Omron E5CS, E5CS-R1KJX-F, E5CS-Q1KJX-F, E5CS-R1PX-F, E5CS-Q1PX-F User Manual

...
R
Temperature Controller
1/16 DIN Sized Controller Offers Selectable Control, Alarm Modes
Accurate to ±0.5% of full scale
H
flexibility to match application
H Field-selectable temperature ranges in
°F and °C
H Selectable ON/OFF and PID control
with auto-tuning of proportional band
H 8-function alarm, standard H Tamper-proof setting, faulty sensor
compensation and controller diagnostics
H Easy-to-read 11 mm high LED display
E5CS-X
RC
H Nonvolatile memory backup H 3-year warranty

Ordering Information

J TEMPERATURE CONTROLLERS
Item Part number Sensor input type Thermocouple
Output
Temperature Ranges
Thermocouple Input Type
Input type Temperature range 0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500 Scale indication °C °C °C/°F °C/°F °C/°F °C/°F °F °C °C °C/°F °C/°F Unit of measure 1° C or F
Platinum RTD Input Type
Temperature range Scale indication °C °C °C °C/°F °C/°F °C °C/°F °F °F Unit of measure 1° C or F 0.1° C or F 1° C or F 0.1° C or F 1° C or F
Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F
Type K Type J
–50 to 50 0.0 to 50.0 –20 to 80 0.0 to 99.9 0 to 200 0 to 300 0 to 400 0 to 600 0 to 800
(Types J and K)
Platinum RTD (Pt: 100 Ω, DIN and JIS standards)
Interchangeable thermistor (THE types)
Thermistor Input Type
Temp. range Scale indication °C °F Unit of measure 1° C or F
–50 to 50 0 to 100 50 to 150 100 to 200 150 to 300 –50 to 100 0 to 200 100 to 300 200 to 400 300 to 600
37
E5CS-X E5CS-X
J ACCESSORIES (ORDER SEPARATELY)
Description Part number Protective cover Hard plastic; protects front panel against dust, dirt and water drops Y92A-48 Panel mounting adapter Replacement for one supplied with each unit Y92F-30

Specifications

Part number Sensor input type Thermocouple
Supply voltage 100 to 240 VAC, 50/60 Hz; operates on 85 to 110% of rated voltage Power consumption Approx. 7 VA Control Contact
output
Voltage Logic load 12 VDC, 20 mA with short-circuit protection Hysteresis 0.2% of full scale during ON/OFF control action Response
time Service life
Alarm output
Setting accuracy Set value coincides with indicated value, so no relative error exists Indication accuracy ±0.5% of full scale, ±1 digit max. Display range –999 to 999 (limited to input type) Control
modes
Materials Plastic case Mounting Fits 1/16 DIN panel cutout; includes panel mounting adapter Connections Screw terminals Weight 170 g (6 oz.) without mounting adapter Enclosure ratings
Approvals
Ambient temperature
Humidity 35 to 85% RH Insulation resistance 20 M minimum at 500 VDC Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals of different polarity Vibration
Shock
Type ON/OFF and PID with automatic tuning of proportional band, switch selectable Proportional band 3% to 20% (in PID mode) automatically adjusted according to the rise time of the
Reset time 4 minutes (in PID mode) Rate time 0.4 minutes (in PID mode) Proportional period 2 or 20 seconds, switch selectable Sampling period 500 ms
Mechanical durability 10 to 55 Hz, 0.75 mm (0.03 in) double amplitude in X, Y, and Z directions for 2 hours each Malfunction durability 2 to 55 Hz, 2 G in X, Y, and Z directions for 10 minutes each Mechanical durability 30 m/s2, in 6 directions, 3 times each Malfunction durability 100 m/s2, in 6 directions, 3 times each
Type SPDT relay Max. load 3 A, 250 VAC (resistive load)
Output 2 seconds for output to change Display 2 seconds for displayed indication to change Mechanical 10 million operation minimum with contact output Electrical 100,000 operations minimum with contact output Type SPST-NO relay Max. load 1 A, 250 VAC (resistive load) Setting range Absolute value alarm: Same as control output setting range
Front panel IP50, NEMA 4 with optional Y92A-48N waterproof cover Rear panel IP30 Terminals IP00 UL Recognized, File Number E68481 CSA Certified, File Number LR59623 CE Conforms to EN61010-1 Operating –10°C to 55°C (14°F to 131°F) Storage –25°C to 65°C (–13°F to 149°F)
E5CS-j1KJX E5CS-j1PX E5CS-j1GX
Type J (IC) and Type K (CA)
Others: 0 to full scale
controlled system
Platinum RTD (Pt: 100Ω) DIN or JIS standard
Thermistor (interchangeable type)
38
E5CS-X E5CS-X

Nomenclature

1. Main
9. Deviation indicators
display
2. Control output indicator
8. Display data identifier
7. Write protection key
6. Return key
5. Down key
Key Description Key Description 1 Main display sequentially displays the present
temperature, set temperature, and an alarm value each
time the return key is pressed. 2 Control output indicator lights when the output is ON. 3 Alarm indicator lights when the alarm output is ON. 4 Up key increases the set temperature or alarm value when
pressed. Increases the value quickly when held down. 5 Down key decreases the set temperature or alarm value
when pressed. Decreases the value quickly when held
down. 6 Return key changes the value displayed on the main
display each time pressed.
7 The hidden write protection key provides protection against
unauthorized setting of temperature and is used in conjunc­tion with the internal protection switch. If the internal protection switch is set to ON, then to obtain Up and Down operation, the hidden key must be pressed simultaneously with the Up and Down keys. If the internal protection switch
with the Up and Down keys. If the internal protection switch is set to OFF, changes can be made simply by pressing the Up and Down keys.
8 Display data identifier lights SP when the set temperature is
displayed on the main display and AL when an alarm value is displayed.
9 Red deviation indicators light up an arrow when the present
temperature is higher than the set temperature and light a down arrow when the present value is lower than the set temperature. The green block indicates the temperature deviation is within ±1% of the full scale.

Dimensions

3. Alarm indicator
4. Up key
Unit: mm (inch)
48
(1.89)
6
(0.24)
106 (4.2)
90 (3.54)
Panel Cutout Side-by-side Mounting of Several Temperature Controllers
Max. 60
(2.36)
45
(1.77)
+0.6 –0
45
(1.77)
+0.6 –0
+0.6 –0
45
(1.77)
L = 48 x number of units – 2.5
(1.89 x number of units –0.1)
Controllers 2 3 4 5 6
L
93.5 (3.68)
+1
141.5
–0
(5.57)
Note: 1. Recommended panel thickness is 1 to 8 mm (0.04 to
0.31 in).
2. Because mounting brackets are attached to the top and bottom of a temperature controller, tight side-by­side mounting is possible.
10
(0.39)
+1
–0
189.5 (7.46)
+1
–0
237.5 (9.35)
+1
–0
285.5 (11.24)
+1
–0
39