
v
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury. Additionally, there may be severe property damage.
!WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury. Additionally, there may be severe property damage.
!Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to
an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 2007
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.

vii
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xix
1 Intended Audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
2 General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxii
5 Application Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xxii
6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxiv
SECTION 1
Features and System Configuration . . . . . . . . . . . . . . . . . . . 1
1-1 EtherNet/IP Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 EtherNet/IP Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1-3 Nomenclature and Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-4 Network Configurator Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SECTION 2
Designing the EtherNet/IP System . . . . . . . . . . . . . . . . . . . . 21
2-1 Design Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-2 Selecting the Network Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2-3 Checking Bandwidth Usage and Adjusting the Packet Interval (RPI) . . . . . . . . . . . . . . . . . 30
SECTION 3
Network Configurator Installation . . . . . . . . . . . . . . . . . . . . 47
3-1 Network Configurator Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SECTION 4
Installation and Initial Setup . . . . . . . . . . . . . . . . . . . . . . . . . 53
4-1 Overview of Initial Setup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4-3 Mounting to a PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-4 Network Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
4-5 Connecting to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
4-6 Creating I/O Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4-7 NTLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4-8 ntlp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4-9 NTLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4-10 NTLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
SECTION 5
Ethernet Unit Memory Allocations . . . . . . . . . . . . . . . . . . . . 77
5-1 NTLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

x
Relevant Manuals
The following table lists CS- and CJ-series manuals that contain information relevant to EtherNet/IP
Units.
Manual
number
Model Name Contents
Z909 CS1W-EIP21
CJ1W-EIP21
EtherNet/IP Units
Operation Manual
(this manual)
Provides information on operating and installing EtherNet/IP Units, including details on basic settings, tag data
links, and FINS communications.
Refer to the Communications Commands Reference
Manual (W342) for details on FINS commands that can
be sent to CS-series and CJ-series CPU Units when
using the FINS communications service.
Refer to the Ethernet Units Operation Manual
Construction of Applications (W421) for details on constructing host applications that use FINS communications.
W420 CS1W-ETN21
CJ1W-ETN21
Ethernet Units Operation Manual
Construction of Networks
Provides information on operating and installing
100Base-TX Ethernet Units, including details on basic
settings and FINS communications. Refer to the Communications Commands Reference Manual (W342) for
details on FINS commands that can be sent to CS-series
and CJ-series CPU Units when using the FINS communications service.
W421 CS1W-ETN21
CJ1W-ETN21
Ethernet Units Operation Manual
Construction of
Applications
Provides information on constructing host applications for
100Base-TX Ethernet Units, including functions for sending/receiving mail, socket service, automatic clock adjustment, FTP server functions, and FINS communications.
W343 CS1W-ETN01
CS1W-ETN11
CJ1W-ETN11
Ethernet Units Operation Manual
Describes the installation and operation of the 10Base-5
and 10Base-T Ethernet Units.
W342 CS1G/H-CPU@@H
CS1G/H-CPU-@@V1
CS1W-SCU21
CS1W-SCB21/41
CJ1G/H-CPU@@H
CJ1G-CPU@@
CJ1W-SCU41
Communications
Commands Reference Manual
Describes the C-series (Host Link) and FINS communications commands used when sending communications
commands to CS-series and CJ-series CPU Units.
W339 CS1G/H-CPU@@H
CS1G/H-CPU-@@V1
Programmable Controllers Operation
Manual
Provides an outline of, and describes the design, installation, maintenance, and other basic operations for the CSseries PLCs. Information is also included on features,
system configuration, wiring, I/O memory allocations, and
troubleshooting.
Use together with the Programmable Controllers Pro-
gramming Manual (W394).
W393 CJ1G/H-CPU@@H
CJ1G-CPU@@
Programmable Controllers Operation
Manual
Provides an outline of, and describes the design, installation, maintenance, and other basic operations for the CJseries PLCs. Information is also included on features,
system configuration, wiring, I/O memory allocations, and
troubleshooting.
Use together with the Programmable Controllers Pro-
gramming Manual (W394).
W394 CS1G/H-CPU@@H
CS1G/H-CPU-@@V1
CJ1G/H-CPU@@H
CJ1G-CPU@@
NSJ@-@@@@(B)-G5D
NSJ@-@@@@(B)-M3D
Programmable Controllers Programming Manual
Describes programming, tasks, file memory, and other
functions for the CS-series, CJ-series, and NS-J-series
PLCs.
Use together with the Programmable Controllers Opera-
tion Manual (W339 for CS-series PLCs and W393 for CJseries PLCs).

xxii
Operating Environment Precautions 4
4 Operating Environment Precautions
!Caution Do not operate the control system in the following locations:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified
in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution Take appropriate and sufficient countermeasures when installing systems in
the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
5 Application Precautions
Observe the following precautions when using the EtherNet/IP Unit.
!WARNING Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
• Always connect to a ground of 100
Ω or less when installing the Units. Not
connecting to a ground of 100
Ω or less may result in electric shock.
• Always turn OFF the power supply to the CPU Unit and Slaves before
attempting any of the following. Not turning OFF the power supply may
result in malfunction or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Memory Packs, or Master Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
!Caution Failure to abide by the following precautions could lead to faulty operation of
the EtherNet/IP Unit or the system, or could damage the Ethernet Unit.
Always heed these precautions.
• Interlock circuits, limit circuits, and similar safety measures in external circuits (i.e., not in the Programmable Controller) must be provided by the
customer.

xxiii
Application Precautions 5
• Always use the power supply voltages specified in the operation manuals.
An incorrect voltage may result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the
rated voltage and frequency is supplied. Be particularly careful in places
where the power supply is unstable. An incorrect power supply may result
in malfunction.
• Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures
• Make sure that all the Backplane mounting screws, terminal block screws,
and cable connector screws are tightened to the torque specified in the
relevant manuals. Incorrect tightening torque may result in malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may
result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals. Connection of bare stranded wires may result in
burning.
• Observe the following precautions when wiring the communications
cable.
• Separate the communications cables from the power lines or high-tension lines.
• Do not bend the communications cables past their natural bending radius.
• Do not pull on the communications cables.
• Do not place heavy objects on top of the communications cables.
• Always lay communications cable inside ducts.
• Use appropriate communications cables.
• Make sure that the terminal blocks, expansion cable connectors, and
other items with locking devices are locked in place.
• Wire all connections correctly according to instructions in this manual.
• Double-check all wiring and switch settings before turning ON the power
supply. Incorrect wiring may result in burning.
• Mount Units only after checking terminal blocks and connectors completely.
• Check the user program (ladder program and other programs) and
parameters for proper execution before actually running it on the Unit. Not
checking the program may result in unexpected operation.
• Confirm that no adverse effect will occur in the system before attempting
any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PLC.
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• After replacing Units, resume operation only after transferring to the new
CPU Unit and/or Special I/O Units the contents of the DM Area, HR Area,
programs, parameters, and other data required for resuming operation.
Not doing so may result in an unexpected operation.
• Before touching a Unit, be sure to first touch a grounded metallic object in
order to discharge any static build-up. Not doing so may result in malfunction or damage.

9
EtherNet/IP Unit Specifications Section 1-2
1-2 EtherNet/IP Unit Specifications
1-2-1 General Specifications
CS-series and NES-series EtherNet/IP Units
Item Specifications
Model number CS1W-EIP21
Type 100Base-TX (Can be used as 10Base-T, but this is not recommended.)
Applicable PLCs CS-series PLCs
Unit classification CS-series CPU Bus Unit
Mounting location CPU Rack or Expansion Rack
Number of Units that can be
mounted
4 max. (including Expansion Racks)
CPU Unit
words used
Allocated CIO Area
words (CPU Bus
Unit words)
25 words/Unit (one unit number’s words)
These words contain control bits and flags, the target node PLC’s operating and error
information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status.
Allocated DM Area
words (CPU Bus
Unit words)
100 words/Unit (one unit number’s words, not supported in the NE1S Series)
These words contain the IP address display/setting area (not supported in the NE1S
Series).
User-set area Any usable data area words
Target node PLC’s operating and error information, and registered/normal target
node information
CPU Bus Unit System Setup
Not used.
Non-volatile memory within EtherNet/IP Unit (See note.)
The following settings are made from the Network Configurator and stored in the EtherNet/IP Unit’s non-volatile memory.
Note Unlike the regular Ethernet Units, the CPU Unit’s CPU Bus Unit System Setup
Area (Unit settings area) is not used for these settings.
1. TCP/IP settings such as the EtherNet/IP Unit’s IP address, DNS server, host name,
and baud rate
2. Device parameter settings (communications settings such as the tag data link setting parameters, FINSUDP settings, and FINS/TCP settings)
Tr an s fe r
specifications
Media access
method
CSMA/CD
Modulation method Baseband
Transmission paths Star form
Baud rate 100 Mbit/s (100Base-TX) 10 Mbit/s (10Base-T)
Transmission media Unshielded twisted-pair (UDP) cable
Categories: 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e
Unshielded twisted-pair (UDP) cable
Categories: 3, 4, 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 Ω at 3, 4, 5, 5e
Transmission distance
100 m (distance between hub and node)
Number of cascade
connections
There is no limitation when a switching hub is used.
Current consumption (Unit) 410 mA max. at 5 V DC
Vibration resistance Conforms to JIS 0040.
10 to 57Hz: 0.075-mm amplitude, 57 to 150 Hz: acceleration 9.8 m/s
2
in X, Y, and Z
directions for 80 minutes each (sweep time: 8 minutes × 10 sweeps = 80 minutes)
Shock resistance Conforms to JIS 0041.
147m/s
2
, 3 times each in X, Y, and Z directions
Ambient operating temperature 0 to 55°C
Ambient humidity 10% to 90% (with no condensation)

10
EtherNet/IP Unit Specifications Section 1-2
CJ-series EtherNet/IP Unit
Atmosphere Must be free of corrosive gas.
Ambient storage temperature −20 to 75°C
Weight 171 g max.
Dimensions 35 × 130 × 101 mm (W × H × D)
Item Specifications
Item Specifications
Model number CJ1W-EIP21
Type 100Base-TX (Can be used as 10Base-T, but this is not recommended.)
Applicable PLCs CJ-series PLCs
Unit classification CJ-series CPU Bus Unit
Mounting location CPU Rack or Expansion Rack
Number of Units that can be
mounted
4 max. (including Expansion Racks)
CPU Unit
words used
Allocated CIO Area
words (CPU Bus
Unit words)
25 words/Unit (one unit number’s words)
These words contain control bits and flags, the target node PLC’s operating and error
information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status.
Allocated DM Area
words (CPU Bus
Unit words)
100 words/Unit (one unit number’s words)
These words contain the IP address display/setting area.
User-set area Any usable data area words
Target node PLC’s operating and error information, and registered/normal target
node information
CPU Bus Unit System Setup
Not used.
Non-volatile memory within EtherNet/IP Unit (See note.)
The following settings are made from the Network Configurator and stored in the EtherNet/IP Unit’s non-volatile memory.
Note Unlike the regular Ethernet Units, the CPU Unit’s CPU Bus Unit System Setup
Area (Unit settings area) is not used for these settings.
1. TCP/IP settings such as the EtherNet/IP Unit’s IP address, DNS server, host name,
and baud rate
2. Device parameter settings (communications settings such as the tag data link setting parameters, FINSUDP settings, and FINS/TCP settings)
Tr an s fe r
specifications
Media access
method
CSMA/CD
Modulation method Baseband
Transmission paths Star form
Baud rate 100 Mbit/s (100Base-TX) 10 Mbit/s (10Base-TX)
Transmission media Unshielded twisted-pair (UDP) cable
Categories: 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e
Unshielded twisted-pair (UDP) cable
Categories: 3, 4, 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 Ω at 3, 4, 5, 5e
Transmission distance
100 m (distance between hub and node)
Number of cascade
connections
There is no limitation when a switching hub is used.
Current consumption (Unit) 410 mA max. at 5 V DC
Vibration resistance Conforms to JIS 0040.
10 to 57Hz: 0.075-mm amplitude, 57 to 150 Hz: acceleration 9.8 m/s
2
in X, Y, and Z
directions for 80 minutes each (sweep time: 8 minute × 10 sweeps = 80 minutes)
Shock resistance Conforms to JIS 0041.
147m/s
2
, 3 times each in X, Y, and Z directions

12
EtherNet/IP Unit Specifications Section 1-2
1-2-2 Communications Specifications
Note (1) In this case, pps means “packets per second” and indicates the number
of packets that can be processed in one second.
(2) To use 505 to 1444 bytes as the data size, the system must support the
Large Forward Open standard (an optional CIP specification). The CS1,
NE1S, and CJ1 CPU Units support this standard, but other companies’
devices may not support it.
Item CS/CJ NE1S
CIP service
Tag data links
(Cyclic communications)
Number of connections 256
Packet interval (refresh
cycle)
0.5 to 10,000 ms (in 0.5-ms units)
Can be set independently for each connection. (Data is
refreshed over the network at the preset interval and does not
depend on the number of nodes.)
Allowed communications
bandwidth per Unit
6000 pps (See note 1.)
Number of tag sets 256
Tag types CIO, DM, EM, HR, WR
Number of tags per connection (= 1 tag set)
8 (7 tags when the tag set contains the PLC status)
Maximum link data size per
node
184,832 words
Maximum data size per connection
252 words or 722 words (See note 2.)
Note Data synchronicity is maintained within each connection.
Number of registrable tag
sets
256
(1 connection = 1 tag set)
Maximum size of 1 tag set 722 words
(The PLC status uses 1 word when the tag set contains the PLC
status.)
Maximum number of tags
that can be refreshed per
CPU Unit cycle (See note 3.)
Output/Transmission (CPU →
EtherNet/IP): 19
Input/Reception (EtherNet/IP
→ CPU): 20 (See note 4.)
---
Data that can be refreshed
per CPU Unit cycle (See note
3.)
Output/Transmission (CPU →
EtherNet/IP): 7,405 words
Input/Reception (EtherNet/IP
→ CPU): 7,405 words
Output/Transmission (CPU →
EtherNet/IP): 6,432 words
Input/Reception (EtherNet/IP
→ CPU): 6,432 words
Changing tag data link
parameters during operation
Supported (See note 5.)
Multi-cast packet filter function (See note 6.)
Supported
Explicit messaging
Class 3 (connected) Number of connections: 128
UCMM (unconnected) Number of clients that can communicate at one time: 32 max.
Number of servers that can communicate at one time: 32 max.
CIP routing CS1W-EIP21
CJ1W-EIP21
CS1W-EIP21
CJ1W-EIP21
NE1S-CPU01
NE1S-DRM21U
NE1S-CNS21U
FINS service FINS/UDP Supported
FINS/TCP 16 connections max.
EtherNet/IP conformance test Conforms to A3.7.3
Ethernet interface 10BASE-T or 100BASE-TX
Auto Negotiation or fixed settings

19
Network Configurator Overview Section 1-4
The node address can be set to any number in the setting range (01 to FE),
as long as the same address is not set on another node in the network.
Note If the node address setting is changed during operation, the MS Indicator will
flash red.
1-4 Network Configurator Overview
1-4-1 Overview
The Network Configurator Ver. 2.0 or later is software designed for building,
setting, and controlling a multi-vendor EtherNet/IP Network using OMRON’s
EtherNet/IP. The Network Configurator provides the following functions for
building, setting, and controlling EtherNet/IP.
Network Control The Network configuration can be created and edited regardless of whether
the Network Configurator is online or offline.The Network configuration can be
read from a file or the network.
Hardware (EDS File)
Control
EDS files used by the Network Configurator can be installed and deleted.
1-4-2 Network Configurator Requirements
Note (1) The following interface card and software are required to connect through
an RSLinx interface.
• Allen-Bradley 1784-PCC Communication Card
• Rockwell RSLinx 2.1 Software
(2) The following Interface Board or Interface Card is required to connect
through a DeviceNet interface.
• OMRON 3G8F7-DRM21 DeviceNet PCI Board
Item Specification
Operating
environment
Hardware Personal computer: IBM PC/AT or compatible
CPU: Pentium 300 MHz or higher
Memory: 256 Mbytes
Hard disk: A minimum of 40 Mbytes available space
Monitor: SVGA (800 ×600 pixels) min.
CD-ROM drive or DVD drive: At least 1 drive
OS Windows 2000 or Windows XP
(Windows is a registered trademark of Microsoft Corporation.)
Network
connection
method
Interface CS/CJ-series port NE1S-series port
Serial interface CPU Unit’s Peripheral or RS-232C port CPU Unit’s USB/RS-232C port
Ethernet interface EtherNet/IP Unit’s Ethernet port CPU Unit’s Ethernet port
RSLinx interface Not supported. ControlNet Unit’s ControlNet port (See
note 1.)
DeviceNet interface Not supported. DeviceNet Unit’s DeviceNet port (See
note 2.)
Location on Network A single node address is used (only when directly connected to EtherNet/IP).
Number of Units that can be connected to Network
A single Network Configurator per Network (More than one Configurator cannot be
used in the same system.)
Main functions
Network control
functions
• The Network configuration can be created and edited regardless of whether the
Network Configurator is online or offline.
• The Network configuration can be read from a file or the network.
Configuration functions
The EDS files used by the Network Configurator can be installed and deleted.
Supported file formats Configurator network configuration files (*.ncf)

22
Design Procedures Section 2-1
2-1 Design Procedures
This section describes how to design an EtherNet/IP system in the following
two cases.
(1) Establishing a new EtherNet/IP system
(2) Modifying an established EtherNet system
2-1-1 Establishing a New EtherNet/IP System
This section describes how to use the Network Configurator to construct a
new EtherNet/IP system by designing the new system and downloading the
parameters to the network devices.
Selecting a Switching
Hub
Always use a switching hub when using tag data links. Select a switching hub
with the functions required for the communications being used in the network.
Refer to 2-2 Selecting the Network Devices.
System Design and Programming (Offline Operations)
1. Starting the Network Configurator
Start the Network Configurator.
Refer to ???7-2-1 Starting and Network Configurator.
2. Registering Devices
Use the Network Configurator to register devices in the EtherNet/IP network.
Refer to ???7-2-3 Registering Devices.
3. Setting Device Parameters
Set the device parameters (communications settings such as tag data link
parameters, FINS/UDP settings, and FINS/TCP settings) for each device
in the network configuration.
Refer to ???7-2-4 Creating Tag Sets and ???7-2-5 Setting the Con-
nections with Target Devices.
4. Verifying the Network Bandwidth Being Used
The network’s communications load capacity is called the bandwidth. Verify that the bandwidth used by the EtherNet/IP tag data links does not exceed the allowed network bandwidth.
If the bandwidth exceeds the allowed level, adjust the packet interval (RPI).
Refer to 2-3 Checking Bandwidth Usage and Adjusting the Packet In-
terval (RPI).
5. Calculating and Verifying the Maximum Response Time
Calculate the maximum response time of all of the tag data links, and verify
that the response time meets the required specifications. If the response
time does not meet the required specifications, evaluate and correct the
network configuration by taking steps such as dividing the network.
Refer to ???Section 11 Communications Performance and Communi-
cations Load.
6. Saving the Network Configuration File
Save the network configuration file with the completed design.
Refer to ???7-2-11 Saving the Network Configuration File.

23
Design Procedures Section 2-1
7. Closing the Network Configurator
Exit from the Network Configurator.
The next steps are wiring the network and connecting the Network Configurator to the network.
Constructing the
Actual System
Wire the network, install the actual devices, and set the devices’ IP
addresses.
8. Clearing the Devices’ Various Parameters
Clear the various parameters stored in the new devices that will be used in
the system.
Refer to ???7-2-10 Clearing Device Parameters.
Note Before connecting newly added devices to the network, clear the parameters
set in the devices. The EtherNet/IP Unit will restart automatically when the
Unit’s device parameters are cleared (reset) from the Network Configurator.
The Unit must restart in order to enable the cleared parameter settings
(default settings). Clear (reset) the device parameters only after verifying that
restarting the Unit will not cause any problems in the system.
9. Changing the Devices’ IP Addresses
Set the actual devices’ IP addresses. Any of the following methods can be
used to set the EtherNet/IP Unit’s local IP address.
• If you want to connect the EtherNet/IP Unit immediately, the default IP
address is 192.168.250.node address. (The node address is set with
the Node Address Setting Switches on the front of the Unit.)
• If you want to set a particular IP address and set (store) that local IP
address in the CPU Unit, set it with the CPU Unit’s allocated DM Area
words.
• If you want to set a particular IP address and set (store) that local IP
address in the EtherNet/IP Unit, set the TCP/IP with the Network Configurator.
Refer to ???4-8 TCP/IP Settings.
Note (1) Before connecting a device to the network, set a suitable IP address for
the device.
(2) When setting the EtherNet/IP Unit’s local IP address with the Network
Configurator, connect the Units one at a time, and download the TCP/IP
setting parameters.
The EtherNet/IP Unit will restart automatically when the TCP/IP setting
parameters are downloaded to the Unit from the Network Configurator.
The Unit must restart in order to enable the parameter settings. Download
the TCP/IP setting parameters only after verifying that restarting the Unit
will not cause any problems in the system.
Downloading Device
Parameters
10. Starting the Network Configurator
Start the Network Configurator.
Refer to ???7-2-1 Starting and Network Configurator.
11. Reading the Network Configuration File
Read the network configuration file, which was saved with the completed
design, into the Network Configurator.
Refer to ???7-2-12 Reading the Network Configuration File.

24
Design Procedures Section 2-1
12. Verifying the IP Addresses
Verify that the devices’ IP addresses in the network configuration file
matches the actual devices’ IP addresses. If one of the IP addresses does
not match, change the IP address so that it matches.
Refer to ???4-8 TCP/IP Settings.
13. Connecting the Network Configurator to the Network
Connect the Network Configurator to the CPU Unit through the serial port
or Ethernet interface.
Refer to ???7-2-6 Connecting the Network Configurator to the Net-
work.
14. Downloading the Device Parameters
Download the parameters to all of the devices in the network.
Refer to ???7-2-7 Downloading Tag Data Link Parameters.
15. Verifying the Downloaded Device Parameters
Compare the parameters in all of the devices in the network, to verify that
the user-set device parameters were properly downloaded and saved in
the devices.
Refer to ???7-2-9 Comparing the Tag Data Link Parameters.
16. Closing the Network Configurator
Exit from the Network Configurator.
Note (1) The EtherNet/IP Unit will restart automatically when the device parame-
ters are downloaded to the Unit from the Network Configurator. The Unit
must restart in order to enable the parameter settings. Download the device parameters only after verifying that restarting the Unit will not cause
any problems in the system.
(2) After the device parameters have been downloaded, compare the param-
eters and verify that the saved parameters are correct.
(3) Before operating the actual system, always verify that the devices in the
network are operating as expected in the system design.
Actual System
Operation
17. Operating the Actual System
Start operating the system.
2-1-2 Modifying an Established EtherNet/IP System
This section describes how to change an EtherNet/IP system after the system
has started operating.
Uploading and Saving
the System’s Network
Configuration
1. Stopping the System
Take steps, such as stopping the CPU Unit’s program, so that device parameter changes will not affect the system.
2. Starting the Network Configurator and Connecting to the Network
Start the Network Configurator and connect it to the network via the CPU
Unit’s serial port or an Ethernet interface.
Refer to ???7-2-1 Starting the Network Configurator and ???7-2-6
Connecting the Network Configurator to the Network.
3. Uploading the Network Configuration
Upload the network information to collect the current network configuration.

25
Design Procedures Section 2-1
Refer to ???7-2-8 Uploading Tag Data Link Parameters.
4. Saving the Network Configuration File
Save a network configuration file containing all of the devices’ verified parameters.
Refer to ???7-2-11 Saving the Network Configuration File.
5. Closing the Network Configurator
Exit from the Network Configurator.
Changing the Actual
System Configuration
Refer to the modified specifications and make the necessary changes, such
as changing network wiring, changing IP addresses, adding devices, and
deleting devices.
6. Clearing Parameters in Added Devices
Clear the various parameters stored in the added devices.
Refer to ???7-2-10 Clearing Device Parameters.
Note Before connecting newly added devices to the network, clear the parameters
set in the devices. The EtherNet/IP Unit will restart automatically when the
Unit’s device parameters are cleared (reset) from the Network Configurator.
The Unit must restart in order to enable the cleared parameter settings
(default settings). Clear (reset) the device parameters only after verifying that
restarting the Unit will not cause any problems in the system.
7. Changing the Devices’ IP Addresses
Set the IP addresses of the added devices.
• If you want to connect the EtherNet/IP Unit immediately, the default IP
address is 192.168.250.node address. (The node address is set with
the Node Address Setting Switches on the front of the Unit.)
• If you want to set a particular IP address and set (store) that local IP
address in the CPU Unit, set it with the CPU Unit’s allocated DM Area
words.
• If you want to set a particular IP address and set (store) that local IP
address in the EtherNet/IP Unit, set the TCP/IP with the Network Configurator.
Refer to ???4-8 TCP/IP Settings.
Note (1) Before connecting a device to the network, set a suitable IP address.
(2) When setting the EtherNet/IP Unit’s local IP address with the Network
Configurator, connect the Units one at a time, and download the TCP/IP
setting parameters.
The EtherNet/IP Unit will restart automatically when the TCP/IP setting
parameters are downloaded to the Unit from the Network Configurator.
The Unit must restart in order to enable the parameter settings. Download
the TCP/IP setting parameters only after verifying that restarting the Unit
will not cause any problems in the system.
Changing Device
Parameters
8. Starting the Network Configurator
Start the Network Configurator to redesign the network.
9. Reading the Network Configuration File
Read the previously saved network configuration file.
Refer to ???7-2-12 Reading the Network Configuration File.

26
Design Procedures Section 2-1
10. Changing the Network Configuration
Make the changes required in the system redesign, such as adding devices, deleting devices, and changing IP addresses.
Refer to ???4-8 TCP/IP Settings.
11. Changing the Device Parameters
Change the device parameters for each device in the network configuration, as required in the system redesign.
Refer to ???7-2-4 Creating Tag Sets and ???7-2-5 Setting the Con-
nections with Target Devices.
12. Verifying the Network Bandwidth Being Used
Verify that the bandwidth used by the EtherNet/IP tag data links does not
exceed the allowed network bandwidth.
If the bandwidth exceeds the allowed level, adjust the packet interval (RPI).
Refer to ???2-3 Checking Bandwidth Usage and Adjusting the Packet
Interval (RPI).
13. Recalculating and Verifying the Maximum Response Time
Calculate the maximum response time of all of the tag data links, and verify
that the response time meets the design requirements. If the response
time does not meet the required specifications, evaluate and correct the
network configuration by taking steps such as using a different switching
hub or dividing the network.
Refer to 2-2 Selecting the Network Devices.
Refer to ???Section 11 Communications Performance and Communi-
cations Load.
14. Saving the Network Configuration File
Save the modified network configuration file.
Refer to ???7-2-11 Saving the Network Configuration File.
15. Closing the Network Configurator
Exit from the Network Configurator.
The next steps are completing the changes in the actual system and connecting the Network Configurator to the network.
Note Changing Target Device Parameters
If the target device parameters are changed, they will no longer agree with the
parameter information registered in the originator device where the target
device is registered. A yellow bar will be displayed next to the target device
icon to indicate when this occurs.
Open the Edit Device Parameters Dialog Box and check target device information.
Downloading the
Changed Device
Parameters
16. Reading the Network Configuration File
Read the network configuration file, which was saved with the completed
design.
Refer to ???7-2-12 Reading the Network Configuration File.
17. Starting the Network Configurator and Connecting to the Network
Start the Network Configurator and connect it to the network via the CPU
Unit’s serial port or an Ethernet interface.
Refer to ???7-2-1 Starting the Network Configurator and ???7-2-6
Connecting the Network Configurator to the Network.

27
Selecting the Network Devices Section 2-2
18. Downloading the Device Parameters
Download the parameters to all of the devices.
Refer to ???7-2-7 Downloading Tag Data Link Parameters.
19. Verifying the Downloaded Device Parameters
Compare the parameters in all of the devices, to verify that the user-set device parameters were properly downloaded and saved in the devices.
Refer to ???7-2-9 Comparing the Tag Data Link Parameters.
20. Closing the Network Configurator
Exit from the Network Configurator.
Note (1) The EtherNet/IP Unit will restart automatically when the device parame-
ters are downloaded to the Unit from the Network Configurator. The Unit
must restart in order to enable the parameter settings. Download the device parameters only after verifying that restarting the Unit will not cause
any problems in the system.
(2) After the device parameters have been downloaded, compare the param-
eters and verify that the saved parameters are correct.
(3) Before operating the actual system, always verify that the devices in the
network are operating as expected in the system design.
Restarting Actual
System Operation
21. Operating the Actual System
Start operating the system.
2-2 Selecting the Network Devices
2-2-1 Recommended Network Devices
The following table shows the devices recommended for use with the EtherNet/IP Unit.
Part Maker Model number Inquires
Switching
Hub
Cisco Systems, Inc. WS-C2955T-12 (12-port switching hub)
Note For use in an FA environment
Cisco Systems, Inc. Main Corporate HQ: (800) 553-6387
Contec USA, Inc. SH-8008(FIT)H CONTEC USA Inc.: (408) 400-8700
Phoenix Contact FL SWITCH SFN 8TX Phoenix Contact USA Customer
Service: (800) 808-7177
Tw is t e d- p ai r
cable
100BASE-TX
Fujikura F-LINK-E 0.5mm × 4P Fujikura America, Inc.:
(408) 748-6991
Specifications: STP cable (shielded,
twisted-pair cable)
Category 5 or 5e
Note Impedance up to 100 Ω max.
Fujikura CTP-LAN5 0.5 mm × 4P
Specifications: UTP cable (unshielded,
twisted-pair cable)
Category 5 or 5e

28
Selecting the Network Devices Section 2-2
Note (1) Always use a switching hub when using tag data links in the network.
(2) If a repeater hub is used for EtherNet/IP tag data links (cyclic communi-
cations), the network’s communications load will increase, data collisions
will occur frequently, and stable communications will be impossible.
2-2-2 Switching Hub Types
Layer 2 (L2) Switching
Hub
These switching hubs use the Ethernet MAC address to switch ports. Ordinary switching hubs have this function.
Layer 3 (L3) Switching
Hub
These switching hubs use the Ethernet MAC address or IP address to switch
ports. When using an EtherNet/IP Unit, select from the following functions.
• L2 switch without multicast filtering function
• L2 switch with multicast filtering function
• L3 switch with multicast filtering function and L2/L3 QoS function
2-2-3 Switching Hub Functions
This section describes the switching hub functions which are important when
using an EtherNet/IP network.
Multicast Filter The multicast filter transfers multicast packets to the specific nodes only. This
function is implemented in the switching hub as IGMP Snooping or GMRP.
“Specific nodes” are nodes equipped with an IGMP client that have made
transfer requests to the switching hub. (OMRON EtherNet/IP Units are
equipped with an IGMP client.)
When the hub does not use the multicast filter, multicast packets are sent to
all nodes, just like broadcast packets, which increases the traffic in the network. Settings must be made in the switching hub to enable this function.
Layer 3/4 QoS (Quality of
Service) Function
This function controls the priority of packet transmissions, so that packets can
be sent with higher priority to a particular IP address and TCP (UDP) port.
When tag data links and message communications are executed on the same
network, tag data links can be sent at higher priority to prevent problems such
as transmission delays due to message communications traffic and packet
losses due to buffer overflow. Settings must be made in the switching hub to
enable this function and give higher priority to tag data link packets.
2-2-4 Precautions When Selecting a Switching Hub
The functions supported by the switching hub may affect tag data link transmission delays and the configuration. In addition, if the switching hub supports
advanced functions, special settings are required for those functions.
Connectors
(Modular
plug)
STP Plug
Panduit Corporation MPS588 Panduit Corporation US Headquar-
ters: (800) 777-3300
UTP Plug
Panduit Corporation MP588-C Panduit Corporation US Headquar-
ters: (800) 777-3300
Boots Tsuko Company MK boot (IV) LV Tsuko Company Japan Headquar-
ters 011-81 (03) 3542-2781
Part Maker Model number Inquires

29
Selecting the Network Devices Section 2-2
When selecting a switching hub, it is necessary to consider whether the
switching hub will be selected based on the kind of communications that will
be performed in the network or the kind of switching hub that you want to use.
Refer to the following precautions when selecting a switching hub.
Selecting the Switching Hub Based on the Types of Network Communications
Executing Tag Data Links
Only
We recommend using an L2 switching hub without multicast filtering or an L2
switching hub with multicast filtering.
Using an L2 switching hub with multicast filtering prevents increased traffic
due to unnecessary multicast packets, so the tag data links can operate at
higher speed. If either of the following conditions exists, the amount traffic will
be the same for both kinds of L2 switching hubs (with or without multicast filtering).
• The tag data links are set to share the same data with all nodes in the network. (The multicast packets are transferred to all nodes in the network,
just like a broadcast.)
• The tag data link settings are all one-to-one (unicast) and multicast packets cannot be used.
If the multicast filter function is being used, settings must be made for that
function in the switching hub.
Executing Tag Data Links
and Message
Communications
We recommend using an L3 switching hub with multicast filtering and L3/L4
QoS.
By setting tag data links for higher-priority transmission, it is possible to prevent problems such as transmission delays due to message communications
traffic and packet losses due to buffer overflow. Settings must be made in the
switching hub to enable this function and give higher priority to tag data link
packets.
Special settings must be made in the switching hub when using the multicast
filtering function and L3/L4 QoS function.
Selecting the Switching Hub Based on the Hub’s Supported Functions
L2 Switching Hub without
Multicast Filtering
We recommend this kind of switching hub when only tag data links are executed and any of the following conditions is met.
• The tag data links are set to share the same data with all nodes in the network. (The multicast packets are transferred to all nodes in the network,
just like a broadcast.)
• The tag data link settings are all one-to-one (unicast) and multicast packets cannot be used.
• There is little traffic in the tag data links.
No special settings are required for an L2 switching hub without multicast filtering.
L2 Switching Hub with
Multicast Filtering
We recommend this kind of switching hub when only tag data links are executed and the following condition is met.
• There are many 1:N links (where N represents some number of nodes in
the network) in the tag data link settings, i.e., there are many multicast
packets used, or there is heavy traffic in the tag data links.
Special settings are required for an L2 switching hub with multicast filtering.
L3 Switching Hub with
Multicast Filtering and L3/
L4 QoS Functions
We recommend this kind of switching hub when both tag data links and message communications are executed.

Terms and Conditions of Sale
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of all quotes, agreements, purchase orders, acknowledgments, price lists,
catalogs, manuals, brochures and other documents, whether electronic or in
writing, relating to the sale of products or services (collectively, the "Products
by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron
objects to any terms or conditions proposed in Buyer’s purchase order or other
documents which are inconsistent with, or in addition to, these Terms.
2. Prices; Payment Terms.
out notice by Omron. Omron reserves the right to increase or decrease prices
on any unshipped portions of outstanding orders. Payments for Products are
due net 30 days unless otherwise stated in the invoice.
3. Discounts.
sent to Buyer after deducting transportation charges, taxes and duties, and will
be allowed only if (i) the invoice is paid according to Omron’s payment terms
and (ii) Buyer has no past due amounts.
4. Interest.
the maximum legal rate, whichever is less, on any balance not paid within the
stated terms.
5. Orders
6. Governmental Approvals.
costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7. Taxes
real property and income taxes), including any interest or penalties thereon,
imposed directly or indirectly on Omron or required to be collected directly or
indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs
duties and sales, excise, use, turnover and license taxes) shall be charged to
and remitted by Buyer to Omron.
8. Financial.
to Omron, Omron reserves the right to stop shipments or require satisfactory
security or payment in advance. If Buyer fails to make payment or otherwise
comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all
amounts, including amounts payable hereunder, whether or not then due,
which are owing to it by Buyer. Buyer shall in any event remain liable for all
unpaid accounts.
9. Cancellation; Etc.
unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure
resulting from causes beyond its control, including earthquakes, fires, floods,
strikes or other labor disputes, shortage of labor or materials, accidents to
machinery, acts of sabotage, riots, delay in or lack of transportation or the
requirements of any government authority.
11. Shipping; Delivery.
a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall
c. All sales and shipments of Products shall be FOB shipping point (unless oth-
d. Delivery and shipping dates are estimates only; and
e. Omron will package Products as it deems proper for protection against nor-
12. Claims.
Products occurring before delivery to the carrier must be presented in writing
to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products
from Omron in the condition claimed.
13. Warranties
Products will be free from defects in materials and workmanship for a period of
twelve months from the date of sale by Omron (or such other period expressed
in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
Cash discounts, if any, will apply only on the net amount of invoices
Omron, at its option, may charge Buyer 1-1/2% interest per month or
. Omron will accept no order less than $200 net billing.
. All taxes, duties and other governmental charges (other than general
If the financial position of Buyer at any time becomes unsatisfactory
except in “break down” situations.
constitute delivery to Buyer;
erwise stated in writing by Omron), at which point title and risk of loss shall
pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid;
mal handling and extra charges apply to special conditions.
Any claim by Buyer against Omron for shortage or damage to the
. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
All prices stated are current, subject to change with-
Buyer shall be responsible for, and shall bear all
Orders are not subject to rescheduling or cancellation
. Omron shall not be liable for any delay or failure in delivery
Unless otherwise expressly agreed in writing by Omron:
. OMRON MAKES NO WARRANTY OR REPRESENTATION,
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
")
INTENDED USE. Omron further disclaims all warranties and responsibility of
any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy
gation hereunder shall be, at Omron’s election, to (i) replace (in the form
originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding
the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the
use of Products in combination with any electrical or electronic components,
circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing,
are not to be construed as an amendment or addition to the above warranty.
See http://www.omron247.com
l
ished information.
14. Limitation on Liability; Etc
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual
price of the Product on which liability is asserted.
15. Indemnities
their employees from and against all liabilities, losses, claims, costs and
expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises
or is alleged to arise from Buyer's acts or omissions under these Terms or in
any way with respect to the Products. Without limiting the foregoing, Buyer (at
its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim
that any Product made to Buyer specifications infringed intellectual property
rights of another party.
16. Property; Confidentiality.
sive property of Omron Companies and Buyer shall not attempt to duplicate it
in any way without the written permission of Omron. Notwithstanding any
charges to Buyer for engineering or tooling, all engineering and tooling shall
remain the exclusive property of Omron. All information and materials supplied
by Omron to Buyer relating to the Products are confidential and proprietary,
and Buyer shall limit distribution thereof to its trusted employees and strictly
prevent disclosure to any third party.
17. Export Controls.
licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
regulated technology or information.
18. Miscellaneous
and no course of dealing between Buyer and Omron shall operate as a waiver
of rights by Omron. (b) Assignment
without Omron's written consent. (c) Law.
law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment
Buyer and Omron relating to the Products, and no provision may be changed
or waived unless in writing signed by the parties. (e) Severability
sion hereof is rendered ineffective or invalid, such provision shall not invalidate
any other provision. (f) Setoff
against the amount owing in respect of this invoice. (g) Definitions
herein, “including
nies” (or similar words) mean Omron Corporation and any direct or indirect
subsidiary or affiliate thereof.
. Buyer shall indemnify and hold harmless Omron Companies and
Buyer shall comply with all applicable laws, regulations and
. (a) Waiver. No failure or delay by Omron in exercising any right
” means “including without limitation”; and “Omron Compa-
or contact your Omron representative for pub-
. OMRON COMPANIES SHALL NOT BE LIABLE
Any intellectual property in the Products is the exclu-
. Buyer may not assign its rights hereunder
These Terms are governed by the
. These Terms constitute the entire agreement between
. Buyer shall have no right to set off any amounts
. Omron’s sole obli-
. If any provi-
. As used
Certain Precautions on Specifications and Use
1. Suitability of Use. Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying
ratings and limitations of use which apply to the Product. This information by
itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application
or use. Buyer shall be solely responsible for determining appropriateness of
the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a
non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical
interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation
systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
2. Programmable Products.
user’s programming of a programmable Product, or any consequence thereof.
3. Performance Data
and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s
test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations
of Liability.
4. Change in Specifications
changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed,
or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for
your application. Please consult with your Omron’s representative at any time
to confirm actual specifications of purchased Product.
5. Errors and Omissions.
checked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading errors or omissions.
Omron Companies shall not be responsible for the
. Data presented in Omron Company websites, catalogs
. Product specifications and accessories may be
Information presented by Omron Companies has been