The E5EK-T is a high-performance programmable digital controller. The E5EK-T
allows the user to carry out the following:
• Set program patterns to each step by time or ramp rise rate
• Execute advance, hold and reset step operations
• Execute continuous operation of all patterns and repeated operation of same pat-
terns
• Check the start of each step or program end time by signals.
• Count time from the beginning of each step (time signal)
• Select from many types of temperature and analog input (multi-input)
• Support position-proportional control (position-proportional type controllers only)
• Select output functions such as control output or alarm output (output assign-
ment)
• Use the HBA (heater burnout alarm) function (standard type controllers only)
• Monitor the control loop by LBA (Loop Break Alarm)
• Use the communications function
• Calibrate input or transfer output
• The E5EK-T also features a watertight construction (NEMA4: equivalent to
IP66).
This User’s Manual describes how to use the E5EK-T.
Before using your E5EK-T thoroughly read and understand this manual in order to
ensure correct use.
Also, store this manual in a safe place so that it can be retrieved whenever necessary.
PRECAUTIONS IN USING THE PRODUCT
When the product is used under the circumstances or environment below, ensure
adherence to limitations of the ratings and functions. Also, take countermeasures
for safety precautions such as fail-safe installations.
(1) Use under circumstances or environments which are not described in this user’s manual.
(2) Use for nuclear power control, railway, air craft, vehicle, incinerator, medical equipment, enter-
tainment equipment, safety device, etc.
(3) Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
About this manual
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
(2) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice.
(3) Every precaution has been taken in the preparation of this manual. Nevertheless, if you find any errors or
omissions, please contact the branch of OMRON or sales office listed at the end of this manual, and inform
them of the catalog No. on the front cover.
I
Page 3
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following:
SymbolTerm
PVProcess value
SP(Present) set point *1
LBALoop break alarm
HBHeater burnout
ATAuto-tuning
EUEngineering unit *2
*1 In program pattern diagrams, the present SP is indicated.
*2 _C, m, g and other units are indicated for scaled data. However, “EU” is used as the mini -
mum unit for the data. For example, for “50.02 (m)”, 1EU is taken as the minimum unit
0.01 (m).
JHow to Read Display Symbols
The following tables show the correspondence b etween the symbols displayed on the displays
and alphabet characters.
ABCDEF GHI J KL M
NOPQRST UVWXYZ
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explanations and how to apply functions.
II
Page 4
JHow This Manual is Organized
PurposeTitleDescription
D Learning about the gener-
al features of the E5EK-T
Chapter 1INTRODUCTION
This chapter describes the features of the E5EK-T, n ames of
parts, and typical functions.
D Setting up
D Basic E5EK-T operations
D Applied E5EK-T opera-
tions
D Using a Position-propor-
tional type controller
D Communications with a
host computer
Chapter 2PREPARATIONS
Chapter 3BASIC OPERATION
Chapter 5PARAMETERS
Chapter 4 APPLIED OPERATION
Chapter 5 PARAMETERS
Chapter 4 APPLIED OPERATION
/4.1 Selecting the Control
Method
Chapter 6USING THE
COMMUNICATIONS
FUNCTION
This chapter describes the operations that you must carry
out (e.g. installation, wiring and
switch settings) before you can
use the E5EK-T.
These chapters describe using
basic control examples how to
use the front panel keys and
how to view the display when
setting the parameters of the
major functions for the E5EK-T.
These chapters describes the
important functions of the
E5EK-T an d how to use the parameters for making full use of
the E5EK-T.
This chapter describes how to
use the functions related specifically to position-proportional
type controllers.
This chapter mai nly describes
how to use the communications
commands, and gives program
examples.
D Calibration
D Troubleshooting
Chapter 7CALIBRATION This chapter describes how the
user should calibrate the E5EKT.
Chapter 8TROUBLESHOOTING
This chapter describes what to
do if any problems o ccur.
III
Page 5
PRECAUTIONS ON SAFETY
F Marks For Ensuring Safe Use and Their Meanings
This manual uses the following marks to indicate precautions for ensuring that the
E5EK-T is used safely.
The precautions indicated below describe important information regarding safety.
Be sure to follow the instructions described in these precautions.
WARNING
Incorrect handling may cause death or injury.
WARNING
Do not touch the terminals while the power is
ON.
This may cause an electric shock.
IV
Page 6
NOTICE
Be sure to observe these precautions to ensure safe use.
F Do not use the product in places where explosive or flammable gases may be present.
F Never disassemble, repair or modify the product.
F Tighten the terminal screws properly.
F Use the specified size of solderless terminals for wiring.
F Use the product within the rated supply voltage.
F Use the product within the rated load.
F The life expectancy of the output relay varies considerably according to its switching capacity
and operating conditions. Be sure to use the output relay within its rated load and electrical life
expectancy. If the output relay is used beyond its life expectancy, its contacts may become fused or
burned.
F If you remove the controller from its case, never touch nor apply shock to the electronic parts
inside.
F Do not cover the E5EK-T. (Ensure sufficient space around the controller to allow heat radiation.)
F Do not use the controller in the following places:
• Places subject to icing, condensation, dust, corrosive gas (especially sulfide gas or ammonia gas).
• Places subject vibration and large shocks.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to intense temperature changes.
• Places subject to heat radiation from a furnace.
F Be sure to wire properly with correct polarity of terminals.
F When wiring input or output lines to your controller, keep the following points in mind to reduce
the influence from inductive noise:
• Allow adequate space between the high voltage/current power lines and the input/output lines.
• Avoid parallel or common wiring with high voltage sources and power lines carrying large cur-
rents.
• Using separating pipes, ducts, and shielded line is also useful in protecting the controller, and its
lines from inductive noise.
F Cleaning: Do not use paint thinner or organic solvents. Use standard grade alcohol to clean the
product.
F Use a voltage (100 to 240 VAC at 50 to 60 Hz). At power ON, the prescribed voltage level must be
attained within two seconds.
F Allow as much space as possible between the controller and devices that generate a powerful high
frequency (high-frequency welders, high-frequency sewing machines, etc.) or surge. These devices
may cause malfunctions.
F If there is a large power-generating peripheral device and any of its lines near the controller, at-
tach a surge suppressor or noise filter to the device to stop the noise affecting the controller system. In particular, motors, transformers, solenoids and magnetic coils have an inductance component, and therefore can generate very strong noise.
F When mounting a noise filter on the power supply to the controller, be sure to first check the fil-
ter’s voltage and current capacity, and then mount the filter as close as possible to the controller.
V
Page 7
F Use within the following temperature and humidity ranges:
• Temperature: -10_Cto55_C, humidity: 35%RH to 85%RH (with no icing or condensation)
If the controller is installed inside a control board, the ambient temperature must be kept to un der 55_C, including the temperature around the controller.
If the controller is subjected to heat radiation, use a fan to cool the surface of the controller to
under 55_C.
F Store within the following temperature and humidity ranges:
• Temperature: -25_Cto65_C, humidity: 35%RH to 85%RH (with no icing or condensation)
F Never place heavy objects on, or apply pressure to the controller that may cause it to deform and
deteriorate during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installation. These
devices can cause radio disturbances which adversely affect the performance of the controller.
This chapter introduces the names of parts on the E5EK-T and their functions.
For details on how to use the controller and parameter settings, see Chapter 2
onwards.
1.1Names of parts1--2..........................................
1.2Input and Output1--5.........................................
This chapter describes each of the parameters required for making full use of the
features of the E5EK-T.
Read this chapter while referring to the parameter descriptions in chapter 5
4.1Selecting the Control Method4--2..............................
This chapter describes how to find out and remedy the cause if the E5EK-T does
not function properly.
Remedy E5EK-T trouble in the order of the descriptions in this chapter
This chapter introduces the names of parts on the E5EK- T and their
functions.
For details on how to use the controller and parameter settings, see
Chapter 2 onwards.
CHAPTER 1 INTRODUCTION
1.1Names of parts1-2........................
Main parts1-2............................
Front panel1-2...........................
About the displays1-3.....................
How to use keys1-4.......................
1.2Input and Output1-5......................
Input1-5.................................
Output1-6................................
1.3Program1-8..............................
How programs are structured1-8...........
Program operation1-8.....................
Alarm output1-8..........................
Program output1-8........................
1.4P arameters and Menus1-9.................
Parameter types1-9.......................
Selecting modes1-10........................
Selecting parameters1-11...................
Fixing settings1-11.........................
1.5About the Communications Function1-12....
1.6About Calibration1-13......................
1--1
Page 12
CHAPTER 1 INTRODUCTION
1.1Names of parts
JMain parts
Terminals
P2-6
Rear case
Front panel
This page
JFront panel
Pattern No.
Operation indicators
OUT1
SUB1
MANU
HOLD
WAIT
Display key
Run/Reset key
RUN/RST
1--2
OUT2
SUB2
RMT
RST
AT
PTN
RMT
OUT1 OUT2
RUN
RST
PV
SV
MANU
RSPSUB1
STOP
No.1 display
No.2 display
SUB2
AT
WAIT
Up k ey
Down ke y
E5EK
Page 13
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Pattern No.
F Program status
indicators
F Op eration statu s
indicators
Displays the process value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
Displays pattern No..
Indicate how the present-SP of the operating step changes.
• OUT1
Lights when the pulse output function assigned to “control output 1”
is ON.
• OUT2
Lights when the pulse output function assigned to “control output 2”
is ON.
• SUB1
Lights when the pulse output function assigned to “auxiliary output
1” is ON.
• SUB2
Lights when the pulse output function assigned to “auxiliary output
2” is ON.
• MANU
Lights in the manual operation mode.
• RST
Lights when the control is in reset status.
• RMT
Lights during remote operation.
• HOLD
Lights when the program is in hold status.
• WAIT
Lights when the program is in wait status.
• AT
Flashes during auto-tuning.
1--3
Page 14
CHAPTER 1 INTRODUCTION
JHow to use keys
RUN/RST
Fkey
Fkey
Fkey
The following describes basic key operations.
To change to run operation from the reset status, press this key for one
second minimum.
To change to the reset status from run operation, press this key for two
seconds minimum.
The functions of this key change according to how long it is pressed. If
the key is pressed for less than one second, the parameters are switched.
If the key is pressed for one second minimum, the menu display appears. In key operations from here on, “press the key” refers to pressing
the key for less than one second.
For details on switching of parameters and menu display items, see
page 1-10.
Each press of
the No.2 display, while each press of thekey decrements or returns
the values or settings on the No.2 display.
Functions vary, for example, when the
key increments or advances the values or settings on
RUN/RST
key is held down simul-
taneously with the
tails, see page 1-10. Also, chapters 3 and 4 describe examples using various key combinations.
key, or a key is held down continuously. For de-
1--4
Page 15
1.2Input and Output
1.2 Input and Output
T emperature input
Voltage input
Current input
CT input
Potentiometer
Event input
Controller
Control output
(heat)
Control output
(cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Time signal 1
Time signal 2
Program end
Stage output
Error 1
Error 2
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
JInput
The E5EK-T supports the following inputs:
Temperature input, Current input, Voltage input, CT input/potentiometer, and Event input.
F Temperature input/Voltage input/Current input
• Only one of temperature input, current input and voltage input can
be selected and connected to the controller.
• The following input sensors can be connected for temperature input:
• The following currents can be connected for current input:
4to20mA,0to20mA
• The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input/Poten -
tiometer
• Connect CT input when using the HBA (heater b urnout alarm) function on a standard type controller (E5EK-TAA2). Note that CT input
cannot be used when the linear output unit is mounted.
• Connect the potentiometer when monitoring the valve opening on a
position-proportional type controller (E5EK-TPRR2).
1--5
Page 16
CHAPTER 1 INTRODUCTION
F Event input
JOutput
F Ou tput assign-
ments
Add on the input unit (E53-CKB) when using event input. You can select from the following five event inputs:
The output functions of the E5EK-T do not operate for five seconds after the
E5EK-T is turned ON.
The E5EK-T supports the following five outputs:
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
When using control output 1 and 2, set the output unit (sold separately). Nine output units are available to suit the output circuit configuration.
When using transfer output, add on the communication unit
(E53-AKF).
• The E5EK-T supports the following thirteen output functions:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA,
LBA, Time Signals 1 and 2, Program End, Stage Output,
Error 1 (input error), Error 2 (A/D converter error)
• Assign these output functions to control output 1, control output 2,
auxiliary output 1, and auxiliary output 2.
However, note that as control output 1 is used as the open output and
control output 2 is used as close output on a position-proportional
type controller (E5EK-TPRR2), control outputs 1 and 2 cannot be
used as assignment destinations. Also, of the output functions, control
output (heat), control output (cool), HBA and LBA are disabled.
• On a standard type controller, there are restrictions on how assignment destinations (control output 1, control output 2, auxiliary output 1, and auxiliary output 2) can be used. For details, see Chapter 3
Basic Operation/3.3 Setting Output Specifications (page 3-7).
• In the example on the previous page, “control output (heat)” is assigned to “control output 1”, “alarm 1” is assigned to “control output
2”, and “alarm 2” is assigned to “auxiliary output 1”. Accordingly, the
configuration is such that heating control output is connected to control output 1, and alarm output is connected to control output 2 and
auxiliary output 1.
• Control outputs 1 and 2 are used depending on the differences in control method as follows:
1--6
Page 17
1.2 Input and Output
F Transfer ou t pu t
Control Method
Standard controlE5EK-TAA2 AC100-240
E5EK-TAA2 AC/DC24
Heating and
cooling control
Position-proportional control
• The E5EK-T supports the following five transfer outputs:
Set point, Process value, Heating side manipulated variable,
Cooling side manipulated variable, Valve opening
However, note that heating/cooling side manipulated variables can be
output only on standard type controllers, and valve opening can be output only on position-proportional type controllers.
• These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out.
E5EK-TAA2 AC100-240
E5EK-TAA2 AC/DC24
E5EK-TPRR2 AC100-240
E5EK-TPRR2 AC/DC24
Model
Control Output 1/
Control Output 2
Control output (heat)
/ Alarm, etc.
Control output (heat)
/ Control output (cool)
Open/Close
1--7
Page 18
CHAPTER 1 INTRODUCTION
1.3Program
JHowprograms
are structured
E5EK-T allows you to configure programs made up of a maximum of
four patterns (pattern 0 to 3).
The number of steps (16 maximum) in each pattern can be specified in
parameters.
Pattern 3
Pattern 1
Pattern 0
Step 0Step 1Step 2Step 15
• Generally, the “time setup method” is used to configure programs. By
this method, set points at each step and time are used as program elements. However, the “ramp rise rate setup method” can also be used.
By this method, the set point, ramp time and soak times are used as
program elements.
JProgramopera-
tion
F Step operation
F Wait operation
JAlarm output
JProgram output
1--8
• Generally, the target patterns are specified before the program is
executed.
• In parameter setup, you can specify repeated execution of the same
pattern (Repeat) or consecutive execution of all patterns 0 to 3 (Run
all).
• During program operation, steps can be skipped (Advance) and the
control monitoring can be paused (Hold).
• When the wait width is specified in parameter setup, the program
does not go to the next step and waits until the PV reaches the specified time (wait width) at the end of each step.
• Alarms that are assigned as outputs operate referenced to the alarm
values preset to each pattern.
• Time signals, program end and stage output can be output accor din g
to output assignment.
• ON/OFF signals are output as time signals according to the timer
that takes a specified step as its start point.
Page 19
1.4Parameters and Menus
1.4 Parameters and Menus
JParameter types
F Protect mode
F Manual mode
F L evel 0 mode
E5EK-T parameters are distributed between the following ten modes:
Protect mode
Manual mode
Level 0 mode
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of eight modes (excluding the protect
mode and manual mode) can be checked and modified by selection on
the menu display.
The protect function is for preventing unwanted modification of param-
eters, and switching between run and reset operation or auto and
manual operation.
In this mode, the controller can be switched to manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode,
you can change the set p oint and pattern during operation, and execute
step operation (e.g. advance). You can only monitor (not change) the
process value, step No., standby time, pattern elapsing time, pattern
execution count and manipulated variable.
F Program mode
F L evel 1 mode
F L evel 2 mode
F Setup mode
This is the programming mode. In this mode, you can set the number of
steps used in each pattern, pattern execution count, alarm values, set
points for each step, step time, and time signals for two steps.
This is the main mode for adjusting control. In this mode, you can
execute AT (auto-tuning), and set up the control period, PID parameters and heater burnout alarm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can
set the parameters for limiting the manipulated variable, switch between the remote and local modes, and set the loop break alarm (LBA),
alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you
can set parameters that must be checked or set before operation such as
the input type, scaling, output assignments and direct/reverse operation.
1--9
Page 20
CHAPTER 1 INTRODUCTION
F Expansion mode
F Option mode
F Calibration mode
JSelecting modes
This is the mode for setting expanded functions. In this mode, you can
set SP setting limitter, switching between advanced PID control or ON/
OFF control, program time unit, selection of step time/rate of rise p rogramming, time unit of ramp rise rate, and the time for automatic return to the monitoring display.
This is the mode for setting optional functions. You can select this mode
only when an option unit is mounted in the controller. In this mode,
you can set the communications conditions, transfer output and event
input parameters to match the type of option unit mount in the control-
ler. Heater burnout alarm function and position-proportional travel
time are also located in this mode.
This mode is provided so that the user can calibrate inputs and output.
When calibrating input, the selected input type is calibrated. Whereas,
transfer output can be calibrated only when the communication unit
(E53-AKF) is set in the controller.
The following diagram shows the order in which modes are selected.
Power ON
+
1 second min.
Level 0 mode
1secondmin.
Manual mode
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
RUN/RST
1 second min.
RUN/RST
1 second min.
+
Protect mode
+
+
1 second min.
RUN/RST
1secondmin.
+
• To select the menu display in any of the above modes (excluding the
protect mode and manual mode), press the
key for 1 second minimum. When you have selected the menu display, the previous mode is
selected. For example, if you selected the menu display while in the
level 0 mode, the No.2 display changes to [
] as shown on the left.
• To move to the desired mode after you have entered the menu display,
select the desired mode using the
keys and hold down the
key for one second minimum. The display switches to the first
parameter of the mode that you specified.
1--10
Page 21
1.4 Parameters and Menus
• Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the program mode.
• If you select [
the level 0, program, level 1 and level 2 modes, respectively, are selected.
These modes are selected with control still continuing.
• If you select[
setup, expansion, option and calibration modes, respectively, are selected.
When these modes are selected, the control is reset. So, control outputs and auxiliary output are turned OFF. When another mode is selected while in these modes control, reset is canceled.
• To set the controller to the protect mode or to return to the level 0
mode from the protect mode, press the
simultaneously for 1 second minimum.
• To set the controller to the manual mode, press the
second minimum with the
modes. To return to the level 0 mode in the manual mode, press the
key for one second minimum with thekey pressed. Be sure
to press the
], [], []or[]inthe menudisplay,
][][]or[]inthe menudisplay,the
RUN/RST
keyhelddowninthelevel0to2
key first in this operation.
key and thekey
key for one
JSelecting
parameters
JFixing settings
• When the controller is not in the manual mode, each press of the
key switches the parameter in the respective mode.
Parameter
1
• If you press thekey when at the final parameter, the display re-
turns to the top parameter for the current mode.
• When you change parameter settings or contents, specify the parameter using the
two seconds or press the
• When another mode is selected, the content of the parameters before
the mode was selected is fixed.
• When you turn the power OFF, you must first fix the settings and parameter contents (by pressing the
mode). The settings and parameter contents are sometimes not
changed by merely pressing the
Parameter
2
orkeys, and either leave the setting for at least
Parameter
Parameter
3
key. This fixes the setting.
key or selecting another
orkeys.
n
1--11
Page 22
CHAPTER 1 INTRODUCTION
1.5About the Communications Function
The E5EK-T can be provided with a communications function that allows you to check and set controller parameters from a host computer.
If the communications function is required, add on the communications
unit.
For details on the communications function, refer to Chapter 6.
F RS-232C
F RS-422
F RS-485
When using the communications function on the RS -232C interface,
add on the communications unit (E53-AK01).
When using the communications function on the RS-422 interface, add
on the communications unit (E53-AK02).
When using the communications function on the RS-485 interface, add
on the communications unit (E53-AK03).
1--12
Page 23
1.6About Calibration
The E5EK-T controller is calibrated before shipment from the factory.
So, the user need not calibrate the E5EK-T controller during regular
use.
However, if the E5EK-T controller must be calibrated by the user, use
the parameters provided for the user to calibrate temperature input,
analog input (voltage, current) and transfer output. In this case, note
that the results of calibration will not be assured.
Also, note that calibration data is updated to the latest value each time
that the E5EK-T controller is calibrated. Calibration data set before
shipment from the factory cannot be returned to after calibration by
the user.
1.6 About Calibration
F Calibrating
inputs
F Calibrating trans -
fer output
F Registering cal-
ibration data
The input type selected in parameters is the item to be calibrated. The
E5EK-T is provided with the following four calibration parameters:
• Thermocouple
• Platinum resistance thermometer
• Current input
• Voltage input
Two parameters are provided for thermocouple and voltage input.
Transfer output also can be calibrated when the communications unit
(E53-AKF) is added on.
When calibrating each item, the calibration data is temporarily registered. This data can be registered as final calibration data only when all
items have been newly calibrated. So, all items must be temporarily
registered when the E5EK-T controller is calibrated.
When registering data, information regarding whether or not calibration has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring devices and equipment. For details on handling these measuring devices
and equipment, refer to the respective manuals.
For details, see Chapter 7 Calibration.
1--13
Page 24
CHAPTER 1 INTRODUCTION
1--14
Page 25
CHAPTER2
CHAPTER2
PREPARATIONS
This chapter describes the operations (e.g. setup, installation and
wiring) you should carry out before turning the E5EK-T ON.
CHAPTER 2 PREPARATIONS
2.1Setup2-2.................................
Draw-out2-2..............................
Setting up the output unit2-3..............
Setting up the option unit2-4...............
2.2Installation2-5............................
Dimensions2-5............................
Panel cutout2-5...........................
Mounting2-6.............................
2.3Wiring Terminals2-8......................
Terminal arrangement2-8.................
Precautions when wiring2-8...............
Wiring2-8................................
2--1
Page 26
CHAPTER 2 PREPARATIONS
2.1Setup
• On a standard type controller, set up the output units for control outputs 1 and 2 before mounting the controller.
• On a position-proportional type controller, the relay output unit is
already mounted. So, this setup operation is unnecessary. (That is, do
not replace the currently mounted unit with other output units.)
• When setting up the output units, draw out the internal mechanism
from the housing, and insert the output units into the sockets for control outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, prepare a
Phillips screwdriver matched to the size of the screw on the lower part
of the front panel.
(1) Press down on the hook on the top of the front panel, and turn the
Phillips screwdriver to the left to loosen the screw on the lower
part of the front panel.
Fixing Screw for
Front Panel
2--2
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 N⋅m (approx. 3 to 5 kgf⋅cm).
Page 27
JSetting up the output unit
2.1 Setup
F Before setup
F Procedure
• Check the type of the output unit you are about to set up.
• For details on types of output unit and main specifications, see page
2-7.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) R emove the power board in the direction of the arrow in the figure
below. The power board is connected to the control board by a connector at the center of the board.
Control board
Power board
(3) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(4) Fasten the output units with the bracket (accessory).
(5) Mount the power board at its original position.
2--3
Page 28
CHAPTER 2 PREPARATIONS
JSetting up the option unit
F Before setup
F Procedure
• Check the type of the option unit you are about to set up.
• For details on types of option unit and main specifications, see Appen-
dix, Model List (page A-11) and Appendix, Option Unit Ratings and
Characteristics (page A-4).
• For details on the relationship between units and terminals, see page
2-8.
(1) R emove the power board and option boards in the order shown in
the following diagram.
2
1
(2) Insert the option unit into the socket for option 1. The following
diagram shows the relationship between option unit and mounting
position.
(3) Mount the option board and the power board in the order shown.
2--4
Page 29
2.2Installation
JDimensions
48
PV
2.2 Installation
13.5100
PTN
MANU
RMT
OUT1 OUT2
STOP
RUN
RST
JPanel cutout
Unit (mm)
SV
91
SUB2RSPSUB1
AT
WAIT
E5EK
96
112
60 mm min
120 mm min
45
+0.6
0
92
+0.8
0
• Recommended panel thickness is 1 to 8
mm.
• Maintain the specified vertical and horizontal mounting space between each controller.
Controllers must not be closely mounted
vertically or horizontally.
2--5
Page 30
CHAPTER 2 PREPARATIONS
JMounting
(1) Insert the E5EK-T controller into the mounting hole in the panel.
(2) Fit the mounting b racket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the two mounting bracket screws alternately a little at a
time until the ratchet starts to slide.
2--6
Page 31
F Setting up the terminal covers
• Fasten the terminal covers (E53-COV0809) to protect terminals.
• E5EK-VV2-500 controller is provided with terminal covers.
• Use E53-COV09 for terminals 1 to 10, and E53-COV08 for terminals
11 to 33.
• Fasten the terminal covers as follows by using the snap pins.
2.2 Installation
E5EK-- T
E53-COV08
• To remove the terminal covers, pull the edges of the snap pins.
2--7
Page 32
CHAPTER 2 PREPARATIONS
2.3Wiring Terminals
JTerminal arrangement
SOURCE
OUT1
OUT2
SUB1
SUB2
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
EV1/2
TRSF
RS232C
RS422
RS485
CT
PTMR
TC
Pt
I
V
JPrecautions
when wiring
JWiring
F Power supply
10
21 22
9
8
7
6
5
4
3
2
23
2--8
1
20
19
18
17
16
15
14
13
12
11
TRSF: Transfer output
EV1/2: Event inputs
PTMR: Potentiometer
SOURCE : 100 to 240 VAC, 50/60 Hz 15VA or 24VAC/DC, 50/60 Hz, 12VA 8W
• On some models, terminals are not used and are left free. Do not wire
these terminals.
• Separate input leads and power lines in order to protect the controller
and its lines from external noise.
• We recommend using solderless terminals when wiring the controller.
• Tighten the terminal screws using a torque no greater than 0.78 N¡m
(8kgf¡cm).
• Use the following type of solderless terminals for M3.5 screws.
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indicates the inside of the controller.
• Input power to terminals Nos. 9 and 10. Powe r specifications are as follows:
100 to 240 VAC, 50/60 Hz, approx. 15 VA
or
24 VAC, 50/60 Hz, approx. 12 VA
24 VDC, 8W
Page 33
2.3 Wiring Terminals
F Sensor input
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
F Control output
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
• Connect the sensor input to terminal Nos. 11 to 14 and 23 as follows
according to the input type.
14
13
12
11
23
Thermocouple Platinum
-
+
resistance
thermometer
14
13
12
11
23
+
14
V
13
12
-
11
23
Voltage inputCurrent input
14
13
12
11
23
-
mA
+
• Term inal Nos. 7 and 8 are for control output 1 (OUT1), and terminal
Nos. 5 and 6 are for control output 2 (OUT2). The following diagrams
show the available output units and their internal equalizing circuits.
86
75
NPN
E53-Q
E53-Q3
+
L
GND
-
86
75
Relay
E53-RE53-SE53-Q4
+
86
mAV
4to20mA/0to20mA
E53-C3
E53-C3D
LL
75
-
86
75
SSRPNP
86
75
0 to 10V/0 to 5V
E53-V34
E53-V35
+v
GND
+
-
+v
86
75
+
L
-
• With E53-Vjj output units, about 2 V is output for one second after
the power is interrupted.
• The following table shows the specifications for each output unit.
ModelOutput TypeOutput ModeSpecifications
E53-RRelayPulse250 VAC, 5 A
E53-SSSRPulse75 to 250 VAC, 1 A
E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
4to20mA
0to20mA
0to10V
0to5V
Pulse
Pulse
Pulse
Linear
Linear
Linear
Linear
NPN : 12 VDC, 40 mA (with short-circuit protection)
NPN : 24 VDC, 20 mA (with short-circuit protection)
PNP : 24 VDC, 20 mA (with short-circuit protection)
0 to 10 VDC, Permissible load impedance: 1 k Ω min., Resolution: Approx. 2600
0 to 5 VDC, Permissible load impedance: 1 k Ω min., Resolution: Approx. 2600
• With E5EK-T PRR2 controllers, relay output (250 VAC, 1A) is fixed.
When the output unit is replaced, use the E53-R. The following diagrams show the relationship between terminals and open/close relay
terminal settings.
8
7
Open
6
5
Close
2--9
Page 34
CHAPTER 2 PREPARATIONS
F Auxiliary output
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
F CT input/
Potentiometer
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
• Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal
Nos.1 and 2 are for auxiliary output 2 (SUB2).
• The internal equalizing circuits for the auxiliary outputs are as follows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
• Output specifications are as follows:
SPST- NO, 250 VAC, 3 A
• When the HBA function on an E5EK-TAA2 controller is used, connect
CT input (CT) to terminal Nos.15 and 17. When monitoring the valve
opening on an E5EK-TPRR2 controller, connect the potentiometer
(PTMR) to terminal Nos.15 to 17. Connect each of these inputs as follows:
17
16
15
CT inputPotentiometer
CT
17
16
15
O
W
C
• For details on CT inputs, see Appendix, About Current Transformer
(CT) Input (page A-5).
• For details on the p otentiometer, see the Instruction Manual for the
valve connected to the controller.
The meaning of terminal symbols is as follows:
O: OPEN, W: WIPE, C: CLOSE
Thevariableresistancerangeis100Ω to 2.5 kΩ.
About Isolation
2--10
The E5EK-T has independent power supplies
for each of the terminal blocks shown on the
right.
AB/CC
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
B
6
5
4
E
3
2
1
FD
Page 35
2.3 Wiring Terminals
F Event input
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
• Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20. How ever, note that terminal Nos.18 to 20 cannot be used on controllers
supporting the communications function.
• Connect the event inputs as follows:
EV1
EV2
COM
Event input 1 and 2
19
18
+
-
+
20
• Use event inputs under the following conditions:
Contact input
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact inputON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
• Polarities during no-contact input are as follows:
+
20
EV1
19
18
+
-
EV2
COM
Event input 1 and 2
F Transfer ou t pu t
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
F Communications
• Connect transfer output (TRSF) to terminal Nos. 21 and 22.
• The internal equalizing circuit for transfer output is as follows:
+
21
4to20mAL
22
-
• Transfer output specifications are as follows:
4to20mADC,Permissibleloadimpedance:600Ω max., R esolution:
Approx. 2600
• Terminal Nos.18 to 20, 21 and 22 can be used only on controllers that
support the communications units (E53-AK01/02/03).
• For details on wiring, see Chapter 6, Using the Communications
Function.
2--11
Page 36
CHAPTER 2 PREPARATIONS
2--12
Page 37
CHAPTER3
CHAPTER3
BASIC OPERATION
This chapter describes actual examples for understanding the basic
operation of the E5EK-T.
3.1 ConventionUsedinthisChapter3-2........
3.2Setting Input Specifications3-4.............
Input type3-4.............................
CHAPTER 3 BASIC OPERATION
Temperature input3-5.....................
Analog input3-5..........................
3.3Setting Output Specifications3-7...........
Output assignments3-7....................
Direct/reverse operation3-8................
Control period3-8.........................
3.4Setting Alarm Type3-10....................
Alarm type3-10............................
Alarm value3-10...........................
Alarm hysteresis3-11.......................
Closeinalarm/openinalarm3-11............
3.5Setting Patterns3-14.......................
Pattern No.3-15............................
Number of steps3-15.......................
Step SP/Step time3-15......................
Alarm value3-16...........................
3.6Protect Mode3-19..........................
Security3-19...............................
Key protect3-19............................
3.7Starting and Stopping Operation3-21........
3.8Adjusting Control Operation3-22............
Changing programs3-22....................
Manual operation3-24......................
Auto-tuning (A.T.)3-25.....................
3--1
Page 38
CHAPTER 3 BASIC OPERATION
3.1Convention Used in this Chapter
This chapter describes basic E5EK-T operations such as how to set up
parameters, start and stop operation, and adjust control operation.
For more complex control examples, refer to Chapter 4 Applied Operation and Chapter 5 Parameters.
F Basic Operation
Flow
The following diagram shows the basic flow of operation.
Power ON
Setup
Setting input specifications
Setting output specifications
Setting alarm output
Setting patterns
Protecting parameters
Operation
Start
Adjustment
3--2
Stop
Power OFF
The descriptions in this chapter follow the order of basic operations
shown in the flow above. Examples of operation of each of the items are
described up to completion of parameter setup. However, you must
move to the top parameter of the following Setting. For example, when
you have finished “setting input specifications” and you want to “set
output specifications,” move to the top parameter of “setting output
specifications” from the bottom parameter of “setting input specifica-
tions.”
For details on moving to parameters between items, refer Chapter, Selecting modes and Selecting parameters (page 1-10).
Page 39
3.1 Convention Used in this Chapter
F Setup examples
This description assumes that the controller is operated under the following conditions.
• A K thermocouple is used as the input.
• Control output (heat), alarm 1 and alarm 2 functions are assigned to
“control output 1,” “control output 2” and auxiliary output 1, respectively. Of these, only control output 1 and auxiliary output 1 are used.
• The relay output unit is mounted at control output 1.
• The upper-limit alarm is set as alarm 2. The alarm is output when the
temperature exceeds 10_C with respect to the PV.
• The program is made up of one pattern comprising four steps.
• The following figures show terminal wiring and the program used in
the setting examples.
Temperature sensor:
K thermocouple
Control target
20
19
18
17
16
15
14
13
12
11
--
+
Alarm 2 (upper limit)
(alarm value=10_C)
10
SOURCE
OUT1
SUB1
E5EK-- TAAjj
(Control output 1: E53--R)
9
8
7
6
5
4
3
2
1
21 22
23
SP
Step 1Step 2Step 3
100
Pattern 0
50
0.200.400.20
Time: hr, min
3--3
Page 40
CHAPTER 3 BASIC OPERATION
3.2Setting Input Specifications
Setting input specifications
Input type
N
Temperature input?
Y
Temperature unit
Decimal point
Temperature input shift
End of setup
Setup mode
Scaling
Level 2 mode
• With temperature input, scaling and decimal point parameters need
not b e set as this information is determined by the input (sensor)
type. (These parameters are not displayed.) Note that temperature
unit and temperature input shift parameters need to be set.
• With analog input, the “scaling upper limit”, “scaling lower limit”
and “decimal point” parameters need to be set.
JInput type
3--4
• Set the type No. (0 to 21) in the “input type” parameter (Set up
mode). The factory setting is “2: K1 (thermocouple).”
• For details on input types and setting ranges, see page 5-31.
Page 41
JTemperature input
F Temperature unit
3.2 Setting Input Specifications
• To switch the temperature unit from “_C” to“_F” when input is tem-
perature, switch the “_C/_F selection” parameter (setup mode) from
”to“ ”.
“
F Temperature
input shift
JAnalog input
• When input is temperature input, the upper and lower limit values of
the sensor can be shifted linearly. For example, if both the upper and
lower limit values are shifted by 1.2_C,theprocessvalue(beforeshift)
is regarded as 201.2_C after shift when input is 200_Cbeforeshift.
• To set input shift, set shift values in the “input shift upper limit” and
“input shift lower limit” parameters (level 2 mode).
Temperature
Input shift upper limit value
Upper limit value
After shift
Before shift
Input shift lower
Lower limit value
0
limit value
Input (%FS)
100
• When the analog input (the voltage input and current input) is selected, scaling matched to the control is required.
• The “scaling upper limit”, “scaling lower limit” and “decimal point”
parameters (setup mode) are used for scaling. These parameters cannot be used when the temperature input type is selected.
• The “scaling upper limit” parameter sets the physical quantity to be
expressed by the upper limit value of input, and the “scaling lower
limit” parameter sets the physical quantity to be expressed by the
lower limit value of input. The “decimal point” parameter sets the
number of digits past the decimal point.
• The following figure shows a scaling example of 4 to 20 mA input. After scaling, the humidity can be directly read. In this case, the “decimal point” parameter is set to “1”.
Readout (humidity)
Scaling upper limit
value (95.0%)
Scaling lower limit
value (10.0%)
0
100%FS
Input (4 to 20 mA)
3--5
Page 42
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
1 second min.
In this example, let’s check the input type and temperature units, and
shift the lower limit by 1_C and the upper limit by 3_C.
(1) Select the menu display, and select “:setup mode”usingthe
orkeys. For details on selecting the menu display, see page
1-10.
(2) Press the
mode. The top parameter in the setup mode “
key for one second minimum to enter the setup
:inputtype”is
displayed. This parameter is factory-set to “2: K1”.
(3) Press the
“
: _C”.
to “
(4) Select the menu display, and select “
key to fix the set value. The display changes to
: _C/_F selection” parameter. This parameter is factory-set
: level 2 mode” using the
orkeys.
(5) Press the
key for one second minimum to enter the level 2
mode. The top parameter in the level 2 mode [] (“local/remote” parameter) is displayed.
(6) Press the
key until [] (“input shift upper limit” parame-
ter) is selected. This parameter is factory-set to “0.0”.
(7) Press the
(8) Press the
key until “3.0” is displayed.
key until [] (“input shift lower limit” parame-
ter) is selected. This parameter is factory-set to “0.0”.
(9) Press the
keyuntil“1.0”isdisplayed.Thissetsthe“inputshift
upper limit” and “input shift lower limit” values.
3--6
Page 43
3.3Setting Output Specifications
Dest
inat
i
Some output specifications are different according to controller type,
standard or position-proportional. The following table summarizes
which output-related parameter settings are supported.
3.3 Setting Output Specifications
JOutput assignments
F Standard type
Parameter
Control output 1 assignmentF
Control output 2 assignmentF
Auxiliary output 1 assignmentFF
Auxiliary output 2 assignmentFF
Direct/reverse operationFF
Control period (heat)F
Control period (cool)F
(F Indicates that an output specification is supported.)
Standard
Typ e
Position-
proportional
Typ e
Output assignments are described according to controller type.
• Thirteen outputs are supported. These functions are assigned to control outputs 1 and 2, and auxiliary outputs 1 and 2.
• Restrictions on assignment destination are placed on some of the outputs.
• The following table shows where outputs may be assigned to.
Assignment
Control OutputAuxiliary Output
on
Output Function
Control output (heat)FF
Control output (cool)FF
Alarm 1FFFF
Alarm 2FFFF
Alarm 3FFFF
HBAFFFF
LBAFFFF
Time signal 1FFFF
Time signal 2FFFF
Program endFFFF
Stage outputFFFF
Error 1 : Input errorFF
Error 2 : A/D convertor errorFF
1212
With control output (cool), the conditions for switching from standard control
to heating and cooling control are reached when the output function is assigned
at the cooling side during heating and cooling control.
In other words, heating and cooling control is carried out when control output (cool) is assigned, and standard control is carried out
when output is not assigned. For details on heating and cooling control, see Chapter 4 Applied Operation/4.1 Selecting the Control Method (page 4-2).
3--7
Page 44
CHAPTER 3 BASIC OPERATION
Dest
inat
i
• Factory settings are as follows:
control output 1 = Control output (heat)
control output 2 = Alarm 1
auxiliary output 1 = Alarm 2
auxiliary output 2 = Alarm 3
• Output assignments are set in the “control output 1 assignment”,
“control output 2 assignment”, “ auxiliary output 1 assignment” and
“ auxiliary output 2 assignment” parameters (setup mode).
F Position -propor-
tional type
JDirect/reverse
operation
• Position-proportional type controllers support nine output functions.
These are assigned to auxiliary outputs 1 and 2.
• Restrictions on assignment destinations are placed on some of the
outputs. The following table shows where outputs may be assigned to.
Assignment
Output Function
Alarm 1FF
Alarm 2FF
Alarm 3FF
Time signal 1FF
Time signal 2FF
Stage outputFF
Program end outputFF
Error 1 : Input errorFF
Error 2 : A/D converter errorFF
• “Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process
value. Alternatively, “reverse operation” refers to control where the manipulated variable is decreased according to the decrease in the process
value.
For example, when the process value (PV) (temperature), is lower
than the set point (SP) (temperature), in a heating control system, the
manipulatedvariableincreasesbythedifferencebetweenthePVand
SP values.
Accordingly, this becomes “reverse operation” in a heating control
system, or alternatively, “direct operation” in a cooling control system.
• Direct/reverse operation is set in the “direct/reverse operation” parameter (setup mode). Default is “
Control OutputAuxiliary Output
on
1212
: reverse operation”.
JControl period
3--8
• On position-proportional type controllers, this item cannot be set.
• On a standard type controller, when the output unit is for pulse out-
put such as relay output, set the pulse output cycle (control period).
Though a shorter control period provides better control performance,
the control period should be set to 20 seconds minimum taking the
life expectancy of the output unit into consideration when the output
unit is for relay output.
• The control period is set in the “control period (heat)” parameter
(level 1 mode). Default of the “control period” parameter is “20:20
seconds.” Default of the “control period (cool)” output function is not
assigned. So, the “control period (cool)” parameter cannot be set.
Page 45
3.3 Setting Output Specifications
Setting Example
1 second min.
1 second min.
1 second min.
All of the above settings in this example are factory settings. In this example, let’s check the parameter settings.
In this example, the parameters are set as follows:
] (“direct/reverse operation” parameter) is displayed.
].
or
keys to select “: l evel 1 mode”. For details on selecting
the menu display, see page 1 -10.
(7) Press the
key for one second minimum to enter the level 1
mode. The top parameter in the level 1 mode “: Proportional
band” is displayed.
(8) Press the
key until [] (“control period (heat)” parameter)
is displayed. Default is “20”. As the setting in this example is to be
left as its is, quit key operation.
3--9
Page 46
CHAPTER 3 BASIC OPERATION
A
l
3.4Setting Alarm Type
• Three alarm outputs are supported: alarms 1 to 3. Of these, only the
alarm assigned as the output can be used.
• Alarm output conditions are determined according to the combination of the “alarm type”, “alarm value” and “alarm hysteresis” parameter settings.
• The contact conditions for when alarm output is ON can be set to
“open” or “closed” in the “close in alarm/open in alarm” parameter.
JAlarm type
• The following table shows the alarm types supported by the E5EK-T
controller and their respective operations.
armType
Upper-and lower-limit alarm
1
(deviation)
Upper-limit alarm
2
(deviation)
Lower-limit alarm
3
(deviation)
Upper-and-lower-limit range
alarm
4
(deviation)
Upper-and-lower-limit alarm
with standby sequence
5
(deviation)
Upper-limit alarm with standby sequence
6
(deviation)
Lower-limit alarm with standby sequence
7
(deviation)
Absolute-value upper-limit
8
alarm
Absolute-value lower-limit
9
alarm
Absolute-value upper-limit
10
alarm with standby sequence
Absolute-value lower-limit
11
alarm with standby sequence
When X is positiveWhen X is negative
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Alarm Output Operation
XX
SP
X
SP
X
SP
XX
SP
XX
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Always ON
ON
OFF
ON
OFF
Always OFF
Always OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
• Alarm types are set independently for each alarm in the “alarm 1 to
3” parameters (setup mode). Default is “2: Upper-limit alarm (deviation)”.
JAlarm value
3--10
• Alarm values are indicated by “X” in the tabl e above. Alarm output
operation differs according to whether the value of the alarm is positive or negative.
• Alarm values are built into the program and are set for each pattern.
For details, see 3.5 Setting Patterns” (page 3-14).
Page 47
3.4 Setting Alarm Type
C
l
O
JAlarm hysteresis
F Standby
sequence
• The hysteresis of alarm outputs when alarms are switched ON/OFF
can be set as follows:
Upper limit alarmLower limit alarm
ON
OFF
Alarm hysteresis
Alarm value
ON
OFF
Alarm value
Alarm hysteresis
• Alarm hysteresis is set independently for each alarm in the “alarm 1
to 3 hysteresis” parameters (level 2 mode). Default is “0.02:
0.02%FS”.
• “Standby sequence” is a function for unconditionally turning alarm
output OFF when the process value has left the alarm range once and
it next enters the alarm range.
• For example, when the alarm type is set to “ lower-limit alarm,” generally the process value is within the alarm range, and alarm output
smaller than the set point, and alarm output becomes ON when this
state continues. However, if the alarm type is set to “ lower-limit
alarm with standby sequence”, alarm output first becomes ON when
theprocessvalueexceedsthe alarm settingvaluetoleavethealarm
range and once again falls below the alarm value.
• The standby sequence is canceled when an alarm is output. It is, however, restarted later by one of the following conditions:
Operation is started or power is turned ON.
A pattern is started.
The program advances to the next step.
The SP of the current step is changed.
The currently running alarm value is changed.
The input shift value is changed.
Advance is executed.
JCloseinalarm/openinalarm
• When the controller is set to “close in alarm,” the status of the alarm
output function is output as it is. When set to “open in alarm,” the
status of the alarm output function is output inverted.
OutputOutput LED
oseinalarm
peninalarm
Alarm
ONONLit
OFFOFFNot lit
ONOFFLit
OFFONNot lit
• Alarm type and close in alarm (normally open)/open in alarm (normally close) can be set independently for each alarm.
• Close in alarm/open in alarm is set in the “alarm 1 to 3 open in
alarm” parameters (setup mode). Default is “
: close in alarm”.
3--11
Page 48
CHAPTER 3 BASIC OPERATION
F Summary of
alarm operations
The figure below visually summarizes the above descriptions of alarm
operations (when alarm type is set to “lower-limit alarm with standby
sequence”):
Alarm type: lower limit alarm with
standby sequence
PV
Alarm value
Alarm hysteresis
Time
Standby sequence
canceled
Alarm
output
ON
OFF
ON (closed)
OFF (open)
3--12
Page 49
3.4 Setting Alarm Type
Setting Example
1 second min.
1secondmin.
Alarm 2 is output when the temperature exceeds alarm value 2 programmed to the SP. Parameter factory settings for “alarm type 2,”
“alarm hysteresis” and “close in alarm/open in alarm” are used.
In this example, the related parameters are set as follows:
“alarm type 2” = “2: upper-limit”
“alarm value 2”= (set in program setting)
“alarm hysteresis: = “0.02”
“close in alarm/open in alarm”= “
: close in alarm”
In this example, let’s check the alarm type.
(1) Select the menu display, and select “: setup mode” pressing
theorkeys. For details on selecting the menu display, see
page 1-9.
(2) Press the
the setup mode “
(3) Press the
key to enter the setup mode. The top parameter in
: input type” is displayed.
key until [] (“alarm type 2” parameter) is dis-
played. Default is “2: upper limit”.
1secondmin.
3--13
Page 50
CHAPTER 3 BASIC OPERATION
3.5Setting Patterns
If you want to set parameters in the program mode during controller operation, you must first stop operation. Operation may continue only in special instances, for example, to change SP during controller
operation.
• Parameters that you use frequently for programming can be set in the
“program mode.” The flow below shows the parameters that are
available in the program mode and the order in which they are set.
Select the program mode.
Select pattern No.
Set number of steps
Step time/Rate of rise
programming
Step time setting
Set step SP/step time
Set pattern execution count
Set alarm value
Set time signal 1, 2
Step/ON time/OFF time
n
All patterns completed?
Rate of rise setting
Set SP/Ramp time
/Soak time of each step
y
3--14
End of program
This chapter describes the basic operation of programming. For details
on the following parameters, refer to Chapter 4 Applied Operation:
“Step time/Rate of rise programming”, “Pattern execution count”,
“Time signal 1, 2”
Page 51
3.5 Setting Patterns
JPattern No.
JNumber of steps
JStep SP/Step
time
:
:
: :0to15
• This parameter cannot be changed during controller operation.
• Set the desired pattern No. Step SP, step time, alarms and other pa-
rameters that follow this parameter are set for the pattern that is set
in this parameter.
• Set within the range 0 to 3 (pattern 0 to 3). Default is “0”.
• Set the number of steps for the pattern that you specified in the “pat-
tern No.” parameter.
• Set within the range 1 to 16 (step). Default is “8”.
• Set only the number of steps used in the program in order from step
0, as “step 0 SP”, “step 0 time”, “step 1 SP”, “step 1 time” and so
forth.
• Set within the range from set point lower limit to set point upper
limit for step SP. Default is “0”.
• Set within the range 0.00 to 99.59 (hours:minutes or minutes:seconds). Default is “0.00”.
SP
Step 0Step 1Step 2Step 3
Step 0 hour
A: SP of steps 0 and 3
B: SP of steps 1 and 2
• As shown in the above figure, step 0 is a fixed value, so when ramp
operation is started, set the “step 0 time” parameter to “0.00” to configure the program so that ramp operation starts from step 1.
Step 1 hourStep 2 hoursStep 3 hours
Time
3--15
Page 52
CHAPTER 3 BASIC OPERATION
JAlarm value
:
: :0to3
• Alarm values can be set onl y for alarms that have been assigned as
output.
• When a deviation alarm i s assigned as output, the alarm value is set
with respect to SP. The following example shows the relationship between the SP and alarm value when the alarm type is set to “upper
limit.”
SP
Step 0Step 1Step 2
Step1SP
Step0SP
Alarm type: upper-limit alarm
Alarm value
Time
Time
About the Alarm
ValueDecimal
Point
3--16
The decimal point of the alarm value conforms to the setting of the “decimal point”
parameter.
Page 53
3.5 Setting Patterns
Setting Example
1 second min.
In this example, let’s set the next program to pattern 0.
(1) Select the menu display, and select “: program” pressing the
orkeys. For details on selecting the menu display, see page
1-10.
(2) Press the
in the program mode “
key to enter the program mode. The top parameter
: pattern” is displayed. Default is “0 :
pattern 0”.
(3) As the setting “0: pattern 0” in this example is to be left as it is,
press the
key. The display changes to the [](“numberof
steps” parameter). Default is “8”.
(4) Set the parameter to “4” pressing the
(5) When you press the
, the display changes to the [](“step0
orkeys.
SP” parameter). Default is “0”.
(6) Set the parameter to “50” pressing the
(7) When you press the
, the display changes to the [](“step0
orkeys.
time” parameter). Default is “0.00”.
(8) As the setting “0.00: 0 minutes” in this example is to be left as it is,
press the
key. The display changes to the [](“step1SP”
parameter). Default is “0”.
(9) Set the parameter to “100” pressing the
(10)Inthesameway,setthe“
: step 1 time”, “:step2SP”,
orkeys.
“: step 2 time”, “:step3SP”,“: step 3 time” parameters, in that order.
(11) When you have finished setting the step SPs and times press the
key. The [] (“pattern execution count” parameter, is dis-
played. Default is “1”.)
3--17
Page 54
CHAPTER 3 BASIC OPERATION
(12) As the setting in this example is to be left as it is, set the alarm val-
(13) Set the parameter to “10: 10 seconds” pressing the
ue. Press the
key until [] (“alarm 2” parameter) is dis-
played. Default is “0”.
keys.
or
3--18
Page 55
3.6Protect Mode
Mod
3.6 Protect Mode
JSecurity
• This parameter allows you to protect until start of operation parameters that do not change during operation to prevent unwanted modification.
• The set value of the “security” parameter (protect mode) limits the
range of protectable parameters. The following table shows the relationship between set values and the range of protection. (Only modes
marked by F can be operated.)
*1 Only the “PV/Present SP” parameter can be displayed.
0123456
• When this parameter is set to “0”, parameters are not protected.
• When this parameter is set to “5”, operations in only the level 0 mode
can be selected, and the mode is not displayed on the menu display.
• When this parameter is set to “6”, the “PV/Present SP” parameter
can only be monitored.
• Default is “1”.
JKey protect
• This parameter disables key operation for switching run/reset or
auto/manual. For example, if you protect the key operation for switching auto/manual by the “key protect” parameter (protect mode) during automatic operation, the controller cannot be set to the manual
mode, preventing manual operation of the controller during operation.
• The following table shows the relationship between set values and
keys that are protected.
Set value
0
1
2
3
Key protection OFF
A/M cannot be selected.
RUN/RST cannot be selected.
Both A/M and RUN/RST cannot be selected.
Description
• Default is “0 : All keys can be operated.”
3--19
Page 56
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
RUN/RST
RUN/RST
In this example, let’s set the parameters as follows:
“Security”“2” (all parameters in modes other than the setup
mode are protected)
“Key protect”“1” (Auto/manual key operation cannot be
switched)
(1) Press the
RUN/RST
andkeys simultaneously for 1 second mini-
mum. The controller enters the protect mode. In the protect mode,
the top parameter in the protect mode “security” is displayed.
Default is “1”.
(2) Press the
(3) Press the
(4) Press the
(5) Press the
key to change the parameter setting to “2”.
key to switch to the “key protect” parameter.
key to change the parameter setting to “1”.
RUN/RST
and
keys simultaneously for 1 second mini-
mum. The display changes to the “PV/Present SP mon itor” param-
eter (level 0 mode).
3--20
Page 57
3.7 Starting and Stopping Operation
3.7Starting and Stopping Operation
• To start program operation (that is, switch from the reset state to run
RUN/RST
operation), press the
• To stop program operation (that is, switch from run operation to the
reset state), press the
the controller has stopped operating (reset state), the RST LED
lights.
• The controller cannot be reset during auto-tuning (A.T.).
RUN/RST
RUN/RST
key for one second minimum.
key from two seconds minimum. When
F Man ip ulated vari-
able at reset
• On a standard type controller, specify the manipulated variable ( -5.0
to 105.0%) in the “MV at reset” parameter (level 2 mode) to output
the manipulated variable during reset. Default is “0.0:0.0%”.
• When the controller is reset in the manual mode, the manual MV
takes precedence.
• Both the MV limitter and MV change rate limitter are ineffective
against the manipulated value at reset.
• On a position-proportional type controller, you can select either of the
open, closed or hold state. In an open state, only control output 1 is
ON. In a closed state, only control output 2 is ON. In a hold state,
both control outputs 1 and 2 are OFF. Default is “
”.
Using Event Input
On the E53-AKB, run/reset can be selected by event input.
For details on how to use event input, see 4.8 How to Use Event Input, page 4-21.
3--21
Page 58
CHAPTER 3 BASIC OPERATION
3.8Adjusting Control Operation
JChanging
programs
F Changing the SP
Before change
• Programs are changed in the pr ogram mode. Note that pattern Nos.
cannot be changed during program operation. So, only the pattern
that is currently running can be changed.
• You cannot change the program when the “security” parameter (protect mode) is set to “5” or “6”.
• When the SP is changed midway through a step, the Present SP is
shifted on a line obtained by taking the new SP as the target point.
SP
After change
Changing point
Time
Step NStep N+1
F Changing the
time value
Before change
After change
AboutChanging
theNumberof
Steps
• Change the time value of steps 0 to 15 in “step 0 to 15 time” parameters (program mode).
• When the time value is changed midway through a step, the step time
changes. The gradient of the line by which SP shifts also changes.
SP
Changing point
Time
Step NStep N+1
Step NStep N+1
If you set the “number of steps” parameter (program mode) to a value smaller
than the current number of steps during program operation, program operation
is immediately exited.
3--22
Page 59
3.8 Adjusting Control Operation
Setting Example
1 second min.
1 second min.
In the following example, let’s change the temperature set point to
“60_C” from “50_C”.
(1) Press thekey for 1 second minimum at the currently executing
“PV/Present SP” display.
(2) The display changes to the menu display.
(3) Set the parameter to “
(4) Press the
key to enter the program mode. The top parameter in
: program” pressing theorkeys.
the program mode “: pattern” is displayed.
(5) Press the
key to display the [] (“number of steps” parame-
ter).
(6) Press the
key. [] (“step 0 SP” parameter) is displayed, and the
No.2 display indicates “50.0”.
(7) Press the
(8) Press the
key to set the parameter to ”60.0”.
key for 1 second minimum. The menu display (“
: program” parameter) is redisplayed.
(9) Select “
the
: level 0 mode” pressing theorkeys, and press
key for 1 second minimum. The “PV/Present SP” display is
redisplayed.
1 second min.
1 second min.
3--23
Page 60
CHAPTER 3 BASIC OPERATION
JManual operation
F Standard type
• On a standard type controller, the manipulated variable is controlled,
and on a position-proportional type controller, the valve opening is
controlled.
• To set manual operation and manually set the manipulated variable
or the valve opening, press the
key andkey simultaneously
for 1 second minimum. Then the controllers enters the manual mode.
To quit the manual mode, press the
key andkey again simultaneously for 1 second minimum. The controller enters the level 0
mode without entering the menu display.
• Though the control shifts to manual operation if the controller is set
to the manual mode during program operation, the program advances. When program operation is started in the manual mode, program also advances.
• In the manual mode, the automatic return of display mode does not
work.
• The process value is displayed on the No.1 display, and the manipulated variable is displayed on the No.2 display.
• To change the manipulated variable, press the
orkeys. After
two seconds, the manipulated variable is updated to the new setting.
• When switching between manual and auto operation, the manipulated variable is subject to balance-less, bump-less operation.
• If the power is interrupted during manual operation, manual operation is resumed at the manipulated variable that was active at power
interruption when the power is reset.
Manipulated variable (%)
Manual
Auto
F Position -propor-
tional type
Balance-less,
Bump-less Operation
Balance-less,
bump-less points
0
Manipulated variable switched
++
OFFON
Power interruption
• When a potentiometer is connected to the controller, the process value
is displayed on the No.1 display, and the valve opening is displayed on
the No.2 display.
• When you press the
press the
To prevent sudden changes in the manipulated variable when switching between
manual and auto operation, operation is resumed using the value that was active
immediately before operation was switched, and the value is brought gradually
closer to the value immediately after operation was switched.
key, the close side becomes ON.
key, the open side becomes ON. When you
Time
3--24
Page 61
3.8 Adjusting Control Operation
JAuto-tuning
(A.T.)
F 40%AT
Deviation at start of AT
execution ≧ 10% FS
• AT (auto-tuning) cannot be executed while operation is reset or during ON/OFF control.
• When you execute auto-tuning, the optimum PID parameters are automatically set by forcibly changing the manipulated variable to calculate the characteristics (called the “limit cycle method”) of the con trol target. During auto-tuning, time counting is stopped and the
“AT ” L E D f la sh e s.
• 40%AT or 100%AT can be selected by the limit cycle o f MV change
width. Specify [
]or[], respectively, in the “A T execute/
cancel” parameter (level 1 mode).
• During heating and cooling control on a standard type controller, and
on a position-proportional type controller, only 100%AT can be
executed. (So, “
• To cancel AT execution, specify “
: 40%AT” is not displayed.)
:ATcancel”.
In order to set the limit cycle of MV change width to 40%, select 40%AT
to execute auto-tuning with fluctuations in the process value kept to a
minimum. However, note that auto-tuning takes longer to execute
compared with 100%AT.
The timing by which limit cycles are generate d varies according to whether or not the deviation (DV) at the start of AT execut ion is 10% full-scale
or less.
Deviation at start of AT
execution < 10% full-scale
Limit cycle of MV change
width 40%
Limit cycle of MV change
width 40%
Set pointSet point
Deviation 10%
full-scale
StartofAT
execution
F 100%AT
End of AT
execution
In order to set the li mi t cycle of MV change width to 100%, select
TimeTime
100%AT to shorten the AT execution time without worrying about fluctuations in the process value.
Limit cycle of MV
change width 100%
Set point
StartofAT
execution
StartofAT
execution
End of AT
Deviation 10%
full-scale
End of AT
execution
Time
3--25
Page 62
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
AT execute
End of AT execution
In this example, let’s execute 40%AT.
(1) Select the menu display, and select “: level 1 mode” using the
orkeys. For details on selecting the menu display, see page
1-10.
(2) Press the
the setup mode “
example, the parameter setting is “
(3) Press the
key to enter the level 1 mode. The top parameter in
: AT execute/cancel” is displayed. In this
:ATcancel”.
key to specify [].
(4) The AT LED flashes, and AT execution starts. When the AT LED
goes out (end of AT execution), the parameter automatically returns to “
:ATcancel”.
3--26
About PID Parameters
AT Execution T iming
When control characteristics are already known, the PID parameters can be set
directly to adjust control.
PID parameters are set in the “proportional band” (P), “integrated time” (I) and
“derivative time” (D) parameters (level 1 mode).
For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode
(page 5-18).
The E5EK-T differs from fixed-value type controllers in that the SP changes automatically. So, the timing of AT execution is the most important factor in control.
To obtain PID parameters for a specific SP, make a fixed-value program as follows
and execute AT.
10 minutes
100
Step 0
Set value
SPTime
Step 01000.10
Page 63
CHAPTER4
CHAPTER4
APPLIED OPERATION
This chapter describes each of the parameters required for making
full use of the features of the E5EK-T.
Read this chapter while referring to the parameter descriptions in
chapter 5.
CHAPTER 4 APPLIED OPERATION
4.1Selecting the Control Method4-2............
Heating and cooling control4 -2.............
Position-proportional control4-4............
ON/OFF control4-5.......................
4.2Operating Condition Restrictions4-7........
Manipulated variable restrictions4-7........
Set point limiter4-8.......................
4.3Ramp Rise Rate Setup Program4-9.........
Runningtherampriseratesetupprogram 4-11
Program example4-12......................
4.4Program Operation4-13....................
Hold/Advance4-13..........................
Pattern operation4-14......................
4.5W ait Operation4-16........................
4.6Program output4-17........................
Time signal4-17............................
Program output4-18........................
4.7Setting Running Conditions4-19.............
Operation at power ON4-19.................
Starting the program run4-19...............
End condition4-20.........................
4.8How to Use Event Input4-21................
Input assignments4-21.....................
Detailed description of input functions4-22...
4.9How to Use the Heater Burnout Alarm4-23...
Heater burnout detection4-23...............
Operating conditions4-23...................
How to calculate the heater burnout
set value4-24..............................
4.10 LBA4-26..................................
4.11 How to Use Transfer Output4-28............
4--1
Page 64
CHAPTER 4 APPLIED OPERATION
4.1Selecting the Control Method
JHeating and
cooling control
When selecting the control method, set the parameters according to the
following table. (Parameters are factory-set to heating control.)
Parameter
Control
Method
Heating control
(Standard)
Cooling control
(Standard)
Heating and cooling
control
(Parameters are factory-set to heating control.)
• For details on how to assign outputs, see 3.3 Setting Output Specifications (page 3-7).
• When heating and cooling control is selected, the “dead band” and
“cooling coefficient” parameters can be used.
F Dead band
The dead band is set with the set point as its center. The dead band
width is the set value of the “dead band” parameter (level 1 mode). Setting a p ositive value produces a dead band, while setting a negative value produces an overlap band.
The dead band is factory-set to “0.00:0.00%FS.”
OutputOutput
Dead band: dead
band width = positive
Control Output 1
Assignment
Control output (heat)
Control output (heat)
Control output (heat)Control output (cool)Reverse operation
Control Output 2
Assignment
-
-
Overlap band: dead
band width = negative
Direct/Reverse
operations
Reverse operation
Direct operation
Heating
side
0
F Cooling
coefficient
Cooling
side
PV
Set pointSet point
Heating
side
0
If the heating and cooling characteristics of the control target greatly
differ, preventing satisfactory control characteristics from being obtained by the same PID parameters, adjust the proportional band (P at
cooling side) using the cooling coefficient to balance control between
the heating and cooling sides. In heating and cooling control, P at the
heating or cooling side is calculated by the following formula:
Heating side P = P; Cooling side P = cooling coefficient ¢ P
Cooling
side
PV
4--2
Page 65
4.1 Selecting the Control Method
F Man ip ulated vari-
able at reset
• In heating and cooling control, the manipulated variable output that
is output when controller operation is stopped is dependent on the set
value of the “MV at reset” parameter (level 2 mode) in the same way
as for standard control.
• However, note that in heating and cooling control, the manipulated
variable at the cooling side is treated as a negative value for the sake
of convenience. When the manipulated variable at reset is a negative
value, the manipulated variable is output to only the cooling side, and
when a positive value, the manipulated variable is output to only the
heating side.
Default is “0”. If the controller is operated with default, the manipulated variable is not output to both the heating and cooling sides.
Switching with
Manual Operation
When the overlap band is set, the bumpless function that operates when switching between manual and automatic operation may not work.
4--3
Page 66
CHAPTER 4 APPLIED OPERATION
JPosition-propor-
tional control
8
Open
7
6
Close
5
O
17
W
16
C
15
Potentiometer
F Travel time
F Valve opening
monitor
• Use the position-proportional type controller for position-proportional control.
• On a position-proportional type controller, control output 1 is used
for open output, and control output 2 is used for closed output. Accordingly, control outputs 1 and 2 cannot be used as output assignments. Special output units are already set on position-proportional
type controllers.
• On a position-proportional type controller, the following functions are
disabled:
MV limitter
P and PD control
40% AT
LBA
HBA
ON/OFF control
• To change the travel time, either set in the “travel time” parameter
(option mode), or execute motor calibration in the “motor calibration” parameter (option mode).
• Default is “30:30 seconds.”
• The valve opening can be monitored when a potentiometer is con-
nected to the controller. However, be sure to execute motor calibration after connecting the potentiometer.
F Man ip ulated vari-
able at reset/PV
error
F Other functions
• Open, closed or hold can be selected as output at reset or PV error. Set
these outputs in the “MV at reset” or “MV at PV error” parameters
(level 2 mode).
• Set the dead band in the “position-proportional dead band” parameter (level 1 mode). Default is “2.0:2.0%”.
• Set the open/close hysteresis in the “open/close hysteresis” parameter
(level 2 mode).
Open/close hysteresis
Dead band
ON
OFF
MV-Valve opening
100%0-100%
4--4
Page 67
4.1 Selecting the Control Method
JON/OFF control
F Hysteresis
• ON/OFF control is selected by the “PID/ON/OFF” parameter (expansion mode). When this parameter is set to [
trol is selected, and when set to [
], ON/OFF control is selected.
The “ON/OFF control” parameter is factory-set to [
], advanced PI D con-
].
• During position-proportional control, ON/OFF control cannot be selected.
• In ON/OFF control, hysteresis is provided in the p rogram when
switching between ON and OFF to stabilize operation. The hysteresis
width provided during ON/OFF control is simply referred to as “hysteresis.” Control output (heat) and control output (cool) functions are
set in the “hysteresis (heat)” and “hysteresis (cool)” parameters, respectively.
• In standard control (heating or cooling control), hysteresis can be set
only for the heating side.
Hysteresis (heat)
ON
OFF
Set point
PV
• In heating and cooling control, a dead band can be set. So, 3-position
control is made possible.
Dead band
Hysteresis (heat)
ON
Heating
side
OFF
Hysteresis (cool)
Cooling side
PV
Set point
4--5
Page 68
CHAPTER 4 APPLIED OPERATION
Parameters
SymbolParameter Name: ModeDescription
Control output 1
assignment : Setup
Control output 2
assignment : Setup
Direct/reverse
operation: Setup
Dead band: Level 1Heating and cooling control
Cooling coefficient: Level 1Heating and cooling control
MV at reset: Level 2Manipulated variable when control
MV at PV error: Level 2Manipulated variable when control
Travel time: OptionPosition-proportional control
Motor calibration: OptionPosition-proportional control
Positional-proportional
dead band: Level 1
Open/close
hysteresis: Level 2
Hysteresis (heat): Level 1ON/OFF control
Hysteresis (cool): Level 1ON/OFF control
PID / ON/OFF: Expansion ON/OFF control
For specifying control method
For specifying control method
For specifying control method
operation is stopped
operation is PV error
Position-proportional control
Position-proportional control
4--6
Page 69
4.2 Operating Condition Restrictions
4.2Operating Condition Restrictions
JManipulated vari-
able restrictions
F MV limiter
The upper- and lower-limit values of the manipulated variable can be
restricted by the MV limitter, and the change rate of manipulated variable can be restricted by the MV change rate limitter.
The upper- and lower-limit values of the manipulated variable are set
in the “MV upper limit” and “MV lower limit” parameters (level 2
mode). When the manipulated variable calculated by the E5EK-T is outside of the range of the MV limitter, actual outputs are dependent on
thesetvalueoftheseparameters.
Output (%)
100
0
MV upper limit value
MV lower
limit value
PV
In heating and cooling control, the manipulated variable at the cooling
side is treated as a negative value for the sake of convenience. The upper limit is set for the heating side (positive value), and the lower limit
is set for the cooling side (negative value) as shown in the following figure.
F MV change rate
limiter
Output (%)
100
MV lower limit value
MV upper limit value
Heating
side
0
Set point
Cooling
side
PV
The “MV change rate limitter” parameter (level 2 mode) sets the maximum permissible change width per second of the manipulated variable.
If a change in the manipulated variable exceeds this parameter setting,
the value calculated by the E5EK-T is reached while changing the value
by the per-second value set in this parameter.
Output (%)
100
MV change rate
limit value
1 second
0
Switching point
Time
4--7
Page 70
CHAPTER 4 APPLIED OPERATION
F Limiter operation
conditions
JSet point limiter
Set pointUpper-and lower-limit values of the limitter
Scaling (sensor) upper-and lower-limitter values
The limitters are disabled or cannot be set when any of the following
conditions occurs:
• During ON/OFF control
• During AT execution (only by MV change rate limitter)
• During manual operation
• When operation is stopped
• When an error has occurred
• During position-proportional control (manipulated variable limitter
only)
The setting range of the set point is limited by the set point limitter.
The upper- and lower-limit values of this set point limitter are set in
the “set point upper limit” and “set point lower limit” parameters (ex-
pansion mode), respectively. However, note that when the set p oint limitter is reset, the set point is forcibly changed to the upper- or lowerlimit value of the set point limitter if the set point is out of the limitter
range. Also, when the input type, temperature unit and scaling (sensor)
range are changed, the set point limitter is forcibly reset to the scaling
(sensor) range.
Set point upper limit : ExpansionFor limiting SP setting
Set point lower limit : ExpansionFor limiting SP setting
Page 71
4.3 Ramp Rise Rate Setup Program
4.3Ramp Rise Rate Setup Program
Chapter 3 described programs that used the “time setup method.” Programs were executed using a combination of SPs and step time values.
The E5EK-T also supports the “ramp rise rate setup method.” By this
method, programs are executed using three program elements: “target
SP”, “rate o f rise” and “soak time.”
To select a ramp rise rate program, set the “Step time/rate of rise pro-
gramming” parameter (expansion mode) to “
Target SP
Time unit of ramp rate
:rateofrise.”
Soak time
Rate of rise
Step
NN+1
Ramp stepSoak step
Set each of the above p rogram elements i n the “target SP 0 to 7”, “rate
of rise 0 to 7” and “soak time 0 to 7” parameters.
In a ramp rise rate program, parameters are set to two steps as shown
in the figure above. The following figure shows the relationship between the pro gram and parameters.
Target SP 1
Soak time 0Soak time 1Soak time 2
Target SP 0
Target SP 2
Step
Parameter
012345
Target SP 0Target SP 1Target SP 2
Rate of rise 0Rate of rise 1Rate of rise 2
Soak time 0Soak time 1Soak time 2
4--9
Page 72
CHAPTER 4 APPLIED OPERATION
F Relationship with
the number of
steps
F When the rate of
rise is set to “0”
When the number of steps is set to an odd number, the final soak time
cannot be set. For example, if we set the “number of steps” parameter
to “7”, the “soak time 3” parameter cannot be set even though the “target SP 3” and “rate of rise 3” parameters can be set.
Accordingly, when the number of steps are set to an even number, the
final step is a soak step. When it is set to an odd number, the final step
is a ramp step.
Number of steps = even numberNumber of steps = odd number
When “rate of rise 0 to 7” parameter is set to “0”, the ramp step is
skipped and the soak step appears to be continuous.
Step N is skipped.
Step
NN-1
Ramp stepSoak step
N+1
Soak step
4--10
Page 73
4.3 Ramp Rise Rate Setup Program
JRunning the ramp
rise rate setup
program
F Changing
parameters
Ramp rise rate setup programs take the PV at start of program op eration as the SP (PV start) when they are started.
When the rate of rise is changed midway during operation, the SP rate
of rise and the step time in the ramp cycle both change.
After change
Before
change
Switching point
Before change
After change
• In the above figure, increasing the rate of rise results in a shorter target step time. Likewise, when the SP is changed, the step time of the
ramp cycle also changes.
• When the soak time is changed, only the step time in the soak cycle
changes.
Step NStep N+1
Step NStep N+1
Time
4--11
Page 74
CHAPTER 4 APPLIED OPERATION
JProgram example
F Program
structure
F How the program
works
Let’s describe a typical example of a ramp rise rate setup program. In
an actual program, set the parameters to match the application.
100
10
Step 0Step 1Step 2Step 3
306090120
Target SP 0 : 100
Rate of rise 0 : 3
Soak time 0 : 0.30
“Number of steps” = 4, “Time unit of ramp rate” = minutes, “PV start” = 10
Target SP 1 : 10
Rate of rise 1 : 3
Soak time 1 : 0.30
In a program comprising four steps, steps 0 and 1 follow the settings of
the “target SP 0”, “rate of rise 0” and “soak time 0” parameters. Steps 2
and 3 follow the settings of the “target SP 1”, “rate of rise 1” and “soak
time 1” parameters.
(1) As the program starts at PV (PV start), the program starts opera-
tion from “10” in this example.
(2) As the rate of rise is set to “3”, the Present SP takes 30 minutes
(100-10/3=30) to reach the target SP value “100” in step 0. If the
PV is “40” when the program is started, this time then becomes 20
minutes using the same formula.
(3) In step 1, the Present SP does not change, and the step time is the
value set to the “soak time 0” parameter (in this example, “30 min-
utes”).
(4) In step2, the Present SP changes according to the value of “rate of
rise 1” parameter from that of “target SP 0” parameter to that of
“target SP 1” parameter It takes 30 minutes in this example.
(5) In step 3, the Present SP does not change, and the step time is the
value set to the “soak time 1” parameter (in this example, “30 minutes”).
Parameters
Operation
at Input Error
4--12
SymbolParameter Name: ModeDescription
Step time/Rate of rise programming: Expansion Ramp rise rate
:Target SP 0 to 3: ProgramRamp rise rate
:
Rate of rise 0 to 3: ProgramRamp rise rate
:
Soak time 0 to 3: ProgramRamp rise rate
: :to
By ramp rise rate setup method, starting at input error, the program start step is
the “step 1”.
Page 75
4.4Program Operation
4.4 Program Operation
JHold/advance
• Steps in currently executing programs can be forcibly stopped (Hold)
and advanced (Advance).
• Hold and Advance operation is according to the following procedure:
Run in level 0 mode
Check step No.
Hold?
Y
Hold = ON
Continue
End of hold?
End
Hold = OFF
Advance
Y
N
N
Advance = ON
Continue
End of advance
End
End: To program operation
• Execute hold/advance operation while making sure the step No. in the
“step No. monitor” parameter (level 0 mode).
• When the “hold” parameter (level 0 mode) is set to “:ON”,step
time counting is paused (held), and the HOLD LED lights. [
]and
the SP appear alternately on the No.2 display when in the “PV/Present SP” parameter.
• Hold is canceled time counting is restarted by one of the following
conditions: “hold” parameter = “
:OFF”,Run,Reset,Endopera-
tion using advance instruction
• Each time that “advance” parameter (level 0 mode) is set to “:
ON”, the pro gram advances one step. With each step advance, the
“Advance” parameter setting returns to “
: O FF”.
• If the advance function is executed with the program in a hold state,
the hold state is continued in the next step.
4--13
Page 76
CHAPTER 4 APPLIED OPERATION
JPattern operation
F Repeatin g execu-
tion of the same
pattern
• To repeatedly execute the same pattern, set the number of times that
the pattern is to be executed in the “pattern execution count” parameter (program mode).
• The pattern execution count can be set up to 9999 (times). (Default is
“0”.)
• Patterns for which the “pattern execution count” parameter is set to
“0” cannot be executed.
• The count of the currently executing pattern in the program can be
verified in the “pattern execution count monitor” parameter (level 0
mode). “0” is indicated in this parameter when the controller of reset
or in a standby state.
F Executing all
patterns
• To execute all preset patterns in order from pattern 0, set the “run all
enable” parameter (expansion mode) to “
OFF”.)
Pattern 0Pattern 1Pattern 2
• When a power interruption occurs during run all execution, if the
“operation at power ON” parameter (expansion mode) is set to “
Continue”, the currently executing pattern No. is held in memory.
When power is restored, program operation resumes from the pattern
that was being executed when the power was interrupted. (For details
on operation at power ON, see page 4-19.)
• Patterns whose “pattern execution count” is set to “0” are skipped.
:ON”.(Default“:
Time
:
4--14
Pattern 0Pattern 1Pattern 3
“pattern execution count” of pattern 2 is set to 0
Time
Page 77
4.4 Program Operation
Parameters
SymbolParameter Name: ModeDescription
Hold: Level 0Pauses program execution.
Advance: Level 0Advances the program one step.
Pattern execution count : Program
Run all:ExpansionExecutes all patterns.
Repeatedly executes current
pattern.
About Reset
• A reset cancels a hold state.
• When the controller is reset during run all execution, the program returns to
step 0 of the currently executing pattern.
4--15
Page 78
CHAPTER 4 APPLIED OPERATION
4.5Wait Operation
• “Wait” is the operation of not advancing the program steps and waiting for the PV to enter the preset wait width at the end of each step.
During wait operation, the “WAIT” LED lights.
• As the PV is smaller than “SP - wait width” at the end of the rising
step in the above figure, control monitoring is stopped, and the control waits for PV to reach “SP - wait width” before the step is updated.
• In the case of a falling step, the control waits for PV to reach “SP +
wait width.”
• Set the wait width in the “wait width” parameter (expansion mode)
within the range 0 to 9999 (EU). (Default is “0”.)
• Setting the “wait width” to “0” disables wait operation.
Wait width
SP
PV
During wait
Counting stopStep updatedTime
Wait width
Parameters
4--16
SymbolParameter Name: ModeDescription
Wait width: ExpansionWait operation
Page 79
4.6Program output
• The E5EK-T outputs the following signals according to how far the
program has elapsed:
• These functions can be used only when they have been assigned as outputs.
4.6 Program output
Time signal 1/2
Program end
Stage output
JTime signal
• Two types of time signals can be set to each pattern.
ON time
Time signal output
OFF time
• There are two timers for time signals: ON time timer and OFF time
timer. These times are counted from the beginning of the step.
• Output is ON from the ON time elapsed point up to the OFF time
elapsed point.
• Set the step at which to output the time signal in the “time signal 1/2
enabled step” parameter (program mode). (Default is “0: step 0.”)
• Set the ON/OFF timing in the “time signal 1/2 ON time” and “time
signal OFF time” parameters (program mode).
Time
F About ON
conditions
About Pattern
Elapsing Time
• When the OFF time is set shorter than the ON time, output is ON
until a reset from the ON time elapsed point onwards or at start of
the next pattern.
• Output does not turn ON when ON and OFF times are set the same.
• When step advance is executed during execution of the time signal
enabled step, the controller judges that the time equivalent to the enabled step has elapsed. For example, in the above figure, output is ON
from the start of the following step up to the OFF time elapsed point.
You can verify the pattern elapsing time in the “pattern elapsing time” parameter (level 0 mode). During repeated execution of patterns or run all execution, the
program is counting for each pattern.
If the count exceeds the monitor range (99 hours:59 minutes or 99 minutes:59
seconds), “99.59” is displayed flashing.
During Hold, time counting is paused.
Executing Advance, the skipped step time is counted.
4--17
Page 80
CHAPTER 4 APPLIED OPERATION
JProgram status
F Program end
F Stage output
• One-second pulse signal is output after the final step is completed.
Time
Program end output
Final step
1s
• One-second pulse signal is output at the beginning of each step.
Parameters
1s
Stage output
SymbolParameter Name: ModeDescription
:
Time signal:set step: ProgramTime signal
Time signal:ON time: ProgramTime signal
:
:
Time signal:ON time: ProgramTime signal
:
Control output:assignment: SetupProgram status
:
Auxiliary output:assignment: SetupProgram status
: :to
Time
4--18
Page 81
4.7Setting Running Conditions
4.7 Setting Running Conditions
JOperation at
power ON
• You can select from one of the following operations at power ON:
Continue,Reset,Run,Manual
• If you select “Continue,” operation is started from the state that was
active when power was interrupted.
• If you select “Reset,” the controller is reset.
• If you select “Run,” normal program operation is started.
• If you select “Manual,” the controller enters the manual mode.
• The following table shows the relationship between operation at pow-
er ON and the operation details that are stored to memory when a
power interruption occurs.
ContinueResetRunManual
Pattern No.ffff
Step No.f--f
Pattern elapsing timef--f
Pattern execution countf--f
Hold statusf--f
Auto/Manualfff-
Run/Resetf--f
MV a t reset *1f--f
Manual MV *2ffff
*1 During auto mode at power interruption on a standard type controller
*2 During manual mode at power interruption on a standard type controller
• Set the desired operation in the “operation at power ON” parameter
(expansion mode). Default is [
:Continue].
4--19
Page 82
CHAPTER 4 APPLIED OPERATION
JStarting the
program run
F PV start
F Standby
operation
JEnd condition
• When the program is configured by the time setup method, a ramppriority “PV start” can be selected as one of the run start conditions.
If you select “PV start” in the “PV start” parameter (expansion
mode), program operation is started from the position of the SP that
first matches the PV when program run is started. If the SP does not
match the PV, the program run is started from the beginning.
SP
Step 0Step 1Step 2Step 3
Disabled time
PV
Start point
Time
• After the run instruction, the controller is reset until the standby
time elapses.
• Set the standby time in the “standby time” parameter (level 2 mode)
within the range 0.00 to 99.59 (hours:minutes). Defaults is “0.00”.
• After end of operation, the controller normally is reset. However, con trol can be continued on the SP of the final step by setting the “end
condition” parameter (expansion mode). If the “end condition” is set,
the SP of the final step and [
display.
• When the “number of steps” parameter is changed after operation has
ended, the controller state does not change state. However, if control
with respect to the SP is continued, the SP switches to the new value
of the final step.
] appears alternately on the No.2
Parameters
4--20
SymbolParameter Name: ModeDescription
Operation at power ON : Expansion
PV start: Expansion Start of program run
Standby time: Level 2Start of p rogram run
End condition: Expansion Operation end program run
Operation when power is
turned ON
Page 83
4.8How to Use Event Input
• When using event input, mount the option unit (E53-AKB).
• Switching by event input is not possible on the menu display.
• Switch event inputs ON and OFF while controller power is ON.
4.8 How to Use Event Input
JInput
assignments
• You can choose from the following six event input functions:
• Event input ON/OFF judgment is carried out on inputs of 200 ms
minimum.
• When event inputs are used as program advance input, the program
step is advanced at the rising (OFF
→ON) edge of the input signal.
When event inputs are used as run/reset input, program operation is
stopped (reset) at the rising (OFF
program operation is started (run) at the falling (ON
→ON) edge of the input signal, and
→OFF) edge.
Other signals are accepted at all times.
• Set event input assignments in the “event input assignments 1 and 2”
parameters (option mode).
• The following table shows the relationship between the settings and
functions of the “event input assignment 1 to 2” parameters.
SettingFunction
Event input disabled
OFF→ON: Reset /ON→OFF: Run
ON: Remote/OFF: Local
ON: Manual/OFF: Auto
ON: Hold/OFF: Hold cancel
Execute at OFF→ON
Specify by combination oftwo inputs (*1).
*1 The following table shows the relationship between pattern select No. and
pattern No.
Pattern No.0123
Pattern select 0ff
Pattern select 1ff
4--21
Page 84
CHAPTER 4 APPLIED OPERATION
JDetailed
description of
input functions
F Run /Reset
ResetRun
F Auto/Manual
F Hold/Hold cancel
F Advan ce
Advance
• There is no order of priority in event input, key operations and communications command setup. However, remote/local, auto/manual,
hold/hold cancel or pattern selection be set to either of ON or OFF. So,
parameters will always follow event input even if you try to switch
settings by key operation and communications commands.
• Program operation is stopped (reset) at the rising (ON→ON) edge of
the event input signal, and the RST LED lights. Program operation is
started (run) at the falling (ON→OFF) edge of the event input signal.
• When event input is set to “ON”, the controller is switched to manual
operation, and the “MANU” LED lights.
• This function is enabled only during program operation.
• The program is paused (Hold) when the event input is ON, and the
“HOLD” LED lights. Holds continue until the state of the event input
changes to O FF.
• This function is enabled only during program operation.
• Program steps are advanced at the ri sing (OFF→ON) edge of the
event input signal. Accordingly, be sure to set event input OFF before
you use this function.
F Pattern select
Parameters
• This function is enabled only when the program is reset.
• Patterns are selected using a combination of pattern select 0 and 1.
• Pattern select 0 and 1 inputs that are not assigned are normally
treated as OFF. For example, when only pattern select 1 is assigned,
pattern select inputs 0 and 1 are treated as OFF, so patterns 0 and 1
are patterns targeted for switching.
SymbolParameter Name: ModeDescription
:Event input assignments 1 to 2: Option
: :to
Event input functions
4--22
Page 85
4.9 How to Use the Heater Burnout Alarm
4.9How to Use the Heater Burnout Alarm
• On a standard type controller, the HBA (heater burnout alarm) function can be used only when the assignment destination of the output
function “control output (heat)” is set to pulsed output.
• When using the HBA function, assign output function “heater burnout alarm” to control outputs 1/2 or auxiliary outputs 1/2.
JHeater burnout
detection
To E5EK-T
CT terminal
CT
Heater wire
F HBA
latch/release
• Heater burnout detection works as follows:
(1) Connect the current transformer (CT) to terminal Nos.15 and 17,
and insert the heater lead through the CT hole.
(2) When current flows through this lead, the current transformer gen-
erates AC current proportional to the current value. The E5EK-T
measures this AC current to calculate the current flowing to the
heater.
(3) If the heater is burned out, the current measured at the current
transformer decreases. This value is compared wi th the value set as
the heater burnout set value and is output as the heater burnout
alarm.
• Set the heater burnout set value in the “heater burnout alarm” parameter. To verify the current value of the current transformer, use
the “heater current monitor” parameter.
• When you are not using the HBA function, set the “heater burnout
alarm” parameter to “0.0 (disabled)”.
• When the HBA latch function is set to “ON”, the heater burnout
alarm is held until either of the following measures is taken:
a Set the heater burnout set value to “0.0A” (default).
b R eset the controller.
(Turn the controller’s power OFF then back ON again.)
• To enable the HBA latch function, set the “HBA latch” parameter to
“ON”.
JOperating
conditions
• Turn the heater power supply ON at the same time as or before turning the E5EK-T power supply ON. If the heater power supply is
turned ON after turning the E5EK-T power supply ON, the heater
burnout alarm is output.
• Control is continued even when the heater burnout alarm is output.
(That is, the controller attempts to control the heater as if the heater
burnout alarm has not occurred.)
• The heater burnout alarm is detected only if the control output is
continuously ON for 190 ms minimum.
• The rated current value may sometimes differ slightly from the actual
current value flowing to the heater. Verify the current value in an actual operating state in the “heater current monitor” parameter.
• If there is little difference between the current in a normal state and
the current in a burnout state, detection may become unstable. On a
heater of current 10.0 A or less, maintain a difference of 1.0 A minimum. On a heater of current 10.0 A minimum, maintain a difference
of 2.5 A mini mum.
4--23
Page 86
CHAPTER 4 APPLIED OPERATION
• The heater burnout alarm function cannot be used when the heater is
controlled by a phase control system or by a cycle control system.
Also, the heater burnout alarm function cannot be applied on 3-phase
heaters.
To detect heater burnout on a 3-phase heater, use the K2CU-FjjA-jGS (with
gate input terminal). (For details, see the respective product catalog.)
JHow to calculate
the heater burnout set value
• Calculate the set value by the following formula:
Set value =
• Setthecurrentvalueatburnoutwhentwoor moreheatersareconnected to the CT to the value at the time that the heater having the
smaller(est) current value burns out (the value when one of the heaters burns out with all heaters at the same current).
• Make sure that the following condition is satisfied:
Heater of current 10.0 A or less
Current value at normal operation - current value at heater
burnout ≧ 1A
When resultant current is less than 1 A, detection is unstable.
Heater of current 10.0 A minimum
Current value at normal operation - current value at heater
burnout ≧ 2.5 A
When resultant current is less than 2.5 A, detection is unstable.
• Thesetvaluecanbesetwithintherange0.1to49.9A.Heaterburnout is not detected when the setting is “0.0” or “50.0”. When the setting is “0.0”, the heater burnout alarm is set to “OFF,” and when the
setting is “50.0”, the heater burnout alarm is set to “ON.”
• Set the total current value at normal heater operation to 50 A or less.
When set to 55.0 A minimum, [
rent monitor” parameter.
(current value at normal operation + current value at burnout)
2
] is displayed in the “heater cur-
4--24
Page 87
4.9 How to Use the Heater Burnout Alarm
F Examples of use
CT
17
1KWx3
CT
17
15
15
Control output
Control output
Heater
1KW
E5EK-T
Heater
E5EK-T
Example 1 : when using a 200 VAC, 1 kW heater
Current at normal operation =
1000
200
Current at heater burnout = 0A
AC200V
Set value =
5+0
2
=2.5A
(current at normal operation-current at heater burnout
=5-0=5A(≧ 1A)
Example 2 : when using three 200 VAC, 1 kW heaters
1000
200
1000
200
AC200V
Current at normal operation =
Current at burnout of one heater =
Set value =
15+10
2
= 12.5A
(current at normal operation-current at heater burnout
=15-10=5A(≧ 2.5A)
=5A(< 10A)
×3 = 15A (≧ 10A )
×2 = 10A
Parameters
SymbolParameter Name: ModeDescription
Heater current monitor: Level 1Heater current value monitor
• The LBA (Loop Break Alarm) function can be used only on standard
type controllers.
• The LBA function can be used only when i t is assigned as an output.
Also, the LBA function does not work when a memory error or A/D
convertererrorresults.
• LBA (Loop Break Alarm) is a function for judging that an error has
occurred somewhere on the control loop and for outputting an alarm
when the process value does not change with the manipulated variable at a maximum or minimum state. Accordingly, the LBA function
can be used as a means for detecting a malfunctioning control loop.
F L BA detection
time
F L BA detection
width
F L BA detection
example
• Normally, when output is set to maximum or minimum, the process
value rises or falls after the dead time has elapsed. LBA is output if
the process value does not change in the predicted direction after a
fixed amount of time has elapsed. This fixed amount of time is the
“LBA detection time.”
• LBA operation sometimes becomes unstable when the process value
fluctuates considerably due to the control characteristics. The LBA
detection width is provided so that changes with respect to output can
be correctly detected. Changes smaller than the detection width due
to LBA detection timing are not regarded as changes.
• The following example describes what happens when a heater burnout occurs at maximum output.
LBA detection time
PV
LBA detection time
Heater burnout
LBA detection width
Output
Time
LBA=ON
4--26
• LBA judgment is carried out at each LBA detection time from the
point of maximum output. In the above figure, the process value (PV)
is changing greatly at the 1st judgment time band, so LBA remains
OFF.
• At the 2nd judgment time band, the process value increases as indicated by the broken line if the process value is normal. This means
that the change width exceeds the LBA detection width, and LBA output remains OFF.
• If the heater burns out at the point shown in the above figure, the
process value “decreases.” Accordingly, it is judged that “the process
value is not changing in the increasing direction” at the 2nd judgment time band and the LBA output becomes ON.
Page 89
4.10 LBA
F Setting the LBA
detection time
F Determining the
LBA detection
time
• The LBA detection time is automatically set by auto-tuning (except in
heating and cooling control).
• If the optimum LBA detection time cannot be obtained by auto-tuning, set the time in the “LBA detection time” parameter (level 2
mode).
• When using transfer output, add on the communications unit
(E53-AKF).
F Transfer ou t pu t
type
F Transfer ou t pu t
scaling
Transfer outputTransfer output
• You can select the following five data items in the “transfer output
type” parameter (option mode) as the transfer outputs:
Present SP (default), Process value, Manipulated variable (heat),
Manipulated variable (cool), Valve opening
However, note that heating/cooling side manipulated variables can be
output only on standard type controllers, and valve opening can be
output on position-proportional type controllers.
• If the output assignment is changed when either the “manipulated
variable (heat)” or “manipulated variable (cool)” parameter is selected, the factory setting “set point” is returned to.
• Thesetransferoutputscanbescaled according to the settings of the
“transfer output upper limit” and “transfer output lower limit” parameters before output. Setting of an upper limit value smaller than
the lower limit value is allowed, so reverse scaling can also be carried
out. Also, the scale can be enlarged by the upper- and lower-limit
width specified for each data item. The following example shows scaling of the heating side manipulated variable.
20
(mA)
Reverse scalingEnlarged scale
(mA)
20
Parameters
4--28
4
Transfer output
upper limit: 0
SymbolParameter Name: ModeDescription
Transfer
output lower
limit: 100
Transfer output type: OptionTransfer output designation
Transfer output upper limit : OptionTransfer output scaling
Transfer output lower limit : OptionTransfer output scaling
Manipulated
variable
(%)
4
0
Transfer
output lower
limit: 10
Transfer
output upper
limit: 80
100
Manipulated
variable (%)
Page 91
CHAPTER5
CHAPTER5
PARAMETERS
This chapter describes the parameters of the E5EK-T.
Use this chapter as a reference guide.
CHAPTER 5 PARAMETERS
ConventionsUsedinthisChapter5-2............
Protect Mode5-3...............................
Manual Mode5-5..............................
Level 0 Mode5-6...............................
Program Mode5-11.............................
Level 1 Mode5-17...............................
Level 2 Mode5-24...............................
Setup Mode5-30................................
Expansion Mode5-38............................
Option Mode5-46...............................
Calibration Mode5-52...........................
5--1
Page 92
CHAPTER5PARAMETERS
Conventions Used in this Chapter
JThe meaning of icons used in this chapter
Describesthefunctionsoftheparameter.
Function
Describes the range and defaults of the parameter setting.
Setting
Used for monitor-dedicated parameters.
Describes the range of the monitor values.
Monitor
Describes a procedure using parameters in operating instructions.
Example
of use
Describes related parameters and items.
See
Describes models of the E5EK-T or optional units that support the parameter being
described.
Model
JAbout parameter display
On the E5EK-T controller, only parameters that can be used are displayed. These parameters are
displayed only when the “Conditions of Use” on the right of the paramete r heading are satisfie d .
However, note that the settings of protected parameters are still valid, and are not displayed
regardless of the conditions of use.
AT Execute/cancel
Conditions of Use
The controller must
be in operation.
JAbout the Order in Which Parameters Described in This Chapter
Parameters are described mode by mode
The first page of each mode lists the parameters available in that mode. The parameter
names in these contents are listed in the order that they are displayed on the controller.
5--2
Page 93
Mod
Protect Mode
• The protect function restricts key use to prevent unwanted key operation. Before
changing parameters in this mode, first make sure that protecting the keys will
not cause any problems in operation.
• To select this mode, press the
RUN/RST
minimum. To exit this mode, press the
again for 1 second minimum.
• The following table shows the parameters supported in this mode and the page
where the parameter is described.
andkeys simultaneously for 1 second
RUN/RST
andkeys simultaneously
Function
Setting
Symbol
Parameter NamePage
Security5-3
Key protect5-4
Security
• This parameter specifies which parameters are protected. Note that the protect
mode and manual mode cannot be pr otected.
• Only the modes indicated by the “F” mark in the table below can be selected on
the menu display. For example, when this parameter is set to “3”, only levels 0 and
1 and the program mode can be selected.
*1 The “PV/Present SP” parameter is only displayed.
Setting value
• When this parameter is set to “0”, the protection function is disabled.
• When this parameter is set to “5”, only the parameters in the level 0 mode can be
used, and the menu display is not selected.
• When this parameter is set to “6”, “PV/Present SP” parameter can only be displayed. (The set point cannot be changed.)
• Default is “1”. (Only the calibration mode is protected.)
F Related description
3.6 Protect Mode (page 3-19)
See
5--3
Page 94
CHAPTER5PARAMETERS
Protect Mode
Key protect
• Disables key operation of the RUN/RESET or AUTO/MANUAL. For example, if
AUTO/MANUAL key operation is disabled (by simultaneously pressing the
Function
andkeys) in the “key protect” parameter (protect mode) during automatic
operation, manual operation is no longer possible.
• The following table shows the relationship between set values and protected keys.
Setting
See
Set value
1No keys are protected.
2AUTO/MANUAL key operation cannot be selected.
3“RUN/RST” key cannot be selected.
4
RUN/RST
Both the AUTO/MANUAL and RUN/RESET key operations
cannot be selected.
• Default is “0” (all keys can be operated).
F Related description
3.6 Protect Mode (page 3-19)
Description
5--4
Page 95
Function
Manual Mode
• In this mode, manual operation is possible, and the “MANU” LED lights.
• When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. To change the manipulated variable,
use the
ing is canceled.
• To select this mode when in the level 0 to 2 modes, press the
simultaneously for 1 second minimum. To exit this mode, press theand
keys simultaneously again for 1 second minimum. The mode changes to the level 0
mode.
• “Manual MV” is the only parameter available in this mode.
Manual MV
• Sets the manipulated variable or the valve opening for manual operation. On a stan-
dard type controller, when you press theorkeys, the manipulated variable
is changed. On a position-proportional type controller, when you press the
the open side becomes ON, and when you press the
ON.
• On standard type controllers, the process value is displayed on the No.1 display
and the manipulated variable is displayed on the No.2 display.
• On position-proportional controllers, the process value is displayed on the No.1
display, and the valve opening is displayed on the No.2 display when the potentiometer is connected.
• On standard type controllers, the manual MV is held when the power is inter-
rupted.
orkeys. If this mode is switched to during auto-tuning, auto-tun-
andkeys
key,
key, the close side becomes
• Standard type
Control MethodSetting Range
Setting
Standard-5.0 to 105.0%0.0
Heating and cooling-105.0 to 105.0%0.0
• Position-proportional type
Control Method
Position-proportional-10.0 to 110.0%
F Related description
3.8 Adjusting Control Operation/Manual operation (page 3-22)
See
UnitDefault
Monitor RangeUnit
5--5
Page 96
CHAPTER5PARAMETERS
Level 0 Mode
• The parameters in this mode can be used only when the “security” parameter
(protect mode) is set to “0” to “5”. Only the “PV/Present SP” parameter can be
used when the “security” parameter is set to “6”.
• The parameters in this mode comprise step operation parameters and parameters
required for monitoring program operating states.
• To select this mode, press the
to the menu display. If you select [
minimum, the controller enters the level 0 mode.
• To select parameters in this mode, press the
tings, use the
• The following table shows the parameters supported in the level 0 mode and the
page where the parameter is described.
key for 1 second minimum. The display changes
]thenpressthekey for 1 second
key. To change parameter set-
orkeys.
Function
SymbolParameter Name
PV/Present SP5-6
Pattern No.5-7
Step No. monitor5-7
Hold5-8
Advance5-8
Standby time monitor5-9
Pattern elapsing time5-9
Pattern execution count monitor5-9
MV monitor (heat)5-10
MV monitor (cool)5-10
Valve opening monitor5-10
Page
PV/Present SP
• The process value is displayed on the No.1 display, and the Present SP is displayed
on the No.2 display.
• The decimal point position is dependent on the selected sensor during tempera-
tures input and on the results of scaling during analog input.
Process Value
Monitor
Present SP
• During temperature input, the range of the currently selected sensor is taken as
the PV monitor range.
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (set u p
mode)
See
“Set point upper limit” “Set point lower limit” (expansion mode)
5--6
Monitor Range
Scaling lower limit -10%FS to scaling upper limit +10%FS
Set point lower limit to set point upper limit
Unit
EU
EU
Page 97
Function
Setting
See
Level 0 Mode
Pattern No.
• This parameter can be set only when the controller is reset.
• Displays the execution pattern during program operation, and the set pattern
after the controller is reset.
• This parameter can also be used in the program mode.
Setting RangeUnitDefault
0to3None0
F Related description
3.5 Setting Patterns (page 3-14)
F Related parameters
All parameters in the program mode
Function
Monitor
See
Step No. monitor
• Monitors the current step No. (This parameter is reset to “0” when the controller
is reset.)
Monitor Range
0 to Number of steps-1None
F Related description
4.4 Program Operation (page 4-13)
F Related parameters
“Hold” “Advance” (level 0 mode)
Unit
5--7
Page 98
CHAPTER5PARAMETERS
Level 0 Mode
Hold
• This parameter can only be used for monitoring when the controller is reset.
• Pauses (holds) or cancels program operation.
Function
• When the event input to which “hold/hold cancel” is assigned is ON, [
displayed, and when OFF [
• In addition to the setting of this parameter, hold is canceled by the following
conditions:
](hold)is
] (hold cancel) is displayed.
Setting
See
Function
Example
of use
Setting Range
OFF : Hold cancel / ON:Hold
Default
F Related description
4.4 Program Operation (page 4-13)
4.8 How to Use Event Input (page 4-21)
F Related parameters
“Event input assignment 1 to 2” (option mode)
Advance
• This parameter can only be used for monitoring when the controller is reset.
• Forcibly advances program operation by one step.
• When the event input to which “hold/hold cancel” is assigned is ON, [
(advance) i s displayed.
• Selecting this parameter, it is set to [
• When [
] (ON) is selected, program operation is advanced by one step.
] (OFF).
• After program execution is completed, the setting automatically returns to [
• Hold is also continued after the program step is advanced when the program is
executed in a hold state.
]
].
F Related description
4.4 Program Operation (page 4-13)
4.8 How to Use Event Input (page 4-21)
See
F Related parameters
“Event input assignment 1 to 2” (option mode)
5--8
Page 99
Level 0 Mode
Function
Monitor
See
Standby time monitor
Conditions of Use
The controller must be in a standby
state.
• Displays the remaining standby time. (This time is not displayed when the con-
troller is reset.)
Monitor Range
0.00 to 99.59Hour, minute
Unit
F Related description
4.7 Setting Running Conditions (page 4-19)
F Related parameter
“Standby time” (level 2 mode)
Pattern elapsin g time
Function
Monitor
Function
Monitor
• Displays the time that has elapsed since the start of the pattern. When a pattern is
repeatedly executed or all patterns are executed, the time counting restarts at the
top of each pattern.
Monitor Range
0.00 to 99.59Program time unit
Unit
When the time exceeds “99.59”, “99.59” blinks on the display.
Pattern execution count monitor
• Displays the number of times that the current pattern has been executed. “0” is
displayed when the controller is reset or when the controller is in a standby state.
Monitor Range
0 to pattern execution countTimes
F Related parameter
“Pattern execution count” (program mode)
Unit
See
5--9
Page 100
CHAPTER5PARAMETERS
Level 0 Mode
Function
Monitor
MV monitor (heat)
Conditions of Use
The control must be standard control or
heating and cooling control.
MV monitor (cool)
• This parameter cannot be set.
• Monitors the manipulated variable on the heating or cooling side.
• The manipulated variable in a standard control system is monitored in the “MV
monitor (heat)” parameter.
• The “MV monitor (cool)” parameter can be used only during heating and cooling
control.
• MV monitor (heat)
Control
Standard-5.0 to 105.0%
Heating and cooling0.0 to 105.0%
Monitor Range
• MV monitor (cool)
Control
Heating and cooling0.0 to 105.0%
Monitor Range
Unit
Unit
Model
Function
Monitor
See
E5EK-TAA2
Valve opening monitor
Conditions of Use
The control must be position-proportional control.
• Monitors the valve opening during position-proportional control.
Monitor Range
-10.0 to +110.0%
Unit
“----” is displayed when a potentiometer is not connected.
F Related description
4.1 Selecting the Control Method/Position-proportional control (page 4-3)
E5EK-TPRR2
Model
5--10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.