unit and scaling (sensor)
range are changed, the set point limitter is forcibly reset to the scaling (sensor) range.
Scaling (sensor) range
Set point limiter
Setting range
Changed to upper limit value
Input type changed
Changed to the new up­per limit value
A
○B×
C
CB
(setting impossible)
(setting possible)
Set Point
Set Point
Set Point
Parameters
4--8
Symbol
Parameter Name: Mode Description
MV upper limit : Level 2 For limiting manipulated variable
MV lower limit : Level 2 For limiting manipulated variable
MV change rate limit : Level 2 For limiting manipulated variable
Set point upper limit : Expansion For limiting SP setting
Set point lower limit : Expansion For limiting SP setting
Page 71
4.3 Ramp Rise Rate Setup Program
4.3 Ramp Rise Rate Setup Program
Chapter 3 described programs that used the “time setup method.” Pro­grams were executed using a combination of SPs and step time values.
The E5EK-T also supports the “ramp rise rate setup method.” By this method, programs are executed using three program elements: “target SP”, “rate o f rise” and “soak time.” To select a ramp rise rate program, set the “Step time/rate of rise pro-
gramming” parameter (expansion mode) to “
Target SP
Time unit of ramp rate
:rateofrise.”
Soak time
Rate of rise
Step
NN+1
Ramp step Soak step
Set each of the above p rogram elements i n the “target SP 0 to 7”, “rate of rise 0 to 7” and “soak time 0 to 7” parameters.
In a ramp rise rate program, parameters are set to two steps as shown
in the figure above. The following figure shows the relationship be­tween the pro gram and parameters.
Target SP 1
Soak time 0 Soak time 1 Soak time 2
Target SP 0
Target SP 2
Step
Parameter
012345
Target SP 0 Target SP 1 Target SP 2
Rate of rise 0 Rate of rise 1 Rate of rise 2
Soak time 0 Soak time 1 Soak time 2
4--9
Page 72
CHAPTER 4 APPLIED OPERATION
F Relationship with
the number of steps
F When the rate of
rise is set to “0”
When the number of steps is set to an odd number, the final soak time cannot be set. For example, if we set the “number of steps” parameter to “7”, the “soak time 3” parameter cannot be set even though the “tar­get SP 3” and “rate of rise 3” parameters can be set.
Accordingly, when the number of steps are set to an even number, the final step is a soak step. When it is set to an odd number, the final step is a ramp step.
Number of steps = even number Number of steps = odd number
When “rate of rise 0 to 7” parameter is set to “0”, the ramp step is skipped and the soak step appears to be continuous.
Step N is skipped.
Step
NN-1
Ramp step Soak step
N+1
Soak step
4--10
Page 73
4.3 Ramp Rise Rate Setup Program
JRunning the ramp
rise rate setup program
F Changing
parameters
Ramp rise rate setup programs take the PV at start of program op era­tion as the SP (PV start) when they are started.
When the rate of rise is changed midway during operation, the SP rate of rise and the step time in the ramp cycle both change.
After change
Before change
Switching point
Before change
After change
In the above figure, increasing the rate of rise results in a shorter tar­get step time. Likewise, when the SP is changed, the step time of the ramp cycle also changes.
When the soak time is changed, only the step time in the soak cycle changes.
Step N Step N+1
Step N Step N+1
Time
4--11
Page 74
CHAPTER 4 APPLIED OPERATION
JProgram example
F Program
structure
F How the program
works
Let’s describe a typical example of a ramp rise rate setup program. In an actual program, set the parameters to match the application.
100
10
Step 0 Step 1 Step 2 Step 3
30 60 90 120
Target SP 0 : 100
Rate of rise 0 : 3
Soak time 0 : 0.30
“Number of steps” = 4, “Time unit of ramp rate” = minutes, “PV start” = 10
Target SP 1 : 10
Rate of rise 1 : 3
Soak time 1 : 0.30
In a program comprising four steps, steps 0 and 1 follow the settings of
the “target SP 0”, “rate of rise 0” and “soak time 0” parameters. Steps 2 and 3 follow the settings of the “target SP 1”, “rate of rise 1” and “soak time 1” parameters.
(1) As the program starts at PV (PV start), the program starts opera-
tion from “10” in this example.
(2) As the rate of rise is set to “3”, the Present SP takes 30 minutes
(100-10/3=30) to reach the target SP value “100” in step 0. If the PV is “40” when the program is started, this time then becomes 20 minutes using the same formula.
(3) In step 1, the Present SP does not change, and the step time is the
value set to the “soak time 0” parameter (in this example, “30 min-
utes”).
(4) In step2, the Present SP changes according to the value of “rate of
rise 1” parameter from that of “target SP 0” parameter to that of “target SP 1” parameter It takes 30 minutes in this example.
(5) In step 3, the Present SP does not change, and the step time is the
value set to the “soak time 1” parameter (in this example, “30 min­utes”).
Parameters
Operation at Input Error
4--12
Symbol Parameter Name: Mode Description
Step time/Rate of rise programming : Expansion Ramp rise rate
: Target SP 0 to 3 : Program Ramp rise rate
:
Rate of rise 0 to 3 : Program Ramp rise rate
:
Soak time 0 to 3 : Program Ramp rise rate
: : to
By ramp rise rate setup method, starting at input error, the program start step is the “step 1”.
Page 75
4.4 Program Operation
4.4 Program Operation
JHold/advance
Steps in currently executing programs can be forcibly stopped (Hold) and advanced (Advance).
Hold and Advance operation is according to the following procedure:
Run in level 0 mode
Check step No.
Hold?
Y
Hold = ON
Continue
End of hold?
End
Hold = OFF
Advance
Y
N
N
Advance = ON
Continue
End of advance
End
End: To program operation
Execute hold/advance operation while making sure the step No. in the “step No. monitor” parameter (level 0 mode).
When the “hold” parameter (level 0 mode) is set to “ :ON”,step time counting is paused (held), and the HOLD LED lights. [
]and the SP appear alternately on the No.2 display when in the “PV/Pres­ent SP” parameter.
Hold is canceled time counting is restarted by one of the following conditions: “hold” parameter = “
:OFF”,Run,Reset,Endopera-
tion using advance instruction
Each time that “advance” parameter (level 0 mode) is set to “ : ON”, the pro gram advances one step. With each step advance, the “Advance” parameter setting returns to “
: O FF”.
If the advance function is executed with the program in a hold state, the hold state is continued in the next step.
4--13
Page 76
CHAPTER 4 APPLIED OPERATION
JPattern operation
F Repeatin g execu-
tion of the same pattern
To repeatedly execute the same pattern, set the number of times that the pattern is to be executed in the “pattern execution count” param­eter (program mode).
The pattern execution count can be set up to 9999 (times). (Default is “0”.)
Patterns for which the “pattern execution count” parameter is set to “0” cannot be executed.
The count of the currently executing pattern in the program can be verified in the “pattern execution count monitor” parameter (level 0 mode). “0” is indicated in this parameter when the controller of reset or in a standby state.
F Executing all
patterns
To execute all preset patterns in order from pattern 0, set the “run all enable” parameter (expansion mode) to “ OFF”.)
Pattern 0 Pattern 1 Pattern 2
When a power interruption occurs during run all execution, if the “operation at power ON” parameter (expansion mode) is set to “ Continue”, the currently executing pattern No. is held in memory. When power is restored, program operation resumes from the pattern that was being executed when the power was interrupted. (For details on operation at power ON, see page 4-19.)
Patterns whose “pattern execution count” is set to “0” are skipped.
:ON”.(Default“ :
Time
:
4--14
Pattern 0 Pattern 1 Pattern 3
“pattern execution count” of pattern 2 is set to 0
Time
Page 77
4.4 Program Operation
Parameters
Symbol Parameter Name: Mode Description
Hold : Level 0 Pauses program execution.
Advance : Level 0 Advances the program one step.
Pattern execution count : Program
Run all :Expansion Executes all patterns.
Repeatedly executes current pattern.
About Reset
A reset cancels a hold state.
When the controller is reset during run all execution, the program returns to
step 0 of the currently executing pattern.
4--15
Page 78
CHAPTER 4 APPLIED OPERATION
4.5 Wait Operation
“Wait” is the operation of not advancing the program steps and wait­ing for the PV to enter the preset wait width at the end of each step. During wait operation, the “WAIT” LED lights.
As the PV is smaller than “SP - wait width” at the end of the rising step in the above figure, control monitoring is stopped, and the con­trol waits for PV to reach “SP - wait width” before the step is up­dated.
In the case of a falling step, the control waits for PV to reach “SP + wait width.”
Set the wait width in the “wait width” parameter (expansion mode) within the range 0 to 9999 (EU). (Default is “0”.)
Setting the “wait width” to “0” disables wait operation.
Wait width
SP
PV
During wait
Counting stop Step updated Time
Wait width
Parameters
4--16
Symbol Parameter Name: Mode Description
Wait width : Expansion Wait operation
Page 79
4.6 Program output
The E5EK-T outputs the following signals according to how far the program has elapsed:
These functions can be used only when they have been assigned as out­puts.
4.6 Program output
Time signal 1/2 Program end Stage output
JTime signal
Two types of time signals can be set to each pattern.
ON time
Time signal output
OFF time
There are two timers for time signals: ON time timer and OFF time timer. These times are counted from the beginning of the step.
Output is ON from the ON time elapsed point up to the OFF time elapsed point.
Set the step at which to output the time signal in the “time signal 1/2 enabled step” parameter (program mode). (Default is “0: step 0.”)
Set the ON/OFF timing in the “time signal 1/2 ON time” and “time signal OFF time” parameters (program mode).
Time
F About ON
conditions
About Pattern Elapsing Time
When the OFF time is set shorter than the ON time, output is ON until a reset from the ON time elapsed point onwards or at start of the next pattern.
Output does not turn ON when ON and OFF times are set the same.
When step advance is executed during execution of the time signal
enabled step, the controller judges that the time equivalent to the en­abled step has elapsed. For example, in the above figure, output is ON from the start of the following step up to the OFF time elapsed point.
You can verify the pattern elapsing time in the “pattern elapsing time” parame­ter (level 0 mode). During repeated execution of patterns or run all execution, the program is counting for each pattern. If the count exceeds the monitor range (99 hours:59 minutes or 99 minutes:59 seconds), “99.59” is displayed flashing. During Hold, time counting is paused. Executing Advance, the skipped step time is counted.
4--17
Page 80
CHAPTER 4 APPLIED OPERATION
JProgram status
F Program end
F Stage output
One-second pulse signal is output after the final step is completed.
Time
Program end output
Final step
1s
One-second pulse signal is output at the beginning of each step.
Parameters
1s
Stage output
Symbol Parameter Name: Mode Description
:
Time signal:set step : Program Time signal
Time signal:ON time : Program Time signal
: :
Time signal:ON time : Program Time signal
:
Control output:assignment : Setup Program status
:
Auxiliary output:assignment : Setup Program status
: : to
Time
4--18
Page 81
4.7 Setting Running Conditions
4.7 Setting Running Conditions
JOperation at
power ON
You can select from one of the following operations at power ON:
Continue,Reset,Run,Manual
If you select “Continue,” operation is started from the state that was active when power was interrupted.
If you select “Reset,” the controller is reset.
If you select “Run,” normal program operation is started.
If you select “Manual,” the controller enters the manual mode.
The following table shows the relationship between operation at pow-
er ON and the operation details that are stored to memory when a power interruption occurs.
Continue Reset Run Manual
Pattern No. f f f f Step No. f - - f Pattern elapsing time f - - f Pattern execution count f - - f Hold status f - - f Auto/Manual f f f - Run/Reset f - - f MV a t reset *1 f - - f Manual MV *2 f f f f
*1 During auto mode at power interruption on a standard type controller
*2 During manual mode at power interruption on a standard type controller
Set the desired operation in the “operation at power ON” parameter (expansion mode). Default is [
:Continue].
4--19
Page 82
CHAPTER 4 APPLIED OPERATION
JStarting the
program run
F PV start
F Standby
operation
JEnd condition
When the program is configured by the time setup method, a ramp­priority “PV start” can be selected as one of the run start conditions. If you select “PV start” in the “PV start” parameter (expansion mode), program operation is started from the position of the SP that first matches the PV when program run is started. If the SP does not match the PV, the program run is started from the beginning.
SP
Step 0 Step 1 Step 2 Step 3
Disabled time
PV
Start point
Time
After the run instruction, the controller is reset until the standby time elapses.
Set the standby time in the “standby time” parameter (level 2 mode) within the range 0.00 to 99.59 (hours:minutes). Defaults is “0.00”.
After end of operation, the controller normally is reset. However, con ­trol can be continued on the SP of the final step by setting the “end condition” parameter (expansion mode). If the “end condition” is set, the SP of the final step and [ display.
When the “number of steps” parameter is changed after operation has ended, the controller state does not change state. However, if control with respect to the SP is continued, the SP switches to the new value of the final step.
] appears alternately on the No.2
Parameters
4--20
Symbol Parameter Name: Mode Description
Operation at power ON : Expansion
PV start : Expansion Start of program run
Standby time : Level 2 Start of p rogram run
End condition : Expansion Operation end program run
Operation when power is turned ON
Page 83
4.8 How to Use Event Input
When using event input, mount the option unit (E53-AKB).
Switching by event input is not possible on the menu display.
Switch event inputs ON and OFF while controller power is ON.
4.8 How to Use Event Input
JInput
assignments
You can choose from the following six event input functions:
Run/Reset Remote/Local Auto/Manual Hold/Hold cancel Advance Pattern select
Event input ON/OFF judgment is carried out on inputs of 200 ms minimum.
When event inputs are used as program advance input, the program step is advanced at the rising (OFF
ON) edge of the input signal.
When event inputs are used as run/reset input, program operation is stopped (reset) at the rising (OFF program operation is started (run) at the falling (ON
ON) edge of the input signal, and
OFF) edge.
Other signals are accepted at all times.
Set event input assignments in the “event input assignments 1 and 2” parameters (option mode).
The following table shows the relationship between the settings and functions of the “event input assignment 1 to 2” parameters.
Setting Function
Event input disabled
OFFON: Reset /ONOFF: Run
ON: Remote /OFF: Local
ON: Manual /OFF: Auto
ON: Hold /OFF: Hold cancel
Execute at OFFON
Specify by combination oftwo inputs (*1).
*1 The following table shows the relationship between pattern select No. and
pattern No.
Pattern No. 0 1 2 3
Pattern select 0 f f Pattern select 1 f f
4--21
Page 84
CHAPTER 4 APPLIED OPERATION
JDetailed
description of input functions
F Run /Reset
Reset Run
F Auto/Manual
F Hold/Hold cancel
F Advan ce
Advance
There is no order of priority in event input, key operations and com­munications command setup. However, remote/local, auto/manual, hold/hold cancel or pattern selection be set to either of ON or OFF. So, parameters will always follow event input even if you try to switch settings by key operation and communications commands.
Program operation is stopped (reset) at the rising (ON→ON) edge of the event input signal, and the RST LED lights. Program operation is started (run) at the falling (ONOFF) edge of the event input signal.
When event input is set to “ON”, the controller is switched to manual operation, and the “MANU” LED lights.
This function is enabled only during program operation.
The program is paused (Hold) when the event input is ON, and the
“HOLD” LED lights. Holds continue until the state of the event input changes to O FF.
This function is enabled only during program operation.
Program steps are advanced at the ri sing (OFFON) edge of the
event input signal. Accordingly, be sure to set event input OFF before you use this function.
F Pattern select
Parameters
This function is enabled only when the program is reset.
Patterns are selected using a combination of pattern select 0 and 1.
Pattern select 0 and 1 inputs that are not assigned are normally
treated as OFF. For example, when only pattern select 1 is assigned, pattern select inputs 0 and 1 are treated as OFF, so patterns 0 and 1 are patterns targeted for switching.
Symbol Parameter Name: Mode Description
: Event input assignments 1 to 2: Option
: : to
Event input functions
4--22
Page 85
4.9 How to Use the Heater Burnout Alarm
4.9 How to Use the Heater Burnout Alarm
On a standard type controller, the HBA (heater burnout alarm) func­tion can be used only when the assignment destination of the output function “control output (heat)” is set to pulsed output.
When using the HBA function, assign output function “heater burn­out alarm” to control outputs 1/2 or auxiliary outputs 1/2.
JHeater burnout
detection
To E5EK-T CT terminal
CT
Heater wire
F HBA
latch/release
Heater burnout detection works as follows:
(1) Connect the current transformer (CT) to terminal Nos.15 and 17,
and insert the heater lead through the CT hole.
(2) When current flows through this lead, the current transformer gen-
erates AC current proportional to the current value. The E5EK-T measures this AC current to calculate the current flowing to the heater.
(3) If the heater is burned out, the current measured at the current
transformer decreases. This value is compared wi th the value set as the heater burnout set value and is output as the heater burnout alarm.
Set the heater burnout set value in the “heater burnout alarm” pa­rameter. To verify the current value of the current transformer, use the “heater current monitor” parameter.
When you are not using the HBA function, set the “heater burnout alarm” parameter to “0.0 (disabled)”.
When the HBA latch function is set to “ON”, the heater burnout alarm is held until either of the following measures is taken:
a Set the heater burnout set value to “0.0A” (default). b R eset the controller.
(Turn the controller’s power OFF then back ON again.)
To enable the HBA latch function, set the “HBA latch” parameter to “ON”.
JOperating
conditions
Turn the heater power supply ON at the same time as or before turn­ing the E5EK-T power supply ON. If the heater power supply is turned ON after turning the E5EK-T power supply ON, the heater burnout alarm is output.
Control is continued even when the heater burnout alarm is output. (That is, the controller attempts to control the heater as if the heater burnout alarm has not occurred.)
The heater burnout alarm is detected only if the control output is continuously ON for 190 ms minimum.
The rated current value may sometimes differ slightly from the actual current value flowing to the heater. Verify the current value in an ac­tual operating state in the “heater current monitor” parameter.
If there is little difference between the current in a normal state and the current in a burnout state, detection may become unstable. On a heater of current 10.0 A or less, maintain a difference of 1.0 A mini­mum. On a heater of current 10.0 A minimum, maintain a difference of 2.5 A mini mum.
4--23
Page 86
CHAPTER 4 APPLIED OPERATION
The heater burnout alarm function cannot be used when the heater is controlled by a phase control system or by a cycle control system. Also, the heater burnout alarm function cannot be applied on 3-phase heaters.
To detect heater burnout on a 3-phase heater, use the K2CU-FjjA-jGS (with gate input terminal). (For details, see the respective product catalog.)
JHow to calculate
the heater burn­out set value
Calculate the set value by the following formula:
Set value =
Setthecurrentvalueatburnoutwhentwoor moreheatersarecon­nected to the CT to the value at the time that the heater having the smaller(est) current value burns out (the value when one of the heat­ers burns out with all heaters at the same current).
Make sure that the following condition is satisfied:
Heater of current 10.0 A or less Current value at normal operation - current value at heater burnout 1A When resultant current is less than 1 A, detection is unstable.
Heater of current 10.0 A minimum Current value at normal operation - current value at heater burnout 2.5 A When resultant current is less than 2.5 A, detection is unstable.
Thesetvaluecanbesetwithintherange0.1to49.9A.Heaterburn­out is not detected when the setting is “0.0” or “50.0”. When the set­ting is “0.0”, the heater burnout alarm is set to “OFF,” and when the setting is “50.0”, the heater burnout alarm is set to “ON.”
Set the total current value at normal heater operation to 50 A or less. When set to 55.0 A minimum, [ rent monitor” parameter.
(current value at normal operation + current value at burnout)
2
] is displayed in the “heater cur-
4--24
Page 87
4.9 How to Use the Heater Burnout Alarm
F Examples of use
CT
17
1KWx3
CT
17
15
15
Control output
Control output
Heater
1KW
E5EK-T
Heater
E5EK-T
Example 1 : when using a 200 VAC, 1 kW heater
Current at normal operation =
1000
200
Current at heater burnout = 0A
AC200V
Set value =
5+0
2
=2.5A
(current at normal operation-current at heater burnout
=5-0=5A(≧ 1A)
Example 2 : when using three 200 VAC, 1 kW heaters
1000
200
1000
200
AC200V
Current at normal operation =
Current at burnout of one heater =
Set value =
15+10
2
= 12.5A
(current at normal operation-current at heater burnout
=15-10=5A(≧ 2.5A)
=5A(< 10A)
×3 = 15A (10A )
×2 = 10A
Parameters
Symbol Parameter Name: Mode Description
Heater current monitor : Level 1 Heater current value monitor
Heater burnout detection : Level 1 Heater burnout detection
Heater burnout latch : Option Heater burnout detection alarm latch
4--25
Page 88
CHAPTER 4 APPLIED OPERATION
4.10 LBA
The LBA (Loop Break Alarm) function can be used only on standard type controllers.
The LBA function can be used only when i t is assigned as an output. Also, the LBA function does not work when a memory error or A/D convertererrorresults.
LBA (Loop Break Alarm) is a function for judging that an error has occurred somewhere on the control loop and for outputting an alarm when the process value does not change with the manipulated vari­able at a maximum or minimum state. Accordingly, the LBA function can be used as a means for detecting a malfunctioning control loop.
F L BA detection
time
F L BA detection
width
F L BA detection
example
Normally, when output is set to maximum or minimum, the process value rises or falls after the dead time has elapsed. LBA is output if the process value does not change in the predicted direction after a fixed amount of time has elapsed. This fixed amount of time is the “LBA detection time.”
LBA operation sometimes becomes unstable when the process value fluctuates considerably due to the control characteristics. The LBA detection width is provided so that changes with respect to output can be correctly detected. Changes smaller than the detection width due to LBA detection timing are not regarded as changes.
The following example describes what happens when a heater burn­out occurs at maximum output.
LBA detection time
PV
LBA detection time
Heater burnout
LBA detection width
Output
Time
LBA=ON
4--26
LBA judgment is carried out at each LBA detection time from the point of maximum output. In the above figure, the process value (PV) is changing greatly at the 1st judgment time band, so LBA remains OFF.
At the 2nd judgment time band, the process value increases as indi­cated by the broken line if the process value is normal. This means that the change width exceeds the LBA detection width, and LBA out­put remains OFF.
If the heater burns out at the point shown in the above figure, the process value “decreases.” Accordingly, it is judged that “the process value is not changing in the increasing direction” at the 2nd judg­ment time band and the LBA output becomes ON.
Page 89
4.10 LBA
F Setting the LBA
detection time
F Determining the
LBA detection time
The LBA detection time is automatically set by auto-tuning (except in heating and cooling control).
If the optimum LBA detection time cannot be obtained by auto-tun­ing, set the time in the “LBA detection time” parameter (level 2 mode).
Calculate the LBA detection time as follows:
(1) Set output to maximum.
(2) Measurethetimeittakesfortheinputchangewidthtoreachthe
LBA detection width (factory setting: 0.2% FS).
Measurement time Tm
PV
0.2%FS
Output
Time
LBA detection time = Tm x 2
(3) Take a value twice that of the measurement time as the LBA detec-
tion time.
Parameters
Symbol Parameter Name: Mode Description
AT execute/Cancel : Level 1 For automatic setting of LBA
detection time
LBA detection time : Level 2 For setting LBA detection time
LBA detection width : Expansion For changing LBA detection
width
4--27
Page 90
CHAPTER 4 APPLIED OPERATION
4.11 How to Use Transfer Output
When using transfer output, add on the communications unit (E53-AKF).
F Transfer ou t pu t
type
F Transfer ou t pu t
scaling
Transfer output Transfer output
You can select the following five data items in the “transfer output type” parameter (option mode) as the transfer outputs:
Present SP (default), Process value, Manipulated variable (heat),
Manipulated variable (cool), Valve opening However, note that heating/cooling side manipulated variables can be output only on standard type controllers, and valve opening can be output on position-proportional type controllers.
If the output assignment is changed when either the “manipulated variable (heat)” or “manipulated variable (cool)” parameter is se­lected, the factory setting “set point” is returned to.
Thesetransferoutputscanbescaled according to the settings of the “transfer output upper limit” and “transfer output lower limit” pa­rameters before output. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out. Also, the scale can be enlarged by the upper- and lower-limit width specified for each data item. The following example shows scal­ing of the heating side manipulated variable.
20
(mA)
Reverse scaling Enlarged scale
(mA)
20
Parameters
4--28
4
Transfer output upper limit: 0
Symbol Parameter Name: Mode Description
Transfer output lower limit: 100
Transfer output type : Option Transfer output designation
Transfer output upper limit : Option Transfer output scaling
Transfer output lower limit : Option Transfer output scaling
Manipu­lated variable (%)
4
0
Transfer output lower limit: 10
Transfer output upper limit: 80
100
Manipulated variable (%)
Page 91
CHAPTER5
CHAPTER 5
PARAMETERS
This chapter describes the parameters of the E5EK-T. Use this chapter as a reference guide.
CHAPTER 5 PARAMETERS
ConventionsUsedinthisChapter 5-2............
Protect Mode 5-3...............................
Manual Mode 5-5..............................
Level 0 Mode 5-6...............................
Program Mode 5-11.............................
Level 1 Mode 5-17...............................
Level 2 Mode 5-24...............................
Setup Mode 5-30................................
Expansion Mode 5-38............................
Option Mode 5-46...............................
Calibration Mode 5-52...........................
5--1
Page 92
CHAPTER 5 PARAMETERS
Conventions Used in this Chapter
JThe meaning of icons used in this chapter
Describesthefunctionsoftheparameter.
Function
Describes the range and defaults of the parameter setting.
Setting
Used for monitor-dedicated parameters. Describes the range of the monitor values.
Monitor
Describes a procedure using parameters in operating instructions.
Example of use
Describes related parameters and items.
See
Describes models of the E5EK-T or optional units that support the parameter being described.
Model
JAbout parameter display
On the E5EK-T controller, only parameters that can be used are displayed. These parameters are displayed only when the “Conditions of Use” on the right of the paramete r heading are satisfie d . However, note that the settings of protected parameters are still valid, and are not displayed regardless of the conditions of use.
AT Execute/cancel
Conditions of Use The controller must be in operation.
JAbout the Order in Which Parameters Described in This Chapter
Parameters are described mode by mode The first page of each mode lists the parameters available in that mode. The parameter names in these contents are listed in the order that they are displayed on the controller.
5--2
Page 93
Mod
Protect Mode
The protect function restricts key use to prevent unwanted key operation. Before
changing parameters in this mode, first make sure that protecting the keys will not cause any problems in operation.
To select this mode, press the
RUN/RST
minimum. To exit this mode, press the again for 1 second minimum.
The following table shows the parameters supported in this mode and the page where the parameter is described.
and keys simultaneously for 1 second
RUN/RST
and keys simultaneously
Function
Setting
Symbol
Parameter Name Page
Security 5-3 Key protect 5-4
Security
This parameter specifies which parameters are protected. Note that the protect
mode and manual mode cannot be pr otected.
Only the modes indicated by the “F” mark in the table below can be selected on the menu display. For example, when this parameter is set to “3”, only levels 0 and 1 and the program mode can be selected.
e
Calibration F Option F F Expansion F F Setup F F Level 2 F F F Level 1 F F F F Program F F F F F Level 0 F F F F F F *1
0 1 2 3 4 5 6
*1 The “PV/Present SP” parameter is only displayed.
Setting value
When this parameter is set to “0”, the protection function is disabled.
When this parameter is set to “5”, only the parameters in the level 0 mode can be
used, and the menu display is not selected.
When this parameter is set to “6”, “PV/Present SP” parameter can only be dis­played. (The set point cannot be changed.)
Default is “1”. (Only the calibration mode is protected.)
F Related description
3.6 Protect Mode (page 3-19)
See
5--3
Page 94
CHAPTER 5 PARAMETERS
Protect Mode
Key protect
Disables key operation of the RUN/RESET or AUTO/MANUAL. For example, if AUTO/MANUAL key operation is disabled (by simultaneously pressing the
Function
and keys) in the “key protect” parameter (protect mode) during automatic operation, manual operation is no longer possible.
The following table shows the relationship between set values and protected keys.
Setting
See
Set value
1 No keys are protected.
2 AUTO/MANUAL key operation cannot be selected.
3 “RUN/RST” key cannot be selected.
4
RUN/RST
Both the AUTO/MANUAL and RUN/RESET key operations cannot be selected.
Default is “0” (all keys can be operated).
F Related description
3.6 Protect Mode (page 3-19)
Description
5--4
Page 95
Function
Manual Mode
In this mode, manual operation is possible, and the “MANU” LED lights.
When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. To change the manipulated variable, use the ing is canceled.
To select this mode when in the level 0 to 2 modes, press the
simultaneously for 1 second minimum. To exit this mode, press the and keys simultaneously again for 1 second minimum. The mode changes to the level 0 mode.
“Manual MV” is the only parameter available in this mode.
Manual MV
Sets the manipulated variable or the valve opening for manual operation. On a stan-
dard type controller, when you press the or keys, the manipulated variable is changed. On a position-proportional type controller, when you press the the open side becomes ON, and when you press the ON.
On standard type controllers, the process value is displayed on the No.1 display and the manipulated variable is displayed on the No.2 display.
On position-proportional controllers, the process value is displayed on the No.1
display, and the valve opening is displayed on the No.2 display when the poten­tiometer is connected.
On standard type controllers, the manual MV is held when the power is inter-
rupted.
or keys. If this mode is switched to during auto-tuning, auto-tun-
and keys
key,
key, the close side becomes
Standard type
Control Method Setting Range
Setting
Standard -5.0 to 105.0 % 0.0 Heating and cooling -105.0 to 105.0 % 0.0
Position-proportional type
Control Method
Position-proportional -10.0 to 110.0 %
F Related description
3.8 Adjusting Control Operation/Manual operation (page 3-22)
See
Unit Default
Monitor Range Unit
5--5
Page 96
CHAPTER 5 PARAMETERS
Level 0 Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “5”. Only the “PV/Present SP” parameter can be used when the “security” parameter is set to “6”.
The parameters in this mode comprise step operation parameters and parameters
required for monitoring program operating states.
To select this mode, press the to the menu display. If you select [ minimum, the controller enters the level 0 mode.
To select parameters in this mode, press the tings, use the
The following table shows the parameters supported in the level 0 mode and the page where the parameter is described.
key for 1 second minimum. The display changes
]thenpressthe key for 1 second
key. To change parameter set-
or keys.
Function
Symbol Parameter Name
PV/Present SP 5-6
Pattern No. 5-7
Step No. monitor 5-7
Hold 5-8
Advance 5-8
Standby time monitor 5-9
Pattern elapsing time 5-9
Pattern execution count monitor 5-9
MV monitor (heat) 5-10
MV monitor (cool) 5-10
Valve opening monitor 5-10
Page
PV/Present SP
The process value is displayed on the No.1 display, and the Present SP is displayed on the No.2 display.
The decimal point position is dependent on the selected sensor during tempera-
tures input and on the results of scaling during analog input.
Process Value
Monitor
Present SP
During temperature input, the range of the currently selected sensor is taken as the PV monitor range.
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (set u p mode)
See
“Set point upper limit” “Set point lower limit” (expansion mode)
5--6
Monitor Range
Scaling lower limit -10%FS to scaling upper limit +10%FS
Set point lower limit to set point upper limit
Unit
EU EU
Page 97
Function
Setting
See
Level 0 Mode
Pattern No.
This parameter can be set only when the controller is reset.
Displays the execution pattern during program operation, and the set pattern
after the controller is reset.
This parameter can also be used in the program mode.
Setting Range Unit Default
0to3 None 0
F Related description
3.5 Setting Patterns (page 3-14)
F Related parameters
All parameters in the program mode
Function
Monitor
See
Step No. monitor
Monitors the current step No. (This parameter is reset to “0” when the controller is reset.)
Monitor Range
0 to Number of steps-1 None
F Related description
4.4 Program Operation (page 4-13)
F Related parameters
“Hold” “Advance” (level 0 mode)
Unit
5--7
Page 98
CHAPTER 5 PARAMETERS
Level 0 Mode
Hold
This parameter can only be used for monitoring when the controller is reset.
Pauses (holds) or cancels program operation.
Function
When the event input to which “hold/hold cancel” is assigned is ON, [ displayed, and when OFF [
In addition to the setting of this parameter, hold is canceled by the following conditions:
](hold)is
] (hold cancel) is displayed.
Setting
See
Function
Example of use
Setting Range
OFF : Hold cancel / ON:Hold
Default
F Related description
4.4 Program Operation (page 4-13)
4.8 How to Use Event Input (page 4-21)
F Related parameters
“Event input assignment 1 to 2” (option mode)
Advance
This parameter can only be used for monitoring when the controller is reset.
Forcibly advances program operation by one step.
When the event input to which “hold/hold cancel” is assigned is ON, [
(advance) i s displayed.
Selecting this parameter, it is set to [
When [
] (ON) is selected, program operation is advanced by one step.
] (OFF).
After program execution is completed, the setting automatically returns to [
Hold is also continued after the program step is advanced when the program is
executed in a hold state.
]
].
F Related description
4.4 Program Operation (page 4-13)
4.8 How to Use Event Input (page 4-21)
See
F Related parameters
“Event input assignment 1 to 2” (option mode)
5--8
Page 99
Level 0 Mode
Function
Monitor
See
Standby time monitor
Conditions of Use
The controller must be in a standby state.
Displays the remaining standby time. (This time is not displayed when the con-
troller is reset.)
Monitor Range
0.00 to 99.59 Hour, minute
Unit
F Related description
4.7 Setting Running Conditions (page 4-19)
F Related parameter
“Standby time” (level 2 mode)
Pattern elapsin g time
Function
Monitor
Function
Monitor
Displays the time that has elapsed since the start of the pattern. When a pattern is repeatedly executed or all patterns are executed, the time counting restarts at the top of each pattern.
Monitor Range
0.00 to 99.59 Program time unit
Unit
When the time exceeds “99.59”, “99.59” blinks on the display.
Pattern execution count monitor
Displays the number of times that the current pattern has been executed. “0” is displayed when the controller is reset or when the controller is in a standby state.
Monitor Range
0 to pattern execution count Times
F Related parameter
“Pattern execution count” (program mode)
Unit
See
5--9
Page 100
CHAPTER 5 PARAMETERS
Level 0 Mode
Function
Monitor
MV monitor (heat)
Conditions of Use
The control must be standard control or heating and cooling control.
MV monitor (cool)
This parameter cannot be set.
Monitors the manipulated variable on the heating or cooling side.
The manipulated variable in a standard control system is monitored in the “MV
monitor (heat)” parameter.
The “MV monitor (cool)” parameter can be used only during heating and cooling control.
MV monitor (heat)
Control
Standard -5.0 to 105.0 % Heating and cooling 0.0 to 105.0 %
Monitor Range
MV monitor (cool)
Control
Heating and cooling 0.0 to 105.0 %
Monitor Range
Unit
Unit
Model
Function
Monitor
See
E5EK-TAA2
Valve opening monitor
Conditions of Use
The control must be position-propor­tional control.
Monitors the valve opening during position-proportional control.
Monitor Range
-10.0 to +110.0 %
Unit
“----” is displayed when a potentiometer is not connected.
F Related description
4.1 Selecting the Control Method/Position-proportional control (page 4-3)
E5EK-TPRR2
Model
5--10
Loading...