Omron E5EK User Manual

Digital Controller
(Programmable Type)
User's Manual
Cat. No. H085-E1-03
Preface
Select from many types of temperature and analog input (multiple input)
Support position-proportional control (position-proportional type controllers
only).
Select output functions such as control output or alarm (output assignment)
Use the HBA (heater burnout alarm) function (standard type controllers only).
Use four setpoints (multi-SP function)
UseremoteSPinput.
Monitor the control loop by LBA (Loop Break Alarm)
Use the communications function
Calibrate input or transfer output
It also features a watertight construction (NEMA4: equivalent to IP66)
This User’s Manual describes how to use the E5EK compact, high-function digital controller. Before using your E5EK, thoroughly read and understand this manual in order to ensure correct use.
About this manual
E OMRON, 1996 (1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or other-
wise, without the prior written permission of OMRON. (2) No patent liability is assumed with respect to the use of the information contained herein. (3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability
assumed for damages resulting from the use of the information contained in this publication.
I
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following.
Abbreviation Term
PV Process value
SP Set point
RSP Remote set point
LSP Local set point
LBA Loop break alarm
HB Heater burnout
AT Auto -tuning
ST Self-tuning
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters.
ABCDEFGH I JKLM
NOPQRSTUVWXYZ
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explana­tions and how to apply functions.
II
JNotice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Al­ways heed the information provided with them. Failure to heed precautions can result in inju­ry to people or damage to the product.
DANGER
WARNING
Caution
Indicates information that, if not heeded, is likely to result in loss of life or serious injury.
Indicates information that, if not heeded, could possibly result in loss of life or serious injury.
Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
III
JHow this Manual is Organized
Purpose Title Description
D Learning about the gen-
eral features of the E5EK
Chapter 1 Introduction This chapter describes the fea-
tures of the E5EK, names of parts, and typical functions.
D Setting up the E5EK
D Basic E5EK operations
D Applied E5EK operations
D Using a Position-propor-
tional Type Controller
D Communications with a
host computer
Chapter 2 Preparations This chapter describes the
operations that you must carry out (e.g. installation, wiring and switch settings) before you can use the E5EK.
Chapter 3 Basic Operation Chapter 5 Parameters
Chapter 4 Applied Opera­tion Chapter 5 Parameters
Chapter 4 Applied Opera­tion/4.1 Selecting the Con­trol Method
Chapter 6 Using the Com­munications Function
These chapters describe how to use the front panel keys and how to view the display when setting the parameters of the major functions for the E5EK.
These chapters describe the important functions of the E5EK and how to use the parameters for making full use of the E5EK.
This chapter describes the func­tions related specifically to posi­tion-proportional type control­lers.
This chapter mainly describes the commun ications commands, and gives program examples.
D Calibration
D Troubleshooting
IV
Chapter 7 Calibration This chapter describes how the
user should calibrate the E5EK.
Chapter 8 Troubleshooting This chapter describes what to
do if any problems occur.
PayAttention to the Following when Installing this Controller
F If you remove the controller from its case, never touch nor apply shock to the elec-
tronic parts inside.
F Do not cover the area around the E5EK. (Ensure sufficient space around the control-
ler to allow heat radiation.)
F Use a voltage (AC100-240V
scribed voltage level must be attained within two seconds.
F When wiring input or output lines to your controller, keep the following points in
mind to reduce the influence from inductive noise:
Allow adequate space between the high voltage/current power lines and the input/ output lines.
Avoid parallel or common wiring with high voltage sources and power lines carrying large currents.
Using separating pipes, duct, and shielded line is also useful in protecting the con­troller, and its lines form inductive noise.
F Allow as much space as possible between the controller and devices that generate a
powerful, high frequency (high-frequency welders, high-frequency sewing machines, and so forth) or surge. T hese devices may cause malfunctions.
F If there is a large power-generating peripheral device and any of its lines, attach a
surge suppressor or noise filter to the device to stop the noise affecting the controller system. In particular, motors, transformers, solenoids and magnetic coils have an inductance component, and therefore can generate very strong noises.
F When mounting a noise filter, be sure to first check the filter’s voltage and current
capacity, then mount the filter as close as possible to the controller.
F Do not use the controller in places where icing, condensation, dust, corrosive gas
(especially sulfurized gas or ammonia gas), shock, vibration, splashing liquid, or oil atmosphere occur. Also, avoid places where the controller can be subjected to intense heat radiation (like from a furnace) or sudden temperature changes.
or AC/DC24V at 50 to 60 Hz). At power ON, the pre-
F Ambient temperature must be kept between -10_Cto55_C. Ambient humidity must
be kept between 35%RH to 85%RH (with no icing or condensation). If the controller is installed inside a control board, the ambient temperature must be kept under 55_C, including the temperature around the controller. If the controller is subjected to heat radiation, use a fan to cool the surface of the controller to under 55_C.
F Store the controller at an ambient temperature between -25_Cto65_C. The amb ient
humidity must be between 35%RH to 85%RH (with no icing or condensation).
F Never place heavy objects on, or apply pressure to the controller that may cause it to
deform an d deterioration during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installa-
tion. These devices can cause radio disturbances which adversely affect the perfor­mance of the controller.
V
Table of Contents
Preface I......................................
Conventions Used in This Manual II...............
Pay Attention to the Following when Installing
this Controller V.................................
CHAPTER 1 INTRODUCTION 1--1...........................
This chapter introduces the E5EK. First-time users should read this chapter with­out fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
1.1 Names of parts 1--2..........................................
1.2 Input and Output 1--4.........................................
1.3 Parameters and Menus 1--7...................................
1.4 About the Communications Function 1--10.......................
1.5 About Calibration 1--11........................................
CHAPTER 2 PREPARATIONS 2--1...........................
This chapter describes the operations you should carry out before turning the E5EK ON.
2.1 Setting up 2--2...............................................
2.2 Installation 2--5..............................................
2.3 Wiring Terminals 2--8.........................................
CHAPTER 3 BASIC OPERATION 3-- 1........................
This chapter describes an actual example for understanding the basic operation of the E5EK.
3.1 Convention Used in this Chapter 3--2...........................
3.2 Setting Input Specifications 3--4...............................
3.3 Setting Output Specifications 3--6..............................
3.4 Setting Alarm Type 3--9.......................................
3.5 Protect Mode 3--12............................................
3.6 Starting and Stopping Operation 3--13...........................
3.7 Adjusting Control Operation 3--14...............................
CHAPTER 4 APPLIED OPERATION 4-- 1......................
This chapter describes each of the parameters required for making full use of the features of the E5EK. Read this chapter while referring to the parameter descrip­tions in chapter 5.
4.1 Selecting the Control Method 4--2..............................
4.2 Operating Condition Restrictions 4--5...........................
4.3 How to Use Event Input 4--8..................................
4.4 How to Use the Remote SP 4--11...............................
4.5 How to Use the Heater Burnout Alarm 4--13......................
4.6 LBA 4--15....................................................
4.7 How to Use Transfer Output 4--17...............................
CHAPTER 5 PARAMETERS 5-- 1.............................
This chapter describes the parameters of the E5EK. Use this chapter as a refer­ence guide.
Protect Mode 5--3................................................
Manual Mode 5--5................................................
Level 0 Mode 5--6................................................
Level 1 Mode 5--10................................................
Level 2 Mode 5--18................................................
Setup Mode 5--25.................................................
Expansion Mode 5--32.............................................
Option Mode 5--37.................................................
Calibration Mode 5--46.............................................
CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6--1..
This chapter mainly describes communications with a host computer and com­munications commands.
6.1 Outline of the Communications Function 6--2....................
6.2 Preparing for Communications 6--3............................
6.3 Command Configuration 6--5..................................
6.4 Commands and Responses 6--6...............................
6.5 How to Read Communications Error Information 6--12.............
6.6 Program Example 6--14.......................................
CHAPTER 7 CALIBRATION 7-- 1.............................
This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated.
7.1 Structure of Parameters 7--2..................................
7.2 Calibrating Thermocouple 7--4.................................
7.3 Calibrating Platinum Resistance T hermometer 7--7..............
7.4 Calibrating Current Input 7--9..................................
7.5 Calibrating Voltage Input 7--10..................................
7.6 Checking Indication Accuracy 7--12.............................
CHAPTER 8 TROUBLESHOOTING 8-- 1......................
This chapter describes how to find out and remedy the cause if the E5EK does not function properly.
8.1 Initial Checks 8--2............................................
8.2 How to Use the Error Display 8--3..............................
8.3 How to Use Error Output 8--5..................................
8.4 Checking Operation Restrictions 8--6...........................
APPENDIX
SPECIFICATIONS A--2........................
ABOUT CURRENT TRANSFORMER (CT) A--5...
CONTROL BLOCK DIAGRAM A--6..............
SETTING LIST A--8...........................
MODEL LIST A--11.............................
PARAMETER OPERATIONS LIST A--12..........
FUZZY SELF-TUNING A--14....................
XFORMAT A--17...............................
ASCII CODE LIST A--20........................
INDEX
REVISION HISTORY
CHAPTER1
CHAPTER 1
INTRODUCTION
This chapter introduces the E5EK. First-time users should read this chapter without fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
CHAPTER 1 INTRODUCTION
1.1 Names of parts 1-2........................
Main parts 1-2............................
Front panel 1-2...........................
About the displays 1-3.....................
How to use keys 1-3.......................
1.2 Input and Output 1-4......................
Input 1-4.................................
Output 1-5................................
1.3 P arameters and Menus 1-7.................
Parameter types 1-7.......................
Selecting modes 1-8........................
Selecting parameters 1-9...................
Fixing settings 1-9.........................
1.4 About the Communications Function 1-10....
1.5 About Calibration 1-11......................
1-- 1
CHAPTER 1 INTRODUCTION
1.1 Names of parts
JMain parts
Terminals
P2-6
JFront panel
Operation indicators
OUT1 SUB1 MANU STOP RMT RST AT
Display key
A/M key
A/M
Rear case
OUT2 SUB2
RMT
RSP SUB1
OUT1 OUT2
A
M
PV
MANU
STOP
Front panel
This page
No.1 display
SV
No.2 display
SUB2
AT
Up k ey
Down ke y
E5EK
1-- 2
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Operation indica-
tors
JHow to use keys
Displays the p rocess value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
OUT1 : Lit when the pulse output function assigned to control output 1” is ON.
OUT2 : Lit when the pulse output function assigned to control
out- put 2” is ON.
SUB1 : Lit when the output function assigned to “auxiliary output 1” is ON.
SUB2 : Lit when the output function assigned to “auxiliary output 2” is ON.
MANU : Lit in the manual operation mode.
STOP : Lit when operation has stopped.
RMT : Lit during remote operation.
RSP : Lit during remote SP operation.
AT : Flashes during auto-tuning.
The following describes basic key operations.
A/M
F key
F key
F key
Each press of this key switches between the auto and manual opera­tions.
The functions of this key change according to how long it i s pressed. If the key is pressed for less than one second, the parameters are switched. If the key is pressed for one second or more, the menu display appears. In key operations from here on, press the key” refers to pressing the
key for less than one second. For details on parameter switching and menu display items, see page 1-8.
Each press of the on the No.2 display, while each press of the returns the values or settings on the No.2 disp lay.
Functions vary, for example, when the neously with the display key, or a key is held down continuously. For
details, see page 1-8. Also, chapters 3 and 4 describe examples using various key combinations.
key increments or advances the values or settings
key decrements or
A/M
key is held down simulta -
1-- 3
CHAPTER 1 INTRODUCTION
1.2 Input and Output
JInput
Temperature input Voltage input Current input
CT input Potentiometer
Remote SP input
Event input
Controller
Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Error 1
Error 2
Error 3
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
The E5EK supports following inputs: temperature input, current input, voltage input, CT input/Potentiometer, remote SP input and event input.
F Temperature input/Voltage input/Current input
Only one of temperature input, voltage input and current input can
be selected and connected to the controller. The above figure shows temperature input connected to the controller.
The following input sensors can be connected for temperature input:
Thermocouple:K,J,T,E,L,U,N,R,S,B,W,PLII Platinum resistance thermometer: JPt100, Pt100
The following currents can be connected for current input:
4to20mA,0to20mA
The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input/Poten-
tiometer
F Remote SP input
Connect CT input when using the HBA (heater burnout alarm) func-
tion on a standard type controller (E5EK-AA2).
Connect the potentiometer when monitoring the valve opening on a
position-proportional type controller (E5EK-PRR2). However, note that the potentiometer cannot be used simultaneously with remote SP input.
Remote SP input cannot be used simultaneously with potentiometer.
When the remote SP function is enabled, inputs within the range 4 to
20 mA are used as the remote SP.
1-- 4
1.2 Input and Output
F Event input
JOutput
When using event input, add on the input unit (E53-CKB). You can select from the following four event inputs:
Multi-SP Run/Stop Auto/Manual SP mode
The E5EK supports the following five outputs.
Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2 Transfer output
When using control outputs 1 and 2, set the output unit (sold sepa­rately). Nine output units are available to suit the output circuit config­uration.
When using transfer output, add on the communication unit (E53-AKF).
Note: The output functions of the E5EK do not operate for five seconds
after the E5EK is turned ON.
F Output assign-
ments
The E5EK supports the following ten output functions.
Control output (heat) Control output (cool) Alarms 1 to 3 HBA LBA Error 1 (input error) Error 2 (A/D converter error) Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2, auxiliary output 1, and auxiliary output 2. However, note that as control output 1 is used as the open output and control output 2 is used as close output on a position-proportional type controller (E5EK-PRR2), control outputs 1 and 2 cannot be used as assignment destinations. Also, of the output functions, control output (heat), control output (cool), HBA and LBA are disabled.
On a standard type controller, there are restrictions on how assignment destinations (control output 1, control output 2, auxiliary output 1, and auxiliary output 2) can be used. For details, see 3.3 Setting Output Specifications.
In the example on the previous p age, “control output (heat)” is assigned to “control output 1”, “alarm 1” is assigned to “control output 2”, and “alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configu­ration is such that heating control output is connected to control output 1, and alarm output is connected to control output 2 and auxiliary out­put 1.
1-- 5
CHAPTER 1 INTRODUCTION
Control outputs 1 and 2 are used depending on the differences in con­trol method as follows.
F Transfer output
Control Method
Standard control E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Heating and cooling control
Position-proportional control
The E5EK supports the following six transfer outputs.
Set point
Set point during SP ramp Process value Heating side manipulated variable Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be output only standard type controllers, and valve opening can be output
on position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out.
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24
Model
Control Output 1/
Control Output 2
Control output (heat) / Alarm, etc.,
Control output (heat) / Control output (cool)
Open/Close
1-- 6
1.3 Parameters and Menus
1.3 Parameters and Menus
JParameter types
F Protect mode
F Manual mode
F Level 0 mode
E5EK parameters are distributed between the following nine modes.
Protect mode Manual mode Level 0 mode Level 1 mode Level 2 mode Setup mode Expansion mode Option mode Calibration mode
The settings of parameters in each of seven modes (excluding the pro­tect mode and manual mode) can be checked and modified by selection on the menu display.
This mode is used to limit use of the menu and function is for preventing unwanted modification of parameters and switching between the auto and manual operation.
In this mode, the controller can be switched manual operation. The manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you may change the set point during operation, and stop and start op­eration. You can also monitor (not change) the process value, ramp SP and manipulated variable.
A/M
keys. The protect
F Level 1 mode
F Level 2 mode
F Setup mode
F Expansion mode
F Option mode
This is the main mode for adjusting control. In this mode, you can execute AT (auto-tuning), and set alarm values, the control period and PID parameters.
This is the auxiliary mode for adjusting control. In this mode, you can set the parameters for limiting the manipulated variable, switch between the remote and local modes, switch between the SP modes, and set the loop break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the b asic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse opera­tion.
This is the mode for setting expanded functions. In this mode, you can set ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF control, specification of the standby sequence resetting method, time for automatic return to the monitoring display.
This is the mode for setting option functions. You can select this mode only when the option unit is set in the controller. In this mode, you can
1-- 7
CHAPTER 1 INTRODUCTION
set the communications conditions, transfer output and event input parameters to match the type of option unit set in the controller. Heater burnout latch function, position-proportional travel time and remote SP scaling parameters are also located in this mode.
F Calibration mode
JSelecting modes
This mode is provided so that the user can calibrate inputs and transfer
output. When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when the communications unit (E53-AKF) is set in the controller.
The following diagram shows the order in which modes are selected.
Power ON
1 second min.
Level 0 mode
1 second min.
Level 1 mode
1 second min.
Level 2 mode
1 second min.
Setup mode
1 second min.
Expansion mode
1 second min.
Option mode
A/M
1secondmin.
Manual mode
A/M
++
1 second min. 1 second min.
Protect mode
A/M
1secondmin.
A/M
A/M
+
1secondmin.
F Menu display
F Level 0 to 2
modes
1 second min.
Calibration mode
To select the menu display in any of the above modes (excluding the
protect mode and manual mode), press the mum. If you select the desired mode using the press the
key, the top parameter in the specified mode is dis-
key for 1 second mini-
or keys and
played.
When you have selected the menu display, the previous mode is
selected. For example, if you selected the menu display while in the level 0 mode, the No.2 display changes to [
] as shown on the left.
Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the level 1 mode.
If you select [
][ ]or[ ] in the menu display , the level 0,
level 1 and level 2 modes, respectively, are selected.
These modes are selected with control still continuing.
1-- 8
1.3 Parameters and Menus
F Setup mode F Expansion mode F Option mode F Calibration mode
F Protect mode
F Manual mode
JSelecting
parameters
If you select [
the setup, expansion, option and calibration modes, respectively, are selected.
When these modes are selected, the control is reset. So, control out-
puts and auxiliary output are turned OFF. When another mode is selected while in these modes, reset is canceled.
To set the controller to the protect mode or to return to the level 0
mode from the protect mode, press the cond minimum simultaneously.
To set the controller to the manual mode, press the
cond minimum in the level 0 to 2 mode. To return to the level 0 mode from the manual mode, press the
When not in the manual mode, each press of the
parameter.
If you press the
turns to the first parameter.
Parameter
1
][ ][ ]or[ ]inthe menudisplay,
A/M
key and key for 1 se-
A/M key for 1 se-
A/M key for 1 second minimum.
key switches the
key when at the final parameter, the display re-
Parameter
2
Parameter
3
Parameter
n
JFixing settings
When you have changed a parameter setting, specify the parameter
using the seconds or press the
When another mode is selected, the content of the parameters before
the mode was selected is fixed.
When turning the power OFF, you must first fix the settings and
parameter contents (by pressing the mode). The settings and parameter contents are sometimes not changed by merely pressing the
or keys, and either leave the setting for at least two
key. This fixes the setting.
key or selecting another
or keys.
1-- 9
CHAPTER 1 INTRODUCTION
1.4 About the Communications Function
The E5EK can be provided with a communications function that allows you to check and set controller parameters from a host computer. If the
communications function is required, add on the communications unit. For details on the communications function, refer to Chapter 6.
F RS-232C
F RS-422
F RS-485
When using the communications function on the RS-232C interface, add on the communications unit (E53-AK01).
When using the communications function on the RS-422 interface, add on the communications unit (E53-AK02).
When using the communications function on the RS-485 interface, add on the communications unit (E53-AK03).
1-- 10
1.5 About Calibration
The E5EK controller is calibrated before shipment from the factory. So, the user need not calibrate the E5EK controller during regular use.
However, if the E5EK controller must be calibrated by the user, use the parameters provided for user to calibrate temp erature input, analog input (voltage, current) and transfer output. Also, note that calibration data is updated to the latest value each time
the E5EK controller is calibrated. Calibration data set before shipment from the factory cannot be returned to after calibration by the user.
1.5 About Calibration
F Calibrating
inputs
F Calibrating trans-
fer output
F Registering cal-
ibration data
The input type selected in the parameter is the item to be calibrated. The E5EK is provided with the following four calibration parameters.
Thermocouple
Platinum resistance thermometer
Current input
Voltage input
Two parameters are provided for thermocouple and voltage input.
Transfer output can be calibrated when the communications unit (E53-AKF) is added on.
When calibrating each item, the calibration data is temporarily regis­tered. This data can be registered as final calibration data only when all items have been newly calibrated. So, all items must be temporarily
registered when calibrating the E5EK controller. When registering data, information regarding whether or not calibra­tion has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring
devices and equipment. For details on handling these measuring devices and equipment, refer to the respective manuals.
For details, see chapter 7 Calibration.
1-- 11
CHAPTER 1 INTRODUCTION
1-- 12
CHAPTER2
CHAPTER 2
PREPARATIONS
This chapter describes the operations you should carry out before turning the E5EK ON.
CHAPTER 2 PREPARATIONS
2.1 Setting up 2-2.............................
Draw-out 2-2..............................
Setting up the output unit 2-3..............
Setting up the option unit 2-4...............
2.2 Installation 2-5............................
Dimensions 2-5............................
Panel cutout 2-5...........................
Mounting 2-6.............................
Setting up the terminal covers 2-7...........
2.3 Wiring Terminals 2-8......................
Terminal arrangement 2-8.................
Precautions when wiring 2-8...............
Wiring 2-8................................
2-- 1
CHAPTER 2 PREPARATIONS
2.1 Setting up
On a standard type controller, set up the output units for control out-
puts 1 and 2 before mounting the controller.
On a position-proportional type controller, the relay output unit is
already set. So, this setup operation unnecessary. (Do not replace with other output units.)
When setting up the output units, draw out the internal mechanism
from the housing and insert the output units into the sockets for con­trol outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, prepare a phillips screwdriver matched to the size of the screw on the lower part of the front panel.
(1) Press down on the hook on the top of the front panel and turn the
phillips screwdriver to the left to loosen the screw on the lower part of the front panel.
2-- 2
Fixing Screw for Front Panel
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 Nm, or approx. 3 to 5 kgfcm.
JSetting up the output unit
2.1 Setting up
F Before setu p
F Procedure
Check the type of the output unit you are about to set up.
For details on types of output unit and main specifications, see page
2-9.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) Remove the power board in the direction of the arrow shown in the
figure. The power board is connected to the control board b y a cen­ter connector. Remove this connector taking care not to bend the connector pins.
Control board
Power board
(3) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(4) Fasten the output units with the bracket (accessory).
(5) Return the power board to its original position.
2-- 3
CHAPTER 2 PREPARATIONS
JSetting up the option unit
F Before setu p
F Procedure
Check the type of the option unit you are about to set up.
For details on types of option unit and main specifications, see Appen-
dix, Model List (page A -11) and Appendix, Option Unit Ratings and Characteristics (p age A-4).
For details on the relationship between units and terminals, see page
2-8.
(1) Remove the power board and option boards in the order shown in
the following diagram.
2
1
(2) Insert the option unit into the socket for option 1. The following
diagram shows the relationship between option unit and mounting position.
Option 1 E53--AKB: Event inputs 1/2 E53--AK01: RS --232C E53--AK02: RS --422 E53--AK03: RS --485 E53--AKF: Transfer output
2-- 4
(3) Mount the option board and the power board in the order shown.
2.2 Installation
JDimensions
48
PV
SV
MANU
RMT
OUT1 OUT2
STOP
SUB2RSP SUB1
AT
96
13.5 100
2.2 Installation
91
112
A
M
JPanel cutout
Unit (mm)
120 mm min
E5EK
45
Thewidthoftherearcaseis44mm.
60 mm min
R ecommended panel thickness is 1 to 8 mm.
Maintain the specified vertical and hori­zontal mounting space between each controller. Controllers must not be closely mounted vertically or horizontally.
+0.6
0
92
+0.8
0
2-- 5
CHAPTER 2 PREPARATIONS
JMounting
(1) Insert the E5EK controller into the mounting hole in the panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the mounting bracket screws alternately a little at a time
until the ratchet start to slide.
2-- 6
F Setting up the terminal covers
Fasten the terminal cover (E53-COV08) to protect terminals.
E5EK-VV2-500 controller is provided with terminal covers.
Fasten the terminal cover as follows by using the snap pins.
2.2 Installation
E5EK
E53-COV08
To remove the terminal cover, pull the edges of the snap pins.
2-- 7
CHAPTER 2 PREPARATIONS
2.3 Wiring Terminals
JTerminal arrangement
AC100-240V (AC/DC24V )
SOURCE
OUT1
OUT2
SUB1
SUB2
~
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
EV1/2 TRSF
RS232C
RS422 RS485
RSP
CT
PTMR
TC
Pt
I
V
JPrecautions
when wiring
JWiring
F Power supply
10
21 22
9
8 7 6 5
4 3 2
23
1
20 19
18 17 16 15
14 13 12
11
TRSF : Transfer output EV1/2 : Event inputs PTMR : Potentiometer
Use ducts to separate input leads and power lines in order to protect the controller and its lines from external noise.
We recommend using solderless terminals when wiring the controller.
Ti ghten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too tightly.
Use the following type of solderless terminals for M3.5 screws.
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indi­cates the inside of the controller
Input power to terminal Nos. 9 and 10. Power spe cificat ions are as fol­lows:
AC100-240V
(AC/DC24V
, 50/60Hz, 15VA
, 50/60Hz, 12VA 8W)
2-- 8
2.3 Wiring Terminals
F Sensor input
10
9 8
7 6 5 4 3
2 1
21 22
23
20 19
18 17 16 15
14 13 12 11
F Control output
10
9
8
7 6 5
4 3
2 1
21 22
23
20 19
18
17 16 15 14 13
12 11
Connect the sensor input to terminal Nos. 11 to 14 and 33 as follows according to the input type.
14
13
12
11
23
Thermocouple Platinum
--
+
resistance
thermometer
14
13
12
11
23
+
14
V
13
12
--
11
23
Voltage input Current input
14
13
12
11
23
mA
+
--
Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos. 5 and 6 are for control output 2 (OUT2). The following diagrams show the available outpu t units and their internal equ a liz ing circuits.
86
75
NPN
E53-Q E53-Q3
+
L
GND
--
86
75
Relay
E53-R E53-S E53-Q4
+
86
mA V
4to20mA/0to20mA
E53-C3 E53-C3D
LL
75
--
86
75
SSR PNP
86
75
0 to 10V/0 to 5V
E53-V34 E53-V35
+v
GND
+
--
+v
86
75
+
L
--
With E53-VVV output units, about 2 V is output for one second after the power is interrupted.
The following table shows the specifications for each output unit.
Model Output Type Specifications
E53-R Relay 250 VAC, 5 A
E53-S SSR 75 to 250 VAC, 1 A
E53-Q E53-Q3 E53-Q4
E53-C3 E53-C3D
E53-V34 E53-V35
Voltage (NPN) Voltage (NPN) Voltage (PNP)
4to20mA 0to20mA
0to10V 0to5V
NPN : 12 VDC, 40 mA (with short-circuit protection) NPN : 24 VDC, 20 mA (with short-circuit protection) PNP : 24 VDC, 20 mA (with short-circuit protection)
4 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600
0 to 10 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600 0 to 5 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600
With E5EK-PRR2 controllers, relay output (250 VAC, 1 A) is fixed.
When replacing the output unit, use the E53-R. The following diagrams show the relationship between terminals and open/close relay settings.
8
7
Open
6
5
Close
2-- 9
CHAPTER 2 PREPARATIONS
F Auxiliary output
10
9 8 7 6 5
4 3 2 1
21 22
23
20 19 18 17 16 15
14 13 12 11
F CT input/
Potentiometer
10
9 8 7 6 5 4
3 2
1
21 22
23
20 19 18
17 16 15
14
13 12
11
Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal Nos.1 and 2 are for auxiliary output 2 (SUB2).
The internal equalizing circuits for the auxiliary outputs are as fol­lows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
Output specifications are as follows:
SPST-NO, AC250V, 3A
When using the HBA function on the E5EK-AA2 controller, connect CT input (CT) to terminal Nos.15 to 17. When monitoring the valve opening on the E5EK-PRR2 controller, connect the potentiometer (PTMR) to terminal Nos.15 to 17. Connect each of these inputs as fol­lows:
17
16
15
CT input Potentiometer
CT
17
16
15
O
W
C
For details on CT inputs, see Appendix, About current transformer.
For details on the potentiometer, see the Instruction Manual for the
valve connected to the controller. The variable resistance range is 100 to 2.5 k.
F Remote SP input
10
9 8
7 6 5 4 3 2 1
About the power blocks
21 22
23
20 19
18 17
16 15
14 13 12 11
Connect an input (RSP) to be used as the remote SP to terminal Nos.15 and 16. However, note that the remote SP can not be used on the E5EK-PRR2 controller.
Only 4 to 20 mA inputs can be connected. Connect the input as fol­lows:
+
16
4to20mA
15
--
The E5EK has independent power supplies for each of the terminal blocks shown on the right.
AB/CC
21 22
23
20 19
18 17 16 15 14 13 12 11
10
9 8
7
B
6 5 4
E
3 2 1
FD
2-- 10
2.3 Wiring Terminals
F Event input
10
21 22
9
8 7 6 5 4 3 2
23
1
20 19
18
17 16 15 14 13 12 11
Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20. How­ever, note that terminal Nos.18 to 20 cannot be used on controllers having a communications function.
Connect the event inputs as follows:
EV1
EV2
COM
Event input 1 and 2
19
18
+
--
+
20
Use event inputs under the following conditions:
Contact input
ON: 1 kmax., OFF: 100 kmin.
No-contact input ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Polarities during no-contact input are as follows:
+
20
EV1
19
18
+
--
EV2
COM
Event input 1 and 2
F Transfer output
F Communications
Connect transfer output (TRSF) to terminal Nos. 21 and 22.
The internal equalizing circuit for transfer output is as follows:
+
21
4to20mA L
22
--
Transfer output specifications are as follows:4 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600
Terminal Nos.18 to 22 can be used only on controllers having a com­munications units (E53-AK01/02/03).
For details on wiring, see Chapter 6, Using the Communications Function.
2-- 11
CHAPTER 2 PREPARATIONS
2-- 12
CHAPTER3
CHAPTER 3
BASIC OPERATION
This chapter describes an actual example for understanding the basic operation of the E5EK.
CHAPTER 3 BASIC OPERATION
3.1 ConventionUsedinthisChapter 3-2........
3.2 Setting Input Specifications 3-4.............
Input type 3-4.............................
Scaling 3-4................................
3.3 Setting Output Specifications 3-6...........
Output assignments 3-6....................
Direct/reverse operation 3-7................
Control period 3-7.........................
3.4 Setting Alarm Type 3-9....................
Alarm type 3-9............................
Alarm value 3-9...........................
Alarm hysteresis 3-10.......................
Closeinalarm/openinalarm 3-10............
3.5 Protect Mode 3-12..........................
Security 3-12...............................
A/M key protect 3-12........................
3.6 Starting and Stopping Operation 3-13........
3.7 Adjusting Control Operation 3-14............
Changing the set point 3-14.................
Manual operation 3-14......................
Auto-tuning (A.T.) 3-16.....................
3-- 1
CHAPTER 3 BASIC OPERATION
3.1 Convention Used in this Chapter
This chapter describes basic E5EK operations such as how to set up parameters, start and stop operation, and adjusting control operation.
For more complex control examples, refer to Chapter 4 Applied Opera­tion and Chapter 5 Parameters.
F Basic Operation
Flow
The following diagram shows the basic operation flow.
Power ON
Setup
Setting input specifications
Setting output specifications
Setting alarm output
Protecting parameters
Operation
Start
Adjustment
Stop
3-- 2
Power OFF
3.1 Convention Used in this Chapter
F Setup
This description assumes that the controller is operated under the fol­lowing conditions.
A humidity sensor of output 4 to 20 mA is connected to the controller. The measuring range of the humidity sensor is set to 10 to 95%.
A humidifier is controlled by pulse output to maintain humidity at a constant 60%.
An alarm is output when the humidity exceeds the upper limit value (70%) or lower limit value (50%).
Output unit: relay type (E53-R) for OUT1.
Humidity sensor
Humidifier
Control target
OUT1
Alarm 1 (deviation
upper-and lower-limit)
SUB1
AC100-240V (AC/DC24V )
SOURCE
E5EK-AA2 (Control output 1 : E53-R)
~
10
9
8
7
6
5
4
3
2
1
21 22
23
20
19
18
17
16
15
14
13
12
11
--
4to20mA
+
3-- 3
CHAPTER 3 BASIC OPERATION
3.2 Setting Input Specifications
JInput type
JScaling
Set the type No. (0 to 21) in the “input type” parameter. The factory setting is “2: K1 (thermocouple).”
For details on input types and setting ranges, see page 5-26.
When the voltage input and current input are selected, scaling
matched to the control is required.
The “scaling upper limit”, “scaling lower limit” and “decimal point” parameters (setup mode) are use for scaling.
The “scaling upper limit” parameter sets the physical quantity to be expressed by the upper limit value of input, and the “scaling lower limit” parameter sets the physical quantity to be expressed by the lower limit value of input. The “decimal point” parameter sets the number of digits past the decimal point.
The following figure shows scaling example of 4 to 20 mA input. After scaling, the humidity can be directly read. In this case, the “decimal point” parameter is set to “1”.
Readout (humidity)
Scaling upper limit value (95.0%)
F Input shift
Scaling lower limit
value (10.0%)
0
100%FS
Input (4 to 20 mA)
When temperature input is selected, scaling is not required. This is because input is treated as the “temperature” as it is matched to the input type. However, note that the upper and lower limit values of the sensor can be shifted. For example, if both the upper and lower limit values are shifted by 1.2_C, the process value (before shift) is regarded as 201.2_C after shift when input is 200_Cbeforeshift.
To set input shift, set shift values in the “input shift upper limit” and “input shift lower limit” parameters (level 2 mode).
Temperature
Input shift upper limit value
Upper limit value
After shift
Before shift
Input shift lower
Lower limit value
0
limit value
Input (%FS)
100
3-- 4
About the tempera­ture unit
To switch the temperature unit from “_C” to “_F” for temperature unit, switch the setting of the _C/_F selection” parameter to [ ] from [ ].
3.2 Setting Input Specifications
Setting Example
1 second min.
In this example, let’s set the p arameters as follows:
“inputtype” =“17(4to20mA)” “scaling upper limit val ue” = “950” “scaling lower limit value” = “100”
“decimal point” = “1”
(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page
1-8.
(2) Press the
the setup mode [
key to enter the setup mode. The top parameter in
] “input type” is displayed. The parameter
default is “2”.
(3) Press the
(4) Press the
[
] (“scaling upper limit value” parameter). The parameter
key until the display indicates “17”.
key to fix the set value. The display changes to
default is “100”.
(5) Press the
(6) Press the
[
](“scaling lower limit value” parameter). The parameter
key until the display indicates “950”.
key to fix the set value. The display changes to
default is “0”.
(7) Press the
(8) Press the
key until the display indicates “100”.
key to fix the set value. The display changes to
[ ] (“decimal point” parameter). The parameter default is “0”.
(9) Press the
key until the display indicates “1”.
3-- 5
CHAPTER 3 BASIC OPERATION
Dest
inat
i
3.3 Setting Output Specifications
Some output specifications are different according to controller type, standard or position-proportional. The following table summarizes which output-related parameter settings are supported.
Parameter
Control output 1 assignment F
Control output 2 assignment F
Auxiliary output 1 assignment F F
Auxiliary output 2 assignment F F
Direct/reverse operation F F
Control period (heat) F
Control period (cool) F
(F Indicates that an output specification is supported.)
Standard
Typ e
Position-
proportional
Typ e
JOutput assignments
F Standard type
Output assignments are described according to controller type.
Ten output are supported :
control output (heat) control output (cool) alarm outputs 1 to 3 HBA LBA, and error 1 (input error) error 2 (A/D converter error) error 3 (RSP input error).
These functions are assigned to control outputs 1 and 2, and auxil-
iary output 1 and 2.
Restrictions on assignment destination are placed on some of the out­puts. The following table shows where outputs may be assigned to.
Assignment
Control Output Auxiliary Output
on
Output Function
Control output (heat) F F Control output (cool) F F Alarm 1 F F F F Alarm 2 F F F F Alarm 3 F F F F HBA F F F F LBA F F F F Error 1; Input error F F Error 2; A/D converter error F F Error 3; RSP input error F F
1 2 1 2
With control output (cool), the conditions for switching from standard control to heating and cooling control are reached when the output function is assigned at the cooling side during heating and cooling control.
In other words, heating and cooling control is carried out when con­trol output (cool) is assigned, and standard control is carried out when output is not assigned. For details on heating and cooling con­trol, see 4.1 Selecting the Control Method (page 4-2).
3-- 6
3.3 Setting Output Specifications
Dest
inat
i
Factory settings are as follows:
control output 1 = Control output (heat) control output 2 = Alarm 1 auxiliary output 1 = Alarm 2 auxiliary output 2 = Alarm 3.
Output assignments are set in the “control output 1 assignment”, “control output 2 assignment”, “aux output 1 assignment” and “aux output 2 assignment” parameters (setup mode).
F Position-propor-
tional type
JDirect/reverse
operation
Position-proportional type controllers support six output functions. These are assigned to auxiliary outputs 1 and 2.
Restrictions on assignment destinations are placed on some of the outputs. The following table shows where outputs may be assigned to.
Assignment
Output Function
Alarm 1 F F Alarm 2 F F Alarm 3 F F Error 1 : Input error F F Error 2 : A/D converter error F F Error 3 : RSP input error F F
“Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the manipulated variable is decreased according to the decrease in the process value. For example, when the process value (PV), is lower than the set point (SP), in a heating control system, the manipulated variable increases by the difference between the PV and SP values. Accordingly, this becomes “reverse operation” in a heating control sys­tem. Alternatively, this becomes “direct operat ion” in a cooling control system.
Direct/reverse operation is set in the [ tion” parameter (setup mode).
Control Output Auxiliary Output
on
1 2 1 2
]“direct/reverse opera-
JControl period
When the output unit is pulse output such as relay output, set the pulse output cycle (control period). Though a shorter pulse period provides better control performance, the control period should be set taking the life expectancy of the output unit into consideration when theoutputunitisrelay.
The control period is set in the “control period (heat)” parameter (level 1 mode). Factory setting is “20:20 seconds.”
The “control period (cool)” output function is not allocated. So, the “control period (cool)” parameter cannot be set.
3-- 7
CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
1 second min.
In this example, let’s set the p arameters as follows:
“control output 1 assignment” = “control output (heat)” “control output 2 assignment” = “alarm output 1” “direct/reverse operation” = “reverse operation”
“control period” = “20 secs”
“run/stop” = “run” All of the above settings in this example are factory settings. So, in this example, we are only going to check the parameter settings.
(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page
1-8.
(2) Press the
key to enter the setup mode. The top parameter in
the setup mode [ ] “input type” is displayed. In this example, the parameter setting is “17: 4 to 20 mA.”
(3) Press the
key until [ ] (“control output 1 assignment”
parameter) is displayed. The parameter default is [ ].
(4) Asthesettinginthisexampleistobeleftasitis,pressthe
The display changes to [ parameter). The parameter default is [
] (“control output 2 assignment”
].
(5) Asthesettinginthisexampleistobeleftasitis,pressthe
until [ The parameter default is [
] (“direct/reverse operation” parameter) is displayed.
].
(6) Asthesettinginthisexampleistobeleftasitis,pressthe
key.
key
or
keys to select [ ] (level 1 mode). For details on selecting
the menu display, see page 1-8.
(7) Press the
the level 1 mode [
(8) Press the
key to enter the level 1 mode. The top parameter in
] “AT execute/cancel” is displayed.
key until [ ] (“control period” parameter) is dis­played. The parameter default is “20”. As the setting in this exam-
ple is to be left as it is, quit key operation.
3-- 8
3.4 Setting Alarm Type
A
l
Three alarm outputs are supported: alarms 1 to 3. Of these, only the alarm assigned as the output can be used.
Alarm output conditions are determined according to the combina­tion of the “alarm type”, “alarm value” and “alarm hysteresis” parameter settings.
The contact conditions when alarm output is ON can be set to “open” or “closed” in the “close in alarm/open in alarm” parameter.
3.4 Setting Alarm Type
JAlarm type
The following table shows the alarm types supported by the E5EK controller and their respective operations.
armType
Upper-and lower-limit alarm
1
(deviation)
Upper-limit alarm (deviation)
2
Lower-limit alarm (deviation)
3
Upper-and-lower-limit range
4
alarm (deviation)
Upper-and-lower-limit alarm with standby sequence
5
(deviation)
Upper-limit alarm with
6
standby sequence (deviation)
Lower-limit alarm with
7
standby sequence (deviation)
Absolute-value upper-limit
8
alarm
Absolute-value lower-limit
9
alarm
Absolute-value upper-limit
10
alarm with standby sequence
Absolute-value lower-limit
11
alarm with standby sequence
When X is positive When X is negative
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
Alarm Output Operation
XX
SP
X
SP
X
SP
XX
SP
XX
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Always ON
ON OFF
ON OFF
Always OFF
Always OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
Alarm types are set independently for each alarm in the “alarm 1 to 3” parameters (setup mode). Factory setting is “2: Upper-limit alarm (deviation)”.
JAlarm value
Alarm values are indicated by “X” in the table above. Alarm output operation differs according to whether the value of the alarm is posi­tive or negative.
Alarm values are set independently for each alarm in the “alarm value 1 to 3” parameters (level 1 mode). Factory setting is “0”.
3-- 9
CHAPTER 3 BASIC OPERATION
C
l
O
JAlarm hysteresis
The hysteresis of alarm outputs when alarms are switched ON/OFF can be set as follows.
Upper limit alarm Lower limit alarm
ON
OFF
Alarm hysteresis is set independently for each alarm in the “alarm 1 to 3 hysteresis” parameters (level 2 mode). Factory setting is “0.02:
0.02%FS”.
F Standby
sequence
“Standby sequence” is a function for unconditionally turning alarm output OFF when the process value has left the alarm range once and it next enters the alarm range.
For example, when the alarm type is set to “deviation lower limit,” generally the process value is within the alarm range, and alarm out­put become ON as it is as the process value when the power is turned ON is smaller than the set point. However, if the alarm type is set to “deviation lower limit with standby sequence”, alarm output first becomes ON when the process value exceeds the alarm setting value to leave the alarm range and once again falls belo w the alarm value.
JCloseinalarm/openinalarm
Alarm hysteresis
Alarm value
Alarm hysteresis
ON
OFF
Alarm value
F Summary of
alarm operations
When the controller is set to “close in alarm,” the status of the alarm output function is output as it is. When set to open in alarm,” the status of the alarm output function is output inverted.
Output Output LED
oseinalarm
peninalarm
Alarm
ON ON Lit
OFF OFF Not lit
ON OFF Lit
OFF ON Not lit
Alarm type and close in alarm (normally open)/open in alarm (nor­mally close) can be set independently for each alarm.
Close in alarm/open in alarm is set in the “alarm 1 to 3 open in alarm” parameters (setup mode). Factory setting is [
] “close in
alarm”.
The figure b elow visually summarizes the above description of alarm operations (when alarm type is set to “lower limit alarm (deviation) with standby sequence”):
Alarm type: lower limit alarm (deviation) with standby sequence
PV
Alarm value
Alarm hysteresis
Time
Standby sequence canceled
Alarm output (close in alarm)
Close (ON) Open (OFF)
3-- 10
3.4 Setting Alarm Type
Setting Example
1 second min.
1 second min.
1 second min.
When a set point for a temperature exceeds 10%, alarm1 will be out­put. In this example, let’s set the p arameters as follows:
“alarm type 1” = “1: (deviation upper-and lower-limit)”
“alarm value 1” = “10” “alarm hysteresis” = “0.20” “close in alarm/open in alarm”= “
: close in alarm”
Meanings of p arameters, “alarm hysteresis” and “open in alarm/close in alarm” are the same settings at the shipment, so settings for opera­tions are omitted.
(1) Select the menu display, and select [
] (setup mode) using the
or keys. For details on selecting the menu display, see page
1-8.
(2) Press the
the setup mode [
key to enter the setup mode. The top parameter in
] “input type” is displayed. In this example,
the parameter setting is “17: 4 to 20 mA ”.
(3) Press the
key until [ ] (“alarm type 1” parameter) is dis-
played. The parameter default is “2: deviation upper limit”.
(4) Press the
key to return to “1: deviation upper-and-lower lim-
it”.
(5) Select the menu key, and select [
](level1mode)usingthe
or keys. For details on selecting the menu display, see page
1-8.
(6) Press the
the level 1 mode [
(7) Press the
key to enter the level 1 mode. The top parameter in
] “AT execute/cancel” is displayed.
key until [ ] (“alarm value 1” parameter) is dis-
played.
(8) In this example, the parameter setting is “0.0” so press the
key
until “10.0” is displayed.
About the Decimal PointoftheAlarm Val u e
The decimal point of the alarm value conforms to the setting of the “decimal point” parameter (setup mode). In this example, the “decimal point” parameter is set to “1”. (During temperature input, the decimal point of the alarm value conforms to the set sensor.)
3-- 11
CHAPTER 3 BASIC OPERATION
3.5 Protect Mode
JSecurity
JA/M key protect
This parameter allows you to protect until start of operation parame­ters that do not change during operation to prevent unwanted modifi­cation.
The set value of the “security” (protect) parameter specifies the range of protected parameters.
When this parameter is set to “0”, parameters are not protected.
When this parameter is set to “1” to “3”, the number of modes that
can be displayed on the menu display is limited. When set to “1”, level 0 to 2, setup, expansion and option modes only can be selected. When set to “2”, only level 0 to 2 modes can be selected. When set to “3”, only level 0 and 1 modes can be selected.
When this parameter is set to “4” to “6”, operations in only the level 0 mode can be selected, and the mode is not displayed on the menu dis­play.
When this parameter is set to “5”, only the “PV/SP” parameter can be used.
When this parameter is set to “6”, only the “PV/SP” parameter can be used. (The set point can not change.)
Default is “1”.
This parameter disables use of the
example, if you protect use of the
A/M key during operation. For
A/M keybythe“A/M keyprotect”
parameter (protect mode) during auto operation, the controller can­not be set to the manual mode, preventing manual operation of the controller during operation.
Setting Example
A/M
A/M
Let’s protect the setup, expansion, option and calibration modes. Set
the parameters as follows:
“security” = “2: Usable only in level 0 to 2 modes”
(1) Press for 1 second minimum the A/M and keys simultaneously,
the controller enters the protect mode.
(2) In the protect mode, the top parameter in the protect mode “secu-
rity” is displayed. The parameter default is “1”. Press the
key
to change the parameter setting to “2”.
(3) Press for 1 second minimum the
A/M and keys simultaneously,
the display changes to the “PV/SP monitor” parameter (level 0 mode).
3-- 12
3.6 Starting and Stopping Operation
3.6 Starting and Stopping Operation
You can start and stop operation by changing the setting of the “run/ stop” parameter (level 0 mode).
You can switch the RUN/STOP function up to 100,000 times.
To stop operation, set the “run/stop” parameter to [ ](stop).In
a stop state, the “STOP” LED lights.
Operation cannot be stopped during auto-tuning.
F Manipulated vari -
able at stop
Setting Example
1 second min.
On a standard type controller, specify the manipulated variable (--- 5.0 to 105.0%) in the “MV at stop” parameter (level 2 mode) to output the manipulated variable during stop. Factory-set to “0.0 : 0.0%”
On a position-proportional type controller, you can select either of the open, close or hold status. In an open status, only control output 1 is ON. In a close status, only control output 2 is ON. In a hold status, both control outputs 1 and 2 are Factory-set to “hold.”
The following example describes the procedure to follow to stop control
during operation of the controller.
(1) Select the menu display, and select [ ](level0mode)usingthe
or keys. For details on selecting the menu display, see page
1-8.
(2) Press the
displayed.
(3) Press the
played.
(4) Press the
lights, and operation stops.
key to enter the level 0 mode. The PV and SP are
key until [ ] (“run/stop” parameter) is dis-
key to select [ ](stop).The“STOP”LED
Using Event Input
To resume operation, follow the above procedure to select [ (“run”). The “STOP” LED goes out and operation starts.
Using the E53-AKB, run/stop can be selected by event input. For details on how to use event input, see 4.3 How to Use Event Input, page 4 --- 8.
]
3-- 13
CHAPTER 3 BASIC OPERATION
3.7 Adjusting Control Operation
JChanging the set
point
Setting Example
JManual operation
You can change the set point in the “set point” parameter (level 0 mode).
However , note that you cannot change the set point when the “securi­ty” parameter (protect mode) is set to “6”.
To change the set p oint, press the
or keys to select the desired value. If you leave the setting for two seconds, the set point is updated to the new setting.
In the following example, let’s change the temperature set point from “60_C” to “50_C”.
(1) Select the PV/SP monitor display.
(2) Press the
key to change the setting to “50.0: 50.0_C”.
On standard type controller, the manipulated variable is controlled, and on a position-proportional type controller, the valve opening is controlled.
To set manual operation and manually set the manipulated variable or the valve opening, press for 1 second minimum the
A/M
key. The
controller enters the manual mode.
F Standard type
Process value
Manipulated variable
[MANU] LED
Balance-less, Bump-less Opera­tion
The process value is displayed on the No.1 display, and the manipu­lated variable is displayed on the No.2 display.
To change the manipulated variable, press the
or keys. After
two seconds, the manipulated variable is updated to the new setting.
Other modes cannot be selected while in the manual mode. To select other modes, press for 1 second minimum the
A/M key . The manual
mode is quit.
The automatic return of display function does not work while in the manual mode.
When switching between manual and auto operation, the manipu­lated variable is subject to balance-less, bump-less operation.
If the power is interrupted during manual operation, manual opera­tion is resumed at the manipulated variable at power interruption when the power is reset.
You can switch the AUTO/MANUAL function up to 100,000 times.
To prevent sudden changes in the manipulated variable when switching between manual and auto operation, operation is resumed using the value that was active immediately before operation was switched, and the value is brought gradually closer to the value immediately after operation was switched.
3-- 14
3.7 Adjusting Control Operation
The following diagram summarizes manual operation.
Manipulated variable (%)
Balance-less, bump-less points
0
Manual
A/M
Auto
F Position-proportional type
When a potentiometer is connected to the controller, the process value is displayed on the No.1 display, and the valve opening is displayed on the No.2 display. When a potentiometer is not connected to the controller, [----] is dis­played on the No.2 display.
Potentiometer connected Potentiometer not connected
When you press the key, the open side b ecomes ON. When you press the
Other modes cannot be selected while in the manual mode. To select other modes, press for 1 second minimum the mode is quit.
The automatic return of display function does not work while in the manual mode.
You can switch the AUTO/MANUAL function up to 100,000 times.
Manipulated variable switched
[MANU] LED
OFF ON
Power inter­ruption
Process value
Valve opening
key, the close side becomes ON.
Time
Process value
Valve opening
[MANU] LED
A/M key . The manual
3-- 15
CHAPTER 3 BASIC OPERATION
JAuto-tuning
(A.T.)
F 40%AT
Deviation at start of A T execution 10% full-scale
AT (auto-tuning) cannot be executed while operation is canceled or during ON/OFF control.
When you execute auto-tuning, the optimum PID parameters are automatically set by forcibly changing the manipulated variable to calculate the characteristics (called the “limit cycle method”) of the control target. During auto-tuning, the AT LED flashes.
40%AT or 100%AT can be selected by the limit cycle of MV change width. Specify [
]or[ ], respectively, in the “AT execute/
cancel” parameter (level 1 mode).
During heating and cooling control and with position-proportional type, only 100%AT can be executed. (So, [
](40%AT)willnotbe
displayed.)
To cancel AT execution, specify [
](“ATcancel”).
In order to set the limit cycle of MV change width to 40%, select 40%AT to execute auto-tuning with fluctuations in the process value kept to a minimum. However, note that auto-tuning takes longer to execute compared with 100%AT. The timing by which limit cycles are generated varies according to whether or not the deviation (DV) at the start of AT execution is 10% full-scale or less.
Deviation at start of AT execution < 10% full-scale
Limit cycle of MV change width 40%
Limit cycle of MV change width 40%
Set point Set point
Deviation 10% full-scale
StartofAT execution
F 100%AT
End of AT Start of AT
In order to set the limit cycle of MV change width to 100% , select 100%
Time Time
AT to shorten the AT execution time without worrying about fluctua­tions in the process value.
Limit cycle of MV change width 100%
Set point
Deviation 10% full-scale
End of AT
execution
3-- 16
StartofAT execution
Time
End of AT
3.7 Adjusting Control Operation
Setting Example
1 second min.
AT execute
In this example, let’s execute 40%AT.
(1) Select [ ](level1mode)usingthe or keys. For details
on selecting the menu display, see page 1-8.
(2) Press the
key to enter the level 1 mode. The top parameter in
the setup mode [ ] “ AT execute/cancel” is displayed. In this example, the parameter setting is [
(3) Press the
key to specify [ ].
]“ATcancel”
(4) The AT LED flashes, and AT execution starts. When the AT LED
goes out (end of AT execution), the parameter automatically returns to [
](“ATcancel”).
In addition to AT, the E5EK is also provided with fuzzy self-tuning (ST) that allows automatic calculation of the PID parameters suited to the control target. However, note that the ST function op­erates only during standard control by temperature input. For fur­ther information regarding the ST, please see page 5-34 and A-14.
About PID Parame­ters
When control characteristics are already known, the PID parameters can be set directly to adjust control. PID parameters are set in the “proportional band” (P), “integrated time” (I) and “derivative time” (D) parameters (level 1 mode). For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode (page 5-13).
3-- 17
CHAPTER 3 BASIC OPERATION
3-- 18
CHAPTER4
CHAPTER 4
APPLIED OPERATION
This chapter describes each of the parameters required for making full use of the features of the E5EK. Read this chapter while referring to the parameter descriptions in chapter 5.
CHAPTER 4 APPLIED OPERATION
4.1 Selecting the Control Method 4-2............
Heating and cooling control 4-2.............
Position-proportional control 4-3............
ON/OFF control 4-4.......................
4.2 Operating Condition Restrictions 4-5........
Manipulated variable restrictions 4-5........
Set point limiter 4-6.......................
SP ramp 4-6..............................
4.3 How to Use Event Input 4-8................
Input assignments 4-8.....................
Multi-SP 4-9..............................
Other event input functions 4-10.............
4.4 How to Use the Remote SP 4-11..............
Scaling 4-11................................
SP mode 4-11..............................
Remote SP monitor 4-12....................
SP tracking 4-12............................
Operating conditions 4-12...................
4.5 How to Use the Heater Burnout Alarm 4-13...
Heater burnout detection 4-13...............
Operating conditions 4-13...................
How to calculate
the heater burnout set value 4-14............
4.6 LBA 4-15..................................
4.7 How to Use Transfer Output 4-17............
4-- 1
CHAPTER 4 APPLIED OPERATION
4.1 Selecting the Control Method
When selecting the control method, set the parameters according to the following table. (Parameters are factory-set to heating control.)
Parameter
Control Method
Heating control
(Standard)
Cooling control
(Standard)
Heating and cooling
control
For details on how to assign outputs, see 3.3 Setting Output Specifica­tions (page 3-6).
JHeating and
cooling control
F Dead band
When heating and cooling control is selected, the “deadband” and “cooling coefficient” parameters can be used.
The dead band is set with the set point as its center . The dead band width is the set value of the “dead band” parameter (level 1 mode). Set­ting a positive value produces a dead band, while setting a negative value produces an overlap band.
Output Output
Dead band: dead band width = positive
Control output 1
assignment
Control output (heat)
Control output (heat)
Control output (heat) Control output (cool) Reverse operation
Control output 2
assignment
-
-
Overlap band: dead band width = negative
Direct/Reverse
operations
Reverse operation
Direct operation
Heating side
0
Set point Set point
F Cooling coeffi-
cient
F Manipulated vari -
able at stop
Cooling side
PV
Heating side
0
Cooling side
PV
If the heating and cooling characteristics of the control target greatly differ, preventing satisfactory control characteristics from being obtained by the same PID parameters, adjust the proportional band (P at cooling side) using the cooling coefficient to balance control b etween the heating and cooling sides. In heating and cooling control, P at the heating or cooling side is calculated by the following formula:
Heating side P = P; Cooling side P = cooling coefficient ¢ P
In heating and cooling control, the manipulated variable output that is output when controller operation is stopped is dependent on the set value of the MV at stop” parameter (level 2 mode) in the same way as for standard control.
However, note that in heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. When the manipulated variable at STOP is a negative value, the manipulated variable is output to only the cooling side, and when a positive value, the manipulated variable is output to only the heating side. The factory setting is “0”. If the controller is operated using the factory setting, the manipulated variable is not output to both the heating and cooling sides.
4-- 2
Switching with Manual operation
When the overlap band is set, the bumpless function that operates when switch­ing between manual and automatic operation may not work.
4.1 Selecting the Control Method
JPosition-propor-
tional control
F Travel time
Use the position-proportional type controller for position-propor­tional control.
On a position-proportional type controller, control output 1 is used for open output, and control output 2 is used for close output. Accord­ingly, control outputs 1 and 2 cannot be used as output assignments. Special output units are already set on position-proportional type controllers.
On a position-proportional type controller, the following functions are disabled.
ST MV limiter P and PD control 40% AT LBA HBA ON/OFF control
Thetraveltimeisfactory-setto“30seconds.”
To change the travel time, either set in the “travel time” parameter
(option mode), or execute motor calibration in the “motor calibra­tion” parameter (option mode).
F Valve opening
monitor
F Manipulated vari -
able at stop/PV error
F Other functions
The valve opening can be monitored when a potentiometer is con­nected to the controller. However, be sure to execute motor calibra ­tion after connecting the potentiometer.
Open, close or hold can be selected as output at stop or PV error. Set these outputs in the “manipulated variable at stop” or “manipulated variable at PV error” parameters (level 2 mode).
Set the dead band in the “position-proportional dead band” parame­ter (level 1 mode).
Set the open/close hysteresis in the “open/close hysteresis” parameter (level 1 mode).
Open/close hysteresis
Dead band
ON
OFF
MV--Valve opening
100%0-100%
4-- 3
CHAPTER 4 APPLIED OPERATION
JON/OFF control
F Hysteresis
Switching between advanced PID control and ON/OFF control is car ­ried out by the “PID / ON/OFF” parameter (expansion mode). When this parameter is set to [ when set to [
], ON/OFF control is selected. Default is [ ].
], advanced PID control is selected, and
During position-proportional control, ON/OFF control cannot be selected.
In ON/OFF control, hysteresis is provided in the program when switching between ON and OFF to stabilize operation. The hysteresis width provided during ON/OFF control is simply referred to as hys­teresis.” Control output (heat) and control output (cool) functions are set in the hysteresis (heat)” and hysteresis (cool)” parameters, re­spectively.
In standard control (heating or cooling control), hysteresis can be set only for the heating side.
Hysteresis (heat)
ON
OFF
Set point
PV
In heating and cooling control, a dead band can be set. So, 3 -position control is made possible.
Dead band
Parameters
Hysteresis (heat)
OFF
Symbol
Control output 1
Control output 2
Direct/Reverse
Dead band : Level 1 Heating and cooling control
Cooling coefficient : Level 1 Heating and cooling control
MV at stop : Level 2 Manipulated variable when control
MV at PV error : Level 2 Manipulated variable when control
Travel time : Option Position-proportional control
Motor calibration : Option Position-proportional control
Positional-proportional
Open/close
Hysteresis (heat) : Level 1 ON/OFF control
Hysteresis (cool) : Level 1 ON/OFF control
PID / ON/OFF : Expansion ON/OFF control
Hysteresis (cool)
ON
Heating side
Set point
Parameter Name: Mode Description
assignment : Setup
assignment : Setup
operation : Setup
dead band : Level 1
hysteresis : Level 2
Cooling side
For specifying control method
For specifying control method
For specifying control method
operation is stopped
operation is PV error
Position-proportional control
Position-proportional control
PV
4-- 4
4.2 Operating Condition Restrictions
4.2 Operating Condition Restrictions
JManipulated vari-
able restrictions
F MV limiter
The upper-and lower-limit values of the manipulated variable can be restrictedbytheMVlimiter,andthechangerateofthe manipulated variable can be restricted by the MV change rate limiter.
The upper-and lower-limit values of the manipulated variable are set in the “MV upper limit” and “MV lower limit” parameters (level 2 mode). When the manipulated variable calculated by the E5EK is outside of the range of the MV limiter, actual outputs are dependent on the set value of these parameters.
Output (%)
100
0
MV upper limit value
MV lower limit value
PV
In heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. The upper limit is set for the heating side (positive value), and the lower limit is set for the cooling side (negative value) as shown in the follow­ing figure.
F MV change rate
limiter
Output (%)
100
MV lower limit value
MV upper limit value
Heating side
0
Set point
Cooling side
PV
The “MV change rate limit” parameter (level 2 mode) sets the maxi­mum permissible change width per second of the manipulated variable. If a change in the manipulated variable exceeds this parameter setting, the value calculated by the E5EK is reached while changing the value by the per-second value set in this parameter.
Output (%)
100
MV change rate limit value
1 second
0
Switching point
Time
4-- 5
CHAPTER 4 APPLIED OPERATION
F Limiter operation
conditions
JSet point limiter
The limiters are invalid or cannot be set when any of the following conditions occurs:
During ON/OFF control
During ST execution
During AT execution (only by MV change rate limiter)
During manual operation
When operation is stopped
When an error has occurred.
During position-proportional control (manipulated variable limiter
only)
The setting range of the set point is limited by the set point limiter. The upper-and lower-limit values of this set point limiter are set in the Set point upper limit” and Set point lower limit” parameters (expansion mode), respectively. However, note that when the set point limiter is
reset, the set point is forcibly changed to the upper-or lower-limit value of the set point limiter if the set point is out of the limiter range. Also, when the input type, temperature unit and scaling (sensor) range are
changed, set point limiter is forcibly reset to the scaling (sensor) range.
Scaling (sensor) range
Set point limiter
Setting range
Changed to upper limit value
Changed to the new up­per limit value
A
○B×
SP
SP
JSP ramp
Input type changed
Set point Upper-and lower-limit values of the limiter
Scaling (sensor) upper-and lower-limit values
With the SP ramp function, the controller operates according to the val­ue (set point during SP ramp) limited by a change rate, instead of the
changed set point when set point is changed. The interval in which the set point during SP ramp is limited is referred to as the SP ramp”.
SP
Set point
Switching point
SP ramp
SP ramp set value
SP ramp time un it
Time
CB
4-- 6
4.2 Operating Condition Restrictions
The change rate during the SP ramp is specified by the SP ramp set value” and SP ramp time unit” parameters. At the SP ramp set value” default 0”, the SP ramp function is disabled. The set point changing in SP ramp can be monitored in the Set point
during SP ramp” parameter (level 0 mode).
F Operation at start
Set point
PV
The limiters are invalid or cannot be set when any of the following conditions occurs:
If the SP ramp function is enabled when the power is turned ON, and when run” is switched to from stop,” process value may reach the set
point after SP ramp in the same way as when the set point is changed. In this case, operation is carried out with the process value regarded as the set point before the change was made. The direction of the SP ramp changes according to the relationship be-
tween the process value and the set point.
PV < SP PV > SP
SP
SP ramp
Set point
Time Time
Power ON
SP
SP ramp
PV
Same change rate
Power ON
F Restrictions dur-
ing SP ramp
Parameters
Execution of auto-tuning starts after the end of SP ramp.
When the controller is switched to the manual mode, the set point
changes continuously until SP ramp ends.
When the controller is in the stop state or an error occurs, the SP ramp function becomes invalid.
Symbol Parameter Name: Mode Description
MV upper limit : Level 2 Manipulated variable restrictions
MV lower limit : Level 2 Manipulated variable restrictions
MV change rate limit : Level 2 Manipulated variable restrictions
SP setting upper limit: Expansion SP setting restrictions
SP setting lower limit : Expansion SP setting restrictions
SP ramp set value : Level 2 SP changing restrictions
SP ramp time unit : Level 2 SP changing restrictions
4-- 7
CHAPTER 4 APPLIED OPERATION
4.3 How to Use Event Input
When using event input, mount the option unit (E53-AKB).
Event inputs can be switched up to 100,000 times.
JInput
assignments
Multi-SP function
01,2
Auto/Manual
SP mode
You can choose from the following four event input functions:
Multi-SP Run/Stop Auto/Manual SP mode
In the case of the multi-SP function, the number of event inputs
Multi-SPRun/Stop
(event input 1 or 2) set in the “multi-SP function” parameter (option mode) are used.
Other functions are assigned to event inputs 1 and 2 not used for the multi-SP function according to the setting of the “event input assign­ment 1 and 2” parameters (option mode). However, note that “eve nt input ass ignm ent 1/2” parameters cannot be used when only one unit of the E53-AKB is installe d.
Event input
0
1
12
Multi-SP
Other event input functions
Multi-SP function
2
The following table shows the relationship between the settings and functions of the “event input assignment 1 and 2” parameters.
Setting Function
Event input disabled
ON : Stop /OFF : Run
ON : Manual /OFF : Auto
ON :RSP /OFF :LSP
4-- 8
4.3 How to Use Event Input
F Assignment
example
JMulti-SP
In this example, set two event inputs are used, the multi-SP function to “1”, and event input 2 to “Run/Stop”. Set as follows: (1) Set “multi-SP function” parameter to “1”
(2) Set “event input assignment 2” parameter to “
Event input 1 2
Run/Stop
Multi-SP
Set points 0 to 3 are set as the set point according to event input. However, note that these parameters can not be set when the mul­ti-SP function is not selected. The following table shows the relation­ship between event inputs and set points 0 to 3.
Multi-SP Function 1 2
Event Input 1 1 2
Set Point 0 OFF OFF OFF Set Point 1 ON ON OFF Set Point 2 - OFF ON Set Point 3 - ON ON
When you have changed the set point in the PV/SP display , the set point of the currently selected is also simultaneously changed.
When you have switched between set point 0 to 3, the SP ramp function works if the SP ramp funct ion is enabled. The following example shows how the set point change s when you swit ch from set point 0 to set point
1.
set point 1
set point 0
Event input
SP
OFF
SP
ramp
Time
ON
4-- 9
CHAPTER 4 APPLIED OPERATION
JOther event input functions
Switch the parameter settings for each of the run/stop, remote/local and SP modes.
The switching operation of auto/manual is the same as that of the key.
There is no order of priority in event input and key operations. How­ever, run/stop or auto/manual event inputs must be set to either of ON or OFF. So, parameters will always follow event input even if you try to switch settings by key operation.
A/M
F Run/Stop
F Auto/Manual
F SP mode
When event input is set to “ON”, controller operation is stopped and the “STOP” LED lights. The content of event input is reflected in the run/stop” parameter (level 0 mode).
When event input is set to “ON”, the controller is switched for manual operation, and the “MANU” LED lights.
Turn event input ON/OFF while the controller is ON.
This function is enabled only when the “SP mode enable” parameter
(option mode) is set to “ON”.
When event input is set to “ON”, the remote SP (RSP) is taken as the set point, and the “RSP” LED lights. When event input is set to “OFF”, the local SP (LSP) is taken as the set point. The content of event input is reflected in the “SP mode” parameter (level 2 mode). For details on RSP/LSP, see 4.4 How to Use the Remote SP (page 4-11).
Parameters
4-- 10
Symbol Parameter Name: Mode Application
Multi-SP function : Option Event input functions
Event input assignment 1 and 2 : Option Event input functions
*
Set point 0 to 4 : Level 1 Multi-SP
**
*: and ** : to
4.4 How to Use the Remote SP
Taking a remote SP input (4 to 20 mA) as the set point is referred to as the “remote SP” function. The remote SP function is enabled only when the “remote SP (RSP) enable” parameter (option mode) is set to “ON”.
4.4 How to Use the Remote SP
JScaling
F Relationship with
set point limiter
Remote SP upper-and lower-limit values can be set by scaling.
Inputs within the range 4 to 20 mA (-10 to 110%) are allowed as
remote SP inputs. Inputs not within this range are regarded as out-of­range input values. In this case, input is clamped at the remote SP lower or upper limit values, and the “RSP” LED blinks.
If the output function “RSP input error” is assigned for when an out­of-range remote SP is input, the “RSP input error” output is turned ON. Control output also switches to the setting of the “MV at PV error” parameter.
Set the upper limit value in the “remote SP upper limit” parameter and the lower limit value in the “remote SP lower limit” parameter (option mode).
RSP (%)
Out-of-range input
Upper limit value
Lower limit value
(blinks of upper-and lower-limit values)
420
2.4 (-10%)
Input (mA)
21.6 (-110%)
When the “Set point upper limit” or “Set point lower limit” parame­ters are changed, the remote SP upper-and lower-limit values are for­cibly changed to the set point upper-and lower-limit values. The fol­lowing example shows how the remote SP upper-and lower-limit values are changed when the set point upper limit value is changed from A to B.
JSP mode
LSP
RSP
RSP enable
SP mode
Set point limiter
Before change
Changed to
upper limit value
RSP scaling range
Upper-and lower-limit values of the limiter
RSP scaling upper-and lower-limit values
A
B
Set point
Upper limit value changed from A to B
Set point
The set point held internally by the E5EK controller is referred to as the “local SP (LSP).”
If the multi-SP function is enabled, set points 0 to 3 are enabled for use as the local SP.
Use the “SP mode” parameter to switch between the remote SP and local SP. When the SP mode parameter is set to “
”(remoteSP), the “RSP” LED lights. When the SP mode parameter is set to “
”, the controller is in the local SP.
4-- 11
CHAPTER 4 APPLIED OPERATION
JRemote SP
monitor
JSP tracking
IntheremoteSP mode,theremoteSPcanbe monitoredontheNo.2 display for PV/SP. In the local SP mode, the remote SP can be moni­tored in the “remote SP monitor” parameter.
When the local SP is switched to from the remote SP when the SP tracking function is enabled, the local SP is changed so that the remote SP value is held at the SP value used immediately before switching. To use the SP tracking function, set the “SP tracking” parameter to “ON”.
The following figure shows how SP tracking works when the SP mode is switched.
RSP input
LSP1 LSP2
RSP2
SP mode LSP RSP LSP
JOperating
conditions
(1) When the remote SP is switched to when the set point is “LSP1”,
the SP is switched to “RSP2”.
(2) The SP shifts according to remote SP input.
(3) When the local SP is switched to, the set point becomes “LSP2” if
the SP tracking function is enabled. If this function is disabled, the SP will be switched to “LSP1”.
When the local SP is switched to the remote SP, the SP ramp will operate if the SP ramp function is enabled.
When the SP function is set to “ON”, the “SP mode” parameter is for­cibly changed to [
] and the local SP is taken as the set point.
During auto-tuning, remote SP input is not accepted. Auto-tuning is executed on the set point at the start of auto-tuning.
Remote SP is not subject to the standby sequence reset conditions.
Parameters
4-- 12
Symbol
Parameter Name: Mode Application
Remote SP enable : Option Remote SP function
Remote SP upper limit : Option RSP scaling
Remote SP lower limit : Option RSP scaling
SP mode : Level 2 LSP/RSP switching
SP tracking : Option LSP/RSP switching
4.5 How to Use the Heater Burnout Alarm
4.5 How to Use the Heater Burnout Alarm
On a standard type controller, the HBA (heater burnout alarm) func­tion can be used only when the assignment destination of the output function “control output (heat)” is set to pulsed output.
When using the HBA function, assign output function “heater burn­out (HB) alarm” to auxiliary outputs 1 or 2.
JHeater burnout
detection
To E5EK CT terminal
CT
Heater wire
F HBA
latch/release
Heater burnout detection works as follows.
(1) Connect the current transformer (CT) to terminal Nos.15 and 17,
and insert the heater lead through the CT hole.
(2) When current flows through this lead, the current transformer gen-
erates AC current proportional to the current value. The E5EK measures this AC current to calculate the current flowing to the heater.
(3) If heater is burned out, the current measured at the current trans-
former decreases. This value is compared with the value set as the heater burnout set value and is output as the heater burnout alarm.
Set the heater burnout set value in the “heater burnout alarm” parameter. To check the current value of the current transformer, use the “heater current monitor” parameter.
When you are not using the HBA function, set the “heater burnout alarm” parameter to “0.0 (disabled)”.
When the HBA latch function is set to “ON”, the heater burnout alarm is held until either of the following measures is taken:
a Set the heater burnout set value to “0.0”. b Reset the controller.
(Turn the controller’s power OFF then back O N again.)
To enable the HBA latch function, set the “HBA latch” parameter to “ON”.
JOperating
conditions
Turn the heater power supply ON at the same time as or before turn­ing the E5EK power supply ON. If the heater p ower supply is turned ON after turning the E5EK power supply On, the heater burnout alarm is output.
Control is continued even when the heater burnout alarm is output. (That is, the controller attempts to control the heater as if the heater burnout alarm has not occurred.) So, remedy the condition such as repairs which are caused by the heater burnout alarm.
The heater burnout alarm is detected only if the control output is continuously ON for 190 ms or more.
The rated current value may sometimes differ slightly from the actual current value flowing to the heater. Check the current value in an actual operating status in the “heater current monitor” parameter.
If there is little difference between the current in a normal status and the current in a burnout status, detection may become unstable. On a heater of current 10.0 A or less, maintain a difference of 1.0 A or more. On a heater of current 10.0 A or more, maintain a difference of
2.5 A or more.
Heater burnout alarm function cannot be used when controlling the heater by a phase control metho d or by a cycle control method. Also, 3-phaseheaterscannotbeused.
When detecting heater burnout on a 3-phase heater, use the K2CU-FVVA-VGS (with gate input terminal). (For details, see the respective data sheet.)
4-- 13
CHAPTER 4 APPLIED OPERATION
JHow to calculate
the heater burn­out set value
Calculate the set value by the following formula:
Set value =
(current value at normal operation + current value at burnout)
2
Setthecurrentvalueatburnoutwhentwoor moreheatersarecon­nected to the CT to the value at the time that the heater having the smallest current value burns out (the value when one of the heaters burns out with all heaters at the same current).
Make sure that the following condition is satisfied:
Heater of current 10.0 A or less Current value at normal operation --- current value at heater burnout 1A When resultant current is less than 1 A, detection is unstable. Heater of current 10.0 A or more Current value at normal operation --- current value at heater burnout 2.5 A When resultant current is less than 2.5 A, detection is unstab le.
The setting range is 0.1 to 49.9 A. Heater burnout is not detected when the setting is “0.0” or “50.0”. When the setting is “0.0”, the heater burnout alarm is set to “OFF”, and when the setting is “50.0”, the heater burnout alarm is set to “ON”.
Set the total current value at normal heater operation to 50 A or less. When set to 55.0 A or more, [
] is displayed in the “heater cur-
rent monitor” parameter.
F Examples of use
CT
17
1KWx3
CT
17
15
15
Control output
Control output
Heater
1KW
E5EK
Heater
E5EK
Example 1 : when using a 200 VAC, 1 kW heater
Current at n ormal operation =
1000
200
Current at heater burnout = 0A
AC200V
Set value =
5+0
2
=2.5A
Example 2 : when using three 200 VAC, 1 kW heaters
1000
200
1000
200
AC200V
Current at n ormal operation =
Current at burnout of one heater =
Set value =
15+10
2
= 12.5A
(current at nor mal operation---current at heater burn-
out = 15 --- 10 = 5A (2.5A)
= 5A (<10A)
×3 = 15A (10A)
×2 = 10A
Parameters
4-- 14
Symbol Parameter Name: Mode Application
Heater current monitor : Level 1 Heater current value monitor
Heater burnout : Level 1 Heater burnout detection
Heater burnout latch : Option Heater burnout detection alarm latch
4.6 LBA
4.6 LBA
The LBA (Loop Break Alarm) function can be used only on standard type controllers.
The LBA function can be used only when assigned as an output. Also, the LBA function does not work when a memory error or A/D con­verter error results.
LBA (Loop Break Alarm) is a function for judging that an error has occurred somewhere on the control loop and outputting an alarm when the process value does not change with the manipulated vari­able at a maximum or minimum state. Accordingly, the LBA function can be used as a means for detecting a malfunctioning control loop.
F LBA detection
time
F LBA detection
width
F LBA detection
example
Normally, when output is set to maximum or minimum, the process value rises or falls after the dead time has elapsed. LBA is output if the process value does not change in the predicted direction after a fixed amount of time has elapsed. This fixed amount of time is the “LBA detection time.”
LBA operation sometimes becomes unstable when the process value fluctuates considerably due to the control characteristics. The LBA detection width is provided so that changes with respect to output can be correctly detected. Changes smaller than the detection width due to LBA detection timing are not regarded as changes.
The following example describes what happens when a heater burn­out at maximum output.
LBA detection time
PV
LBA detection time
LBA detection width
Output
Time
Heater burnout
LBA judgment is carried out at each LBA detection time from the point of maximum output. In above figure, the process value (PV) is changing greatly at the 1st judgment timing, so LBA remains OFF.
At the 2nd judgment timing, the process value increases as indicated by the broken line of the process value is normal. This means that the change width exceeds the LBA detection width, and LBA output remains OFF.
If the heater burns out at the point shown in the above figure, the process value “decreases.” Accordingly, it is judged that “the process value is not changing in the increasing direction” at the 2nd judg­ment timing and the LBA output becomes ON.
LBA=ON
4-- 15
CHAPTER 4 APPLIED OPERATION
F Setting the LBA
detection time
F Determining the
LBA detection time
The LBA detection time is automatically set by auto-tuning (except in heating and cooling control).
If the optimum LBA detection time cannot be obtained by auto-tun­ing, set the time in the LBA detection time” parameter (level 2 mode).
Calculate the LBA detection time as follows:
(1) Set output to maximum.
(2) Measurethetimeittakesfortheinputchangewidthtoreachthe
LBA detection width (default: 0.2 % full-scale).
(3) Take a value twice that of the measurement time as the LBA detec-
tion time.
Measurement time Tm
PV
0.2%FS
Output
Time
LBA detection time = Tm x 2
(4) In the case of ON/OFF operation, set the LBA detection time to a
value longer than the control period.
Parameters
4-- 16
Symbol Parameter Name: Mode Application
AT Execute/Cancel : Level 1 Automatic setting of LBA detec-
tion time
LBA detection time : Level 2 Setting of LBA detection time
LBA detection width : Expansion Changing of LBA detection
width
4.7 How to Use Transfer Output
When using transfer output , add on the communications unit (E53-AKF).
4.7 How to Use Transfer Output
F Transfer output
type
F Transfer output
scaling
You can select the following data items in the “transfer output type” parameter (option mode) as the transfer outputs:
Set point Set point during SP ramp Process value Manipulated variable (heat) Manipulated variable (cool), and Valve opening.
However, note that heating/cooling side manipulated variables can be output only standard type controllers, and valve opening can be out­put on position-proportional type controllers
If the output assignment is changed when either ”mani pulated vari­able (heat)” or ”manipulated variable (cool)” parameter is selected, the default ”set point” is returned to.
Thesetransferoutputscanbescaled according to the settings of the “transfer output upper limit” and “transfer output lower limit” parameters before output. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out. Also, the scale can be enlarged by the upper-and lower­limit width specified for each data item. The following example shows scaling of the reading side manipulated variable.
Transfer output Transfer output
(mA)
20
4
Transfer output upper limit: 0
Reverse scaling Enlarged scale
Manipu-
Transfer output lower limit: 100
lated variable (%)
(mA)
20
4
0
Transfer output lower limit: 10
Transfer output upper limit: 80
100
Manipulated variable (%)
4-- 17
CHAPTER 4 APPLIED OPERATION
If “input type”, “scaling upper/lower limit”, “SP limitter upper/lower limit”, or “°C/°F selection” parameters is changed when “set point”, “set point during SP ramp”, or “process value” parameter is selected, each of the “transfer output upper limit” and “transfer output lower limit” parameters are forcibly changed to their respective upper or lower limit values.
Change value
SP limitter
Transfer type scaling range
A
Change upper limit value A to B.
Set point
Limitter upper limit
change value
Limitter upper/lower limit values
Transfer ty pe scaling upper/lower limit values
B
Set point
Parameters
4-- 18
Symbol Parameter Name: Mode Application
Transfer output type : Option Transfer output designation
Transfer output upper limit : Option Transfer output scaling
Transfer output lower limit : Option Transfer output scaling
CHAPTER5
CHAPTER 5
PARAMETERS
This chapter describes the parameters of the E5EK. Use this chapter as a reference guide.
CHAPTER 5 PARAMETERS
ConventionsUsedinthisChapter 5-2............
Protect Mode 5-3...............................
Manual Mode 5-5..............................
Level 0 Mode 5-6...............................
Level 1 Mode 5-10...............................
Level 2 Mode 5-18...............................
Setup Mode 5-25................................
Expansion Mode 5-32............................
Option Mode 5-37...............................
Calibration Mode 5-46...........................
5-- 1
CHAPTER 5 PARAMETERS
Conventions Used in this Chapter
JThe meaning of icons used in this chapter
Describesthefunctionsoftheparameter.
Function
Describes the range and defaults of the parameter setting.
Comment
Used for monitor-dedicated parameters. Describes the range of the monitor values.
Monitor
Describes a procedure using parameters in operating instructions.
Example of use
Describes related parameters and items.
See
Describes models of the E5EK or option units supporting the parameter being described.
Model
JAbout parameter display
On the E5EK controller, only parameters that can be used are displayed. These parameters are displayed only when the “Conditions of Use” on the right of the parameter heading are satisfied. However, note that the settings of protected parameters are still valid, and are not displayed regardless of the conditions of use.
AT Execute/cancel
Conditions of Use The controller must be in operation.
5-- 2
Mod
Protect Mode
The protect mode is for disabling (protecting) the functions of the menu key or
A/M
key. Before changing parameters in this mode, first make sure that protecting
A/M
the menu key or
key will not cause any problems in operation.
Function
Comment
To select this mode, press the minimum. To exit this mode, press the
A/M key and key simultaneously for 1 second
A/M
key and key down again simulta-
neously for 1 second minimum.
The following table shows the parameters supported in this mode and the page where the parameter is described.
Symbol
Parameter Name Page
Security 5-3
[A/M] key protect 5-4
Security
This parameter specifies which parameters are protected. However, note that the
protect mode and manual mode cannot b e protected.
When this parameter is set to “0” to “3”, only the modes indicated by the “f”
mark in the table below can be selected on the menu display. For example, when this parameter is set to “2”, only level 0 to 2 modes can be selected.
e
Calibration f Option f f Expansion f f Setup f f Level 2 f f f Level 1 f f f f Level 0 f f f f
Set value
0 1 2 3
When this parameter is set to “4” to “6”, operations in only the level 0 mode can
be selected, and the mode is not displayed o n the menu display.
When this parameter is set to “5”, only the “PV/SP” parameter in the level 0 mode can be used.
When this parameter is set to “6”, only the “PV/SP” parameter in the level 0 mode canbeused.(Thesetpointcannotchange.)
Default is “1”. (Only the calibration mode is protected.)
F Related article
3.5 Protect Mode (page 3-12)
See
5-- 3
CHAPTER 5 PARAMETERS
Protect Mode
[A/M] key protect
Invalidate the function of the key. In other words, you cannot switch between the auto and manual operations by key operation.
Function
Comment
See
[
[
Default = [
]:
]:
A/M
key protect ON
A/M
key protect canceled
]
F Related article
3.5 Protect Mode (page 3-12)
5-- 4
Function
Manual Mode
In this mode, manual operations are possible, and the “MANU” LED lights.
When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. When changing the manipulated vari­able, change it using the If this mode is switched to during auto-tuning, auto-tuning is canceled.
To select this mode when in the level 0 to 2 modes, press the minimum. To exit this mode, press the changes to the level 0 mode.
“Manual MV” is the only parameter available in this mode.
Manual MV
Sets the manipulated variable for manual operation or the valve opening. On a stan­dard type controller when you press the
changed . On a position-proportional type controller when you press the key, the open side becomes ON, and when you press the
On a standard type controller, the process value is displayed on the No.1 display
and the manipulated variable is displayed on the No.2 display.
or keys.
A/M
A/M
key for 1 second
key for 1 second minimum. The mode
or keys, the manipulate d variable is
key, the close sid e becomes ON.
Comment
Process value
Manipulated variable
[MANU] LED
When a potentiometer is connected on a position-proportional type controller, the process value is displayed on the No.1 displayed, and the valve opening is dis­played on the No.2 display. When a potentiometer is not connected to the control­ler, [----] is displayed on the No.2 display.
Potentiometer connected Potentiometer not connected
Process value
Valve opening
[MANU] LED
Process value
Valve opening
[MANU] LED
On standard type controllers, the manual MV is held when the power is inter­rupted.
Standard type
Control Method Setting Range
Standard -5.0 to 105.0 % 0 Heating and cooling -105.0 to 105.0 % 0
Unit Default
See
Position-proportional type
Control Method
Position-proportional -10.0 to 110.0 %
Monitor Range Unit
F Related article
3.7 Adjusting Control Operation (page 3-14)
5-- 5
CHAPTER 5 PARAMETERS
Level 0 Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “4”.
The “PV/SP” parameter can be used when the “security” parameter is set to “5” or “6”. However, note that the SP cannot be changed when it is set to “6”.
This mode is used for monitoring the process value, set point and manipulated variable during operation, and for checking and setting the SP setting value. It is also used for starting and stopping controller operation.
To select this mode when in the levels 1 and 2, setup, expansion, option and cal­ibration modes, press the the menu display. If you select [ the controller enters the level 0 mode.
To select parameters in this mode, press the tings, use the
The following table shows the parameters supported in this mode and the page where the parameter is described.
key for 1 second minimum. The display changes to
]thenpress key for 1 second minimum,
key. To change parameter set-
or keys.
Function
Symbol
Parameter Name
PV/SP 5-6
Remote SP monitor 5-7
Set point during SP ramp 5-8
MV monitor (heat) 5-8
MV monitor (cool) 5-8
Valve opening monitor 5-9
Run/Stop 5-9
Page
PV/SP
The process value is displayed on the No.1 display, and the set point is displayed on the No.2 display. The set point can be set.
Either of the local SP or remote SP is displayed as the set point depending on the SP mode. In the remote SP mode, the set point is only monitored.
Local SP mode Remote SP mode
5-- 6
Process value
Set point
[RSP] LED not lit
[RSP] LED lit
Monitor only
The selected set point is linked when the multi-SP function is in use in the local SP mode. For example, when set point 1 is selected, set point 1 is displayed on the No.2 display, and the setting of the “set point 1” p arameter (level 1 mode) also is changed when the val ue of set point 1 is changed.
The decimal point position is dependent on the selected sensor during tempera­ture input and on the results of scaling during analog input.
Comment
See
Level 0 Mode
Level 0 Mode
Process value
Monitor Range
Scaling lower limit -10%FS to scaling upper limit +10%FS
Unit
EU
During temperature input, the range of the currently selected sensor is taken as the monitor range.
Set point
Setting Range/Monitor Range
Local SP : Local SP lower limit to local SP setting upper limit
Remote SP: Remote SP lower limit to remote SP upper limit
Unit Default
EU 0 EU -
F Related article
3.7 Adjusting Control Operation (page 3-14)
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decim al point” (setup mode) “SP setting upper limit” “SP setting lower limit” (expansion mode) “SP mode” (level 2 mode) “Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option mode)
Function
Monitor
See
Remote SP monitor
Conditions of Use
The controller must be in the local SP mode with the remote SP function enabled.
Monitors remote SP in the local SP mode.
Monitor Range
Remote SP lower limit to Remote SP upper limit
Unit
EU
F Related article
4.2 Operating Condition Restrictions/SP ramp (page 4-6)
F Related parameters
“SP mode” (level 2 mode) “Remote SP enable” “Remote SP lower limit” “Remote SP upper limit” (option
mode)
5-- 7
CHAPTER 5 PARAMETERS
Level 0 Mode
Function
Monitor
See
Set point during SP ramp
Conditions of Use
The remote SP function must be enabled. When the remote SP function is disabled, this function can be used only when the SP ramp function is enabled.
Monitors the set point during SP ramp
Matches the set point of the “PV/SP” parameter when the set point is not during
SP ramp.
Monitor Range
Local SP : Local SP setting lower limit to local SP setting upper limit EU Remote SP : Remote SP lower limit to remote SP upper limit EU
Unit
F Related article
4.2 Operating Condition Restriction/SP ramp (page 4-6)
F Related parameters
“PV/SP” (level 0 mode) “SP ramp time unit” “SP ramp set value” (level 2 mode) “Set point upper limit” “Set point lower limit” (expansion mode) “SP mode” (level 2 mode) “Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option mode)
Function
Monitor
MV monitor (heat)
Conditions of Use
Control must be standard control or heating and cooling control.
MV monitor (cool)
This parameter cannot be set.
Monitors the manipulated variable on the heating or cooling side.
The manipulated variable in a standard control system is checked in the “MV
monitor (heat)” parameter.
The “MV monitor (cool)” parameter can be used only during heating and cooling control.
MV monitor (heat)
Control
Standard -5.0 to 105.0 % Heating and cooling 0.0 to 105.0 %
Monitor Range
MV monitor (cool)
Control
Heating and cooling 0.0 to 105.0 %
Monitor Range
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Unit
Unit
5-- 8
Model
Level 0 Mode
Function
Monitor
See
Model
Valve opening monitor
Conditions of Use
Control must be position-proportional control
Monitors the valve opening during position-proportional control.
Monitor Range
-10to+110 EU
Unit
F Related article
4.1 Selecting the Control Method/Position-proportional control (page 4-3)
E5EK-PRR2 AC100-240
E5EK-PRR2 AC/DC24
Function
Example of use
See
Run/Stop
This parameter is used for checking the operating status of the controller, and for specifying start and stop of operation.
When the “run/stop” function is assigned to event input, “stop” is set when event input is ON, and “run” is set when event input is OFF. There is no order of prior -
ity in key operations.
To start operation, set this parameter to [
stop operation, set this parameter to [ ]. When operation is stopped, the “STOP” LED lights.
Default is [
]
F Related article
3.6 Starting and Stopping Operation (page 3-13)
]pressthe or keys. To
5-- 9
CHAPTER 5 PARAMETERS
Level 1 Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “3”.
This mode contains the main parameters for adjusting control. These parameters include parameters for executing AT (auto-tuning), setting the alarm values, set­ting the control period, and setting PID parameters.
To select this mode when in the levels 0 and 2, setup, expansion, option and cal­ibration modes, press the the menu display. If you select [ mum, the controller enters the level 1 mode.
To select parameters in this mode, press the tings, use the
The following table shows the parameters supported in this mode and the page
where the parameter is described.
key for 1 second minimum. The display changes to
]thenpressthe key for 1 second mini-
key. To change parameter set-
or keys.
Symbol Parameter Name Page
AT Execute/Cancel 5-11
Set point 0
Set point 1
Set point 2
Set point 3
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
Cooling coefficient
Dead band
Position-proportional dead band 5-14
Manual reset value
Hysteresis (heat)
Hysteresis (cool)
Control period (heat)
5-11
5-11
5-11
5-11
5-12
5-12
5-12
5-12
5-12
5-12
5-13
5-14
5-15
5-15
5-15
5-16
5-- 10
Control period (cool)
Heater current monitor 5-17
Heater burnout 5-17
5-16
Level 1 Mode
Function
Example of use
See
AT Execute/Cancel
Conditions of Use
The controller must be in operation, con­trol must be advanced PID control, and ST must be set to OFF.
Selects the limit cycle of MV change width (40% or 100%) for execution. After AT execution, the “PID” and the “LBA detection time” (LBA: Loop Break Alarm) parameters are set automatically.
During heating and cooling control or position-proportional control, only 100%AT can be executed.
When this parameter is selected, the setting becomes [
To execute 40%AT, select [
], and to execute 100%AT, select [ ]. During
].
execution of auto-tuning, the AT LED flashes. However, note that during heating and cooling control or position-proportional control, [
] is not displayed.
When AT execution ends, the parameter setting automatically returns to [ ].
F Related article
3.7 Adjusting Control Operation (page 3-16)
F Related parameters
“Run/Stop” (level 0 mode) “Proportional band” “Integral time” “Derivative time” (level 1 mode) “LBA detection time” (level 2 mode)
Function
Set point 0
Set point 1
Set point 2
Set point 3
Conditions of Use
The controller must be in the local SP mode with the multi-SP function enabled.
Switches set points 0 to 3 by event input for use as the set point (local SP).
Of set points 0 to 3, the number of valid set points is designated by the “multi-SP
function” parameter.
The following table shows the relationship between event input and the selected parameter.
Multi-SP Function 1 2
Event Input 1 1 2
Set Point 0 OFF OFF OFF Set Point 1 ON ON OFF Set Point 2 - OFF ON Set Point 3 - ON ON
When the set point has been changed, the setting of whichever is selected in event input, “set point 0” to “set point 3”, is linked and changed.
The decimal point position is dependent on the selected sensor during tempera­ture input and on the results of scaling during analog input.
5-- 11
CHAPTER 5 PARAMETERS
Level 1 Mode
Comment
See
Model
Setting Range
Set point lower limit to Set point upper limit EU 0
Unit Default
F Related article
4.3 How to Use Event Input (page 4-8)
F Related parameters
“Multi-SP function” “Remote SP enable” (option mode) “Set point” (level 0 mode) “SP mode” (level 2 mode) “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
F Option unit
E53-AKB
Alarm value 1
Conditions of Use
Alarms must be assigned as outputs. For
Alarm value 2
example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm value 3”
Alarm value 3
parameter cannot be used.
Function
Comment
See
This parameter is used for monitoring or changing the alarm values of alarm outputs 1to3.
During temperature input, the decimal point position is dependent on the cur­rently selected sensor, and during analog input on the results of scaling.
Setting Range
-1999 to 9999 EU 0
Unit Default
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” Decimal point” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assign­ment” “Auxiliary output 2 assignment” “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Standby sequence reset method” (expansion mode)
5-- 12
Level 1 Mode
Function
Comment
Proportional band
Conditions of Use
Control must be advanced PID control,
Integral time
and ST must be set to OFF.
Derivative time
Sets the PID parameters. However, note that the PID parameter settings are changed to optimum values when auto-tuning is executed, and self-tuning is selected.
Parameter Setting Range
Proportional band 0.1 to 999.9 %FS 10.0 Integral time 0 to 3999 (see note1) Second 233 Derivative time 0 to 3999 Second 40
note1 : During p osition-proportional con tro l, the setting range become 1 to 3999s.
F Related parameter
“AT Execute/Cancel” (level 1 mode)
Unit Default
See
Function
Comment
See
Cooling coefficient
Conditions of Use
The control must be either heating and cooling control, or advanced PID control.
In heating and cooling control, P at the cooling side is calculated by the following formula: Cooling side P = cooling coefficient ¢ P
Setting Range
0.01 to 99.99 None 1.00
Unit Default
F Related article
4.1 Selecting the Control Method (page 4-2)
F Related parameter
“Proportional band” (level 1 mode)
Model
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
5-- 13
CHAPTER 5 PARAMETERS
Level 1 Mode
Function
Comment
See
Model
Dead band
Conditions of Use
The control system must be heating and cooling control.
Sets the output dead band width in a heating and cooling control system. A nega­tive setting sets an overlap band.
Setting Range
-19.99 to 99.99 %FS 0.00
Unit Default
F Related article
4.1 Selecting the Control Method (page 4-2)
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Position-proportional dead band
Conditions of Use
Control must be position-proportional control
Function
Comment
See
Sets the output hold width during position-proportional control (ON/OFF switch­ing point for open and close output).
Open/close hysteresis
Dead band
ON
OFF
Setting Range
0.1 to 10.0 % 2.0
Unit Default
MV--Valve opening
100%0-100%
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4 -3).
F Related parameter
“Open/close hysteresis” (level 2 mode)
E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24
5-- 14
Model
Level 1 Mode
Function
Comment
Model
Manual reset value
Conditions of Use
The control must be either standard con­trol or advanced PID control, ST must be set to OFF , and the “integral time” parameter must be set to “0”.
Sets the required manipulated variable to remove offset during stabilization of P
or PD control.
Setting Range
0.0 to 100.0 % 50.0
Unit Default
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Hysteresis (heat)
Conditions of Use
The control system must be ON/OFF
Hysteresis (cool)
control.
Function
Comment
See
Sets the hysteresis for ensuring stable operation at ON/OFF switching.
In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)”
parameter cannot be used.
In heating and cooling control, the hysteresis can be set independently for heating and cooling. Use the “hysteresis (heat)” parameter to set the heating side hystere-
sis, and use the “hysteresis (cool)” parameter to set the cooling side hysteresis.
Parameter Setting Range
Hysteresis (heat) 0.01 to 99.99 %FS 0.10
Hysteresis (cool) 0.01 to 99.99 %FS 0.10
Unit Default
F Related article
4.1 Selecting the Control Method
/ON/OFF control (page 4-4)
F Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode) “PID / ON/OFF” (expansion mode)
E5EK-AA2 AC100-24 E5EK-AA2 AC/DC24
Model
5-- 15
CHAPTER 5 PARAMETERS
Level 1 Mode
Function
Comment
See
Control period (heat)
Conditions of Use
Relay or voltage output must be set as the outputs, and the control must be set
Control period (cool)
to advanced PID control, standard con­trol or heating and cooling control.
Sets the pulse output period. Set the control period taking the control characteris­tics and life expectancy of the controller into consideration.
In standard control, use the “control period (heat)” parameter. The “control period (cool)” parameter cannot be used.
In heating and cooling control, the control period can be set independently for heating and cooling. Use the “control period (heat)” parameter to set the heating side control period, and use the “control period (cool)” parameter to set the cool-
ing side control period.
Parameter Setting Range
Control period (heat) 1to99 Second 20
Control period (cool) 1to99 Second 20
Unit Default
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
Model
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
5-- 16
Level 1 Mode
Function
Monitor
See
Model
Heater current monitor
Conditions of Use
The HBA output function must be assigned.
Measures the current value of the heater from CT input.
Monitor Range Unit
0.0 to 55.0 A
[ ] is displayed when 55.0 A is exceeded.
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
“Heater burnout” (level 1 mode) “HBA latch” (option mode)
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Function
Comment
See
Heater burnout
Conditions of Use
The HBA output function must be assigned.
Outputs the heater burnout alarm when the heater current value falls below this parameter setting.
When the set value is “0.0”, the heater burnout alarm is “OFF”. When the set value is “50.0”, the heater burnout alarm is “ON”.
Setting Range Unit Default
0.0 to 50.0 A 0.0
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
“Heater current monitor” (level 1 mode) “HBA latch” (option mode)
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
5-- 17
CHAPTER 5 PARAMETERS
Level 2 Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “2”.
This mode contains the auxiliary parameters for adjusting control. These parame­ters include parameters for limiting the manipulated variable and set point, parameters for switching between remote and local operation, and parameters for
setting the LBA (Loop Break Alarm), alarm hysteresis, and input digital filter values.
To select this mode when in the levels 0 and 1, setup, expansion, option and cal­ibration modes, press the
the menu display. If you select [ ]usingthe key then press the key for 1 second minimum, the controller enters the level 2 mode.
To select parameters in this mode, press the
tings, use the or keys.
The following table shows the parameters supported in this mode and the page where the parameter is described.
key for 1 second minimum. The display changes to
key. To change parameter set-
Symbol Parameter Name Page
Remote/Local 5-19
SP mode
SP ramp time un it
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
Input digital filter
Open/close hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
5-19
5-20
5-20
5-21
5-21
5-21
5-22
5-22
5-22
5-23
5-23
5-24
5-24
5-24
5-- 18
Input shift upper limit (temperature)
Input shift lower limit (temperature)
5-24
5-24
Level 2 Mode
Function
Comment
See
Remote/Local
Conditions of Use
The communications function must be in use.
Switches between remote and local operation.
To change the parameter setting during remote operation, use the communica-
tions function. To change the parameter setting during local operation, change the setting on the E5EK controller.
You can check the parameter setting by both communications and on the E5EK controller regardless of whether the controller is switched to remote or local operation.
Setting Range
[ ]: remote / [ ]: local
Default
[]
F Related article
Chapter 6 Using the Communications Function
F Related parameters
“Communication stop bit” “Communication data length” “Communication par­ity” “Communication baud rate” “Communication unit No.” “Event input assign­ment 1” “Event input assignment 2” (option mode)
F Option units
E53-AK01/02/03
Model
Function
Comment
See
SP mode
Conditions of Use
The remote SP function must be enabled and ST must be set to OFF.
Switches between remote SP and local SP.
Switches the SP to the remote SP when an event input to which the “SP mode”
has been assigned is ON. Switches the SP to the local SP when an event input to which the “SP mode” has been assigned is OFF.
Setting Range Default
[ ]: Remote SP/[ ]: Local SP
F Related article
4.4 How to Use the Remote SP (page 4-11)
F Related parameters
“Remote SP enable” “Event input assignment 1” “Event input assignment 2” “Event input assignment 3” “Event input assignment 4” (option mode)
5-- 19
CHAPTER 5 PARAMETERS
Level 2 Mode
Function
Comment
SP ramp time unit
Conditions of Use
ST must be set to OFF.
SP ramp set value
Specifies the change rate during SP ramp operation. Set the maximum permissi-
ble change width per unit of time (minute or hour) as the “SP ramp set value”. However, note that when set to “0”, the SP ramp function is disabled.
The time unit and SP ramp set value are independent of each other. For example, when setting “30 per minute”, set the “SP ramp set value” parameter to “30” and
the “SP ramp time unit” parameter to [ thetimeunitonlyto[
] (“hour”), the set time becomes “30 per hour.”
During temperature input, the decimal point position of the SP ramp set value is
dependent on the currently selected sensor, and during analog input on the results of scaling.
Parameter Setting Range
SP ramp time un it
SP ramp set value 0 to 9999 EU 0
[ ]: minute/ [ ]: hour
During temperature input, the range of the currently selected sensor it taken as the setting range for the “SP ramp set value” parameter.
] (“minute”). However, if you change
Unit Default
None
See
F Related article
4.2 Operating Condition Restrictions/SP ramp (page 4-6)
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
5-- 20
Level 2 Mode
Function
Comment
See
LBA detection time
Conditions of Use
The LBA (Loop Break Alarm) function must be assigned as an output.
This parameter is automatically set by AT execution (excluding AT execution in a ON/OFF control).
The LBA is output if the change width of the process value falls below 0.2 %full­scale of the time preset to this parameter when the manipulated variable is set in the “MV upper limit” or “MV lower limit” parameters.
The LBA function is disabled when this parameter is set to “0”.
Setting Range
0 to 9999 Second 0
Unit Default
F Related article
4.4 LBA (p age 4-9)
7.3 How to Use Error Output (page 7-5)
F Related parameters
“AT Execute/Cancel” (level 1 mode) “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” (setup mode)
Function
Comment
MV at stop
Conditions of Use
Advanced PID control
MV at PV error
The “MV at stop” parameter sets the manip ulated variable when operation stops on a standard type controller. On a position-proportional type controller, this parameter sets the action (close/hold/open) when operation stops.
The “MV at PV error” parameter sets the manipulated variable when an input error occurs. On a position-proportional type controller, this parameter sets the action (close/hold/open) when an input error occurs.
Standard type
Control Method Setting Range
Standard -5.0 to 105.0 % 0 Heating and cooling -105.0 to 105.0 % 0
The manipulated variable at the cooling side during heating and cooling control is expressed as a negative value.
Position-proportional type
Setting Range
[ ]: Hold/[ ]: Open/[ ]: Close None
Unit Default
Unit Default
See
F Related articles
MV at stop : 3.6 Starting and Stopping Operation (page 3-13) MV at P V error : 8.2 How to Use the Error Display (page 8-3)
5-- 21
CHAPTER 5 PARAMETERS
Level 2 Mode
Function
MV upper limit
Conditions of Use
The control must be advanced PID con-
MV lower limit
trol, and ST must be set to OFF.
MV change rate limit
The “MV upper limit” and “MV lower limit” parameters set the upper and lower
limits of the manipulated variable. When the manipulated variable calculated by the E5EK controller is outside of the upper-and lower-limit range, the upper limit or lower limit set to these parameters is output, respectively. However, note that these parameters are disabled during position-proportional
control.
The “MV change rate limit” parameter sets the maximum permissible change width per second of the manipulated variable (On the position-proportional con­trol, valve, opening). If a change in the manipulated variable (On the position-pro­portional control, valve, opening) causes this parameter setting to be exceeded, the
calculated value is reached while changing the value by the per-second value set in this parameter. This function is disabled when the set value is “0.0”.
Comment
MV upper limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value.
Control Method Setting Range
Standard MV lower limit +0.1 to 105.0 % 105.0 Heating and cooling 0.0 to 105.0 % 105.0
Unit Default
MV lower limit The setting ranges during standard control and heating and cooling control are
different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value.
Control Method Setting Range
Standard -5.0 to MV upper limit -0.1 % -5.0 Heating and cooling -105.0 to 0.0 % -105.0
Unit Default
MV change rate limit
Setting Range
0.0 to 100.0 % 0.0
Unit Default
5-- 22
F Related article
4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-5)
See
Level 2 Mode
Input digital filter
Sets the time constant of the input digital filter. The following figures shows the effect on data after passing through the digital filter.
Function
Comment
PV before passing through filter
A
Tim e constant
Input digital filter
Setting Range
0 to 9999 Second 0
Unit Default
Open/close hysteresis
PV after passing through filter
0.63A
Time
Conditions of Use
Control must be position-proportional control.
Function
Comment
See
Model
Provides hysteresis at ON/OFF switching of open or close output in position-pro­portional control.
Setting Range
0.1 to 20.0 % 0.8
Unit Default
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4 -3)
E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24
5-- 23
CHAPTER 5 PARAMETERS
Level 2 Mode
Function
Comment
See
Alarm 1 hysteresis
Conditions of Use
Alarms must be assigned as outputs.
Alarm 2 hysteresis
For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm
Alarm 3 hysteresis
3 hysteresis” parameter cannot be used.
This parameter is for checking the hysteresis of alarm outputs 1 to 3.
Setting Range
0.01 to 99.99 %FS 0.02
Unit Default
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
“Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode)
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
Function
Comment
See
Input shift upper limit
Conditions of Use
The input type must be set to tempera-
Input shift lower limit
ture input (thermocouple or platinum resistance thermometer).
Sets each of the shift amounts for the input shift upper and lower limit values.
Setting Range
-199.9 to 999.9 _Cor_F 0.0
Unit Default
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
“Input type” (setup mode)
5-- 24
Setup Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” and “1”.
This mode contains the parameters for setting the basic specifications of the E5EK controller. These parameters include parameters for specifying the input type, scaling, output assignments, and direct/reverse operation.
To select this mode when in the levels 0 to 2, expansion, option and calibration modes, press the display. If you select [ second minimum, the controller enters the setup mode.
To select parameters in this mode, press the tings, use the
The following table shows the parameters supported in this mode and the page
where the parameter is described.
Symbol Parameter Name Page
key for 1 second minimum. The display changes to the menu
]usingthe key then press the key for 1
key. To change parameter set-
or keys.
Input type 5-26
Scaling upper limit
Scaling lower limit
Decimal point
_C/_F selection
Parameter initialize
Control output 1 assignment
Control output 2 assignment
Auxiliary output 1 assignment
Auxiliary output 2 assignment
Alarm 1 type
Alarm 1 open in alarm
Alarm 2 type
Alarm 2 open in alarm
Alarm 3 type
Alarm 3 open in alarm
Direct/Reverse operation
5-27
5-27
5-27
5-28
5-27
5-28
5-28
5-29
5-29
5-30
5-31
5-30
5-31
5-30
5-31
5-31
5-- 25
CHAPTER 5 PARAMETERS
Thermocoupl
e
Voltageinpu
t
Setup Mode
Input type
Sets the sensor type by the code.
Function
Set the code according to the following table. Default is “2: K1 thermocouple”.
Set value Input Type
Comment
0 JPt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F) 1 Pt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F) 2 K1 -200 to 1300 (_C) /-300 to 2300 (_F) 3 K2 0.0 to 500.0 (_C) /0.0 to 900.0 (_F) 4 J1 -100 to 850 (_C) /-100 to 1500 (_F) 5 J2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F) 6 T -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F) 7 E 0 to 600 (_C) /0 to 1100 (_F) 8 L1 -100 to 850 (_C) /-100 to 1500 (_F) 9 L2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
10 U -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
11 N -200 to 1300 (_C) /-300 to 2300 (_F) 12 R 0 to 1700 (_C) /0 to 3000 (_F) 13 S 0 to 1700 (_C) /0 to 3000 (_F) 14 B 100 to 1800 (_C) /300 to 3200 (_F) 15 W 0 to 2300 (_C) /0 to 4100 (_F) 16 PLII 0 to 1300 (_C) /0 to 2300 (_F) 17 4to20mA 18 0to20mA 19 1to5V 20 0to5V 21 0to10V
Platinum resistance thermometer
Thermocouple
Current input
Voltage input
5-- 26
See
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameters
When input type is set to temperature input: “_C/_F selection” (setup mode) When input type is set to voltage input or current input:
“Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
Setup Mode
Function
Comment
Scaling upper limit
Conditions of Use
The input type must be set to analog
Scaling lower limit
input (voltage or current input).
Decimal point
This parameter can be used only when voltage input or current input is selected as the input type.
When voltage input or current input is selected as the input type, scaling is car­ried out. Set the scaling upper limit in the “scaling upper limit” parameter and the scaling lower limit in the “scaling lower limit” parameter.
The “decimal point” parameter specifies the decimal point position of parameters (set point, etc.) whose unit is set to EU (Engineering Unit).
Scaling upper limit, Scaling lower limit
Parameter Setting Range
Scaling upper limit Scaling lower limit +1 to 9999 EU 100 Scaling lower limit -1999 to scaling upper limit -1 EU 0
Decimalpoint:default:0
Unit Default
See
Function
Set Value
0 1 2 3
0 digits past decimal point 1 digit past decimal point 2 digits past decimal point 3 digits past decimal point
Setting Example
1234
123.4
12.34
1.234
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
“Input type” (setup mode)
Parameter initialize
Returns parameter settings to their defaults. However, note that the following parameters are not affected by execution of this parameter: “input type”, “scaling upper limit”, “scaling lower limit”, “decimal point” and “_C/_F selection”.
When this parameter is selected, [ parameters, press the
key to specify [ ] (“yes”).
] (“no”) is first displayed. To initialize
Example of use
5-- 27
CHAPTER 5 PARAMETERS
Setup Mode
Function
Comment
See
_C/_F selection
Conditions of Use
The input type must be set to tempera­ture input (thermocouple or platinum resistance thermometer).
This parameter can be used when thermocouple or platinum resistance thermom­eter is selected as the input type.
Set the temperature input unit to either of “_C” or “_F”.
Setting Range
: _C/ :_F
Default
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
“Input type” (setup mode)
Control output 1 assignment
Conditions of Use
The control must be standard control or heating and cooling control.
Control output 2 assignment
Function
Comment
See
Assigns the output functions to either of control output 1 or 2.
The following seven output functions can be assigned as outputs:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, and LBA.
Errors 1, 2 and 3 cannot be assigned as outputs.
When the output function assigned to control output 1 is ON, the “OUT1” LED
lights. However , note that the OUT1 LED does not light when control output (heat) or control output (cool) are assigned to linear outputs such as curre nt and voltage.
When the output function assigned to control output 2 is ON, the “OUT2” LED lights.
Symbol
Function
Control output
(heat)
Control output
(cool)
Alarm 1 Alarm 2 Alarm 3 HBA LBA
Defaults: “Control output 1” = [
], “Control output 2” = [ ]
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameters
Alarm-related parameters
Heating and cooling related parameter
“LBA detection time” (level 2 mode)
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
5-- 28
Model
Function
Comment
Setup Mode
Auxiliary outp ut 1 assign ment
Auxiliary outp ut 2 assign ment
Assigns output functions to either of auxiliary output 1 or 2.
The following eight output functions can be assigned as outputs:
Alarms 1 to 3, HBA, LBA, Error 1 (input error), Error 2 (A/D converter error), and Error 3 (remote SP input error).
Control output (heat) and control output (cool) cannot be assigned as outputs.
Error 3 can be assigned only when the remote SP function is enabled.
When the output function assigned to auxiliary output 1 or auxiliary output 2 is
ON, the “SUB1” or “SUB2” LED lights.
Symbol
Function Alarm 1 Alarm 2 Alarm 3 HBA LBA Error 1 Error 2 Error 3
Defaults: “Auxiliary output 1”= [ ], “Auxiliary output 2”= [ ]
See
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameter
Alarm-related parameter “LBA detection time” (level 2 mode)
5-- 29
CHAPTER 5 PARAMETERS
Setup Mode
Function
Comment
Alarm 1 type
Conditions of Use
Alarms must be assigned as outputs.
Alarm 2 type
For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm
Alarm 3 type
3 type” parameter cannot be used.
“Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of the set values in the following table. For details of operation at an alarm, see page 3-9.
Set Value Settings Set Value Settings
1 Upper-and lower-limit alarm
(deviation)
2 Upper-limit alarm (deviation) 8 Absolute-value upper-limit alarm 3 Lower-limit alarm (deviation) 9 Absolute-value lower-limit alarm 4 Upper-and lower-limit range alarm
(deviation)
5 Upper-and lower-limit alarm with
standby sequence (deviation)
6 Upper-limit alarm with standby
sequence (deviation)
7 Lower-limit alarm with standby
sequence (deviation)
10 Absolute-value upper-limit alarm with
standby sequence
11 Absolute-value lower-limit alarm with
standby sequence
Defaults: 2 (Deviation upper limit)
See
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Con­trol output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 as­signment” “Auxiliary output 2 assignment” (setup mode)
5-- 30
C
l
O
Setup Mode
Function
Comment
Alarm1openinalarm
Conditions of Use
Alarms must be assigned as outputs. For
Alarm2openinalarm
example, if alarm outputs 1 and 2 only are assigned as outputs, the alarm 3 open in
Alarm3openinalarm
alarm” parameter cannot be used.
Selects the output states of alarms 1 to 3.
When the controller is set to “close in alarm,” the status of the alarm output func-
tion is output as it is. When set to “open in alarm,” the status of the alarm output function is output inverted. T he following table shows the relationship between alarm output functions, output and output LEDs.
Alarm
oseinalarm
peninalarm
Setting Range
[ ] : Close in alarm/ [ ]:Open in alarm
ON ON Lit
OFF OFF Not lit
ON OFF Lit
OFF ON Not lit
Output Output LED
Default
[]
See
Function
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” “Auxiliary output 2 assignment”(setup mode)
Direct/Reverse operation
“Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the manipulated variable is increased
according to the decrease in the process value.
Setting Range
[ ] : Reverse operation/ [ ]:Direct operation []
Default
Comment
F Related article
3.3 Setting Output Specifications/Direct/reverse operation (page 3-7)
See
5-- 31
CHAPTER 5 PARAMETERS
Expansion Mode
The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” and “1”.
This mode contains the parameters for setting expanded functions. These parame­ters include parameters for setting ST (self-tuning), setting the SP setting limiter, selecting advanced PID and ON/OFF control, specifying the standby sequence re-
set method, and automatic return of display mode.
To select this mode when in the levels 0 to 2, setup, option and calibration modes, press the play. If you select [
cond minimum, the controller enters the expansion mode.
To select parameters in this mode, press the tings, use the
The following table shows the parameters supported in this mode and the page where the parameter is described.
Symbol Parameter Name Page
key for 1 second minimum. The display changes to the menu dis-
]usingthe key then press the key for 1 se-
key. To change parameter set-
or keys.
Set point upper limit 5-33
Set point lower limit 5-33
PID / ON/OFF 5-33
ST 5-34
ST stable range 5-34
α 5-34
AT calculated gain 5-35
Standby sequence reset method 5-35
Automatic return of display mode 5-36
AT hysteresis 5-36
LBA detection width 5-36
5-- 32
Loading...