OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGERIndicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
!WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
!CautionIndicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to
an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3...1. Indicates lists of one sort or another, such as procedures, checklists, etc.
Before Installing the CX-Process Monitor Plus
Installing the CX-Process Monitor Plus signifies that you accept the software user’s license agreement
displayed during the installation process. Do not install this software if you do not accept the user’s
license agreement. Warranty and after-sales services are available only to users that register with the
enclosed registration form. Please fill in the registration form and return it to OMRON.
OMRON, 2005
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
This manual describes the installation and operation of the WS02-LCMC1-EV2 CX-Process Monitor
Plus software package and includes the sections described below. The CX-Process Monitor Plus is
used to control and monitor the operation of the CS1W-LC001 Loop Control Unit, the CS1W-LCB01
Loop Control Board, the CS1W-LCB05 Loop Control Board, the CS1D-CPU@@P Process-control CPU
Units, and the CJ1G-CPU@@P Loop-control CPU Units.
Please read this manual carefully and be sure you understand the information provided before
attempting to install and operate the CX-Process Monitor Plus. Please read the following manuals
carefully and be sure you understand the information provided before setting up or using an application
for a Loop Control Unit or Loop Control Board.
ProductManual nameCat. No.Contents
WS02-LCMC1-EV2CX-Process Monitor
Plus Operation Manual
WS02-LCTC1-EV5
CX-Process Tool
CS1W-LC001
Loop Control Unit
CS1W-LCB01/05
Loop Control Boards,
CS1D-CPU@@P
Process-control CPU
Units, and
CJ1G-CPU@@P
Loop-control CPU
Units
CS1W-LC001
Loop Control Unit
CS1W-LCB01/05
Loop Control Boards,
CS1D-CPU@@P
Process-control CPU
Units, and
CJ1G-CPU@@P
Loop-control CPU
Units
CX-Process Tool
Operation Manual
Loop Control Unit
Operation Manual
Loop Control Boards
Operation Manual
Loop Control Unit
Function Block Reference Manual
Loop Control Boards
Function Block Reference Manual
W428
(this manual)
W372Installation and operation procedures for the
W374Installation and operation procedures for the
W406Installation and operation procedures for the
W375Detailed information on function blocks for
W407Detailed information on function blocks for
Installation and operation procedures for the
CX-Process Monitor Plus.
CX-Process Tool.
Loop Control Unit (except for function blocks).
Loop Control Boards (except for function
blocks).
Loop Control Units.
Loop Control Boards.
Section 1 introduces the CX-Process Monitor Plus.
Section 2 describes installing the CX-Process Monitor Plus and connections to the PLC.
Section 3 described data exchange for the CX-Process Monitor Plus
Section 4 describes the monitor screens used with the CX-Process Monitor Plus.
Section 5 describes the procedures to create screens and monitor using the CX-Process Monitor
Plus.
Section 6 describes errors that can occur while using the CX-Process Monitor Plus.
The Appendix provides a list of ITEM settings for function blocks.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section
in its entirety and be sure you understand the information provided in the section and
related sections before attempting any of the procedures or operations given.
ix
x
PRECAUTIONS
This section provides general precautions for using the CX-Process Monitor Plus.
The information contained in this section is important for the safe and reliable application of the CX-Process
Monitor Plus. You must read this section and understand the information contained before attempting to set up or
operate the CX-Process Monitor Plus.
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent) and
knowledge about instrumentation system.
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the
manual or applying the product to nuclear control systems, railroad systems,
aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, petrochemical plants, and other systems,
machines, and equipment that may have a serious influence on lives and
property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide
the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be
sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!WARNING It is extremely important that a PC and all PC Units be used for the specified
purpose and under the specified conditions, especially in applications that can
directly or indirectly affect human life. You must consult with your OMRON
representative before applying a PC System to the above-mentioned applications.
3Safety Precautions
!WARNING Check the following items before starting Loop Control Unit operation:
Analog I/O Units used in combination with the Loop Control Unit must be
mounted correctly, and the unit number set on the front panel of the Analog I/
O Unit must be the same as the unit number set on the Field Terminal Function Block. If the unit numbers are not the same, I/O (read/write) will be performed on the data for another Special I/O Unit (i.e., the one whose unit
number is set in the Field Terminal Function Block).
The initial settings of the System Common Block on the Loop Control Unit
must be set correctly. In particular, make sure that the Data Memory for the
Node Terminals in the CPU Unit controlling the Loop Control Unit is not used
for other applications on the PC. If the same words in Data Memory are used
for more than one application, the PC system may act unexpectedly and
cause injury.
xii
Safety Precautions3
When writing data to the I/O memory in the CPU Unit with function blocks
(e.g., using Send All Blocks, Expanded DO/AO Terminal to CPU Unit, or DO/
AO Terminal to CPU Unit), be sure that the words written to in the I/O memory
are not being used for any other purpose. If I/O memory words are allocated
to more than one purpose, the PC system may act unexpectedly and cause
injury.
!WARNING Check the following items before starting to run the Loop Control Board:
• Do not allow the bank of the EM Area with the number specified for allocation to the HMI (human-machine interface) data to be used by the CPU
Unit or other Units for any other purpose. The bank allocated for the HMI
is specified in ITEM 050 (EM Area Bank Allocated for HMI Memory = 0 to
12) of the System Common block. If the same memory area is used for
more than one purpose, the system may operate in an unexpected fashion, which may result in injury.
• Do not allow the area to which user link table data is written to be used by
the CPU Unit or other Units for any other purpose. If the same memory
area is used for more than one purpose, the system may operate in an
unexpected fashion, which may result in injury.
• Analog Input/Output Units used in combination with the Loop Control
Board must be mounted correctly, and the unit number set on the front
panel of the Analog Input/Output Unit must match the unit number set on
the Field Terminal block. If the unit numbers do not match, input/output
(read/write) will be performed on the data of another Special I/O Unit (i.e.,
the one whose unit number is set on the Field Terminal block).
• The defaults of the System Common block on the Loop Control Board
must be set correctly.
!WARNING Always stop the operation of the Loop Control Board before converting any of
the EM Area to file memory. If any part of the EM Area that is being used by
the Loop Control Board for the HMI is converted to file memory during Board
operation, the system may operate in an unexpected fashion, which may
result in injury.
!WARNING Do not perform processing in such a way that the Loop Control Unit/Board
and CPU Unit write to identical I/O memory words allocated to a contact output or analog output of an external Unit. If the same words are written to, the
externally connected loads may act unexpectedly and cause injury.
!WARNING Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
!Caution Before transferring function block data (initial setting data or operation data) to
the Loop Control Unit/Board, confirm that the destination for the data is correct and also confirm the overall safety of the system (including the Loop Control Unit/Board). Not doing so may result in unexpected operation.
xiii
Application Precautions4
!Caution After updating the tag settings or network configuration for CX-Process Moni-
tor Plus, always confirm that the Monitor Plus screens will operate properly
with the new settings or configuration before attempting actual operation. If
the settings or configuration is not appropriate, unexpected operation may
result.
4Application Precautions
Observe the following precautions when using CX-Process Monitor Plus.
!Caution Loop Control Unit/Board data is monitored and operated using CX-Process
Monitor Plus based on the tag files for Monitor Plus created using CX-Process
Tool. CX-Process Tool can be used on Microsoft Windows 95, 98, Me, 2000,
or NT (Service Pack 4 or later). CX-Process Tool Ver. 3.2 or higher must be
used to output tag files for the CX-Process Monitor Plus.
!Caution Before using function block data in actual operation, confirm operation by
monitoring run status (to check the load rate; select Execute/Operation/Mon-itor Run Status) and validating actions (select Validate Action/Start) with
CX-Process Tool. In particular, be sure to confirm that the load rate will be
less than 60%. (For details on the load rate, refer to the Loop Control Unit/Board Operation Manual.)
!Caution The Loop Control Unit/Board can read and write I/O memory in the CPU Unit
using the Field Terminal Function Blocks or CPU Terminal Blocks independent of the user program (Step Ladder Program) in the CPU Unit. Do not write
to the same I/O memory words from both the Loop Control Unit/Board and the
CPU Unit.
!Caution To hold an analog output or contact output at a specific value (for example, the
maximum value or minimum value) when the Loop Control Unit/Board stops
running, create a Step Ladder Program in the CPU Unit so that the corresponding output bit allocated to Analog Output Unit or Contact Output Unit is
set to the desired value using an NC condition of the Loop Control Unit/Board
Running Flag (bit 00 in allocated CIO word “n”) as an input condition.
!Caution If a fatal error occurs in the CPU Unit (including fatal errors created by execu-
tion of an FALS instruction), the Loop Control Unit/Board will also stop running. To hold analog outputs to the previous values before the stop occurred,
and to set analog outputs to either the minimum value or maximum value, use
the output hold function of the Analog Output Unit or Analog I/O Unit.
!Caution Before turning ON the power to the PC, make sure that the facilities are safe.
The analog output values and contact outputs from the Loop Control Unit/
Board are updated when the power to the PC is turned ON regardless of the
operating mode of the CPU Unit (including in the PROGRAM mode). (Internally, the analog output values and contact outputs are sent from the CPU
Unit to Basic I/O Units and Analog Output Units.)
xiv
!Caution Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
Application Precautions4
!Caution Confirm that no adverse effect will occur in the system before attempting any
of the following:
• Changing the operating mode of the PC (including the setting of the Startup Mode)
• Force-setting/force-resetting any bit in memory
• Changing the present value or any set value in memory
!Caution Be sure that all mounting screws, terminal screws, and cable connector
screws are tightened to the torque specified in the user manuals. Incorrect
tightening torque may result in malfunction.
!Caution In the event of system or power failure, CX-Process function files (extension
“.ist”) may not be saved. It is recommended that function files are saved regularly.
!Caution If the power supply is turned OFF while function block data is being backed up
from RAM to flash memory, the backup will not be completed normally. If the
power supply is turned back ON within 24 hours, however, the super capacitor
will have held the RAM data. The backup operation will restart when power is
turned ON and operation will start when the backup has been completed. If
the power supply is turned OFF for more than 24 hours, however, RAM data
will be lost and operation will be started with the data that was previously
saved to flash memory. If this happens, the Cold Start Auto-execution Flag
(A35807) will turn ON to show that the previous data has been used. Use this
bit in programming to take whatever steps are necessary, such as downloading the most recent function block data.
xv
Application Precautions4
xvi
This section introduces the CX-Process Monitor Plus.
The CX-Process Monitor Plus is a Windows NT-based application that monitors the Function Block data within a Loop Control Unit/Board using Control
screens (on-site instrument images), Trend screens, Graphic screens, and
Annunciator screens, etc., via the Controller Link, serial communications, or
Ethernet. The CX-Process Monitor Plus is used together with the CX-Process
Tool to create function blocks for Loop Control Units/Boards.
You can also perform the following four functions.
Monitoring Function
Blocks in a Loop Control
Unit/Board
Controlling Function
Blocks in a Loop Control
Unit/Board
Monitoring Function Block
Alarm Status in a Loop
Control Unit/Board
Configuring CX-Process
Monitor Plus Screens
Monitor PV, SP, and MV, etc., within the Control Block, monitor analog signals,
and monitor contact signals.
Perform Run/Stop instructions in the Loop Control Unit/Board.
Display the status of the CPU Unit, such as the current operating mode.
Change settings, switch between auto and manual, and perform manual operations, tune PID constants, etc., in the Control Block.
You can perform stop block operation commands for each Control Block
(when using the Tuning screen).
Display Control Block and Alarm Block alarms if they occur, and store the
alarms in the alarm history.
You can configure the screen to suit your needs.
2
CX-Process Monitor PlusSection 1-1
CX-Process Monitor Plus Functions
---ScreenMonitoring operating
User-defined
screens
System screensAlarm Log------OK (Stored when an
Overview------OK
ControlOK (Display PV bar)OK (Change SP, switch
TuningOK (Display PV, SP, and
MV trends for 1 loop)
TrendOK (Display Control Block
or analog signal trends)
Batch TrendOK (Display Control Block
Segment
Program 2
GraphicOK (Display status for
Annunciator------OK (Use colors or sound
Operation Guide OK (Display message
System Monitor OK (Display the run/stop
Operation Log---OK (Stores run operation
System Monitor
Log
or analog signal trends)
OK (Display Segment
Program 2 trends)
contact or analog signal
graphics)
when Internal Switch is
turned ON)
status for the Loop Control Unit/Board, display
Execution errors, RAM
checksum errors, and
battery errors, and monitor the status of the CPU
Unit control mode, etc.)
OK (Displays run/stop
command history and
Execution error history
when an error occurs)
status
Controlling operationMonitoring alarm status
between auto/manual,
and perform manual operations)
OK (Change SP, and
change P, I, D, etc.)
---OK
------
OK (Run/stop operation
at the relevant Segment
Program 2 Block)
OK (Turn ON/OFF the
contact, and set the analog value)
---OK
OK (Run/stop command
for the Loop Control Unit/
Board)
history, e.g., SP change,
etc.)
---OK
OK
OK (Change bar graph
colors)
OK (Errors related to the
relevant Segment Program 2 Block)
OK
to notify of an alarm)
OK
alarm occurs)
OK
NoteOnly the following data can be monitored and set with the CX-Process Moni-
tor Plus and tag names must be set to enable monitoring and setting. Use CXProcess Tool Ver. 3.2 or higher to set the tag names.
3
CX-Process Monitor PlusSection 1-1
Data set/monitored
by CX-Process
Monitor Plus
Function block dataControl Blocks:
Contact signalsContact signals through Contact Distributor (Block Model
Analog
signals
Sent to
Monitor Plus
Set from
Monitor Plus
Loop Control UnitLoop Control Board
Basic PID (Block Model 011), Advanced PID (Block Model
012), Blended PID (Block Model 013), Batch Flowrate Capture (Block Model 014), Indication and Setting (Block Model
031), Indication and Operation (Block Model 032), Ratio
Setting (Block Model 033), Indicator (Block Model 034), 2position ON/OFF (Block Model 001), and 3-position ON/
OFF (Block Model 002)
Operation Blocks:
High/Low Alarm (Block Model 111), Segment Program 2
(Block Model 157), ON/OFF Valve Manipulator (Block
Model 221), Motor Manipulator (Block Model 222), Reversible Motor Manipulator (Block Model 223), Motor Opening
Manipulator (Block Model 224), Timer (Block Model 205)
and Counter (Block Model 208)
201) + Internal Switch (Block Model 209)
Analog signals through Input Selector (Block Model 162)
Analog signals through Constant Generator (Block Model
166)
1-1-2Screen Outlines
Overview ScreenPossesses the functions of all menu screens and alarm display screens.
4
CX-Process Monitor PlusSection 1-1
Control ScreensMonitor and set the Control Block and part of the Operation Block, monitor
analog signals, and monitor and set contact signals.
Tuning ScreensUse this screen to change Control Block P, I, D constants.
5
CX-Process Monitor PlusSection 1-1
Trend ScreensDisplay as an image changes due to the passage to time of the Control Block
PV, SP, MV, or other analog signals.
Batch Trend ScreensDisplay a recorder image of the changes over time of the Control Block PV,
SP, MV, or other analog signals. Trend sampling is started and ended with tag
data (digital or analog) as the trigger.
6
CX-Process Monitor PlusSection 1-1
Segment Program 2
Screens
Display a recorder image of PV trends for Segment Program 2 (Block Model
157) set values. Segments can be set in table format while observing a time
axis graph.
Graphic ScreensUse the screen to display the device status as a schematic.
7
CX-Process Monitor PlusSection 1-1
Annunciator ScreensUse this screen to display comprehensively the status (mainly the alarm sta-
tus) of the contacts.
Operation Guide ScreensUse this screen to display registered messages when the contact signal is
ON.
8
CX-Process Monitor PlusSection 1-1
Alarm Log ScreensUse this screen to display the alarm history.
Operation Log ScreensUse this screen to display the operation history.
9
CX-Process Monitor PlusSection 1-1
System Monitor ScreensUse this screen to display the system status, and run/stop the Loop Control
Unit/Board.
System Monitor Log
Screens
Use this screen to display the run/stop history and Execution error history, and
to record the time at which they occurred.
1-1-3CX-Process Monitor Plus System Requirements
FinsGatewayAs shown below, the CX-Process Monitor Plus uses the communications
driver FinsGateway (Embedded version) to communicate with the PLC (Programmable Controller) mounted to the Loop Control Unit/Board.
CX-Process ToolCX-Process Monitor Plus
Software
FinsGateway (Embedded version)
Hardware
RS-232C port
Controller Link
Support Board
Ethernet board
10
CX-Process Monitor PlusSection 1-1
You can use any one of the FinsGateway (Embedded version) given below.
• Serial Unit driver
• Controller Link driver
• CLK (PCI) driver
• ETN_UNIT driver
Note1. You cannot start CX-Process Monitor Plus if FinsGateway (Embedded ver-
sion) is not installed.
2. CX-Process (Monitor Plus and Tool) cannot use FinsGateway Version 1 as
a communications driver. Be sure to use Version 3 or later.
3. If CX-Programmer, CX-Protocol, CX-Motion, or other Support Software
(i.e., CX-Server communications software), or applications that use special serial drivers, are connected online, they use the same COM port, so
CX-Process (Monitor Plus and Tool) cannot connect online (i.e., initialize
serial communications) using the Host link (SYSWAY). First disconnect offline other Support Software or applications that use special serial drivers,
before reconnecting online (i.e., initializing serial communications) CXProcess. Conversely, while CX-Process is connected online (i.e., initializing serial communications), other Support Software that communicate using CX-Server cannot connect online.
4. You cannot install CX-Process and FinsGateway Version 1 on the same
IBM PC/AT or compatible.
5. If using Windows NT 4.0 as your OS, you must use Service Pack 6a or later.
6. Both FinsGateway Version 3 and Version 2003 (Embedded version) are
bundled with the CX-Process Monitor Plus software.
When using FinsGateway for the communications driver, install one of
these versions. The FinsGateway Runtime Version can also be used. If the
runtime version is already installed, it is not necessary to install the embedded version.
Set Network Address,
Node Address, and Unit
Address.
NoteThe CX-Process Monitor and CX-Process Monitor Plus use FinsGateway as
The network address, node address, and unit address for communications
between the CX-Process Monitor Plus and PLC are set using the CX-Process
Tool address settings (Settings/Network Settings).
the communications driver for connections with the PLC. When using the CXProcess Monitor or CX-Process Monitor Plus, always set FinsGateway as the
communications driver for the CX-Process Tool. If the CX-Server is set, the
CX-Process Monitor or CX-Process Monitor Plus will not be able to go online
with the PLC.
11
CX-Process Monitor PlusSection 1-1
Register the Function
Blocks to Exchange Data
with the CX-Process
Monitor Plus.
Items to
monitor
Function
block data
Contact
signals
Analog
signals
Registrations and
connections
Only register the function blocks.
Register and connect
the function blocks.
Register and connect
the function blocks.
Register and connect the function blocks to exchange data with the CX-Process Monitor Plus. The following function blocks can be used depending on
the items to be monitored.
Loop Control UnitLoop Control Board
Send All Blocks block (Block Model 462)
and Receive All Blocks block (Block
Model 461)
Contact Distributor (Block Model 201) or Internal Switch (Block Model 209)
Input Selector block (Block Model 162) and Constant Generator block (Block Model
166)
Block to input analog signals from
the CX-Process Monitor Plus.
Main function blocksBlock to output analog signals to
HMI settings in the System Common
block (Block Mode 000)
the CX-Process Monitor Plus.
Blocks to monitor function
block ITEM tags from the
CX-Process Monitor Plus.
Set CSV Tags and Tags for
CX-Process Monitor Plus.
1,2,3...1. Register the Send All Blocks block (Block Model 642) and Receive All
Blocks to manipulate or display contacts
from the CX-Process Monitor Plus.
The CX-Process Monitor Plus uses tags set from the CX-Process Tool (Ver.
3.2 or higher) to read and write data in Loop Control Units/Boards. To use the
CX-Process Monitor Plus, therefore, CSV tags and tags for the CX-Process
Monitor Plus must be set.
Loop Control Units
Blocks block (Block Model 641).
2. Set tags as follows:
• Function block data: Set CSV tags.
• Individual contact signals: Set tags for Monitor Plus for the contacts in the
Internal Switch block (Block Model 209).
• Individual analog signals from LCU to computer: Set tags for Monitor Plus
for the analog signals in the Input Selection block (Block Model 162).
• Individual analog signals from computer to LCU: Set tags for Monitor Plus
for the analog signals in the Constant Generator block (Block Model 166).
12
CX-Process Monitor PlusSection 1-1
Loop Control Boards
1,2,3...1. Make the settings for the HMI in the System Common block (Block Model
000).
2. Set tags as follows:
• Function block data: Set CSV tags.
• Individual contact signals: Set tags for Monitor Plus for the contacts in the
Internal Switch block (Block Model 209).
• Individual analog signals from LCU to computer: Set tags for Monitor Plus
for the analog signals in the Input Selection block (Block Model 162).
• Individual analog signals from computer to LCU: Set tags for Monitor Plus
for the analog signals in the Constant Generator block (Block Model 166).
Note For both the Loop Control Unit and Loop Control Board, the follow-
ing function blocks must be created and connected separately to
enable monitoring and setting individual contact signals and individual analog signals (i.e., other than function block data).
• To monitor and set individual contact signals, contact signals must be
input/output using the Contact Distributor block (Block Model 201) and
Internal Switch block (Block Model 209).
• To monitor individual analog signals, analog signals must be output
from the Input Selection block (Block Model 162).
• To set individual analog signals, analog signals must be input to the
Constant Generator block (Block Model 166).
Compile the Tag File for
the CX-Process Monitor
Plus.
NoteThe following dialog box will be displayed if a tag file for Monitor Plus is output
Download Function Block
Data to the Loop Control
Unit/Board.
Compile the Monitor Tag
Files.
The tag file for Monitor Plus must be compiled (Execute – Create Tag File –
Monitor Plus Tag).
while the CX-Process Monitor Plus is running.
Tag information will not be updated if a tag file for Monitor Plus is output during CX-Process Monitor Plus operation. To update the tag file, restart the CXProcess Monitor Plus.
Download the function blocks.
Start the CX-Process Monitor Plus. In the Main Window, click the Run Button
or the Setup Button. The monitor tag files (mtagmst and mtagsubmst) will be
automatically generated based on the tag file for Monitor Plus (monitor.csv).
13
CX-Process Monitor PlusSection 1-1
1-1-4Relationship to CX-Process Tool
Tag NamesAs shown earlier in CX-Process Monitor Plus Conditions of Use, if monitoring
or operating Function Blocks using CX-Process Monitor Plus, you must first
perform the following steps using CX-Process Tool.
1,2,3...1. Set the network address, node address, and unit address.
2. Register the blocks for which data is to be exchanged with the CX-Process
Monitor Plus.
3. Set the CSV tags and tags for Monitor Plus.
4. Generate the tag file for Monitor Plus.
5. Download the function block data to the Loop Control Unit/Board.
6. Compile the monitor tag file.
CX-Process Monitor Plus handles all items allocated tag names as one string.
CX-Process Monitor Plus does not differentiate which Function Block was
used to specify the tag names.
ITEM SettingsFunction block ITEMs are set as shown in the following table. The CX-Process
Tool is normally used to set initial data S and the CX-Process Monitor Plus is
normally used to set operation data O.
CX-Process Tool
data classification
Initial settingsSInitial setting parameter
Operation dataOOperation parameters
TypeITEMExample: PID BlockCX-Process
for each function block
for each function block
NoteInitial settings O and operation data S classifications are displayed on ITEM
Setting Screens of the CX-Process Tool. For details on the ITEMs set each
function block, refer to the Function Block Reference Manual.
Example
ITEM type ITEMContentsR: Read, W: Write,
Parameter 004Operation cycle (s)R/W (S)---
Parameter 008High/Low alarmR/W (O)R/W
012Hysteresis set valueR/W (S)---
Parameter 023Local SP set valueR/W (O)R/W
024SP set method (Initial setting)
0: Local, 1: Remote/Local
Forward/Reverse direction,
SP setting method, compensation method, etc.
Example: PID Block SP,
alarm settings, PID constants, etc.
R/W (S)R
Tool
SetCannot be set
Set in special
cases
R/W: Read/write,
---: R/W disabled
r, t/w: CX-Process Tool
operation monitor/Operation
monitor read and write
(S): Initial setting,
(O): Operation data
CX-Process
Tool
CX-Process
Monitor Plus
Set
CX-Process
Monitor Plus
14
NoteAnalog values are normally set with the CX-Process Monitor Plus. They can
be set with the CX-Process Tool provided that they are in percentage increments between 0% and 100%. Scaling engineering units cannot be set with
the CX-Process Tool.
CX-Process Monitor PlusSection 1-1
1-1-5Relation between Screens and Function Blocks
The relation between screens and function blocks is shown below.
Userdefined
screens
System
screens
ScreenLoop Control Unit: Register Send All
Overview
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch Trend
Screen
Segment
Program 2
Screen
Graphic
Screens
Annunciator
Screens
Operation
Guide
Screens
System
Monitor
Screens
Alarm Log
Screens
Operation
History
Screens
System
Monitor Log
Screens
Blocks and Receive All Blocks blocks
Loop Control Boards: Make HMI settings
in the System Common block
------------
Basic PID, Advanced PID, Blended PID
(Block Model 013), Batch Flowrate Capture
(Block Model 014), Indication and Setting,
Indication and Operation, Ratio Setting,
Indicator, 2-Position ON/OFF, 3-Position
ON/OFF, High/Low Alarm, Segment Program 2, ON/OFF Valve Manipulator, Motor
Manipulator, Reversible Motor Manipulator,
Motor Opening Manipulator, Timer, Counter
Segment Program 2---------
Basic PID, Advanced PID, Blended PID
(Block Model 013), Batch Flowrate Capture
(Block Model 014), Indication and Setting,
Indication and Operation, Ratio Setting,
Indicator, 2-Position ON/OFF, 3-Position
ON/OFF (PV, SP, MV only), Segment Program 2, ON/OFF Valve Manipulator, Motor
Manipulator, Reversible Motor Manipulator,
Motor Opening Manipulator
Segment Program 2Can be desig-
Same tag ITEMs as for Control screens.Analog signal
Same tag ITEMs as for Control screens.---Contact signal
------Contact signal
------------
Contacts for which alarms were automatically allocated when registering tags
------------
------------
Input Selector
block (Block
Model 162)
Analog signal
or analog value
parameters
Analog signal
or analog value
parameters
nated as
expansion measurement tags
or analog value
parameters
---Contacts for
Internal Switch
block (Block
Model 209)
Contact signal
or contact
parameters
Contact signal
or contact
parameters
Can be designated as
expansion measurement tags
Contact signal
or contact
parameters
or contact
parameters
or contact
parameters
which alarms
were automatically allocated
when registering tags
Constant
Generator
block (Block
Model 166)
Analog output
Analog output
Can be designated as
expansion measurement tags
Analog output
---
---
---
15
Loading...
+ 242 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.