This high-function digital controller uses CompoBus/D (DeviceNet) as the communications function on a regular E5EK controller. From here on, the E5EKjjj-DRT controller that supports the CompoBus/D (DeviceNet) communications
function is abbreviated to E5EK-DRT.
• Use the CompoBus/D (DeviceNet) for communications.
• Select from many types of temperature and analog input (multiple input)
• Select output functions such as control output or alarm (output assignment)
• Use the HBA (heater burnout alarm) function.
• UseremoteSPinput.
• Monitor the control loop by LBA (Loop Break Alarm)
• Calibrate input
• It also features a watertight construction (NEMA4: equivalent to IP66)
This User’s Manual describes how to use the E5EK-DRT digital controller.
Before using your E5EK-DRT, thoroughly read and understand this manual in
order to ensure correct use.
PRECAUTIONS IN USING THE PRODUCT
When the product is used under the circumstances or environment below, ensure
adherence to limitations of the ratings and functions. Also, take countermeasures
for safety precautions such as fail-safe installations.
(1) Use under circumstances or environments which are not described in this user’s manual.
(2) Use for nuclear power control, railway, air craft, vehicle, incinerator, medical equipment, enter-
tainment equipment, safety device, etc.
(3) Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
This product has been tested by ODVA’s authorized Independent T est Lab and found to comply with
ODVA Conformance Test Software Version 2.0-1.00.
About this manual
E OMRON, 1997
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or other-
wise, without the prior written permission of OMRON.
(2) No patent liability is assumed with respect to the use of the information contained herein.
(3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability
assumed for damages resulting from the use of the information contained in this publication.
I
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text
explanations. These abbreviations mean the following.
AbbreviationTerm
PVProcess value
SPSet point
RSPRemote set point
LSPLocal set point
LBALoop break alarm
HBHeater b ur nout
ATAuto -tuning
EUEngineering unit *1
*1 _C, m, g and other units are indicated for scaled data. However, “EU” is used as the mini-
mum unit for the data. For example, for “50.02 (m)”, 1EU is taken as the minimum unit
0.01 (m).
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays
and alphabet characters.
ABCDEFGH I JKLM
NOPQRS TUVWXY Z
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explanations and how to apply functions.
II
JHow this Manual is Organized
PurposeTitleDescription
D Learning about the
general features of the
E5EK-DRT
Chapter 1 IntroductionThis chapter describes the fea-
tures of the E5EK-DRT, names
of parts, and typical functions.
D Setting up
D Basic E5EK-DRT
operations
D Applied E5EK-DRT
operations
D CompoBus/D (DeviceNet)
communication
D Calibration
Chapter 2 PreparationsThis chapter describes the
operations that you must carry
out (e.g. installation, wiring and
switch settings) before you can
use the E5EK-DRT.
Chapter 3 Basic Operation
Chapter 5 Parameters
Chapter 4 Applied Operation
Chapter 5 Parameters
Chapter 6 Using the CompoBus/D (DeviceNet)
Chapter 7 CalibrationThis chapter describes how the
These chapters describe how to
use the front panel keys and
how to view the display when
setting the parameters of the
major functions for the E5EKDRT.
These chapters describe the
important functions of the
E5EK-DRT and how to use the
parameters for making full use
of the E5EK-DRT.
This chapter mainly describes
using for the E5EK-DRT on the
CompoBus/D (DeviceNet).
user should calibrate the E5EKDRT.
D Troubleshooting
Chapter 8 TroubleshootingThis chapter describes what to
do if any problems occur.
III
PRECAUTIONS ON SAFETY
F Marks For Ensuring Safe Use and Their Meanings
This manual uses the following marks to indicate precautions for ensuring that the
E5EK-DRT is used safely.
The precautions indicated below describe important information regarding safety.
Be sure to follow the instructions described in these precautions.
WARNING
Indicates information that, if not heeded, could
possibly result in loss of life or serious injury.
CAUTION
Indicates information that, if not heeded, could
result in relatively serious or minor injury, damage to the product, or faulty operation.
F Warning Symbols
WARNING
Do not touch the terminals while the power is ON.
This may cause an electric shock.
CAUTION
D The life expectancy of the output relay varies considerably according to its the output relay
within its rated load and electrical life expectancy, if the output relay is used beyond its life
expectancy, its contacts may become fused or burned.
D Do not allow metal fragments or lead wire scraps to fall inside this product.
This may cause electric shock, fire or malfunction.
D Never disassemble, repair or modify the product.
This may cause electric shock, fire or malfunction.
D Use the product within the rated load.
This may cause damage or burning.
D Use this product within the rated supply voltage.
This may cause damage or burning.
D Tighten the terminal screws properly. Tightening torque:0.78NSm
Loose screws might cause malfunction.
Correctly set the settings on this product matched to the control target.
If the settings are not compatible with the control target, the product might operate in an unex-
pected manner, resulting in damage to the product or an accident.
D To maintain safety in the event of a product malfunction, we recommend taking safety mea-
sures, for example, installing an excessive temperature rise prevention alarm on a separate
line.
If malfunction prevents control, this may result in a major accident.
D Use a screwdriver or similar tool to remove the output unit if it is hard to remove.
If you attempt to remove it by applying excessive force, you may be injured by pointed pins.
IV
NOTICE
Be sure to observe these precautions to ensure safe use.
(1) Do not wire the terminals which are not used.
(2) Be sure to wire properly with correct polarity of terminals.
(3) To reduce induction noise, separate the high-voltage or large-current power lines from other
lines, and avoid parallel or common wiring with the power lines when you are wiring to the
terminals. We recommend to use separating pipes, ducts, or shielded lines.
(4) Do not use this product in the following places:
• P laces subject to dust or corrosive gases (in particular, sulfide gas and ammonia gas)
• Places subject to high humidity, condensation or freezing.
• Places subject to direct sunlight.
• P laces subject vibration and large shocks.
• Places subject to splashing liquid or oil atmosphere.
• Places directly subject to heat radiated from heating equipment.
• Places subject to intense temperature changes.
• Places subject to flammable or explosive gas.
(5) To allow heat to escape, do not block the area around the product. (Ensure enough space for
heat to escape.)
(6) If you remove the controller from its case, never touch nor apply shock to the electronic parts
inside.
(7) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the prod-
uct.
(8) Use specified size (M3.5, width 7.2mm or less) crimped terminals for wiring.
(9) Allow as much space as possible between the controller and devices that generate a powerful
high-frequency (e.g. high-frequency welders, high-frequency sewing machines) or surge.
PRECAUTIONS FOR ENSURING CORRECT USE
F Use a 100 to 240 V AC (50/60 Hz), 24 VAC (50/60 Hz) or 24 VDC power supply matched to the
power specifications of the E5EK-DRT. Also, make sure that rated voltage is attained within two
seconds of turning the power ON.
F Attach a surge suppress or or noise filter to periphe ra l devices that generate noise (in particular,
motors, transformers, solenoids, magnetic coils or other equipment that have an inductance component).
F When mounting a noise filter on the power supply, be sure to first check the filter’s voltage and
current capacity, and then mount the filter as close as possible to the controller.
F Insert a noise filter (TDK ZCB2206-11 or equivalent) on the AC power l ine to satisfy conducted
emission rating (FCC Regulation Class A EN50081-2-compliant).
F Use within the following temperature and humidity ranges:
• Temperature: -10 to 55°C, Humidity: 35 to 85% (with no icing or condensation)
If the E5EK-DRT is installed inside a control board, the ambient temperature must be kept to
under 55°C, including the temperature around the controller.
If the controller is subjecte d to heat radiation, use a fan to cool the surface of the controller to under
55°C.
F Store within the following temperature and humidity ranges:
• Temperature: -25 to 65°C, Humidity: 35 to 85% (with no icing or condensation)
F Never place heavy objects on, or apply pressure to the controller that may cause it to deform and
deteriorate during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installation. These
devices can cause radio disturbances which adversely affect the performance of the controller.
This chapter introduces the E5EK-DRT. First-time users should read this chapter
without fail.
For details on how to use the controller and parameter settings, see Chapters 2
onwards.
1.1Names of parts1-2..........................................
1.2Input and Output1-4.........................................
1.3Parameters and Menus1-6...................................
1.4About the Communications Function for
the CompoBus/D (DeviceNet) Network1-9.....................
This chapter describes each of the parameters required for making full use of the
features of the E5EK-DRT. Read this chapter while referring to the parameter
descriptions in chapter 5.
4.1Selecting the Control Method4-2..............................
This chapter introduces the E5EK-DRT. First-time users should read
this chapter without fail.
For details on how to use the controller and parameter settings, see
Chapters 2 onwards.
CHAPTER 1 INTRODUCTION
1.1Names of parts1-2........................
Main parts1-2............................
Front panel1-2...........................
About the displays1-3.....................
How to use keys1-3.......................
1.2Input and Output1-4......................
Input1-4.................................
Output1-5................................
1.3Parameters and Menus1-6.................
Parameter types1-6.......................
Selecting modes1-7........................
Selecting parameters1-8...................
Fixing settings1-8.........................
1.4About the Communications Function for
the CompoBus/D (DeviceNet) Network1-9...
1.5About Calibration1-10......................
1--1
CHAPTER 1 INTRODUCTION
1.1Names of parts
JMain parts
Terminals
P2-7
JFront panel
Operation indicators
OUT1
SUB1
MANU
STOP
RMT
RST
AT
Mode key
A/M key
A/M
Rear case
OUT2
SUB2
RMT
OUT1 OUT2
A
M
PV
SV
MANU
RSPSUB1
STOP
AT
SUB2
MS NS
E5EK
Front panel
This page
No.1 display
No.2 display
Down ke y
Up ke y
MS/NS indicators
1--2
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Operation
indicators
F MS/NS indicators
Displays the p rocess value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
• OUT1: Lit when the pulse output function assigned to “control
output 1” is ON.
• OUT2: Lit when the pulse output function assigned to “control
out-put 2” is ON.
• SUB1: Lit when the output function assigned to “auxiliary output
1” is ON.
• SUB2: Lit when the output function assigned to “auxiliary
output 2” is ON.
• MANU : Lit in the manual operation mode.
• STOP: Lit when operation has stopped.
• RMT: Lit during remote operation.
• RSP: Lit during remote SP operation.
• AT: Flashes during auto-tuning.
Indicates the CompoBus/D (DeviceNet) status.
For details on indicated statuses, see “Chapter 8, 8.1 Initial Checks.”
(page 8-2).
JHow to use keys
A/M
Fkey
Fkey
Fkey
The following describes basic key operations.
Each press of this key switches between the auto and manual operations.
The functions of this key change according to how long it is pressed. If
the key is pressed for less than one second, the parameters are switched.
If the key is pressed for one second or more, the menu display appears.
In key operations from here on, “press the key” refers to pressing the
key for less than one second.
For details on parameter switching and menu display items, see pages
1-7 and 1-8.
Each press of the
on the No.2 display, while each press of the
returns the values or settings on the No.2 display.
Functions vary, for example, when the
neously with
see page 1-8. Also, chapters 3 and 4 describe examples using vari ous key
combinations.
key increments or advances the values or settings
key decrements or
A/M
key is held down simulta-
key, or a key is held down continuously. For details,
1--3
CHAPTER 1 INTRODUCTION
1.2Input and Output
JInput
Temperature input
Voltage input
Current input
CT input
Remote SP input
Controller
Control output
(heat)
Control output
(cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Error 1
Error 2
Error 3
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
The E5EK-DRT supports following inputs: temperature input, current
input, voltage input, CT input and remote SP input.
F Temperature input/Voltage input/Current input
• Only one of temperature input, voltage input and current input can
be selected and connected to the controller. The above figure shows
temperature input connected to the controller.
• The following input sensors can be connected for temperature input:
• The following currents can be connected for current input:
4to20mA,0to20mA
• The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input
F Remote SP input
• Connect CT input when using the HBA (heater burnout alarm) func-
tion. Note that the HBA function cannot be used simultaneously with
the linear output unit.
• When the remote SP function is enabled, inputs within the range 4 to
20 mA are used as the remote SP.
1--4
JOutput
1.2 Input and Output
The E5EK-DRT supports the following four outputs.
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
When using control outputs 1 and 2, set the output unit (sold separately). Nine output units are available to suit the output circuit configuration.
Note: The output functions of the E5EK-DRT do not operate for five
secondsaftertheE5EK-DRTisturnedON.
F Output
assignments
The E5EK-DRT supports the following ten output functions.
Control output (heat)
Control output (cool)
Alarms 1 to 3
HBA
LBA
Error 1 (input error)
Error 2 (A/D converter error)
Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2,
auxiliary output 1, and auxiliary output 2.
There are restrictions on how assignment destinations (control output
1, control output 2, auxiliary output 1, and auxiliary output 2) can be
used. For details, see 3.3 Setting Output Specifications.
In the example on the previous page, “control output (heat)” is assigned
to “control output 1”, “alarm 1” is assigned to “control output 2”,
“alarm 2” is assigned to “auxiliary output 1”, and “alarm 3” is assigned
to “auxiliary output 2”. Accordingly, the configuration is such that heating control output is connected to control output 1, and alarm output is
connected to control output 2 and auxiliary outputs 1 and 2.
Control outputs 1 and 2 are used depending on the differences in control method as follows.
Control Method
Standard controlControl output (heat)/Alarm, etc.,.
Heating and cooling
control
Control output (heat) /
Control output (cool)
Control Output 1/
Control Output 2
1--5
CHAPTER 1 INTRODUCTION
1.3Parameters and Menus
JParameter types
F Protect mode
F Manual mode
F L evel 0 mode
F L evel 1 mode
F L evel 2 mode
F Setup mode
F Expansion mode
E5EK-DRT parameters are distributed between the following nine
modes.
The settings of parameters in each of seven modes (excluding the protect mode and manual mode) can be checked and modified by selection
on the menu display.
This mode is used to limit use of the keys. The protect function is for
preventing unwanted modification of parameters and switching
between the auto and manual operation.
In this mode, the controller can be switched manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode,
you may change the set point during operation, and stop and start operation. You can also monitor (not change) the process value, ramp SP
and manipulated variable.
This is the main mode for adjusting control. In this mode, you can
execute AT (auto-tuning), and set alarm values, the control period, PID
parameters and heater burnout al arm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can
set the parameters for limiting the manipulated variable, switch
between the remote and local modes, switch between the SP modes, and
set the loop break alarm (LBA), alarm hysteresis and the digital filter
value of inputs.
This is the mode for setting the basic specifications. In this mode, you
can set parameters that must be checked or set before operation such as
the input type, scaling, output assignments and direct/reverse operation.
This is the mode for setting expanded functions. In this mode, you can
set, SP setting limiter, selection of 2 -PID control or ON/OFF control,
specification of the standby sequence resetting method, time for automatic return to the monitoring display.
1--6
Differences from
General-purpose
Models
New function
CompoBus/D
(DeviceNet)
Functions not supported
Serial communications
Position-proportional control
Event input
Multi-SP
Transfer output
Self-tuning (ST)
1.3 Parameters and Menus
F Option mode
F Calibration mode
JSelecting modes
This is the mode for setting option functions. CompoBus/D (DeviceNet)
communications conditions, heater burnout alarm function, and remote
SP scaling parameters are also located in this mode.
This mode is provided so that the user can calibrate inputs.
When calibrating input, the selected input type is calibrated.
The following diagram shows the order in which modes are selected.
Power ON
1 second min.
Level 0 mode
1 second min.
Level 1 mode
1 second min.
Level 2 mode
1 second min.
Setup mode
1 second min.
Expansion mode
1 second min.
Option mode
A/M
1secondmin.
Manual mode
A/M
++
1 second min.1 second min.
Protect mode
A/M
1secondmin.
A/M
A/M
+
1secondmin.
F Menu display
F L evel 0 to 2
modes
F Setup mode
F Expansion mode
F Option mode
F Calibration mode
1 second min.
Calibration mode
• To select the menu display in any of the above modes (excluding the
protect mode and the manual mode), press the
key for 1 second
minimum. The previously specified mode is selected. For example, if
you selected the menu display while in the level 0 mode, the No.2 display change to [
• If you select the destination mode using the
press the
key for 1 second minimum when you have selected the
] as shown on the left.
orkeys and
menu display, the top parameter in the specified mode is selected.
• Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the level 1 mode.
• If you select [
][]or[] in the menu display, the level
0, level 1 and level 2 modes, respectively, are selected.
• These modes are selected with control still continuing.
• If you select [
][][]or[]inthemenudisplay,the
setup, expansion, option and calibration modes, respectively, are
selected. When these modes are selected, the control is reset. So, control outputs and auxiliary output are turned OFF. When another
mode is selected while in these modes, reset is canceled.
1--7
CHAPTER 1 INTRODUCTION
F Protect mode
F Manual mode
JSelecting
parameters
JFixing settings
• To set the controller to the protect mode or to return to the level 0
A/M
mode from the protect mode, press the
cond minimum simultaneously.
• To set the controller to the manual mode, press the
cond minimum in the level 0 to 2 mode. To return to the level 0 mode
from the manual mode, press the
• When not in the manual mode, each press of the
parameter.
• If you press the
turns to the first parameter.
Parameter
1
• If you press thekey when at the final parameter, the display
returns to the first parameter.
• When you have changed a parameter setting, specify the parameter
using the
seconds or press the
• When another mode is selected, the content of the parameters before
the mode was selected is fixed.
• When turning the power OFF, you must first fix the settings and
parameter contents (by pressing the
mode). The settings and parameter contents are sometimes not
changed by merely pressing the
key when at the final parameter, the display re-
Parameter
2
orkeys, and either leave the setting for at least two
key. This fixes the setting.
A/M key for 1 second minimum.
Parameter
orkeys.
key andkey for 1 se-
A/M key for 1 se-
key switches the
Parameter
3
key or selecting another
n
1--8
1.4 About the Communications Function for the CompoBus/D (DeviceNet) Network
1.4About the Communications Function for
the CompoBus/D (DeviceNet) Network
The E5EK-DRT operates as a slave on the CompoBus/D (DeviceNet)
network. Items (parameters, operation instructions and statuses) that
have been assigned as communication data on the E5EK-DRT can be
uploaded and downloaded between masters and slaves.
16 read and write operations can be assigned as communication data,
and can be assigned.
MasterE5EK-DRT
Input area
16
channels
max.
Parameter (read)
Status
Communications read
data assignment
Output area
16
channels
max.
Parameter (write)
Operation instruction
Communications write
data assignment
As the data structure is flexible like this, communications is possible
using numerous parameter configurations, and the number of parameters can be limited to increase processing speed.
For details on the type of communication data and how to assign data,
see Chapter 6 Using CompoBus/D (DeviceNet).
For details on cable connections on the CompoBus/D (DeviceNet) net-
work, see Chapter 2 Preparations, 2.3 Wiring Terminals (page 2-7).
For details on CompoBus/D (DeviceNet) such as the network configuration and related system devices, see the CompoBus/D (DeviceNet)
Operation Manual (catalog No.: W267).
1--9
CHAPTER 1 INTRODUCTION
1.5About Calibration
The E5EK-DRT controller is calibrated before shipment from the factory. So, the user need not calibrate the E5EK-DRT controller during
regular use.
However, if the E5EK-DRT controller must be calibrated by the user,
use the parameters provided for user to calibrate temperature input,
analog input (voltage, current). In this case, note that the results of
calibration will not be assured.
Also, note that calibration data is updated to the latest value each time
the E5EK-DRT controller is calibrated. Calibration data set before shipment from the factory cannot be returned to after calibration by the
user.
F Calibrating
inputs
F Registering
calibration data
The input type selected in the parameter is the item to be calibrated.
The E5EK-DRT is provided with the following four calibration parame-
ters.
• Thermocouple
• Platinum resistance thermometer
• Current input
• Voltage input
Two parameters are provided for thermocouple, platinum resistance
thermometer and voltage input.
When calibrating each item, the calibration data is temporarily registered. This data can be registered as final calibration data only when all
items have been newly calibrated. So, all items must be temporarily
registered when calibrating the E5EK-DRT controller.
When registering data, information regarding whether or not calibration has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring
devices and equipment. For details on handling these measuring devices
and equipment, refer to the respective manuals.
1--10
For details, see chapter 7 Calibration.
CHAPTER2
CHAPTER2
PREPARATIONS
This chapter describes theoperations you should carry out before turning the E5EK-DRT ON.
CHAPTER 2 PREPARATIONS
2.1Setting up2-2.............................
Draw-out2-2..............................
Setting up the output unit2-3..............
2.2Installation2-4............................
Dimensions2-4............................
Panel cutout2-4...........................
Mounting2-5.............................
2.3Wiring Terminals2-7......................
Terminal arrangement2-7.................
Precautions when wiring2-7...............
Wiring2-7................................
2--1
CHAPTER 2 PREPARATIONS
2.1Setting up
• Set up the output units for control outputs 1 and 2 before mounting
the controller.
• When setting up the output units, draw out the internal mechanism
from the housing and insert the output units into the sockets for control outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, p repare a
phillips screwdriver matched to the size of the screw on the lower part
of the front panel.
(1) Press down strongly on the hook on the top of the front panel, and
turn the Phillips screws to the left to loosen the screw on the lower
part of the front panel.
Press down here strongly
2--2
Fixing Screw for
Front Panel
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 N⋅m.
JSetting up the output unit
2.1 Setting up
F Before setup
F Procedure
• Check the type of the output unit you are about to set up.
• For details on types of output unit and main specifications, see page
2-8.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) Remove the power board in the direction of the arrow shown in the
figure. The power board is connected to the control board by a cen-
ter connector. Remove this connector taking care not to bend the
connector pins.
Control board
Power board
(3) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(4) Fasten the output units with the bracket (accessory).
(5) Return the power board to its original position.
2--3
CHAPTER 2 PREPARATIONS
2.2Installation
JDimensions
48
PV
SV
MANU
RMT
OUT1 OUT2
STOP
SUB2RSPSUB1
AT
96
13.5100
Unit (mm)
91
112
A
M
JPanel cutout
Unit (mm)
120 min
MS NS
E5EK
45
+0.6
0
• Thewidthoftherearcaseis44mm.
60 min
• Recommended panel thickness is 1 to 8
mm.
• Maintain the specified vertical and horizontal mounting space between each
controller.
Controllers must not be closely mounted
vertically or horizontally.
2--4
92
+0.8
0
2.2 Installation
JMounting
(1) Insert the E5EK-DRT controller into the mounting hole in the
panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the mounting bracket screws alternately a little at a time
until the ratchet start to slide.
2--5
CHAPTER 2 PREPARATIONS
F Setting up the terminal covers
• Fasten the terminal cover (E53-COV08) to protect terminals.
• E5EK-AA2-DRT-500 controller is provided with terminal covers.
• Fasten the terminal cover as follows by using the snap pins.
E5EK
-AA2
-DRT
E53-COV08
• To remove the terminal cover, pull the edges of the snap pins.
2--6
2.3Wiring Terminals
JTerminal arrangement
2.3 Wiring Terminals
JPrecautions
when wiring
10
SOURCE
OUT1
OUT2
SUB1
SUB2
SOURCE : 100 to 240VAC, 50/60Hz15VA
21 22
9
8
7
6
5
4
3
2
23
1
or
24VAC, 50/60Hz12VA
24VDC,8W
20
19
18
17
16
15
14
13
12
11
CompoBus/D
RSP
CT
TC
Pt
I
V
(DeviceNet)
• Use ducts to separate input leads and power lines in order to protect
the controller and its lines from external noise.
• We recommend using solderless terminals when wiring the controller.
• Tighten the terminal screws using a torque no greater than 0.78 N·m.
Take care not to tighten the terminal screws too tightly.
• Do not connect anything to unused terminals.
• Use the following type of solderless terminals for M3.5 screws.
JWiring
F Power supply
10
21 22
9
8
7
6
5
4
3
2
23
1
20
19
18
17
16
15
14
13
12
11
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indicates the inside of the controller
• Input power to terminal Nos. 9 and 10. Power specifications are as follows:
100 to 240VAC, 50/60Hz, 15VA
or
24VAC, 50/60Hz, 12VA
24VDC, 8W (Terminals 9 and 10 have no polarities.)
• When using an AC power supply, connect the noise filter (TDK
ZCB2206-11 or equivalent) as shown in the figure below.
1
2
4
3
10
9
E5EK-DRT
2--7
CHAPTER 2 PREPARATIONS
F Sensor input
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
F Control output
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
• Connect the sensor input to terminal Nos. 11 to 14 and 23 as follows
according to the input type.
14
13
12
11
23
Thermocouple Platinum
--
+
resistance
thermometer
14
13
12
11
23
Voltage inputCurrent input
14
13
12
11
23
+
V
--
14
13
12
11
23
--
mA
+
• Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal
Nos. 5 and 6 are for control output 2 (OUT2). The following diagrams
show the available output units and their internal equalizing circuits.
86
75
NPN
E53-Q
E53-Q3
+
L
GND
--
86
75
Relay
E53-RE53-SE53-Q4
+
86
mAV
4to20mA/0to20mA
E53-C3
E53-C3D
LL
75
--
86
75
SSRPNP
86
75
0to10VDC/0to5VDC
E53-V34
E53-V35
+v
GND
+
--
+v
86
75
+
L
--
• With E53-VVV output units, about 2VDC is output for one second
afterthepowerisinterrupted.
• The following table shows the specifications for each output unit.
ModelOutput TypeOutput MethodSpecifications
E53-RRelayPulse250 VAC, 5 A
E53-SSSRPulse75 to 250 VAC, 1 A
E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35
F Auxiliary output
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
4to20mA
0to20mA
0to10VDC
0to5VDC
10
21 22
9
8
7
6
5
4
3
2
23
1
20
19
18
17
16
15
14
13
12
11
Pulse
Pulse
Pulse
Linear
Linear
Linear
Linear
NPN : 12 VDC, 40 mA (with short-circuit protection)
NPN : 24 VDC, 20 mA (with short-circuit protection)
PNP : 24 VDC, 20 mA (with short-circuit protection)
• Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal
Nos.1 and 2 are for auxiliary output 2 (SUB2).
• The internal equalizing circuits for the auxiliary outputs are as follows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
• Output specifications are as follows:
SPST-NO, 250VAC, 3A
2--8
2.3 Wiring Terminals
F CT input
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
F Remote SP input
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
• When using the HBA function connect CT input (CT) to terminal
Nos.15 to 17.
17
16
15
CT input
CT
• For details on CT inputs, see Appendix, about current transformer.
• Connect an input (RSP) to be used as the remote SP to terminal
Nos.15 and 16.
• Only 4 to 20 mA inputs can be connected. Connect the input as follows:
+
16
4to20mA
15
--
F Communications
10
9
8
7
6
5
4
3
2
1
About the power
blocks
21 22
23
20
19
18
17
16
15
14
13
12
11
• Connect the solderless terminal of the CompoBus/D (DeviceNet)
5-core cabl e to terminal Nos. 18 to 22. Connect each of the inputs as
follows:
18
Red (V+)
19
White (CAN H)
20
22
21
(shield)
Blue (CAN L)
Black (V -- )
• For details on the meaning of signals and wiring precautions, see the
“CompoBus/D (DeviceNet) Operation Manual (W267).”
The E5EK-DRT has independent power supplies for
each of the terminal blocks shown on the right.
AC
21 22
23
20
19
18
17
16
15
14
13
12
11
10
9
8
7
B
6
5
4
E
3
2
1
FD
2--9
CHAPTER 2 PREPARATIONS
2--10
CHAPTER3
CHAPTER3
BASIC OPERATION
This chapter describes an actual example for understanding the basic
operation of the E5EK-DRT.
CHAPTER 3 BASIC OPERATION
3.1 ConventionUsedinthisChapter3-2........
3.2Setting Input Specifications3-4.............
Input type3-4.............................
Temper ature input3-5.....................
Analog input3-5..........................
3.3Setting Output Specifications3-7...........
Output assignments3-7....................
Direct/reverse operation3-8................
Control period3-8.........................
3.4Setting Alarm Type3-10....................
Alarm type3-10............................
Alarm value3-10...........................
Alarm hysteresis3-11.......................
Closeinalarm/openinalarm3-11............
3.5Protect Mode3-13..........................
Security3-13...............................
A/M key protect3-13........................
3.6Starting and Stopping Operation3-14........
3.7Adjusting Control Operation3-15............
Changing the set point3-15.................
Manual operation3-15......................
Auto-tuning (A.T.)3-17.....................
3--1
CHAPTER 3 BASIC OPERATION
3.1Convention Used in this Chapter
This chapter describes basic E5EK-DRT operations such as how to set
up parameters, start and stop operation, and adjusting control opera-
tion.
For more complex control examples, refer to Chapter 4 Applied Operation and Chapter 5 Parameters.
F Basic Operation
Flow
The following diagram shows the basic operation flow.
Power ON
Setup
Setting input specifications
Setting output specifications
Setting alarm output
Protecting parameters
Operation
Start
Adjustment
Stop
3--2
Power OFF
This chapter describes basic operation according to this flow. Examples
of operation for each of these items are described at the end of the setting examples for the parameter in question. However, you must pro-
ceed to the first parameter of the subsequent item.
For example, to perform “setting output specifications” after complet-
ing “setting input specifications,” proceed to the first parameter of “setting output specifications” from the final parameter of “setting input
specifications.” For details on moving parameters between items, follow
the procedures in “Selecting modes” and “Selecting parameters”
described on pages 1-7 and 1-8.
Loading...
+ 128 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.