Omron E5EK User Manual

Digital Controller
CompoBus/D
(DeviceNet) Type
User's Manual
Cat. No. H099-E1-02
Preface
This high-function digital controller uses CompoBus/D (DeviceNet) as the commu­nications function on a regular E5EK controller. From here on, the E5EK­jjj-DRT controller that supports the CompoBus/D (DeviceNet) communications function is abbreviated to E5EK-DRT.
Use the CompoBus/D (DeviceNet) for communications.
Select from many types of temperature and analog input (multiple input)
Select output functions such as control output or alarm (output assignment)
Use the HBA (heater burnout alarm) function.
UseremoteSPinput.
Monitor the control loop by LBA (Loop Break Alarm)
Calibrate input
It also features a watertight construction (NEMA4: equivalent to IP66)
This User’s Manual describes how to use the E5EK-DRT digital controller. Before using your E5EK-DRT, thoroughly read and understand this manual in order to ensure correct use.
PRECAUTIONS IN USING THE PRODUCT
When the product is used under the circumstances or environment below, ensure adherence to limitations of the ratings and functions. Also, take countermeasures for safety precautions such as fail-safe installations.
(1) Use under circumstances or environments which are not described in this user’s manual.
(2) Use for nuclear power control, railway, air craft, vehicle, incinerator, medical equipment, enter-
tainment equipment, safety device, etc.
(3) Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
This product has been tested by ODVA’s authorized Independent T est Lab and found to comply with ODVA Conformance Test Software Version 2.0-1.00.
About this manual
E OMRON, 1997 (1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or other-
wise, without the prior written permission of OMRON. (2) No patent liability is assumed with respect to the use of the information contained herein. (3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability
assumed for damages resulting from the use of the information contained in this publication.
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following.
Abbreviation Term
PV Process value
SP Set point
RSP Remote set point
LSP Local set point
LBA Loop break alarm
HB Heater b ur nout
AT Auto -tuning
EU Engineering unit *1
*1 _C, m, g and other units are indicated for scaled data. However, “EU” is used as the mini-
mum unit for the data. For example, for “50.02 (m)”, 1EU is taken as the minimum unit
0.01 (m).
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters.
ABCDEFGH I JKLM
NOPQRS TUVWXY Z
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explana­tions and how to apply functions.
II
JHow this Manual is Organized
Purpose Title Description
D Learning about the
general features of the E5EK-DRT
Chapter 1 Introduction This chapter describes the fea-
tures of the E5EK-DRT, names of parts, and typical functions.
D Setting up
D Basic E5EK-DRT
operations
D Applied E5EK-DRT
operations
D CompoBus/D (DeviceNet)
communication
D Calibration
Chapter 2 Preparations This chapter describes the
operations that you must carry out (e.g. installation, wiring and switch settings) before you can use the E5EK-DRT.
Chapter 3 Basic Operation Chapter 5 Parameters
Chapter 4 Applied Opera­tion Chapter 5 Parameters
Chapter 6 Using the Compo­Bus/D (DeviceNet)
Chapter 7 Calibration This chapter describes how the
These chapters describe how to use the front panel keys and how to view the display when setting the parameters of the major functions for the E5EK­DRT.
These chapters describe the important functions of the E5EK-DRT and how to use the parameters for making full use of the E5EK-DRT.
This chapter mainly describes using for the E5EK-DRT on the CompoBus/D (DeviceNet).
user should calibrate the E5EK­DRT.
D Troubleshooting
Chapter 8 Troubleshooting This chapter describes what to
do if any problems occur.
III
PRECAUTIONS ON SAFETY
F Marks For Ensuring Safe Use and Their Meanings
This manual uses the following marks to indicate precautions for ensuring that the E5EK-DRT is used safely. The precautions indicated below describe important information regarding safety. Be sure to follow the instructions described in these precautions.
WARNING
Indicates information that, if not heeded, could possibly result in loss of life or serious injury.
CAUTION
Indicates information that, if not heeded, could result in relatively serious or minor injury, dam­age to the product, or faulty operation.
F Warning Symbols
WARNING
Do not touch the terminals while the power is ON. This may cause an electric shock.
CAUTION
D The life expectancy of the output relay varies considerably according to its the output relay
within its rated load and electrical life expectancy, if the output relay is used beyond its life expectancy, its contacts may become fused or burned.
D Do not allow metal fragments or lead wire scraps to fall inside this product.
This may cause electric shock, fire or malfunction.
D Never disassemble, repair or modify the product.
This may cause electric shock, fire or malfunction.
D Use the product within the rated load.
This may cause damage or burning.
D Use this product within the rated supply voltage.
This may cause damage or burning.
D Tighten the terminal screws properly. Tightening torque:0.78NSm
Loose screws might cause malfunction. Correctly set the settings on this product matched to the control target. If the settings are not compatible with the control target, the product might operate in an unex-
pected manner, resulting in damage to the product or an accident. D To maintain safety in the event of a product malfunction, we recommend taking safety mea-
sures, for example, installing an excessive temperature rise prevention alarm on a separate
line.
If malfunction prevents control, this may result in a major accident. D Use a screwdriver or similar tool to remove the output unit if it is hard to remove.
If you attempt to remove it by applying excessive force, you may be injured by pointed pins.
IV
NOTICE
Be sure to observe these precautions to ensure safe use.
(1) Do not wire the terminals which are not used. (2) Be sure to wire properly with correct polarity of terminals. (3) To reduce induction noise, separate the high-voltage or large-current power lines from other
lines, and avoid parallel or common wiring with the power lines when you are wiring to the terminals. We recommend to use separating pipes, ducts, or shielded lines.
(4) Do not use this product in the following places:
P laces subject to dust or corrosive gases (in particular, sulfide gas and ammonia gas)
Places subject to high humidity, condensation or freezing.
Places subject to direct sunlight.
P laces subject vibration and large shocks.
Places subject to splashing liquid or oil atmosphere.
Places directly subject to heat radiated from heating equipment.
Places subject to intense temperature changes.
Places subject to flammable or explosive gas.
(5) To allow heat to escape, do not block the area around the product. (Ensure enough space for
heat to escape.)
(6) If you remove the controller from its case, never touch nor apply shock to the electronic parts
inside.
(7) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the prod-
uct. (8) Use specified size (M3.5, width 7.2mm or less) crimped terminals for wiring. (9) Allow as much space as possible between the controller and devices that generate a powerful
high-frequency (e.g. high-frequency welders, high-frequency sewing machines) or surge.
PRECAUTIONS FOR ENSURING CORRECT USE
F Use a 100 to 240 V AC (50/60 Hz), 24 VAC (50/60 Hz) or 24 VDC power supply matched to the
power specifications of the E5EK-DRT. Also, make sure that rated voltage is attained within two seconds of turning the power ON.
F Attach a surge suppress or or noise filter to periphe ra l devices that generate noise (in particular,
motors, transformers, solenoids, magnetic coils or other equipment that have an inductance compo­nent).
F When mounting a noise filter on the power supply, be sure to first check the filter’s voltage and
current capacity, and then mount the filter as close as possible to the controller.
F Insert a noise filter (TDK ZCB2206-11 or equivalent) on the AC power l ine to satisfy conducted
emission rating (FCC Regulation Class A EN50081-2-compliant).
F Use within the following temperature and humidity ranges:
Temperature: -10 to 55°C, Humidity: 35 to 85% (with no icing or condensation) If the E5EK-DRT is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the controller. If the controller is subjecte d to heat radiation, use a fan to cool the surface of the controller to under 55°C.
F Store within the following temperature and humidity ranges:
Temperature: -25 to 65°C, Humidity: 35 to 85% (with no icing or condensation)
F Never place heavy objects on, or apply pressure to the controller that may cause it to deform and
deteriorate during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installation. These
devices can cause radio disturbances which adversely affect the performance of the controller.
V
Table of Contents
Preface I......................................
Conventions Used in This Manual II...............
Precautions on Safety IV.........................
CHAPTER 1 INTRODUCTION 1-1...........................
This chapter introduces the E5EK-DRT. First-time users should read this chapter without fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
1.1 Names of parts 1-2..........................................
1.2 Input and Output 1-4.........................................
1.3 Parameters and Menus 1-6...................................
1.4 About the Communications Function for
the CompoBus/D (DeviceNet) Network 1-9.....................
1.5 About Calibration 1-10........................................
CHAPTER 2 PREPARATIONS 2-1...........................
This chapter describes the operations you should carry out before turning the E5EK-DRT ON.
2.1 Setting up 2-2...............................................
2.2 Installation 2-4..............................................
2.3 Wiring Terminals 2-7.........................................
CHAPTER 3 BASIC OPERATION 3-1........................
This chapter describes an actual example for understanding the basic operation of the E5EK-DRT.
3.1 Convention Used in this Chapter 3-2...........................
3.2 Setting Input Specifications 3-4...............................
3.3 Setting Output Specifications 3-7..............................
3.4 Setting Alarm Type 3-10.......................................
3.5 Protect Mode 3-13............................................
3.6 Starting and Stopping Operation 3-14...........................
3.7 Adjusting Control Operation 3-15...............................
CHAPTER 4 APPLIED OPERATION 4-1......................
This chapter describes each of the parameters required for making full use of the features of the E5EK-DRT. Read this chapter while referring to the parameter descriptions in chapter 5.
4.1 Selecting the Control Method 4-2..............................
4.2 Operating Condition Restrictions 4-4...........................
4.3 How to Use the Remote SP 4-7...............................
4.4 How to Use the Heater Burnout Alarm 4-9......................
4.5 LBA 4-11....................................................
CHAPTER 5 PARAMETERS 5-1.............................
This chapter describes the parameters of the E5EK-DRT. Use this chapter as a reference guide.
Conventions Used in this Chapter 5-2..............................
Protect Mode 5-3................................................
Manual Mode 5-5................................................
Level 0 Mode 5-6................................................
Level 1 Mode 5-10................................................
Level 2 Mode 5-17................................................
Setup Mode 5-24.................................................
Expansion M ode 5-31.............................................
Option Mode 5-36.................................................
Calibration Mode 5-42.............................................
CHAPTER 6 USING CompoBus/D (DEVICENET) 6-1..........
This chapter mainly describes communications with the CompoBus/D (DeviceNet).
6.1 Outline of CompoBus/D (DeviceNet) 6-2.......................
6.2 Data Refreshing by Communications 6-4.......................
6.3 Setting the Communications Conditions 6-6....................
6.4 Data Assignments 6-8.......................................
6.5 Data Structure 6-10...........................................
6.6 Data Timing 6-13.............................................
6.7 Sample Ladder 6-14..........................................
CHAPTER 7 CALIBRATION 7-1.............................
This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated.
7.1 Structure of Parameters 7-2..................................
7.2 Calibrating Thermocouple 7-4.................................
7.3 Calibrating Platinum Resistance Thermometers 7-7.............
7.4 Calibrating Current Input 7-9..................................
7.5 Calibrating Voltage Input 7-10..................................
7.6 Checking Indication Accuracy 7-12.............................
CHAPTER 8 TROUBLESHOOTING 8-1......................
This chapter describes how to find out and remedy the cause if the E5EK-DRT does not function properly.
8.1 Initial Checks 8-2............................................
8.2 How to Use the Error Display 8-3..............................
8.3 How to Use Error Output 8-5..................................
8.4 Checking Operation Restrictions 8-6...........................
APPENDIX
SPECIFICATIONS A-2........................
ABOUT CURRENT TRANSFORMER (CT) A-5...
CONTROL BLOCK DIAGRAM A-6..............
SETTING AND MONITORING
PARAMETER LIST A-7........................
PARAMETER OPERATIONS LIST A-10..........
USING THE E5EK-DRT IN MULTI-VENDOR
APPLICATIONS A-12..........................
INDEX REVISION HISTORY
CHAPTER1
CHAPTER 1
INTRODUCTION
This chapter introduces the E5EK-DRT. First-time users should read this chapter without fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
CHAPTER 1 INTRODUCTION
1.1 Names of parts 1-2........................
Main parts 1-2............................
Front panel 1-2...........................
About the displays 1-3.....................
How to use keys 1-3.......................
1.2 Input and Output 1-4......................
Input 1-4.................................
Output 1-5................................
1.3 Parameters and Menus 1-6.................
Parameter types 1-6.......................
Selecting modes 1-7........................
Selecting parameters 1-8...................
Fixing settings 1-8.........................
1.4 About the Communications Function for the CompoBus/D (DeviceNet) Network 1-9...
1.5 About Calibration 1-10......................
1--1
CHAPTER 1 INTRODUCTION
1.1 Names of parts
JMain parts
Terminals
P2-7
JFront panel
Operation indicators
OUT1 SUB1 MANU STOP RMT RST AT
Mode key
A/M key
A/M
Rear case
OUT2 SUB2
RMT
OUT1 OUT2
A
M
PV
SV
MANU
RSP SUB1
STOP
AT
SUB2
MS NS
E5EK
Front panel
This page
No.1 display
No.2 display
Down ke y
Up ke y
MS/NS indicators
1--2
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Operation
indicators
F MS/NS indicators
Displays the p rocess value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
OUT1 : Lit when the pulse output function assigned to “control output 1” is ON.
OUT2 : Lit when the pulse output function assigned to “control
out- put 2” is ON.
SUB1 : Lit when the output function assigned to “auxiliary output 1” is ON.
SUB2 : Lit when the output function assigned to “auxiliary output 2” is ON.
MANU : Lit in the manual operation mode.
STOP : Lit when operation has stopped.
RMT : Lit during remote operation.
RSP : Lit during remote SP operation.
AT : Flashes during auto-tuning.
Indicates the CompoBus/D (DeviceNet) status.
For details on indicated statuses, see “Chapter 8, 8.1 Initial Checks.” (page 8-2).
JHow to use keys
A/M
F key
F key
F key
The following describes basic key operations.
Each press of this key switches between the auto and manual opera­tions.
The functions of this key change according to how long it is pressed. If
the key is pressed for less than one second, the parameters are switched. If the key is pressed for one second or more, the menu display appears. In key operations from here on, press the key” refers to pressing the
key for less than one second. For details on parameter switching and menu display items, see pages 1-7 and 1-8.
Each press of the on the No.2 display, while each press of the
returns the values or settings on the No.2 display.
Functions vary, for example, when the neously with
see page 1-8. Also, chapters 3 and 4 describe examples using vari ous key combinations.
key increments or advances the values or settings
key decrements or
A/M
key is held down simulta-
key, or a key is held down continuously. For details,
1--3
CHAPTER 1 INTRODUCTION
1.2 Input and Output
JInput
Temperature input Voltage input Current input
CT input
Remote SP input
Controller
Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Error 1
Error 2
Error 3
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
The E5EK-DRT supports following inputs: temperature input, current input, voltage input, CT input and remote SP input.
F Temperature input/Voltage input/Current input
Only one of temperature input, voltage input and current input can
be selected and connected to the controller. The above figure shows temperature input connected to the controller.
The following input sensors can be connected for temperature input:
Thermocouple:K,J,T,E,L,U,N,R,S,B,W,PLII Platinum resistance thermometer: JPt100, Pt100
The following currents can be connected for current input:
4to20mA,0to20mA
The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input
F Remote SP input
Connect CT input when using the HBA (heater burnout alarm) func-
tion. Note that the HBA function cannot be used simultaneously with the linear output unit.
When the remote SP function is enabled, inputs within the range 4 to
20 mA are used as the remote SP.
1--4
JOutput
1.2 Input and Output
The E5EK-DRT supports the following four outputs.
Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2
When using control outputs 1 and 2, set the output unit (sold sepa­rately). Nine output units are available to suit the output circuit config­uration.
Note: The output functions of the E5EK-DRT do not operate for five
secondsaftertheE5EK-DRTisturnedON.
F Output
assignments
The E5EK-DRT supports the following ten output functions.
Control output (heat) Control output (cool) Alarms 1 to 3 HBA LBA Error 1 (input error) Error 2 (A/D converter error) Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2, auxiliary output 1, and auxiliary output 2.
There are restrictions on how assignment destinations (control output 1, control output 2, auxiliary output 1, and auxiliary output 2) can be used. For details, see 3.3 Setting Output Specifications.
In the example on the previous page, “control output (heat)” is assigned to “control output 1”, “alarm 1” is assigned to “control output 2”,
“alarm 2” is assigned to “auxiliary output 1”, and “alarm 3” is assigned to “auxiliary output 2”. Accordingly, the configuration is such that heat­ing control output is connected to control output 1, and alarm output is connected to control output 2 and auxiliary outputs 1 and 2.
Control outputs 1 and 2 are used depending on the differences in con­trol method as follows.
Control Method
Standard control Control output (heat)/Alarm, etc.,.
Heating and cooling control
Control output (heat) / Control output (cool)
Control Output 1/
Control Output 2
1--5
CHAPTER 1 INTRODUCTION
1.3 Parameters and Menus
JParameter types
F Protect mode
F Manual mode
F L evel 0 mode
F L evel 1 mode
F L evel 2 mode
F Setup mode
F Expansion mode
E5EK-DRT parameters are distributed between the following nine modes.
Protect mode Manual mode Level 0 mode Level 1 mode Level 2 mode Setup mode Expansion mode Option mode Calibration mode
The settings of parameters in each of seven modes (excluding the pro­tect mode and manual mode) can be checked and modified by selection on the menu display.
This mode is used to limit use of the keys. The protect function is for preventing unwanted modification of parameters and switching between the auto and manual operation.
In this mode, the controller can be switched manual operation. The manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you may change the set point during operation, and stop and start op­eration. You can also monitor (not change) the process value, ramp SP and manipulated variable.
This is the main mode for adjusting control. In this mode, you can execute AT (auto-tuning), and set alarm values, the control period, PID parameters and heater burnout al arm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can set the parameters for limiting the manipulated variable, switch between the remote and local modes, switch between the SP modes, and set the loop break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse opera­tion.
This is the mode for setting expanded functions. In this mode, you can set, SP setting limiter, selection of 2 -PID control or ON/OFF control, specification of the standby sequence resetting method, time for auto­matic return to the monitoring display.
1--6
Differences from General-purpose Models
New function
CompoBus/D
(DeviceNet)
Functions not supported
Serial communications Position-proportional control Event input Multi-SP Transfer output Self-tuning (ST)
1.3 Parameters and Menus
F Option mode
F Calibration mode
JSelecting modes
This is the mode for setting option functions. CompoBus/D (DeviceNet) communications conditions, heater burnout alarm function, and remote SP scaling parameters are also located in this mode.
This mode is provided so that the user can calibrate inputs. When calibrating input, the selected input type is calibrated.
The following diagram shows the order in which modes are selected.
Power ON
1 second min.
Level 0 mode
1 second min.
Level 1 mode
1 second min.
Level 2 mode
1 second min.
Setup mode
1 second min.
Expansion mode
1 second min.
Option mode
A/M
1secondmin.
Manual mode
A/M
++
1 second min. 1 second min.
Protect mode
A/M
1secondmin.
A/M
A/M
+
1secondmin.
F Menu display
F L evel 0 to 2
modes
F Setup mode F Expansion mode F Option mode F Calibration mode
1 second min.
Calibration mode
To select the menu display in any of the above modes (excluding the
protect mode and the manual mode), press the
key for 1 second minimum. The previously specified mode is selected. For example, if you selected the menu display while in the level 0 mode, the No.2 dis­play change to [
If you select the destination mode using the press the
key for 1 second minimum when you have selected the
] as shown on the left.
or keys and
menu display, the top parameter in the specified mode is selected.
Protected modes cannot be selected. Also, the menu display does not appear when modes are protected up to the level 1 mode.
If you select [
][ ]or[ ] in the menu display, the level
0, level 1 and level 2 modes, respectively, are selected.
These modes are selected with control still continuing.
If you select [
][ ][ ]or[ ]inthemenudisplay,the setup, expansion, option and calibration modes, respectively, are selected. When these modes are selected, the control is reset. So, con­trol outputs and auxiliary output are turned OFF. When another mode is selected while in these modes, reset is canceled.
1--7
CHAPTER 1 INTRODUCTION
F Protect mode
F Manual mode
JSelecting
parameters
JFixing settings
To set the controller to the protect mode or to return to the level 0
A/M
mode from the protect mode, press the cond minimum simultaneously.
To set the controller to the manual mode, press the cond minimum in the level 0 to 2 mode. To return to the level 0 mode from the manual mode, press the
When not in the manual mode, each press of the parameter.
If you press the turns to the first parameter.
Parameter
1
If you press the key when at the final parameter, the display returns to the first parameter.
When you have changed a parameter setting, specify the parameter using the seconds or press the
When another mode is selected, the content of the parameters before the mode was selected is fixed.
When turning the power OFF, you must first fix the settings and parameter contents (by pressing the mode). The settings and parameter contents are sometimes not changed by merely pressing the
key when at the final parameter, the display re-
Parameter
2
or keys, and either leave the setting for at least two
key. This fixes the setting.
A/M key for 1 second minimum.
Parameter
or keys.
key and key for 1 se-
A/M key for 1 se-
key switches the
Parameter
3
key or selecting another
n
1--8
1.4 About the Communications Function for the CompoBus/D (DeviceNet) Network
1.4 About the Communications Function for the CompoBus/D (DeviceNet) Network
The E5EK-DRT operates as a slave on the CompoBus/D (DeviceNet) network. Items (parameters, operation instructions and statuses) that have been assigned as communication data on the E5EK-DRT can be
uploaded and downloaded between masters and slaves. 16 read and write operations can be assigned as communication data, and can be assigned.
Master E5EK-DRT
Input area
16
channels
max.
Parameter (read)
Status
Communica­tions read data assign­ment
Output area
16
channels
max.
Parameter (write)
Operation instruction
Communica­tions write data assign­ment
As the data structure is flexible like this, communications is possible using numerous parameter configurations, and the number of parame­ters can be limited to increase processing speed.
For details on the type of communication data and how to assign data, see Chapter 6 Using CompoBus/D (DeviceNet).
For details on cable connections on the CompoBus/D (DeviceNet) net-
work, see Chapter 2 Preparations, 2.3 Wiring Terminals (page 2-7).
For details on CompoBus/D (DeviceNet) such as the network configura­tion and related system devices, see the CompoBus/D (DeviceNet)
Operation Manual (catalog No.: W267).
1--9
CHAPTER 1 INTRODUCTION
1.5 About Calibration
The E5EK-DRT controller is calibrated before shipment from the fac­tory. So, the user need not calibrate the E5EK-DRT controller during regular use.
However, if the E5EK-DRT controller must be calibrated by the user,
use the parameters provided for user to calibrate temperature input, analog input (voltage, current). In this case, note that the results of calibration will not be assured. Also, note that calibration data is updated to the latest value each time
the E5EK-DRT controller is calibrated. Calibration data set before ship­ment from the factory cannot be returned to after calibration by the user.
F Calibrating
inputs
F Registering
calibration data
The input type selected in the parameter is the item to be calibrated. The E5EK-DRT is provided with the following four calibration parame-
ters.
Thermocouple
Platinum resistance thermometer
Current input
Voltage input
Two parameters are provided for thermocouple, platinum resistance thermometer and voltage input.
When calibrating each item, the calibration data is temporarily regis­tered. This data can be registered as final calibration data only when all items have been newly calibrated. So, all items must be temporarily
registered when calibrating the E5EK-DRT controller. When registering data, information regarding whether or not calibra­tion has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring devices and equipment. For details on handling these measuring devices
and equipment, refer to the respective manuals.
1--10
For details, see chapter 7 Calibration.
CHAPTER2
CHAPTER 2
PREPARATIONS
This chapter describes theoperations you should carry out before turn­ing the E5EK-DRT ON.
CHAPTER 2 PREPARATIONS
2.1 Setting up 2-2.............................
Draw-out 2-2..............................
Setting up the output unit 2-3..............
2.2 Installation 2-4............................
Dimensions 2-4............................
Panel cutout 2-4...........................
Mounting 2-5.............................
2.3 Wiring Terminals 2-7......................
Terminal arrangement 2-7.................
Precautions when wiring 2-7...............
Wiring 2-7................................
2--1
CHAPTER 2 PREPARATIONS
2.1 Setting up
Set up the output units for control outputs 1 and 2 before mounting the controller.
When setting up the output units, draw out the internal mechanism from the housing and insert the output units into the sockets for con­trol outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, p repare a phillips screwdriver matched to the size of the screw on the lower part of the front panel.
(1) Press down strongly on the hook on the top of the front panel, and
turn the Phillips screws to the left to loosen the screw on the lower part of the front panel.
Press down here strongly
2--2
Fixing Screw for Front Panel
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 Nm.
JSetting up the output unit
2.1 Setting up
F Before setup
F Procedure
Check the type of the output unit you are about to set up.
For details on types of output unit and main specifications, see page
2-8.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) Remove the power board in the direction of the arrow shown in the
figure. The power board is connected to the control board by a cen-
ter connector. Remove this connector taking care not to bend the connector pins.
Control board
Power board
(3) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(4) Fasten the output units with the bracket (accessory).
(5) Return the power board to its original position.
2--3
CHAPTER 2 PREPARATIONS
2.2 Installation
JDimensions
48
PV
SV
MANU
RMT
OUT1 OUT2
STOP
SUB2RSP SUB1
AT
96
13.5 100
Unit (mm)
91
112
A
M
JPanel cutout
Unit (mm)
120 min
MS NS
E5EK
45
+0.6
0
Thewidthoftherearcaseis44mm.
60 min
Recommended panel thickness is 1 to 8 mm.
Maintain the specified vertical and hori­zontal mounting space between each controller.
Controllers must not be closely mounted vertically or horizontally.
2--4
92
+0.8
0
2.2 Installation
JMounting
(1) Insert the E5EK-DRT controller into the mounting hole in the
panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the mounting bracket screws alternately a little at a time
until the ratchet start to slide.
2--5
CHAPTER 2 PREPARATIONS
F Setting up the terminal covers
Fasten the terminal cover (E53-COV08) to protect terminals.
E5EK-AA2-DRT-500 controller is provided with terminal covers.
Fasten the terminal cover as follows by using the snap pins.
E5EK
-AA2
-DRT
E53-COV08
To remove the terminal cover, pull the edges of the snap pins.
2--6
2.3 Wiring Terminals
JTerminal arrangement
2.3 Wiring Terminals
JPrecautions
when wiring
10
SOURCE
OUT1
OUT2
SUB1
SUB2
SOURCE : 100 to 240VAC, 50/60Hz 15VA
21 22
9
8
7
6
5
4
3
2
23
1
or 24VAC, 50/60Hz 12VA 24VDC, 8W
20
19
18
17
16
15
14
13
12
11
CompoBus/D
RSP
CT
TC
Pt
I
V
(DeviceNet)
Use ducts to separate input leads and power lines in order to protect the controller and its lines from external noise.
We recommend using solderless terminals when wiring the controller.
Tighten the terminal screws using a torque no greater than 0.78 N·m.
Take care not to tighten the terminal screws too tightly.
Do not connect anything to unused terminals.
Use the following type of solderless terminals for M3.5 screws.
JWiring
F Power supply
10
21 22
9
8 7 6 5
4 3 2
23
1
20 19
18 17 16 15
14 13 12
11
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indi­cates the inside of the controller
Input power to terminal Nos. 9 and 10. Power specifications are as fol­lows:
100 to 240VAC, 50/60Hz, 15VA or 24VAC, 50/60Hz, 12VA 24VDC, 8W (Terminals 9 and 10 have no polarities.)
When using an AC power supply, connect the noise filter (TDK ZCB2206-11 or equivalent) as shown in the figure below.
1
2
4
3
10
9
E5EK-DRT
2--7
CHAPTER 2 PREPARATIONS
F Sensor input
10
9 8
7 6 5 4 3
2 1
21 22
23
20 19
18 17 16 15
14 13 12 11
F Control output
10
9
8
7 6 5
4 3
2 1
21 22
23
20 19
18
17 16 15 14 13
12 11
Connect the sensor input to terminal Nos. 11 to 14 and 23 as follows according to the input type.
14
13
12
11
23
Thermocouple Platinum
--
+
resistance
thermometer
14
13
12
11
23
Voltage input Current input
14
13
12
11
23
+
V
--
14
13
12
11
23
--
mA
+
Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos. 5 and 6 are for control output 2 (OUT2). The following diagrams show the available output units and their internal equalizing circuits.
86
75
NPN
E53-Q E53-Q3
+
L
GND
--
86
75
Relay
E53-R E53-S E53-Q4
+
86
mA V
4to20mA/0to20mA
E53-C3 E53-C3D
LL
75
--
86
75
SSR PNP
86
75
0to10VDC/0to5VDC
E53-V34 E53-V35
+v
GND
+
--
+v
86
75
+
L
--
With E53-VVV output units, about 2VDC is output for one second afterthepowerisinterrupted.
The following table shows the specifications for each output unit.
Model Output Type Output Method Specifications
E53-R Relay Pulse 250 VAC, 5 A
E53-S SSR Pulse 75 to 250 VAC, 1 A
E53-Q E53-Q3 E53-Q4
E53-C3 E53-C3D
E53-V34 E53-V35
F Auxiliary output
Voltage (NPN) Voltage (NPN) Voltage (PNP)
4to20mA 0to20mA
0to10VDC 0to5VDC
10
21 22
9 8 7 6 5
4 3 2
23
1
20 19 18 17 16 15
14 13 12 11
Pulse Pulse Pulse
Linear Linear
Linear Linear
NPN : 12 VDC, 40 mA (with short-circuit protection) NPN : 24 VDC, 20 mA (with short-circuit protection) PNP : 24 VDC, 20 mA (with short-circuit protection)
4 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600
0 to 10 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600 0 to 5 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600
Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal Nos.1 and 2 are for auxiliary output 2 (SUB2).
The internal equalizing circuits for the auxiliary outputs are as fol­lows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
Output specifications are as follows:
SPST-NO, 250VAC, 3A
2--8
2.3 Wiring Terminals
F CT input
10
9 8 7 6 5 4
3 2
1
21 22
23
20 19 18
17 16 15
14
13 12
11
F Remote SP input
21 22
23
20 19
18 17
16 15
14 13 12 11
10
9 8
7 6 5 4 3 2 1
When using the HBA function connect CT input (CT) to terminal Nos.15 to 17.
17
16
15
CT input
CT
For details on CT inputs, see Appendix, about current transformer.
Connect an input (RSP) to be used as the remote SP to terminal
Nos.15 and 16.
Only 4 to 20 mA inputs can be connected. Connect the input as fol­lows:
+
16
4to20mA
15
--
F Communications
10
9
8 7 6 5 4 3 2 1
About the power blocks
21 22
23
20 19
18
17 16 15 14 13 12 11
Connect the solderless terminal of the CompoBus/D (DeviceNet) 5-core cabl e to terminal Nos. 18 to 22. Connect each of the inputs as follows:
18
Red (V+)
19
White (CAN H)
20
22
21
(shield)
Blue (CAN L)
Black (V -- )
For details on the meaning of signals and wiring precautions, see the “CompoBus/D (DeviceNet) Operation Manual (W267).”
The E5EK-DRT has independent power supplies for each of the terminal blocks shown on the right.
AC
21 22
23
20 19
18 17 16 15 14 13 12 11
10
9 8
7
B
6 5 4
E
3 2 1
FD
2--9
CHAPTER 2 PREPARATIONS
2--10
CHAPTER3
CHAPTER 3
BASIC OPERATION
This chapter describes an actual example for understanding the basic operation of the E5EK-DRT.
CHAPTER 3 BASIC OPERATION
3.1 ConventionUsedinthisChapter 3-2........
3.2 Setting Input Specifications 3-4.............
Input type 3-4.............................
Temper ature input 3-5.....................
Analog input 3-5..........................
3.3 Setting Output Specifications 3-7...........
Output assignments 3-7....................
Direct/reverse operation 3-8................
Control period 3-8.........................
3.4 Setting Alarm Type 3-10....................
Alarm type 3-10............................
Alarm value 3-10...........................
Alarm hysteresis 3-11.......................
Closeinalarm/openinalarm 3-11............
3.5 Protect Mode 3-13..........................
Security 3-13...............................
A/M key protect 3-13........................
3.6 Starting and Stopping Operation 3-14........
3.7 Adjusting Control Operation 3-15............
Changing the set point 3-15.................
Manual operation 3-15......................
Auto-tuning (A.T.) 3-17.....................
3--1
CHAPTER 3 BASIC OPERATION
3.1 Convention Used in this Chapter
This chapter describes basic E5EK-DRT operations such as how to set up parameters, start and stop operation, and adjusting control opera-
tion.
For more complex control examples, refer to Chapter 4 Applied Opera­tion and Chapter 5 Parameters.
F Basic Operation
Flow
The following diagram shows the basic operation flow.
Power ON
Setup
Setting input specifications
Setting output specifications
Setting alarm output
Protecting parameters
Operation
Start
Adjustment
Stop
3--2
Power OFF
This chapter describes basic operation according to this flow. Examples of operation for each of these items are described at the end of the set­ting examples for the parameter in question. However, you must pro-
ceed to the first parameter of the subsequent item.
For example, to perform “setting output specifications” after complet-
ing “setting input specifications,” proceed to the first parameter of “set­ting output specifications” from the final parameter of “setting input specifications.” For details on moving parameters between items, follow
the procedures in “Selecting modes” and “Selecting parameters” described on pages 1-7 and 1-8.
Loading...
+ 128 hidden pages