1/16 DIN Sized Controller Offers
Selectable Control, Alarm Modes
Accurate to ±0.5% of full scale
H
H Multiple temperature scale ranges allow
flexibility to match application
H Field-selectable temperature ranges in
°F and °C
H Selectable ON/OFF and PID control
with auto-tuning of proportional band
H 8-function alarm, standard
H Tamper-proof setting, faulty sensor
compensation and controller diagnostics
H Easy-to-read 11 mm high LED display
E5CS-X
RC
H Nonvolatile memory backup
H 3-year warranty
Ordering Information
J TEMPERATURE CONTROLLERS
ItemPart number
Sensor input typeThermocouple
Output
Temperature Ranges
Thermocouple Input Type
Input type
Temperature range0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500
Scale indication°C°C°C/°F°C/°F°C/°F°C/°F°F°C°C°C/°F°C/°F
Unit of measure1° C or F
Platinum RTD Input Type
Temperature range
Scale indication°C°C°C°C/°F°C/°F°C°C/°F°F°F
Unit of measure1° C or F0.1° C or F 1° C or F0.1° C or F 1° C or F
–50 to 500.0 to 50.0–20 to 800.0 to 99.90 to 2000 to 3000 to 4000 to 6000 to 800
(Types J and K)
Platinum RTD (Pt: 100 Ω,
DIN and JIS standards)
Interchangeable thermistor
(THE types)
Thermistor Input Type
Temp. range
Scale indication °C°F
Unit of measure 1° C or F
–50 to 500 to 10050 to 150100 to 200150 to 300–50 to 1000 to 200100 to 300200 to 400300 to 600
37
Page 2
E5CS-XE5CS-X
J ACCESSORIES (ORDER SEPARATELY)
DescriptionPart number
Protective coverHard plastic; protects front panel against dust, dirt and water dropsY92A-48
Panel mounting adapterReplacement for one supplied with each unitY92F-30
Specifications
Part number
Sensor input typeThermocouple
Supply voltage100 to 240 VAC, 50/60 Hz; operates on 85 to 110% of rated voltage
Power consumptionApprox. 7 VA
ControlContact
output
VoltageLogic load12 VDC, 20 mA with short-circuit protection
Hysteresis0.2% of full scale during ON/OFF control action
Response
time
Service life
Alarm output
Setting accuracySet value coincides with indicated value, so no relative error exists
Indication accuracy±0.5% of full scale, ±1 digit max.
Display range–999 to 999 (limited to input type)
Control
modes
MaterialsPlastic case
MountingFits 1/16 DIN panel cutout; includes panel mounting adapter
ConnectionsScrew terminals
Weight170 g (6 oz.) without mounting adapter
Enclosure ratings
Approvals
Ambient temperature
Humidity35 to 85% RH
Insulation resistance20 MΩ minimum at 500 VDC
Dielectric strength2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals of different polarity
Vibration
Shock
TypeON/OFF and PID with automatic tuning of proportional band, switch selectable
Proportional band3% to 20% (in PID mode) automatically adjusted according to the rise time of the
Reset time4 minutes (in PID mode)
Rate time0.4 minutes (in PID mode)
Proportional period2 or 20 seconds, switch selectable
Sampling period500 ms
Mechanical durability10 to 55 Hz, 0.75 mm (0.03 in) double amplitude in X, Y, and Z directions for 2 hours each
Malfunction durability2 to 55 Hz, 2 G in X, Y, and Z directions for 10 minutes each
Mechanical durability30 m/s2, in 6 directions, 3 times each
Malfunction durability100 m/s2, in 6 directions, 3 times each
TypeSPDT relay
Max. load3 A, 250 VAC (resistive load)
Output2 seconds for output to change
Display2 seconds for displayed indication to change
Mechanical10 million operation minimum with contact output
Electrical100,000 operations minimum with contact output
TypeSPST-NO relay
Max. load1 A, 250 VAC (resistive load)
Setting rangeAbsolute value alarm: Same as control output setting range
Front panelIP50, NEMA 4 with optional Y92A-48N waterproof cover
Rear panelIP30
TerminalsIP00
ULRecognized, File Number E68481
CSACertified, File Number LR59623
CEConforms to EN61010-1
Operating–10°C to 55°C (14°F to 131°F)
Storage–25°C to 65°C (–13°F to 149°F)
E5CS-j1KJXE5CS-j1PXE5CS-j1GX
Type J (IC) and Type K (CA)
Others: 0 to full scale
controlled system
Platinum RTD (Pt: 100Ω)
DIN or JIS standard
Thermistor
(interchangeable type)
38
Page 3
E5CS-XE5CS-X
Nomenclature
1. Main
9. Deviation indicators
display
2. Control output indicator
8. Display data identifier
7. Write protection key
6. Return key
5. Down key
KeyDescriptionKeyDescription
1Main display sequentially displays the present
temperature, set temperature, and an alarm value each
time the return key is pressed.
2Control output indicator lights when the output is ON.
3Alarm indicator lights when the alarm output is ON.
4Up key increases the set temperature or alarm value when
pressed. Increases the value quickly when held down.
5Down key decreases the set temperature or alarm value
when pressed. Decreases the value quickly when held
down.
6Return key changes the value displayed on the main
display each time pressed.
7The hidden write protection key provides protection against
unauthorized setting of temperature and is used in conjunction with the internal “protection” switch. If the internal
protection switch is set to ON, then to obtain Up and Down
operation, the hidden key must be pressed simultaneously
with the Up and Down keys. If the internal protection switch
with the Up and Down keys. If the internal protection switch
is set to OFF, changes can be made simply by pressing the
Up and Down keys.
8Display data identifier lights SP when the set temperature is
displayed on the main display and AL when an alarm value
is displayed.
9Red deviation indicators light up an arrow when the present
temperature is higher than the set temperature and light a
down arrow when the present value is lower than the set
temperature. The green block indicates the temperature
deviation is within ±1% of the full scale.
Dimensions
3. Alarm indicator
4. Up key
Unit: mm (inch)
48
(1.89)
6
(0.24)
106 (4.2)
90 (3.54)
Panel CutoutSide-by-side Mounting of Several Temperature Controllers
Max. 60
(2.36)
45
(1.77)
+0.6
–0
45
(1.77)
+0.6
–0
+0.6
–0
45
(1.77)
L = 48 x number of units – 2.5
(1.89 x number of units –0.1)
Controllers 23456
L
93.5
(3.68)
+1
141.5
–0
(5.57)
Note: 1. Recommended panel thickness is 1 to 8 mm (0.04 to
0.31 in).
2. Because mounting brackets are attached to the top
and bottom of a temperature controller, tight side-byside mounting is possible.
10
(0.39)
+1
–0
189.5
(7.46)
+1
–0
237.5
(9.35)
+1
–0
285.5
(11.24)
+1
–0
39
Page 4
E5CS-XE5CS-X
Connections
Voltage output type
Contact output type
20 mA, 12 VDC
Thermocouple input type
Platinum RTD input type
Thermistor input type
Operation
J SETTINGS BEFORE APPLYING POWER
Note: Always turn off the power supply to the temperature control-
ler before changing any switch settings.
Before applying power to the temperature controller, set the
following selector switches to specify the temperature range,
functions and alarm mode.
100 to 240 VAC, 50/60 Hz
Alarm output
Temperature range selector switch
Alarm mode selector switch
Protection switch
Control mode selector switch
J ACCESS TO INTERNAL SWITCHES AND
SELECTORS
Push the tab on the underside of the front panel as you draw out
the internal mechanism from the housing. The temperature range
selector, and the alarm mode selector must all be set. A
protection switch can also be set to protect settings. The
following diagrams show the locations of these switches on the
internal mechanism.
Right side view
Select the desired temperature range by using the temperature
range selector switch (rotary DIP type). The other rotary DIP
switch is used to select one of eight alarm functions. Be sure the
set temperature and alarm values are within the new range.
Otherwise, the temperature controller automatically shifts these
values to the maximum or minimum of the newly-set temperature
range.
The protection switch may be used in conjunction with the front
panel “hidden key” to prevent unauthorized changes to
temperature settings. The switch is ON when it is pushed inwards
in the direction of the white arrow.
The function selector switch is a 8-pin in-line DIP switch on the
other side of the internal mechanism. Use it to select ON/OFF or
PID control action, proportional period, control output, input shift
function, temperature sensor input standard and scale indication
for dual-scale temperature ranges.
Left side view
40
Page 5
E5CS-XE5CS-X
J FUNCTION SELECTOR SWITCH
ON
ON
The function selector switch is a 6-pin in-line DIP switch. The
following table shows the selection made by each switch position.
PX
165432
FunctionSwitch numberPX123456
Key protection for
Up/Down keys
Used for factory-authorizedNot used in normal
calibration onlyoperation
Control mode
Enables protectionON
Disables protectionOFF
ON
OFF
PID actionON
ON/OFF actionOFF
Proportional period
2 secondsON
20 secondsOFF
Control output
NormalON
ReverseOFF
Input shift function
EnabledON
DisabledOFF
RTD sensor input standard
DINON
JISOFF
Scale indication for dualscale range selection
°FON
°COFF
J CONTROL MODE SELECTION
ON/OFF Action
Switch 1 of the function selector DIP switch is factory-set to OFF,
so the temperature controller performs ON/OFF control
action.Set switch 3 to ON when the temperature controller is
used to control a cooling device such as a chiller or freezer.
ON
ON
PX
Switch 1 OFF:
Temperature controller performs ON/OFF action.
165432
PID Action
Set switch 1 of the function selector DIP switch to ON to perform
PID control action. Follow the steps described below
Determining Proportional Period
Set switch 2 of the function selector DIP switch to OFF to select a
proportional period of 20 seconds. This is used when the PID
control action is performed with the contact output of the
temperature controller, or when using an external relay or
contactor.
ON
ON
ON
Control output ON
OFF
Set temperature
ON
PX
Switch 3 ON:
Used for cooling operations in ON/OFF action.
Control output ON
165432
OFF
Set temperature
PX
Switch 2 OFF:
Proportional period is 20 seconds.
Control ON
output
165432
OFF
20 seconds
When a quick response in required, set switch 2 to ON to select a
proportional period of 2 seconds. Even when a solid state relay
(SSR) is used, set the 2-second proportional period only when
quick response is essential. Avoid using this setting with a
contact output because it will shorten the relay’s service life.
ON
ON
PX
Switch 2 ON:
Proportional period is 2 seconds.
Control ON
output
165432
OFF
2 seconds
41
Page 6
E5CS-XE5CS-X
Determining Control Output Operation
If the temperature controller is used to control a heater, the control output can be set to perform a reverse (inverted) operation.
Set switch 3 of the control output mode selector switch to OFF
ON
ON
PX
Switch 3 OFF:
Controller performs reverse operation
used with heaters.
ReverseON
output
By contrast, if the temperature controller is used to control a
cooling device such as a chiller or freezer, set switch 3 to ON.
ON
ON
PX
Switch 3 ON:
Controller performs normal operation for
cooling.
Normal ON
output
Auto-tuning of Proportional Band
Upon the initial power-up the proportional band is set to 3%. The
optimum proportional band width, however, is automatically
calculated and set within the range of 3 to 20%, according to the
changes in the temperature of the controlled system. This
automatic adjustment of the proportional band is performed
regardless of whether the controlled system is a heating or
cooling system.
When the power is turned OFF once, and the ON again, the control action starts with the previous proportional band. However,
the new proportional band is automatically calculated and set.
The calculation of the proportional band, however, is not carried
out if the temperature of the controlled system changes at a
faster rate than 7.5% of full scale per 2 seconds (e.g., faster then
3.75% per °C per second with eh full scale of 100°C). In this
case, the previously calculated and set proportional band is used.
The temperature controller has an overshoot suppression
function that reduced second and subsequent overshoots to a
level less than the initial overshoot.
165432
OFF
Set temperature
165432
OFF
Set temperature
J INPUT SHIFT FUNCTION
The temperature indication can be shifted by setting switch 4 of
the function selector DIP switch to ON, and pressing the mode
key repeatedly until the message “H0” (indicating ) input shift) is
displayed on the main display. Then set the shift value by using
the Up or Down key.
ON
ON
PX
Switch 4 ON: Input shift function enabled.
Fine adjustment of the temperature indication and the resulting
controlled temperature is possible without changing or affecting
the set point.
The input shift value can be set within the range from –99.9 to 99
(°F or °C).
For ranges that have resolution to 0.1, the input shift value can
be set within the range from –9.9 to 9.9 (°F or °C. The input shift
function may be useful to make small temperature corrections to
the control system.
Note that the offset value remains effective even after switch 4
has been set to OFF. If the compensation action is not needed,
be sure to set the offset value to 0.
For example:
Dcorrection of known sensor calibration errors
Dcorrection of known steady temperature offset between the
heated work piece (load) and sensor. This is useful for
applications where the sensor cannot be located exactly at
the work piece.
Dalignment of temperature indications in a
multi-zone/multi-controller application, e.g., at ambient
temperature
Note that the input shift changes the value of the controlled
temperature when used in closed loop control. For example, with
a set point and indication of 100°C and input shift set at +10°C,
the controlled temperature will be 90°C.
Main
display
h 0
h 9
l 9
Set input
shift value
0 offset
offset by +9°
offset by –9°
165432
Temperature
measured by
sensor
100°C
100°C
100°C
Displayed
temperature
100°C
109°C
91°C
J MATCHING THE CONTROLLER TO
SENSOR STANDARD
Use switch 5 of the function selector DIP switch to match the
controller to the thermocouple or RTD sensor to be used.
With switch 5 ON, the controller will accept DIN standard
sensors. With switch 5 OFF, the controller accepts JIS standard
sensors.
J SELECTING SCALE INDICATION
Some dual-scale (°C/°F) temperature scale ranges may be
selected by rotary DIP switch. To specify the scale indication to
be displayed, used switch 6 on the in-line function selector DIP
switch.
With switch 6 set to ON, the controller displays Fahrenheit scale.
With switch 6 set to OFF, the controller displays Celsius scale.
42
Page 7
E5CS-XE5CS-X
J SELECTING A SCALE RANGE
Use the rotary DIP switch to select the temperature scale range.
The tables below show the switch setting number for each range.
The temperature indication range is the set temperature range
(full scale) ±10%, unless otherwise noted.
If the set temperature is shifted outside of changing the scale
range, the set temperature is displayed. It is then automatically
Thermocouple Input Type
Thermocouple input models are factory-set to switch position 2
for a temperature range of 0° to 400°, using a type K
thermocouple.
Switch setting01234566789
Temperature range0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500
Scale indication°C°C°C/°F°C/°F°C/°F°C/°F°F°C°C°C/°F°C/°F
Unit of measure1° C or F
Platinum RTD Type
Platinum RTD input models are factory-set to switch position 3
for a temperature range of 0.0° to 99.9°.
changed to the maximum or minimum value of the newly set
temperature scale range.
If the alarm value is shifted outside the temperature scale range
as a result of changing the scale range, it is automatically
changed to the maximum value of the newly set scale range.
Switch setting012345678
Temperature range–50 to 500.0 to 50.0–20 to 800.0 to 99.90 to 2000 to 3000 to 4000 to 6000 to 800
Scale indication°C°C°C°C/°F°C/°F°C°C/°F°F°F
Unit of measure1° C or F0.1° C or F 1° C or F0.1° C or F 1° C or F
Note: 1. Do not set the selector switch to position 9. This will cause error message “FFF” or “–––” to be displayed.
2. When changing scale ranges where the unit of measure changes 1° to 0.1° or vice versa, the set temperature also changes to
reflect the unit of measure. For example, with a set temperature of 100°, a change from a scale range with 1° resolution to 0.1°
makes the set temperature 10°; with a set temperature of 15°, a change in scale range resolution from 0.1° to 1° makes the set
temperature 150°.
Thermistor Input Type
Thermistor input models are factory-set to switch position 0 for a
temperature range of –50° to 50C°.
Switch setting0123456789
Temp. range–50 to 50 0 to 100 50 to
150
Scale indication °C°F
Unit of measure 1° C or F
Note: 1. The temperature indication range for a setting scale of –50° to 50°C is –50° to 60°C. It is the full scale ±10% with the other set-
ting scale ranges.
2. With a temperature range, such as 50° to 150°C, exceeds the factory-set range, the indication unit is automatically adjusted to
the minimum value. The set temperature is displayed upon power application.
100 to
200
150 to
300
–50 to 100 0 to 200 100 to
300
200 to
400
300 to
600
43
Page 8
E5CS-XE5CS-X
J SELECTING ALARM MODES
Select one of the eight alarm modes by using the rotary DIP
switch located next to the rotary DIP switch for temperature scale
range selection. The following table shows alarm functions. The
selector switch is factory-set to position 2, upper-limit alarm.
Switch setting ModeAlarm outputNotes
0, 9No alarmOFFWhen the alarm mode selector switch is 0 or 9,
1Upper- and lower-limit alarms
2Upper-limit alarm
3Lower-limit alarm
4Upper- and lower-limit range alarm
neither the alarm value is displayed nor the AL
indicator lights even when the return key is pressed.
Alarm value setting range X may be 0 to full scale.
If the alarm value is shifted outside the temperature
If the alarm value is shifted outside the temperature
scale range as a result of changing the scale range, it
is automatically changed to the maximum value of the
newly set scale range.
5Upper- and lower-limit alarms with
standby sequence
6Upper-limit alarm with standby
sequence
7Lower-limit alarm with standby
sequence
8Absolute-value alarmAlarm value setting range Y must be within the
temperature scale range.
Standby Sequence
Alarm functions with standby sequence suppress nuisance
alarms when the controller is first powered up. As shown in the
temperature charts at right, the alarm output is suppressed until
the temperature exceeds the alarm band or alarm limit one time.
When temperature rises from the set temperature
Upper-limit alarm
Set temperature
Lower-limit alarm
Alarm outputON
OFF
When temperature falls below the set temperature
Upper-limit alarm
Set temperature
Lower-limit alarm
Alarm outputON
OFF
J SETTING KEY PROTECTION
Protect against unauthorized changes in temperature values by
disabling the operation of Up and Down keys. Set function
selector DIP switch “P” to ON. To enable changes from the front
panel, simultaneously press the hidden write protection key
(lower left corner) with the Up and Down keys. If the internal
protection switch is set to OFF, changes can be made simply by
pressing the Up and Down keys.
44
ON
ON
PX
165432
Page 9
E5CS-XE5CS-X
J WHEN ALL FUNCTIONS HAVE BEEN SELECTED
To Set Temperature
Press the return key until the SP indicator lights. Then set the
desired temperature value by using the Up and Down keys.
To Set Alarm Value
Press the return key until the AL indicator lights. Then set the
desired alarm value in units of °F or °C. If the present temperature exceeds the set alarm value, the alarm output will be issued.
Neither the set alarm value is displayed nor the AL indicator
lights with the integral alarm mode setting switch set to 0 or 9. Be
sure to check the alarm mode setting switch, located inside the
housing, for proper setting.
In Case of Sensor Failure
The error message “FFF” or “–––” will appear on the main display
if the temperature sensor short-circuits or breaks.
Precautions
The E5CS-X temperature controller has self-diagnostic functions that display the following error messages to simplify troubleshooting.
Message
fff
---
fff (blinks)*
--- (blinks)*
e11 or e33*
Note: *Key operations are disabled.
When the alarm outputs are used, an alarm output occurs when the “FFF” and “–––” messages appear in the display. These displays indicate when the temperature has risen beyond or fallen below the temperature scale range.
CauseControl output
(1) Temperature has risen beyond temperature scale range
(2) Thermistor has been short-circuited
(1) Temperature has fallen below temperature scale range
(2) Thermistor has broken
(1) Failure has occurred in thermocouple or platinum RTD
(2) Temperature has risen much beyond scale range
(1) Failure has occurred in platinum RTD
(2) Polarities (positive and negative) of thermocouple are reversed
(3) Temperature has fallen much below scale range
Note: The resistance of the platinum RTD is 100 Ω at 0°C and increases to 140 Ω at 100°C.
fff blinks
--- blinks
---
fff
OFF
OFF
OFF
ON during heating (reverse) action
OFF during cooling (normal) action
ON during heating (reverse) action
OFF during cooling (normal) action
45
Page 10
E5CS-XE5CS-X
Installation
J MOUNTING
All E5CS-X models conform to DIN 43700 standard. Recommended panel thickness is 1 to 4 mm (0.04 to 0.16 in).
Insert the temperature controller, back end first, into the panel
cutout. Mount the adapter (Y92F-30) supplied with each unit by
pushing it forward from the back of the temperature controller.
Push the adapter as close as possible to the front panel of the
temperature controller to eliminate the gap between them. Then,
secure the adapter with screws as shown.
Removal
Loosen the screws on the adapter and push the hook open to
remove the adapter.
Hook
Screw
Precautions
J ENVIRONMENT
Do not install the temperature controller in a location where there
is a lot of dust or corrosive gases. Also avoid a location where
the temperature controller is subjected to heavy vibration, shock,
splashes of water or oil, and high temperatures.
Separate the temperature controller from equipment that
generates strong, high-frequency electrical noise such as welding
equipment.
Sensor Input Connections
The lead wires connecting the platinum RTD to the temperature
controller must be separated from the power lines an the load
lines, wherever possible, to prevent them from being inducted by
electrical noise.
Use the specified compensating conductors for the thermocouple
input type temperature controllers.
c:/H032E12A
J CONNECTIONS
Connection Examples
Use M3.5 solderless terminals with the temperature controller’s
M3.5 self-rising pressure plate screws.
For solder-dipped leads, strip the lead wire 6 to 12 mm (0.24 to
0.47 in) and carefully insert the wire tip. Do not tighten the terminal screw with excessive force.
7.3 (0.29)
7.5
max.
(0.29)
19
(0.75)
Use lead wires having a small resistance for the platinum RTD
type temperature controllers.
6 to 12
(0.24 to 0.47)
Sequence Circuit
Several seconds are required until the relay is turned ON after
the power has been applied to the temperature controller. Be
sure to take this time lag into consideration when designing a
sequence circuit which incorporates this temperature controller.
J RECALIBRATION
The E5CS-X temperature controller can be recalibrated by a
factory-authorized repair service. Contact Omron for the location
near you.
Unauthorized recalibration of the controller will void the warranty
and may lead to erratic
operation.
R
OMRON ELECTRONICS, INC.
One East Commerce Drive
Schaumburg, IL 60173
1-800-55-OMRON
Cat. No. GCTC13 8/00Specifications subject to change without notice.Printed in U.S.A.
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
416-286-6465
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.