CJ1W-NC113/213/413/133/233/433
Position Control Units
Operation Manual
Revised February 2008
iv
Notice:
r
f
OMRON products are manufactured for use according to proper procedures
by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this
manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGERIndicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury. Additionally, there may be severe property damage.
!WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury. Additionally, there may be severe property damage.
!CautionIndicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also
capitalized when it refers to an OMRON product, regardless of whether or not
it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON
products, often means “word” and is abbreviated “Wd” in documentation in
this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
OMRON, 2001
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
The following headings appear in the left column of the manual to help you
locate different types of information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3...1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v
Unit Versions of CJ-series Position Control Units
Unit VersionsA “Unit version” has been introduced to manage Position Control Units in the
CJ Series according to differences in functionality accompanying Unit
upgrades.
Notation of Unit Versions
on Products
CJ-series Position Control Unit
NC113
X
R
U
N
E
R
C
E
R
H
3
4
2
3
4
2
5
1
5
1
0
6
0
6
7
7
9
8
9
8
20
20
CN1
1
1
X
Confirming Unit Versions
with Support Software
1,2,3...1. In the IO Table Window, right-click the Position Control Unit and select Unit
The Unit version is given to the right of the lot number on the nameplate of the
applicable Position Control Units, as shown below.
Product nameplate
CJ1W-NC113
NC UNIT
Unit version
Example for Unit version 2.3
Lot No. 031001 0000 Ver.2.3
OMRON CorporationMADE IN JAPAN
The Unit version of the Position Control Units begins at version 2.0.
The Unit version can be confirmed in Unit Manufacturing Information of CXProgrammer version 4.0 or higher using the following procedure.
Manufacturing information.
2. The following Unit Manufacturing information Dialog Box will be displayed.
vi
Unit version
2.3
Example: Unit version 2.3 will be displayed in the Unit Manufacturinginformation Dialog Box.
Use the above display to confirm the Unit version of the Position Control
Unit.
Using the Unit Version
Label
The following Unit version label is provided with the Position Control Unit.
This label can be attached to the front of the Position Control Unit to differentiate between Position Control Units of different Unit versions.
Unit Version Notation
In this manual, the Unit version of a Position Control Unit is given as shown in
the following table.
Product nameplateNotation used in this manualSpecial remarks
Ver. 2.0 or later number
shown to the right of the
lot number
Blank to the right of lot
number
CJ-series Position Control Unit Ver. 2.0 or later.Information without reference
to specific Unit versions
applies to all versions of the
Pre-Ver. 2.0 CJ-series Position Control Unit
Unit.
Functions Supported by Each Unit Version of Position Control Unit
Unit VersionPre-Ver. 2.0Ver. 2.0Ver. 2.3
Internal system software version1.02.02.3
CJ-series Position Control UnitsCJ1W-NC113/133/213/233/413/433
FunctionsChanging the acceleration
Support SoftwareCX-Position Ver. 1.0
for a multiple start during
relative movement or
absolute movement in
direct operation
Changing acceleration/deceleration time during jog operation
Setting acceleration/deceleration time for axis
parameters until the target
speed is reached
Setting jog operation Not supportedNot supportedSupported
Setting deviation counter
reset output signal
Checking parameters and
data at startup
Not supportedSupportedSupported
Not supportedSupportedSupported
Not supportedSupportedSupported
Not supportedNot supportedSupported
Not supportedNot supportedSupported
Not supportedNot supportedSupported
Not supportedNot supportedSupported
Not supportedNot supportedSupported
Not supportedNot supportedSupported
or later
CX-Position Ver. 1.0 (See note 2.)
CX-Position Ver. 2.0 or later
CX-Position Ver. 1.0 (See note 2.)
CX-Position Ver. 2.0 (See note 2.)
CX-Position Ver. 2.1 (See note 2.)
CX-Position Ver. 2.2 or later
Note1. The Position Control Unit must be installed with CJ1-H or CJ1M CPU Unit
to use the above functions supported for Position Control Unit Ver. 2.0.
These functions cannot be used if the Position Control Unit is installed with
a CJ1 CPU Unit.
2. With CX-Position Ver. 1.0, new functions added to Position Control Units
Ver. 2.0 or higher cannot be used.
vii
Checking Position Control Unit Version and Internal System Software Version
Position Control Units have an internal system software version in addition to
the Unit version used by CS/CJ-series Units to distinguish functions. The following table shows the relationship between the Position Control Unit’s Unit
version and internal system software version.
Version typeUnit versionInternal system software version
DetailsVersion code for distinguishing functions sup-
ported for CS/CJ-series Units.
Checking methodThe Unit version code is displayed to the right
of the lot number on the nameplate attached
to the Position Control Unit.
The Unit version code can also be checked
from CX-Programmer Ver. 4.0 in Unit Manu-facturing information of the I/O Table Window.
CorrelationPre-Ver. 2.01.0
Ver. 2.02.0
Ver. 2.32.3
Version code for internal system software.
Press the Ctrl + V Keys while the CX-Position
NC Monitor Screen is displayed.
viii
Version Upgrade Information
The following tables outline changes made for the most recent version upgrade for SYSMAC CJ-Series
Position Control Units.
■ Enhanced Functions for Unit Version 2.0
Changing Multiple-start Acceleration for Relative and Absolute Movement during Direct Operation
Previous versionPresent version (Ver. 2.0 or later)
When executing multiple starts during direct
operation, the acceleration/deceleration times
set for the first start were used.
Changing Accelerations/Decelerations and Changing Deceleration Following Interrupt Inputs for Interrupt Feeding during Direct Operation
Previous versionPresent version (Ver. 2.0 or later)
The speed command could be changed as
long as it was done before the interrupt signal
was input. If an acceleration/deceleration time
was changed, the change would not be effective until the next interrupt feed command. The
acceleration/deceleration times set for the first
start were used for speed changes. The deceleration time set for the first start was used after
interrupt signal input.
Allowing Changes to Acceleration/Deceleration Time during Jogging
Previous versionPresent version (Ver. 2.0 or later)
The only speed changes allowed during jogging were those made with the speed command. If acceleration/deceleration times
changed, the changes were not effective until
the next JOG command. The deceleration time
set when the JOG operation was started was
used for accelerations/decelerations for speed
changes as well as for JOG stops or deceleration stops.
When executing multiple starts during direct operation, the acceleration time set for each of the multiple starts is used and the deceleration time set for the first start is used.
The acceleration/deceleration times can be changed and changes
can be made with the speed command as long as the changes are
made before the interrupt signal is input. The acceleration/deceleration times can also be changed during acceleration and deceleration. The deceleration time set for when the interrupt input occurs is
used following interrupt signal input.
In addition to changes made during JOG operation with the speed
command, speed changes can also be made during JOG operation
by changing the acceleration/deceleration times. Accelerations/decelerations can also be changed during acceleration/deceleration. Accelerations/decelerations can also be changed during
acceleration/deceleration to a fixed speed. The deceleration time
set when the stopping the JOG operation is executed is used for
JOG stops or deceleration stops.
Setting Acceleration/Deceleration Time in Axis Parameters as Time Required to Reach Target Speed
Previous versionPresent version
Acceleration/deceleration times could be set
only as the time required for each axis to go
from the initial speed to the maximum speed.
The acceleration/deceleration time can be set in one of the following ways.
• Set as the time required for each axis to go from the initial
speed to the maximum speed (previous setting method).
• Set as the time required for each axis to go from the present
speed to the target speed. (This simplifies calculating acceleration/deceleration times.)
Addition of Easy Backup Function
Previous versionPresent version
There was no easy backup function.The easy backup function of the CPU Unit can be used to automat-
ically back up and restore the following data from/to flash memory
in the PCU along with all data from the CPU Unit using a Memory
Card in the CPU Unit. It can also compare the data. This makes it
easier to back up all PLC data or to prepare backup data in case
Units are replaced.
• Axis parameters
• Sequence data
• Speed data
• Acceleration/deceleration time data
• Dwell time data
• Zone data
NoteData for all Unit axes is stored at the same time.
ix
■ Enhanced Functions in the Upgrade from Unit Version 2.0 to
Unit Version 2.3
Setting the Number of Unused Axes
Previous versionPresent version (Ver. 2.3 or later)
Emergency stop input wiring was also required
for unused axes.
Setting the CW/CCW Pulse Output Direction
Previous versionPresent version (Ver. 2.3 or later)
The pulse output direction could not be
changed.
Addition of Origin Search Pattern Setting
Previous versionPresent version (Ver. 2.3 or later)
Operation was uneven if a return was performed at the origin proximity and operation
immediately stopped at the origin input signal.
Setting the Position Data When the Origin Signal Stops
Previous versionPresent version (Ver. 2.3 or later)
The stopping point was always 0.The value of the stopping point can be set. Applications in which
Setting the number of unused axes in the common parameters
eliminates the need for emergency stop input wiring for unused
axes.
Bits for reversing the output direction have been added to the axis
parameter areas. Specifying reversal reverses the output section
and is effective for applications using the same wiring but reversed
coordinates.
Reverse mode 3 has been added to enable stopping at the origin
signal at the proximity speed when a return is performed at the origin proximity.
the stopping point is not 0 do not require presetting the present
position.
Jog Operation Setting
Previous versionPresent version (Ver. 2.3 or later)
Axes could not be operated from the CX-Position.
The following operations are possible in combination with CX-Position version 2.2, which will be included with CX-One version 1.1
scheduled for sale November 2005.
• Parameter settings for jog operation (acceleration/deceleration
time, run signal allocation)
• Error reset
• Keyboard lock/unlock button
• RUN signal ON/OFF
• +Jog/
−jog
• Monitoring the present position, limit sensor, and other functions
while the jog operation is being performed.
Deviation Counter Reset Output Signal Setting
Previous versionPresent version (Ver. 2.3 or later)
The deviation counter reset output could not
be turned ON and OFF from the CX-Position.
The following operations are possible in combination with CX-Position version 2.2, which will be included with CX-One version 1.1
scheduled for sale November 2005.
• Turning ON and OFF the deviation counter reset output.
Checking Parameters and Data at Startup
Previous versionPresent version (Ver. 2.3 or later)
Parameters and data were not checked at startup.
Parameters and data for up to four axes can be checked and up to
four errors (i.e., one per axis) can be detected and output.
This manual describes the operation of the CJ1W-NC113/NC133/NC213/NC233/NC413/NC433 Position Control Units and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before
attempting to install and operate the CJ1W-NC113/NC133/NC213/NC233/NC413/NC433 Position
Control Units.
Section 1 introduces the features of the Position Control Unit and explains the system configuration in
which it is used.
Section 2 gives an overview of the procedures required to use the Position Control Unit.
Section 3 provides information on nomenclature and the function of each part, describes the proce-
dures required for wiring and installation, and gives connection examples. Information on using Servo
Relay Units is also provided.
Section 4 provides an overview of the parameter and data settings used in Position Control Unit operation and provides information on memory allocation.
Section 5 explains how to transfer and save parameters and data using the data transfer bits, the
IOWR and IORD instructions, and CX-Position.
Section 6 explains the origin search and origin return operations.
Section 7 provides an overview of direct operation, describes the parameter and data settings
required to perform direct operation, and gives sample programs.
Section 8 provides an overview of memory operation, describes the parameter and data settings
required to perform memory operation, and gives sample programs.
Section 9 describes the following operations: Jogging, teaching, interrupt feeding, forced interrupt,
deceleration stop, override, error counter reset output/origin-adjustment command output, backlash
compensation, and software limits.
Section 10 provides examples of programs for using the Position Control Unit.
Section 11 describes how to diagnose and correct errors that can occur during operation.
Section 12 describes methods for maintaining the Position Control Unit.
The Appendices provide information on estimating times and pulses for acceleration and deceleration, a memory map for the common parameter area, error code lists, information on replacing the
C200HW-NC@13, and parameter coding sheets.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section
in its entirety and be sure you understand the information provided in the section and
related sections before attempting any of the procedures or operations given.
xv
xvi
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON
representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xvii
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.
xviii
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xix
xx
PRECAUTIONS
This section provides general precautions for using the Position Control Units and related devices.
The information contained in this section is important for the safe and reliable application of the Position Control
Unit. You must read this section and understand the information contained before attempting to set up or operate
a Position Control Unit.
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the
manual or applying the product to nuclear control systems, railroad systems,
aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used
improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide
the systems, machines, and equipment with double safety mechanisms.
This manual provides information for using the Position Control Unit. Be sure
to read this manual before attempting to use the Unit and keep this manual
close at hand for reference during operation.
!WARNING It is extreme important that Position Control Units and related devices be used
for the specified purpose and under the specified conditions, especially in
applications that can directly or indirectly affect human life. You must consult
with your OMRON representative before applying Position Control Units and
related devices to the above mentioned applications.
3Safety Precautions
!WARNING Never attempt to disassemble any Units while power is being supplied. Doing
so may result in serious electric shock.
!WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do
so may result in malfunction, fire, or electric shock.
!WARNING Never touch any of the terminals while power is being supplied. Doing so may
result in serious electric shock.
!WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller or Position Control Unit) to ensure safety in the system if an abnormality occurs due to malfunction of the PLC, malfunction of the PCU (Position
Control Unit), or external factors affecting the operation of the PLC or PCU.
Not providing sufficient safety measures may result in serious accidents.
xxii
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety
measures must be provided in external control circuits.
Safety Precautions3
• The PLC will turn OFF all outputs when its self-diagnosis function detects
any error or when a severe failure alarm (FALS) instruction is executed.
As a countermeasure for such errors, external safety measures must be
provided to ensure safety in the system.
• The PLC or PCU outputs may remain ON or OFF due to deposits on or
burning of the output relays, or destruction of the output transistors. As a
countermeasure for such problems, external safety measures must be
provided to ensure safety in the system.
• When the 24-V DC output (service power supply to the PLC) is overloaded or short-circuited, the voltage may drop and result in the outputs
being turned OFF. As a countermeasure for such problems, external
safety measures must be provided to ensure safety in the system.
• External safety measures must also be taken to ensure safety in the event
of unexpected operation when connecting or disconnecting the PCU’s
connectors.
!Caution When positioning to a position determined using the teaching function, set the
position designation setting in the positioning sequence to absolute positioning. If it is set to relative positioning, positioning will be performed to a position
other than the one obtained with the teaching function.
!Caution Execute online edit only after confirming that no adverse effects will be
caused by extending the cycle time. Otherwise, the input signals may not be
readable.
!Caution Confirm the safety of the destination node before transferring a program to the
node or changing the contents of I/O memory. Doing either of these without
confirming safety may result in injury.
!Caution Do not save data into the flash memory during memory operation or while the
motor is running. Otherwise, unexpected operation may be caused.
!Caution Do not reverse the polarity of the 24-V power supply. The polarity must be cor-
rect. Otherwise, the motor may start running unexpectedly and may not stop.
!Caution Make sure the unit version of the Position Control Unit is 2.3 or later before
using the CW/CCW Pulse Output Selection Function. Otherwise, the pulse
output may be in the opposite direction from what was intended and the
machine may be damaged.
xxiii
Operating Environment Precautions4
4Operating Environment Precautions
!Caution Do not operate the control system in the following locations:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified
in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution Take appropriate and sufficient countermeasures when installing systems in
the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution The operating environment of the PLC System can have a large effect on the
longevity and reliability of the system. Improper operating environments can
lead to malfunction, failure, and other unforeseeable problems with the PLC
System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life
of the system.
xxiv
Application Precautions5
5Application Precautions
Observe the following precautions when using the PCU or the PLC.
!WARNING Failure to abide by the following precautions could lead to serious or possibly
fatal injury. Always heed these precautions.
• Always connect to a ground of 100 Ω or less when installing the Units. Not
connecting to a ground of 100
• Always turn OFF the power supply to the PLC before attempting any of
the following. Not turning OFF the power supply may result in malfunction
or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Memory Cassettes, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
!Caution Failure to abide by the following precautions may lead to faulty operation of
the PLC, the PCU. or the system, or could damage the PLC or PCU. Always
heed these precautions.
Ω or less may result in electric shock.
• Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal
lines, momentary power interruptions, or other causes.
• Interlock circuits, limit circuits, and similar safety measures in external circuits (i.e., not in the Programmable Controller) must be provided by the
customer.
• Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
• Install the PLC Unit as far as possible from sources of strong harmonic
noise.
• Lock the sliders securely until the click into place when connecting the
Power Supply Unit, CPU Unit, I/O Units, Special I/O Units, or CPU Bus
Units. Functions may not work correctly if the sliders are not locked properly.
• Always attach the End Cover provided with the CPU Unit to the Unit on
the right end of the PLC. The CJ-series PLC will not operate properly if
the End Cover is not attached.
• Be sure that the external I/O connector lock screws are tightened to the
torque specified in the relevant manuals. Incorrect tightening torque may
result in malfunction.
• Always use the power supply voltages specified in the operation manuals.
An incorrect voltage may result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the
rated voltage and frequency is supplied in places where the power supply
is unstable. An incorrect power supply may result in malfunction.
xxv
Application Precautions5
• Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals. Connection of bare stranded wires may result in
burning.
• Leave the label attached to the Unit when wiring. Removing the label may
result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Do not apply voltages to the Input Units in excess of the rated input voltage. Excess voltages may result in burning.
• Do not apply voltages or connect loads to the Output Units in excess of
the maximum switching capacity. Excess voltage or loads may result in
burning.
• Check the user program for proper execution before actually running it on
the Unit. Not checking the program may result in an unexpected operation.
• Be sure that the terminal blocks, Memory Units, expansion cables, and
other items with locking devices are properly locked into place. Improper
locking may result in malfunction.
• Double-check all wiring and switch settings before turning ON the power
supply. Incorrect wiring may result in burning.
• Disconnect the LR and GR terminals when performing insulation resistance or withstand voltage tests. Not disconnecting the functional ground
terminal may result in burning.
• Confirm that no adverse effect will occur in the system before attempting
any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PLC (including the operating
mode at power up).
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming
operation. Not doing so may result in an unexpected operation.
• Do not pull on the cables or bend the cables beyond their natural limit.
Doing either of these may break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so
may break the cables.
• Resume operation only after transferring the system parameter data to
the PCU and saving the data to flash memory. Not doing so may result in
an unexpected operation.
• Confirm that set parameters and data operate properly.
• Check the pin numbers before wiring the connectors.
• Perform wiring according to specified procedures.
• Before touching a Unit, be sure to first touch a grounded metallic object in
order to discharge any static build-up. Not doing so may result in malfunction or damage.
• Do not drop the Unit or subject it to abnormal shock or vibration.
xxvi
Conformance to EC Directives6
6Conformance to EC Directives
6-1Applicable Directives
•EMC Directives
6-1-1Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or
machines. The actual products have been checked for conformity to EMC
standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the
customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of
the equipment or control panel in which the OMRON devices are installed.
The customer must, therefore, perform final checks to confirm that devices
and the overall machine conform to EMC standards.
Note Applicable EMC (Electromagnetic Compatibility) standards are as follows:
The PCUs comply with EC Directives. To ensure that the machine or device in
which a PCU is used complies with EC Directives, the PCU must be installed
as follows:
1,2,3...1. The PCU must be installed within a control panel.
2. Reinforced insulation or double insulation must be used for the DC power
supplies used for the communications and I/O power supplies.
3. PCUs complying with EC Directives also conform to the Common Emission Standard (EN61000-6-4). With regard to the radiated emission (10-m
regulations), countermeasures will vary depending on the devices connected to the control panel, wiring, the configuration of the system, and
other conditions. The customer must, therefore, perform final checks to
confirm that devices and the overall machine conform to EC Directives.
6-1-3Installation within Control Panel
Unnecessary clearance in cable inlet or outlet ports, operation panel mounting holes, or in the control panel door may cause electromagnetic wave leakage or interference. In this case, the product may fail to meet EC Directives. In
order to prevent such interference, fill clearances in the control panel with conductive packing. (In places where conductive packing comes in contact with
the control panel, ensure electrical conductivity by removing the paint coating
or masking these parts when painting.)
xxvii
Conformance to EC Directives6
xxviii
SECTION 1
Introduction
This section introduces the features of the Position Control Unit and explains the system configuration in which it is used.
These Position Control Units are CJ-series Special I/O Units. The Units
receive instructions from the Programming Controller’s Work Area and output
pulse trains to various motor drivers for positioning.
1-1-1Functions
High-speed ResponseThe Position Control Unit (PCU) responds to instructions from the CPU Unit
within 2 ms. (For more details on the conditions required, refer to Appendix A
Performance Characteristics.)
Memory Operation and
Direct Operation
There are two different control methods. The first is memory operation, in
which the data required for positioning is transferred to the PCU and then
specified for position control, and the second is direct operation, in which the
target position and target speed are set each time from the CPU Unit.
Number of Control Axes
and Output Type
The PCU is available with 1, 2, or 4 control axes. With 2-axis and 4-axis models, linear interpolation is possible for all axes. Either open collector output or
line driver output is available for any number of control axes. Choose the most
appropriate model according to the number of controlled axes and the desired
output type.
Motor Driver Selectable by
Axis
A stepping motor driver and a pulse train input type Servo Drive can be connected to the PCU. It is possible to set different operating modes for different
axes allowing the combined use of different types of motor driver.
Interrupt FeedingWhen an interrupt is input during pulse output, positioning is continued for
only a specified amount and then stopped.
Position and Speed
Control Ranges
Positioning can be performed for positions in the range –1,073,741,823 to
1,073,741,823 pulses and speeds in the range 1 to 500,000 pps in 1-pulse
units. This means that positioning is possible over a wide range with speed
precision.
2
Fe at ur e sSection 1-1
Data Capacity and BackupThe amounts of data that can be set for memory operation are shown in the
following table:
Type of dataNumber of data items per axis
Positioning sequences, speeds, positions100
Acceleration times, deceleration times9
Dwell times19
Zones3
These data items are transferred to the PCU for use. Once they have been
transferred to the PCU they can be saved to the PCU’s flash memory, so
there is no need for battery maintenance.
NoteThere is a limit to the service life of the flash memory. A total of up to 100,000
data saving operations can be performed.
CX-PositionThe PCU is compatible with the Windows-based NC Support Software (CX-
Position) that enables setting of the PCUs in a Windows environment. Using
the CJ-series single-port multi-access function, creation and transfer of
parameters and data for PCUs as well as operation monitoring are possible
from the same environment as the software used for CPU Unit ladder programming (CX-Programmer).
Simple Programming
Using Function Blocks
(See note.)
Function blocks can be used to simplify operation of the PCU in programming
complicated diagrams. There are function blocks for origin searches, ABSOLUTE MOVEMENT commands, and RELATIVE MOVEMENT commands.
NoteRefer to the following documents for details on function blocks.
• Using Function Blocks for the First Time
Function Block Introduction Guide (R133)
• Using Function Blocks for Specific Devices
OMRON FB Library Start-up Guide (R123)
OMRON FB Library Reference Manual (W442)
3
System ConfigurationSection 1-2
1-2System Configuration
The PCU receives control signals (CW limit, CCW limit, origin, origin proximity, emergency stop, and external interrupt input signals) from devices and a
control panel, and outputs pulse trains to stepping motor drivers and Servo
Drives.
1-2-1CJ1W-NC413 System Configuration Example
Use for setting
data and
monitoring.
Editing parameters and data.
Monitoring status.
File management.
Note(1) A dedicated cable is available for connecting the PCU to the dedicated
terminal block.
(2) Origin input signals cannot be used as external connection terminals with
dedicated terminal blocks. Connect the Z-phase signal to the Servo Drive
using the dedicated cable. The connecting cable required between the
PCU or dedicated terminal block and stepping motor driver is not provided.
4
Basic OperationsSection 1-3
1-3Basic Operations
The PCU’s operations are as follows:
Position
Control Unit
functions
Position controlMemory
operation
Direct operation
Interrupt feeding
Speed control
Other operationsOrigin search
Independent
Automatic
Continuous
Jogging
Teaching
Override
Present position
preset
Backlash
compensation
Zone setting
Deceleration stop
1-3-1Position Control
Positioning can be executed with either an absolute value (i.e., to an absolute
position from the origin) or with an incremental value (i.e., to a relative position
from the present position).
There are two methods for positioning: memory operation and direct operation. Interrupt feeding, in which operation proceeds for a specified amount
after an interrupt input, is also possible.
Direct OperationWith direct operation, positions and speeds are set directly from the CPU Unit
(ladder program), and positioning is executed according to operating commands. It is also possible to change the speed and send commands to move
5
Basic OperationsSection 1-3
to different positions while positioning is being performed. Linear interpolation,
however, is not possible during direct operation.
operations, which include data such as positions and speeds) are transferred
to the PCU in advance, and then positioning is executed from the CPU Unit by
specifying those positioning sequences by number. Depending on the completion code that is set, positioning sequences can be executed using independent positioning, automatic positioning, or continuous positioning. In the
following illustrations, “#0” “#1” “#2” and “#3” indicate positioning sequence
numbers.
Pecuted in Order
ositioning Sequences Ex
Speed
Independent
Positioning
Automatic
Positioning
Continuous
Positioning
"#0""#1""#2""#3"
Time
Start
Stop
Start
Pauses for length
of dwell time that
is set.
Does not stop.
Interrupt FeedingWhen an interrupt input signal is received, positioning is continued for the
specified amount of pulses and then stopped.
Interrupt input signal
Speed
Specified amount
of pulses
Time
6
Basic OperationsSection 1-3
1-3-2Speed Control
When a start is executed once, pulses are continuously output at a constant
rate. The pattern depends on the completion code that is set for “memory
operation” positioning sequences. To stop the sequence, use the STOP command.
Speed
Start
STOP
Time
1-3-3Other Operations
Origin SearchThe origin search operation finds the origin for the designated axis.
JoggingThe jogging operation moves a specified axis at a designated speed and then
stops it.
TeachingThe teaching operation takes the present position for the specified positioning
sequence.
Origin
Present position
Specified positioning sequence number
OverrideWhen the override is enabled during positioning, the target speed is changed
to the override speed.
Changing the Present
Position
Speed
A x 1.5
A
Override enable
1
0
The PRESENT POSITION PRESET command changes the present position
to a specified position.
Override setting: 150%
Time
Backlash CompensationThis operation compensates for the amount of mechanical play, or “loose-
ness,” present in gears.
7
List of FunctionsSection 1-4
ZonesA zone is a range of positions which can be defined so that flags are turned
ON whenever the present position is within the range.
CCWCW
Zone setting
Zone Flag
ON
OFF
Deceleration StopThe STOP command decelerates positioning to a stop.
STOP
Speed
1
0
Time
1-4List of Functions
GroupNameFunctionPage
Origin determinationOrigin searchStarts the motor and establishes the origin.149
Present position presetSets the position at which the motor is stopped to a spec-
Origin returnReturns the axis to the origin.175
Direct operationAbsolute/relative move-
ment
Interrupt feedingDesignates position, speed, and acceleration/decelera-
Memory operationAbsolute/relative move-
ment
Linear interpolationContinuously performs positioning by linear interpolation
Interrupt feedingPerforms interrupt feeding according to positioning
Speed controlOutputs pulses at a fixed speed according to positioning
Forced interruptStops the positioning operation currently being performed
ified value, and establishes the origin.
Designates position, speed, and acceleration/deceleration times, and carries out absolute or relative positioning.
tion times, and after the interrupt signal turns ON, moves
a specified amount before stopping.
Continuously performs absolute or relative positioning
according to positioning sequences previously set in the
PCU.
according to positioning sequences previously set in the
PCU.
sequences previously set in the PCU.
sequences set in the PCU.
and performs another positioning operation.
174
180
239
198
217
239
214
242
8
List of FunctionsSection 1-4
GroupNameFunctionPage
Data saving/transferHigh-speed transferTransfers data between the CPU Unit and the PCU in a
Batch transferTransfers a large amount of data in one operation
SavingSaves parameters, position data, and speed data to non-
Common to direct operation and memory operation
JoggingOutputs pulses at a fixed speed in the CW or CCW direc-
TeachingReads the currently stopped position as position data.237
Deceleration stopDecelerates axes to a stop during positioning. Axes can-
OverrideChanges the axis speed during positioning.249
Error counter resetClears the error counter of the Servo Drive to 0.252
Backlash compensationIncreases positioning accuracy by compensating for play
Software limitIn order to prevent damage to external devices due to
ZonesNotifies the CPU whether or not the position is within a
Acceleration/deceleration curve, acceleration/
deceleration time designation
Initial pulseStarts pulse output in a short time in response to an oper-
Stop functionDetects an error either at the CPU Unit or the PCU and
Release prohibit/error
reset
short time using the IOWR and IORD instructions in the
ladder program.
between the CPU Unit and the PCU.
volatile memory (flash memory) in the PCU.
tion.
not be moved while the STOP Bit is ON.
in the mechanical system.
unexpected positioning caused by malfunction, in addition to CW and CCW limit input signals, positioning is also
monitored using the software.
set region. This function is used when interlocking or performing simultaneous control with peripheral devices.
Specifies performing acceleration/deceleration according
to the basic trapezoidal curve, or an S-curve that greatly
helps to reduce mechanical vibration. Specifies the
method for setting the acceleration/deceleration times.
ating command from the CPU Unit.
stops pulse output either with or without a deceleration
curve.
Releases the pulse output prohibit status and at the same
time clears the error code to 0.
132,
139
121,
127
143
235
244
256
258
104
87
93
261
338
9
SpecificationsSection 1-5
1-5Specifications
1-5-1Basic Specifications
ItemModel
CJ1W-NC113/133CJ1W-NC213/233CJ1W-NC413/433
Power supply voltage
Allowable power
supply voltage
range
Internal current consumption
Current consumption of external
power supply
External dimensions
Weight100 g max.100 g max.150 g max.
Ambient operating
temperature
5 V DC (for the PCU itself)
24 V DC (external power supply)
5 V DC (external power supply; line driver output only)
4.75 to 5.25 V DC (for the PCU itself)
21.6 to 26.4 V DC (external power supply)
4.75 to 5.25 V DC (external power supply; line driver output
only)
250 mA max. at
5VDC
NC113: 30 mA
max. at 24 V DC
NC133: 10 mA
max. at 24 V DC
NC133: 60 mA
max. at 5 V DC
90 (H) × 31 (W) × 65 (D) (all models)
0 to 55°C0 to 50°C
250 mA max. at
5VDC
NC213: 50 mA
max. at 24 V DC
NC233: 20 mA
max. at 24 V DC
NC233: 120 mA
max. at 5 V DC
22.8 to 25.2 V DC
(external power
supply)
360 mA max. at
5VDC
NC413: 100 mA
max. at 24 V DC
NC433: 30 mA
max. at 24 V DC
NC433: 230 mA
max. at 5 V DC
NoteSpecifications not listed above conform to CJ Series general specifications.
Refer to
3-3-5 Mounting Precaution for CJ1W-NC413/NC433 for information
on the ambient operating temperature of the CJ1W-NC413/433.
10
SpecificationsSection 1-5
1-5-2Performance Specifications
ItemModel
CJ1W-NC113/133CJ1W-NC213/233CJ1W-NC413/433
Applicable PLC modelsCJ-series PLCs
I/O requirementsWords5 words10 words20 words
Controlled driverPulse-train input-type Servo Drive or stepping motor driver
NC113/213/413 models have open collector output.
NC133/233/433 models have line driver output.
ControlControl systemOpen-loop control by pulse train output
Number of control
axes
Control unitPulse
Positioning operationsTwo types: memory operation and direct operation
PositionsRange–1,073,741,823 to 1,073,741,823 pulses (See note.)
Data items100/axis
SpeedsRange1 pps to 500 kpps
Data items100/axis
Acceleration and
deceleration times
Functions and settings Origin searchOrigin proximity input signal: selectable (absent, N.O. or N.C. contact).
Range0 to 250 s, until maximum speed is reached.
Data items9/axis for acceleration and deceleration each
JoggingJogging can be executed at a specified speed.
Dwell times19/axis can be set from 0 to 9.99 s (unit: 0.01 s).
Acceleration/
deceleration curves
ZonesZone Flag turns ON when present position is within a specified zone.
Software limitsCan be set within a range of –1,073,741,823 to 1,073,741,823 pulses.
Backlash compensation
TeachingWith a command from the PLC, the present position can be taken as the
Deceleration stopThe STOP command causes positioning to decelerate to a stop accord-
Emergency stopPulse outputs are stopped by an external emergency stop command.
1 axis2 axes4 axes
Origin input signal: selectable (N.O. or N.C. contact)
Origin compensation: –1,073,741,823 to 1,073,741,823 pulses
Origin search speed: High-speed or proximity-speed can be set.
Origin detection method: May be set to stop upon origin input signal
after proximity input signal has turned ON, to stop upon origin input signal after proximity input signal has turned OFF, to stop upon origin input
signal without using proximity input signal, or to stop upon origin input
signal after limit input signal has turned OFF.
N.O. = Normally open
N.C. = Normally closed
Trapezoidal or S-curve (Can be set separately for each axis.)
Three zones can be set for each axis.
0 to 9,999 pulses. Compensation speed can also be set.
position data.
ing to the specified deceleration time.
11
SpecificationsSection 1-5
ItemModel
CJ1W-NC113/133CJ1W-NC213/233CJ1W-NC413/433
Functions and settings Present position pre-
set
OverrideWhen the override enabling command is executed during positioning,
Data saving1) Saving to flash memory. (Can be written 100,000 times.)
External I/OInputsPrepare the following inputs for each axis:
OutputsPrepare the following outputs for each axis:
Pulse output distribution period1-axis operation: 4 ms
Response timeRefer to Appendix A Performance Characteristics.
Self-diagnostic functionFlash memory check, memory loss check, CPU bus check
Error detection functionOvertravel, CPU error, software limit over, emergency stop
The PRESENT POSITION PRESET command can be used to change
the present position to a specified value.
the target speed is changed by applying the override coefficient. Possible to set to a value from 1 to 999% (by an increment of 1%)
2) Reading from PLC area by data reading instruction.
3) Reading by Support Software and saving to personal computer
hard disk or floppy disk.
Pulse outputs
CW/CCW pulses, pulse outputs and direction outputs can be switched.
Either error counter reset or origin-adjustment command outputs can be
selected depending on the mode.
Linear interpolation: 8 ms
Note(1) The additional functions supported by unit version 2.0 can be used only
when the PCU is installed with a CJ1-H or CJ1M CPU Unit (either CPU
Unit Ver. 2.0 or Pre-Ver. 2.0 CPU Unit). These functions cannot be used
if the PCU is installed with a CJ1 CPU Unit.
For details on Unit versions, refer to Unit Versions of CJ-series PositionControl Units on page vi. For details on additional functions supported for
unit version 2.0, refer to Unit Versions of CJ-series Position Control Units
on page vi.
(2) When performing linear interpolation, the distances that can be moved
will vary. For details, refer to 8-6 Linear Interpolation.
12
Comparison with Existing ModelsSection 1-6
1-6Comparison with Existing Models
The differences between the CJ1W-NC4@3/2@3/1@3 Position Control Units
and CS1W-NC4@3/2@3/1@3 and C200HW-NC413/213/113 Position Control
Units are given in the following table.
ItemCJ1W-NC4@3/
Unit number allocationAllocate unit numbers in the range 0 to
Pulse output type2 types: open collector output and line
Format of data exchanged between
PLC and PCU
Position designation range–1,073,741,823 to 1,073,741,823
Present position range–2,147,483,647 to 2,147,483,647
Zone range–1,073,741,823 to 1,073,741,823
Speed designation range1 to 500,000 pps, set in pps units1 to 500,000 pps, set in units of the
CPU Unit scan timeover for END
refresh
CPU Unit scan timeover due to IOWR/
IORD instruction
Time between startup instruction from
the ladder program and pulse output
Operating data areaThe following 3 areas can be specified:
Corresponding EM banksBanks 0 to CBank 0 only
Clearing error codesPossibleNot possible (only cleared to 0 when
Parameter settingSettings only required for the axes being
Mounting on C200H Slave Rack
(remote I/O)
External I/O connector40 pins48 pins48 pins
Support SoftwareCX-Position
2@3/1@3
95.
1-axis and 2-axis PCUs: One unit num-
ber allocated
4-axis PCUs: 2 unit numbers allocated
driver output
Binary format (hexadecimal)
Example: Present position is output to
the PLC in 32-bit signed binary format.
pulses
pulses
pulses
0.5 ms max. per PCU2.6 to 4.5 ms per PCU
1 ms max. per instruction2.4 to 62 ms per instruction
2 ms max. (at optimum conditions)7.51 ms max. (at optimum conditions)
DM Area words allocated to Special I/O
Units, user-specified DM Area words,
and user-specified EM Area words.
used.
Not possiblePossible
(Conversion of parameters and data
created using the SYSMAC-NCT possible.)
CS1W-NC4@3/
2@3/1@3
C200HW-NC413/213/113
Allocate unit numbers in the range 0 to
15.
1-axis and 2-axis PCUs: One unit
number allocated
4-axis PCUs: 2 unit numbers allocated
Open collector output only
BCD format
Example: Present position is output to
the PLC in BCD format.
–9,999,999 to 9,999,999 pulses
–9,999,999 to 9,999,999 pulses
–9,999,999 to 9,999,999 pulses
smallest multiplication factor specified
The following 2 areas can be specified: User-specified DM Area words
and user-specified EM Area words.
(The DM Area words allocated to Special I/O Units cannot be specified.)
startup instruction is made)
Settings required for all axes.
SYSMAC-NCT
13
Control System PrinciplesSection 1-7
1-7Control System Principles
1-7-1Data Flow
Position Control Unit
Stepping motor driver
Pulse train
Stepping motor
CPU Unit
PC BUS
MPU
I/F
Memory
Pulse
generator
I/O
interface
Pulse
generator
I/O connector
Magnetizing distribution circuit
Power
amplifier
External
input
I/O
interface
I/O connector
Pulse train
Servo Drive
Error counterPower amplifier
Servomotor
(Positioning output)
Tachogenerator
Rotary encoder
14
Control System PrinciplesSection 1-7
1-7-2Control System Principles
Open-Loop SystemIn an open-loop system, positioning is controlled according to the number of
input pulses that the motor receives, and no position feedback is provided.
The PCUs all employ pulse-output-type open-loop systems, and the most
commonly used motor for this type of control system is a stepping motor. The
angle of rotation of a stepping motor can be controlled through the number of
pulse signals supplied to the motor driver. The number of rotations of the stepping motor is proportional to the number of pulses supplied by the PCU, and
the rotational speed of the stepping motor is proportional to the frequency of
the pulse train.
Position controller
(e.g., PCU)
Stepping motor or
pulse-train input-type
servomotor
Pulse
train
Reduction gear
Turntable
Ball screw
1-7-3Basic Positioning System Design
The following diagram and parameters illustrate a simplified positioning system.
M: Reduction ratio
P: Feed screw pitch (mm/revolution)
V: Feed velocity of object being positioned (mm/s)
θ
: Stepping angle per pulse (degree/pulse)
s
N
Stepping motor
Reduction gear
M
Object being
positioned
V
Feed screw pitch
P
The travel distance per pulse sent to the motor driver is called the “pulse rate”
and is calculated according to the following equation:
Pulse rate = P/(pulses per revolution x M)
= P/((360/
= (P x
θ
) x M))
s
θ
)/(360 x M)
s
Using the pulse rate, the number of pulses required to move the object a distance L is given by the following calculation:
No. of pulses= Travel distance
÷ Pulse rate
= L
÷ (P x θ
= L
= (360
× M × L)/(P x θ
÷ Pulse rate
)/(360 x M)
s
)
s
The pulse speed required to move the object with a feed speed of V mm/s is
given by the following calculation:
Pulse speed= Feed speed
÷ Pulse rate
= V
÷ (P x θ
= V
= (360
× M × V)/(P x θ
÷ Pulse rate
)/(360 x M)
s
)
s
The PCU performs positioning control by providing the number of pulses and
the pulse speed in the form of position instructions and speed instructions.
15
Control System PrinciplesSection 1-7
16
Basic Procedures
This section gives an overview of the procedures required to use the Position Control Unit.
SECTION 2
17
Basic ProceduresSection 2
The following table shows the basic flow of operation for the PCU.
Flow of operationReference
InstallationSECTION 3 Installation and Wir-
Mount the PCU.
Set the unit number of the PCU.
START
ing
3-1 Nomenclature and Functions
3-3 Installation
Wiring3-5 Wiring
Connect the PCU to the external input device(s).
Connect the motor and the motor driver.
(See note 1.)
Connect the motor driver and the PCU.
------
Setting the
PCU
Turn ON power to the CPU Unit.
Create I/O tables for the PLC.
Set the common parameters for the PCU in
the DM Area of the CPU Unit.
(See note 3.)
When operating according to the axis
(See note 2.)
SECTION 4 Data Areas
4-3 Common Parameter Area
parameters in the CPU Unit's DM Area.
When operating
according to the axis
parameters saved in
Set the axis parameters for the PCU
in the CPU Unit's DM Area.
4-4 Axis Parameter Area
the PCU.
Set the axis parameters saved in the PCU.
SECTION 5 Transferring and
Read the axis parameters saved in the PCU.
Write the axis parameters to the PCU.
Save the written axis parameters in the PCU.
Enable the set parameters by either turning the
power OFF and ON, or by restarting the PCU.
Saving Data
5-3 Reading Data with the
READ DATA Bit
5-5 Reading Data with IORD
5-2 Writing Data with the
WRITE DATA Bit
5-4 Writing Data with IOWR
5-6 Saving Data
5-7 Transferring Data with
CX-Position
18
(Continued on next page.)
Basic ProceduresSection 2
Flow of operationReference
Programming
and test operation
(Continued from previous page.)
Establish the origin of the motor axis
for operation.
SECTION 6 Defining the Origin
Directly set the target position and speed
from the CPU Unit and start the motor.
Record a positioning sequence (including
positions and speeds) and operate the
motor in accordance with this sequence.
Read the sequence data saved in the PCU.
Write the sequence data to the PCU.
Save the written sequence data in the PCU.
Execute other PCU functions, such as
jogging or teaching.
DebuggingSECTION 11 Troubleshooting
Is there an error?
No
!
Check the LED indicators on the
front of the PCU.
Ye s
SECTION 7 Direct Operation
SECTION 8 Memory Operation
SECTION 9 Other Operations
Read the PCU's error code.
Remove the cause of the error
and clear the error status.
OperationSECTION 10 Program Exam-
Start PLC (and PCU) operation.
MaintenanceSECTION 12 Maintenance and
Perform regular inspections.
END
ples
Inspection
Note1. Perform wiring according to instructions given in the motor and motor driv-
er’s operation manuals.
2. Refer to the operation manual for the CPU Unit.
3. Use the axis parameter designation setting in the common parameter area
to specify whether for operation is performed according to axis parameters
saved in the PCU or the axis parameters set in the CPU Unit’s DM Area.
19
Basic ProceduresSection 2
20
SECTION 3
Installation and Wiring
This section provides information on nomenclature and the function of each part, describes the procedures required for
wiring and installation, and gives connection examples. Information on using Servo Relay Units is also provided.
on the CJ1W-NC213/ NC233 (Unit Versions Earlier Than 2.3) . . . 62
21
Nomenclature and FunctionsSection 3-1
3-1Nomenclature and Functions
CJ1W-NC4@3CJ1W-NC2@3CJ1W-NC1@3
NC413
MACH
No.
10
2020
Z
X
Y
3
2
1
0
9
8
1
RUN
U
ERC
ERH
3
2
4
4
1
5
5
0
6
6
7
7
9
8
LED indicators
Show the PCU's
0
10
operating status.
Unit number setting
switch
Sets the unit number
NC213
X
Y
3
2
4
MACH
1
5
0
6
No.
7
9
8
1
10
2020
RUN
ERC
ERH
3
2
4
1
5
0
6
7
9
8
0
10
NC113
X
3
2
4
MACH
1
5
0
6
No.
7
9
8
1
10
2020
3
2
4
1
5
0
6
7
9
8
for the PCU.
X/Y axis connector
X/Y axis
connector
Connect to
stepping motor
driver or Servo
Drive. (Controls
CN1
CN2
Z/U axis connector
Connect to stepping
motor driver or Servo
Drive. (Controls 2
axes.)
CN1
CN1
2 axes.)
11
Y X
U Z
11
YX
11
X
LED Indicators
NameColorStatusExplanation
RUNGreenLitLit during normal operation.
Not litHardware error, or PLC notified of PCU error.
ERCRedLitAn error has occurred.
Not litNo error has occurred.
ERHRedLitAn error has occurred IN the CPU Unit.
Not litNo error has occurred at the CPU Unit.
XOrangeLitPulses are being output to the X axis (either forward or reverse).
FlashingAn error has occurred, such as incorrect cable type for the X axis or faulty data.
Not litNone of the above has occurred.
YOrangeLitPulses are being output to the Y axis (either forward or reverse).
FlashingAn error has occurred, such as incorrect cable type for the Y axis or faulty data.
Not litNone of the above has occurred.
ZOrangeLitPulses are being output to the Z axis (either forward or reverse).
FlashingAn error has occurred, such as incorrect cable type for the Z axis or faulty data.
Not litNone of the above has occurred.
UOrangeLitPulses are being output to the U axis (either forward or reverse).
FlashingAn error has occurred, such as incorrect cable type for the U axis or faulty data.
Not litNone of the above has occurred.
NoteFor details regarding errors, refer to SECTION 11 Troubleshooting.
RUN
ERC
ERH
10
0
X axis
connector
22
• For the CJ1W-NC113/NC133, this applies only to the X axis; for the
CJ1W-NC213/NC233, it applies only to the X and Y axes.
• When not all of the axes are used for the CJ1W-NC213/NC233/ NC413/
NC433, either connect the CW/CCW limit inputs for the unused axes to
the input power supply and turn them ON or set the contact logic to N.O.
Connect the emergency stop to the input common and turn it ON. If it is
not connected, the ERC indicator will light. Operation will be normal, however, for all axes that are used.
Area AllocationSection 3-2
Unit Number Setting
Switch
This switch sets the unit number (i.e., the machine number) for the PCU as a
Special I/O Unit.
Memory is allocated to the PCU from the CPU Unit’s Special I/O Unit Area
according to the unit number setting.
CJ1W-NC113/NC133/NC213/NC233 models are allocated 10 words and
CJ1W-NC413/NC433 models are allocated 20 words. The following unit number settings are possible:
As long as the unit number settings do not overlap with those of other Special
I/O Units, any unit numbers in the ranges given above can be set.
!Caution Be sure to turn OFF the power supply before making the settings.
3-2Area Allocation
DM Area for Special I/O
Units
CJ1W-NC113/NC133/NC213/NC233 PCUs are allocated 100 words each
and CJ1W-NC413/NC433 PCUs are allocated 200 words each from D20000
to D29599 in the DM Area as shown below.
MACH
No.
1
× 10
3
4
2
1
5
0
6
7
9
8
3
4
2
1
5
0
6
7
9
8
• CJ1W-NC113/NC133/NC213/NC233: 0 to 95
• CJ1W-NC413/NC433: 0 to 94
× 10
0
CJ1W -NC113/NC133/NC213/NC233 CJ1W -NC413/NC433
D20000 to D20099 Unit #0
D20100 to D20199 Unit #1
D20200 to D20299 Unit #2
D20300 to D20399 Unit #3
: :
D29300 to D29399 Unit #93
D29400 to D29499 Unit #94
D29500 to D29599Unit #95
Unit #0D20000 to D20199
Unit #1D20100 to D20299
Unit #2D20300 to D20399
Unit #3D20400 to D20499
: :
Unit #93 D29300 to D29499
Unit #94 D29400 to D29599
Unit #95 Setting not possible.
Word address
m to m+3
m+4 to m+31
m+32 to m+59
m+60 to m+87
m+88 to m+115
m: D20000+100 x unit number
Contents
Common parameters
Axis
parameters
For X axis
For Y axis
For Z axis
For U axis
Special I/O Unit AreaCJ1W-NC113/NC133/NC213/NC233 PCUs are allocated 10 words, and
CJ1W-NC413/NC433 PCUs are allocated 20 words in the Special I/O Unit
Area.
CJ1W-NC113/NC133/NC213/NC233CJ1W-NC113/NC133
Unit #0
Unit #1
Unit #2
Unit #3
Unit #93
Unit #94
Unit #95
CJ1W-NC413/NC433CJ1W-NC413/NC433
CIO 2000 to CIO 2009
CIO 2010 to CIO 2019
CIO 2020 to CIO 2029
CIO 2030 to CIO 2039
:
CIO 2930 to CIO 2939
CIO 2940 to CIO 2949
CIO 2950 to CIO 2959
CIO 2000 to CIO 2019 Unit #0
CIO 2010 to CIO 2029 Unit #1
CIO 2020 to CIO 2039 Unit #2
CIO 2030 to CIO 2049Unit #3
:
CIO 2930 to CIO 2949 Unit #93
CIO 2940 to CIO 2959Unit #94
Setting not possible.Unit #95
:
:
I/O
Output
I/O
Output
Input
Word address Axis
n to n+1
n+2 to n+4 InputX axis
Word addressAxis
n to n+1 X axis
n+2 to n+3 Y axis
n+4 to n+5 Z axis
n+8 to n+10 X axis
n+11 to n+13 Y axis
n+14 to n+16 Z axis
n+17 to n+19U axis
X axis
CJ1W-NC213/NC233
I/O
Output
Input
n: CIO 2000+10 x unit number
U axisn+6 to n+7
Word addressAxis
n to n+1 X axis
n+2 to n+3 Y axis
n+4 to n+6 X axis
Y axisn+7 to n+9
Note1. The CJ1W-NC413/NC433 are allocated the words for two unit numbers,
i.e., the unit number that is set and also the following number.
23
InstallationSection 3-3
2. Be sure to set the unit numbers so that they do not overlap with the unit
numbers of other Special I/O Units.
3. Since the CJ1W-NC413/433 are allocated the words for two unit numbers,
unit number 95 cannot be set.
3-3Installation
3-3-1System Configuration Considerations
• The additional functions supported by Unit version 2.0 can be used only if
the PCU is installed with a CJ1-H or CJ1M CPU Unit (either CPU Unit Ver.
2.0 or Pre-Ver. 2.0 CPU Unit). These functions cannot be used by PCUs
installed with CJ1 CPU Units.
For details on Unit versions, refer to Unit Versions of CJ-series PositionControl Units on page vi. For details on additional functions supported for
Unit version 2.0, refer to Unit Versions of CJ-series Position Control Units
on page vi.
• The I/O bits allocated to a particular Special I/O Unit are determined by
the unit number that is set by the switch on the front panel of the Unit, and
not by the position in which the Unit is mounted.
• The PCU can be connected to CPU Racks or Expansion Racks (up to 10
PCUs per Rack). Up to 40 PCUs can be connected per CPU Unit.
3-3-2Mounting the Unit
Follow the procedure outlined below to mount the Position Control Unit.
1,2,3...1. Join the PCU to the Rack, ensuring that the connectors engage properly.
2. Secure the PCU by sliding the yellow sliders on the top and bottom until
PA205R
P
O
W
E
R
L1
A
C
10
0
-2
4
0V
IN
P
U
T
L2/N
R
U
N
OU
T
P
U
T
A
C
240
V
D
C
24V
they click into place.
PA205R
PO
W
ER
L
1
A
C
1
00-2
40
V
IN
P
U
T
L2
/N
R
U
N
O
U
TP
U
T
A
C
24
0V
D
C
24
V
Connector
SY
R
U
S
N
MA
C
E
R
R
/A
L
M
CJ1G
-C
P
U44
I
NH
PR
O
GR
A
M
M
A
B
LE
P
RP
H
L
C
O
N
T
R
O
LL
ER
C
O
M
M
O
P
E
N
MCPW
R
BUSY
P
E
RIP
HE
R
A
L
P
OR
T
N
C41
R
U
3
N
X
E
R
C
Z
Y
E
R
H
U
M
AC
3
H
4
2
3
4
2
1
5
1
5
0
6
N
o
.
0
6
7
9
7
8
9
8
1
1
0
0
1
0
20
20
2
1
N
N
C
C
1
1
U
Z
Slider
S
Y
R
UN
S
MA
C
E
R
R/
A
L
M
CJ1G
-C
P
U44
I
N
H
P
R
O
GR
A
M
M
A
B
L
E
P
RP
H
L
C
ON
T
R
O
L
L
E
R
CO
MM
O
P
E
N
MCPWR
BUSY
P
E
RIP
HE
RA
L
P
O
R
T
NC
R
41
U
3
N
X
E
R
C
Z
Y
E
R
H
U
MA
3
C
H
4
2
3
4
2
1
5
1
5
0
6
N
o.
0
6
7
9
7
8
9
8
1
1
0
0
1
0
20
20
2
1
N
N
C
C
1
Lock
Release
24
NoteIf the sliders are not locked into place properly, the PCU may not be able to
maintain full functionality.
InstallationSection 3-3
3. To remove the PCU, slide the sliders in the “release” direction and then
separate the PCU from the Rack.
3-3-3Precautions When Handling the PCU
• Before installing or disconnecting the PCU or connecting cable, be sure to
first turn off both the Programmable Controller and the power supply.
• To minimize any influence from noise, place I/O wiring, high-voltage lines,
and power lines in separate ducts.
• Wire clippings tend to get scattered around during wiring, so leave the
label in place on top of the PCU to prevent any clippings from getting
inside the PCU. Once the wiring has been completed, be sure to remove
the label to provide ventilation.
Remove the label after
completing the wiring.
N
C
R
4
U
1
3
N
X
ER
C
Z
Y
E
R
H
U
M
A
3
C
H
4
2
3
4
2
1
5
1
5
0
6
No.
0
6
7
9
7
8
9
8
1
10
20
0
1
0
20
3-3-4Dimensions
CJ1W-NC113/NC133/NC213/NC233/NC413/NC433
2.7
NC413
X
Y
2
MACH
1
0
No.
1
10
2020
90
CN1
1
CN
1
X
Y
2
CN
1
U
Z
66.5
31
RUN
ERC
Z
ERH
U
3
3
2
4
4
1
5
5
0
6
6
7
7
9
9
8
8
0
10
CN2
65
11
Y X
U Z
2.7
NoteThe above diagram is for the CJ1W-NC413.
25
InstallationSection 3-3
Mounted Dimensions
(112.5)
Connecting cable
66.5
65
3-3-5Mounting Precaution for CJ1W-NC413/NC433
Ambient Operating Temperature
The ambient operating temperature of the CJ1W-NC413/NC433 PCUs is 0 to
°C. The ambient operation temperature range, however, can be increased
50
to 0 to 55
lowing conditions.
• A Space Unit is mounted between CJ1W-NC413/NC433 PCUs and any
adjacent Units other than CJ1W-NC413/NC433 PCUs.
• Whenever there are two or more CJ1W-NC413/NC433 PCUs mounted
together on a Rack, a Space Unit is mounted between every two CJ1WNC413/NC433 PCUs.
The following example shows how to use the Space Units when three CJ1WNC413/NC433 PCUs are mounted to the same Rack.
Power Supply Unit
NoteA maximum of 10 Units can be connected in the CPU Rack or any Expansion
Rack, including Space Units. The CPU Unit and CX-Programmer, however,
will not detect the Space Unit as a Unit on the Rack. An error will thus not
occur for any Rack that exceeds the maximum of 10 Units because of the
presence of Space Units. If there are more than 10 Units on a Rack, operating
errors may occur with other Units, such as Special I/O Unit errors. Always be
careful not to have more than 10 Units in any Rack when using Space Units.
°C if the CJ1W-SP001 CJ-series Space Unit is used under the fol-
Unit other than
CJ1W-NC413/NC433
CPU Unit
CJ1W-NC413/NC433 PCUs
CJ1W-SP001 Space Units
Unit other than
CJ1W-NC413/NC433
26
External I/O CircuitrySection 3-4
CJ1W-SP001 Space Unit Specifications
General Specifications
Weight: 50 g
Other specifications conform to CJ Series general specifications.
Dimensions (Unit: mm)
2.7
90
2.7
Space Unit Precautions
The CPU Unit and CX-Programmer will not detect the Space Unit as a Unit on
a Rack. Always be careful not to have more than 10 Units in any Rack.
3-4External I/O Circuitry
SP001
20
65
3-4-1Connector Pin Arrangement
X/Y axis Z/U axisX/Y axisX axis
B20
B1A1
CJ1W-NC413/433CJ1W-NC213/233CJ1W-NC113/133
A20
B20A20
B1A1
B20A20
B1A1
27
External I/O CircuitrySection 3-4
CJ1W-NC113/213/413 (Pulse Open Collector Output)
Connector pin arrangement for X and Z axesConnector pin arrangement for Y and U axes
Pin
No.
A1INPower supply, 24 V DC (for output signals)B1INPower supply, 24 V DC (for output signals)
A2INGND, 24 V DC (for output signals)B2INGND, 24 V DC (for output signals)
A3---Not usedB3---Not used
A4---Not usedB4---Not used
A5OUT CW pulse outputB5OUT CW pulse output
A6OUT CW pulse output with 1.6-kΩ resistanceB6OUT CW pulse output with 1.6-kΩ resistance
B10OUT Error counter reset output with 1.6-kΩ resis-
* Be sure to wire the 5-V DC pulse output power supply with the correct polar-
ity.
I/ODesignation
command output
tance
Origin-adjustment command output with
1.6-kΩ resistance
Note1. Use either the 24-V origin input signal or the 5-V origin input signal, but not
both.
2. Use 24
±10% V DC for the CJ1W-NC1@3/NC2@3 and 24 ±5% V DC for
the CJ1W-NC4@3 as the output power supply.
3. Use 5
±5% V DC as the output power supply.
4. Do not use the 24-V DC output power supply or the 5-V DC pulse output
power supply together with the power supply for another input or output.
5. Be sure to wire the 5-V DC pulse output power supply with the correct polarity. Wiring with the polarity reversed will result in damage to internal elements.
6. The leakage current must be less than 1.0 mA when two-wire-type sensors
are used.
7. Be sure to connect a load to the output terminals. If the load is short-circuited, it will damage the PCU’s internal components.
8. The 24-V output power supply (A1 and B1) and the 24-V output ground (A2
and B2) are connected in the PCU. There is no connection, however, between the X/Y-axis connector and the Z/U-axis connector.
9. The 5-V pulse output power supply (A4 and B4) and the 5-V pulse output
ground (A3 and B3) are connected in the PCU. There is no connection,
however, between the X/Y-axis connector and the Z/U-axis connector.
10. Input commons (A20 and B20) are connected in the PCU. There is no connection, however, between the X/Y-axis connector and the Z/U-axis connector.
29
External I/O CircuitrySection 3-4
11. When installing connectors to the PCU, tighten the connector screws to a
torque of 0.2 N·m.
12. The commons for all outputs are connected to the 24-V output grounds for
the axes.
13. The commons for all inputs except for the 24-V and 5-V origin input signals
and positioning completed input signals are connected to the input common for the axes.
14. The common for the positioning completed input signal is connected to the
24-V output power supply via a diode.
15. Use the origin common as a pair with the 24-V origin input signal or the
5-V origin input signal.
3-4-2External I/O Connector Arrangement
• The connectors that are included with this PCU are solder-type connectors.
• Use wires with cross-sectional areas of 0.2 mm
• Be careful not to short-circuit neighboring terminals when soldering.
• Cover the soldered part of the wire with insulation tubing.
Wiring Power Lines
2
or less.
Connector Pin Numbers
Pin number marks
A1
A2
A3
A4
A5
A6
A19
A20
Outline of connector
(rear panel)
(Connector viewed from soldered side.)
Insulator
Lead
Connector
AB
B1
B2
B3
51
B4
B5
B6
B19
B20
30
External I/O CircuitrySection 3-4
Assembling Connectors Supplied with the PCU
M2x8 pan-head screws (three)
M2.6x25 pan-head screws (two)
Case
M2.6x6 pan-head
screws (two)
Connector
Cable holder
Case
M2.6 nut (two)
M2 nut (three)
The following connectors (Fujitsu 360 Jack) can be used:
The pulse output and error counter reset circuitry of the PCU are provided
with two types of terminals: terminals with 1.6 k
terminals with no resistance. Select the terminals in accordance with the
power requirements and the specifications of the motor driver to be used.
Ω (1/2 W) limit resistance and
33
External I/O CircuitrySection 3-4
!Caution Connect a load of 7 to 30 mA (or 7 to 16 mA for terminals with 1.6-kΩ limit
resistance) to the output section. If a current greater than this is used, it will
cause damage to the PCU’s internal components. Also, be sure to use the
CW/CCW output method when using pulse output terminals with limit resistance.
Open collector outputOpen collector output with 1.6 kΩ series resistance
7 to 30 mA
Output transistor
(Circuit example)
PCU
Output
Output
7 to 16 mA
Add bypass resistance for loads less than 7 mA.
24 VDC
power
supply
7 mA
1 mA
Bypass resistance
6 mA
Driver
Outputs (Line Driver Outputs on the CJ1W-NC133/NC233/NC433)
A4/B4
A3/B3
A5/B5
A6/B6
A7/B7
A8/B8
NoteError counter reset output is open collector output.
!Caution Connect a load of 20 mA max. to the output section. If a current greater than
this is used, it will cause damage to the PCU’s internal components.
Pulse output power supply, 5 VDC
Pulse output GND, 5 VDC
CW pulse output (+)
CW pulse output (–)
CCW pulse/direction output (+)
CCW pulse/direction output (–)
34
External I/O CircuitrySection 3-4
t
!Caution Be sure to wire the 5-V DC pulse output power supply with the correct polarity.
Wiring with the polarity reversed will result in damage to internal elements.
Inputs
Output power supply, 24 VDC
560 Ω
(680 Ω)
4.7 kΩ (5.6 kΩ)
A11/B11
Positioning completed input signal
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
A20/B20
A15/B15
A16/B16
A17/B17
A18/B18
A19/B19
Input common
External interrupt input (N.O. contact)
Emergency stop (N.C. contact)
(see note 2.)
Origin proximity input
(N.O./N.C. contact) (see
note 2.)
CW limit input (N.O./N.C.
contact) (see note 2.)
CCW limit input (N.O./N.C.
contact) (see note 2.)
4.7 kΩ (5.6 kΩ)
A13/B13
150 Ω
A14/B14
560 Ω
(680 Ω)
A12/B12
Origin input signal (24 V)
(N.O./N.C. contact) (see note 2.)
Origin input signal
(N.O./N.C. contact) (see
note 2.)
Origin common
Line driver outpu
Note(1) The values in parentheses apply for the CJ1W-NC413 and
CJ1W-NC433.
(2) Either N.C. or N.O. can be specified using the axis parameters.
For details, refer to
4-3 Common Parameter Area.
For details on connecting origin input signals, refer to page 44.
!Caution Use either the 24-V DC origin input signal or the 5-V DC origin input signal,
but not both. If both are connected it will damage the internal circuitry.
Do not connect the 5-V DC origin input signal input to any output circuit except
the line driver.
35
External I/O CircuitrySection 3-4
3-4-4I/O Electrical Specifications
Input Specifications
ItemSpecification
CJ1W-NC1@3/2@3CJ1W-NC4@3
Voltage24 V DC ±10%24 V DC ±5%
Current4.66 to 5.15 mA (at 24 V) typ. 3.91 to 4.32 mA (at 24 V) typ.
ON voltage17 V DC min.19 V DC min.
OFF voltage5.0 V DC max.
ON response time1 ms max. (0.1 ms max.: Interrupt input and origin input)
OFF response time1 ms max.
Origin-signal Input
Specifications
ItemConnection
External signal is
open collector
signal
External signal is
line driver signal
X/Z AxisA13
Y/U AxisB13
X/Z AxisA14
Y/U AxisB14
Ter m inal
A12
B12
A12
B12
SpecificationResponse
Conform to above input
specifications
Signal is a line driver output
signal corresponding to
Am26LS31
Time
N.O. contact:
0.1 ms max.
N.C. contact:
1 ms max.
N.O. contact:
0.1 ms max.
N.C. contact:
1 ms max.
Output Specifications
ItemSpecification
CJ1W-NC1@3/2@3CJ1W-NC4@3
Open collector output
Line driver outputCorresponds to Am26LS31.
External power supply24 V DC ±10%
Maximum
switching
capacity
Minimum
switching
capacity
Leakage current 0.1 mA max.
Residual voltage
30 mA at 4.75 to 26.4 V
DC (NPN open collector)
(16 mA: Terminals with
1.6-kΩ limit resistance)
7 mA at 4.75 to 26.4 V
DC (NPN open collector)
0.6 V max. (pulse output)
1.0 V max. (error counter reset output)
Maximum output current: 20 mA
NC213: 50 mA max.
NC113: 30 mA max.
NC233: 20 mA max.
NC133: 10 mA max.
5 V DC±5%
NC233: 120 mA max.
NC133: 60 mA max.
30 mA at 4.75 to 25.2 V
DC (NPN open collector)
(16 mA: Terminals with
1.6-kΩ limit resistance)
7 mA at 4.75 to 25.2 V
DC (NPN open collector)
24 V DC ±5%
NC413: 100 mA max.
NC433: 30 mA max.
5 V DC±5%
NC433: 230 mA max.
The minimum CW/CCW pulse widths are shown below.
The OFF and ON refer to the output transistor.
The output transistor is ON at level “L.”
B
OFF
90%
10%
ON
A
Pulse
frequency
50 Kpps9.7 µs min. 9.7 µs min. 9.8 µs min. 9.8 µs min. 9.7 µs min. 9.7 µs min. 9.7 µs min. 9.7 µs min.
100 Kpps4.7 µs min. 4.7 µs min. 4.8 µs min. 4.8 µs min. 4.7 µs min. 4.7 µs min. 4.8 µs min. 4.8 µs min.
200 Kpps2.3 µs min. 2.3 µs min. 2.3 µs min. 2.3 µs min. 2.2 µs min. 2.2 µs min. 2.3 µs min. 2.3 µs min.
500 Kpps0.76 µs
7 mA/5 V DC±5%30 mA/5 V DC±5%7 mA/24 V DC±10%
ABABABAB
min.
0.82 µs
min.
Open or close current / Loaded power-source voltage
(1.6-kΩ resistance)
0.77 µs
min.
0.88 µs
min.
0.74 µs
min.
0.72 µs
min.
16 mA/24 V DC±10%
(1.6-kΩ resistance)
0.76 µs
min.
0.85 µs
min.
Note1. The load in the above table is the net resistance load, and the connecting
cable impedance with the load is not considered.
2. Due to distortions in pulse waveforms as a result of connecting cable impedance, pulse widths during actual usage may be smaller than those
shown in the above table.
3-5Wiring
This section provides motor driver connection examples. When actually connecting a motor driver, be sure to first check the specifications of the motor
driver to be used.
The maximum length of the wiring between the PCU and the motor driver is
2 m for open collector output models and 5 m for line driver output models.
3-5-1Output Connection Examples
Pulses are not output when the output transistor in the pulse output section is
OFF. (For direction output, OFF indicates CCW.)
37
WiringSection 3-5
Do not use a 24-V DC/5-V DC power supply for pulse output in common with
the power supply for other I/O.
ON
Output transistor
CW/CCW Pulse Outputs
CW
CCW
Pulse and Direction Outputs
Pulses
OFF
During pulse output
CWCCW
CWCCW
Outputting CW and CCW
Pulses, Example 1
Position Control Unit
(open collector outputs on the
CJ1W-NC113/213/413)
24-VDC
input
CW pulse
output
CCW pulse
output
1.6 kΩ
1.6 kΩ
Direction
Output ON
Output OFF
In this example, a 5-V DC photocoupler input motor driver is used for outputting CW and CCW pulses.
24-VDC
power
supply
+–
A1/B1
A6/B6
Approx.
12 mA
A8/B8
Approx.
12 mA
Motor driver (for 5-VDC input)
(For example R=220 Ω)
+
–
+
–
38
A2/B2
NoteIn this example, the 1.6 k
power supply to be used with a motor driver rated at 5 V DC.
Ω resistors of the PCU are used to allow a 24-V DC
WiringSection 3-5
When wiring your system, carefully note the current required by the motor
driver in order to avoid damaging the input circuitry of the motor driver.
Outputting CW and CCW
Pulses, Example 2
Position Control Unit
(open collector outputs on the
CJ1W-NC113/213/413)
24-VDC
input
CW pulse
output
CCW pulse
output
1.6 kΩ
1.6 kΩ
In this example, a 5-V DC photocoupler input motor driver is used for outputting CW and CCW pulses.
24-VDC
power
supply
+–
A1/B1
A5/B5
A7/B7
A2/B2
5-VDC
power
supply
+–
Motor driver (for 5-VDC input)
+
–
+
–
Position Control Unit
(line driver outputs on the
CJ1W-NC133/NC233/NC433)
5-VDC input
CW pulse or
pulse
(CW+CCW)
output
CCW pulse or
direction output
5-VDC
power
supply
Motor driver (for 5-VDC input)
39
WiringSection 3-5
Outputting Pulse and
Direction Signals
Position Control Unit
(open collector outputs on the
CJ1W-NC113/213/413)
24-VDC
input
Pulse
(CW+CCW)
output
Direction
output
1.6 kΩ
1.6 k
In this example, a 5-V DC input motor driver is used for outputting pulse and
direction signals.
24-VDC
power
supply
Motor driver (for 5-VDC input)
Direction input
Pulse input
Ω
A1/B1
A5/B5
A7/B7
A2/B2
+
7 to 30 mA
7 to 30 mA
–
When voltage-level output is used, the level is L for output ON, and H for output OFF.
40
WiringSection 3-5
Outputting CW and CCW
Pulses or Pulse and
Direction Signals
Position Control Unit
(line driver outputs on the
CJ1W-NC133/NC233/NC433)
5-VDC input
CW pulse or
pulse
(CW+CCW)
output
CCW pulse or
direction output
In this example, a motor driver with a line receiver input is used and either CW
and CCW pulses or pulse and direction signals are output.
5-VDC
power
supply
SG
Motor driver
(line receiver input
specifications)
(See note.)
Note: When connecting a line receiver,
connect the signal ground (SG) of
the motor driver's line receiver input
to the ground (GND) of the 5-VDC
power supply.
!Caution Be sure to wire the 5-V DC pulse output power supply with the correct polarity.
Wiring with the polarity reversed will result in damage to internal elements.
41
WiringSection 3-5
Error Counter Reset
Output
There is approximately 20 ms of output when origin search is completed in
modes 1 or 2.
Position Control Unit
24-VDC
24-VDC
power
supply for
output
Position Control Unit
24-VDC
power
supply for
output
1.6 kΩ
A1/B1
A9/B9
A2/B2
A1/B1
A10/B10
A2/B2
+
power
supply
–
5-VDC
power
supply
24-VDC
power
supply
+–
OMRON R88D-WT
Servo Drive
+–
+ECRST
15
14
–ECRST
OMRON R88D-WT
Servo Drive
+ECRST
15
14
–ECRST
Position Control Unit
24-VDC
power
supply for
output
1.6 kΩ
Position Control Unit
24-VDC
power
supply for
output
1.6 kΩ
A1/B1
A9/B9
A2/B2
A1/B1
A9/B9
A2/B2
24-VDC
power
supply
+–
24-VDC
power
supply
+–
OMRON R88D-GT
Servo Drive
+24VIN
7
30
ECRST
OMRON R7D-BP
Servo Drive
+24VIN
1
4
ECRST
42
WiringSection 3-5
3-5-2Connecting Input Signals
!Caution If the switching capacity is too low it may cause damage to the switch. Con-
nect a switch with a switching capacity of at least 5 mA for each input.
With N.C. inputs, be sure to connect a power supply for unused terminals and
turn them on.
This section shows examples of connecting interrupt, emergency stop, and
CW/CCW limit input signals.
The input section has both N.O. and N.C. inputs. Either can be used depending on the axis parameter settings. For details regarding axis parameters,
refer to 4-4 Axis Parameter Area.
Depending on the setting of the origin search operation pattern, the point at
which the origin proximity signal or the CW/CCW limit signal changes from
ON to OFF is used as the timing for origin signal detection. In this case, use a
sensor with no chattering, such as a photoelectric sensor, for the input. Using
a switch with contacts may cause the position of the origin to be displaced due
to chattering. For details on setting operation patterns for origin searches,
refer to page 153.
43
WiringSection 3-5
NameConnection type
External interrupt input signalN.O.
Emergency stop input signalN.C.
Origin proximity input signalN.C. or N.O.
CW limit input signalN.C. or N.O.
CCW limit input signalN.C. or N.O.
24-VDC
Position Control Unit
A20/B20
power
supply
External
interrupt
input signal
Emergency
stop input
signal
Origin
proximity
input signal
CW limit
input signal
CCW limit
input signal
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
560 Ω
(680 Ω)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
4.7 kΩ (5.6 kΩ)
A15/B15
A16/B16
A17/B17
A18/B18
A19/B19
Switch (N.O. contact)
Switch (N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
NoteThe values in parentheses apply for the CJ1W-NC413 and CJ1W-NC433.
3-5-3Connecting Origin and Positioning Completed Input Signals
The examples below show input connections when open collector sensor output and the encoder’s Z-phase line driver output are used.
Use a sensor with no chattering, such as a photoelectric sensor, for the origin
input signal.
!Caution Connect a switch with a switching capacity of at least 5 mA to the 24-V origin
input signal terminal.
44
WiringSection 3-5
!Caution Do not connect the 5-V DC origin input signal input to any output circuit except
the line driver.
!Caution Use either the 24-V origin input signal or the 5-V origin input signal, but not
both. Also, be sure not to connect them to the wrong terminal. Using both signals or connecting them to the wrong terminal will result in damage to internal
circuitry.
NoteThe values in parentheses apply for the CJ1W-NC413 and CJ1W-NC433.
Origin Input Signal (5 V) (Line Driver Input)
Position Control Unit
4.7 kΩ
(5.6 kΩ)
Ω
150
560 Ω
(680 Ω)
A14/B14
A12/B12
NoteThe values in parentheses apply for the CJ1W-NC413 and CJ1W-NC433.
Signal
0 V
OMRON R88D-GT
Servo Drive
23
+z
24
–z
Switch
circuitry
Positioning Completed
Input Signal
The positioning completed input signal is also used as an origin search completed signal in modes 2 and 3. Adjust the setting of the Servo Drive so that
this signal always turns off while the servomotor is operating, and on when the
motor is stopped.
45
WiringSection 3-5
An origin search operation cannot be completed unless the positioning completed input signal turns ON after positioning has been completed.
Position Control Unit
560 Ω
(680 Ω)
4.7 kΩ
(5.6 kΩ)
NoteThe values in parentheses apply for the CJ1W-NC413 and CJ1W-NC433.
3-5-4Wiring Precautions
Operational errors such as dislocation can occur in most electronic control
devices if they are subjected to electronic noise from nearby power lines or
loads. Recovery from such errors is usually very difficult and time consuming.
To avoid such noise-generated operational errors and improve system reliability, always observe the following precautions in wiring the system.
Be sure to use the sizes and materials indicated in the specifications when
connecting power lines and cables.
Power lines (e.g., AC power supply, motor power line) and control lines (e.g.,
pulse output lines, external I/O signal lines) must be wired separately. Never
put these lines into the same duct or make them into a single bundle.
• Attach a multi-layer ceramic capacitor of a thickness of less than 1
the pulse output power supply to improve noise resistance.
• Do not use a 24-V DC or 5-V DC power supply for pulse output in common with the power supply for other I/O.
• Use shielded cable for control lines.
• Connect the shielded cable to the frame ground at both the PCU and the
driver.
A11/B11
24-VDC
power supply
+
–
INPCOM
OMRON R88D-GT
Servo Drive
39
INP
38
µF to
46
Connection Examples for Different Types of Motor DriverSection 3-6
• Attach a surge absorber to all inductive loads, such as relays, solenoids,
and solenoid valves.
DC relays AC relays
+
DC
–
Solenoids, etc.
SolenoidSurge absorber
Diode for surge
absorption
ACSurge
RYRY
absorber
NoteConnect the diode and surge absorber as close as possible to the relay. Use a
diode capable of withstanding a voltage five times higher than the circuit voltage.
• Insert a noise filter into the power supply inlet if noise enters the power
line (e.g., when it is connected to the same power supply as an electric
welder or an electric spark machine or when there is any supply generating high frequency noise).
• Connect to a ground of 100
greater than 1.25 mm
2
Ω or less and use the thickest possible wire,
.
• Twisted-pair cable is recommended for power lines.
3-6Connection Examples for Different Types of Motor Driver
This section provides examples of wiring the X and Y axes. If the Y and U
axes are also to be used, check the connector pin numbers in 3-4 External I/OCircuitry and wire them in the same way.
Note1. Be sure to connect a power supply for unused N.C. input terminals and turn
them on.
2. Use shielded wire for connecting to stepping motor drivers and Servo
Drives. Connect the shielded cable to an FG at both the PCU and the driver.
47
Connection Examples for Different Types of Motor DriverSection 3-6
Example 1: Mode 0 Connection
This example shows the use of a stepping motor with an external sensor signal connected to the origin input signal.
Position Control Unit
(open collector outputs
on the CJ1W-NC@13)
CW output
(with 1.6-kΩ
resistance)
CCW output
(with 1.6-kΩ
resistance)
24-V power supply
for output
24-V GND
for output
Origin proximity input signal
Origin Input
signal
Input common
CCW limit
input signal
CW limit input
signal
Emergency
stop input
signal
A6
A8
A1
A2
A17
A13
A12
A20
A19
A18
A16
FG
+
24 VDC
24 VDC
+
Shield
N.O. contact
0 V
24 V
Signal
N.C. contact
Example:
DFU1514W stepping motor driver, made by Oriental Motor Co.
Connection Examples for Different Types of Motor DriverSection 3-6
WordBitsSettingContents
m+500 to 030Mode 0
04 to 070Reverse mode 1
08 to 111Takes origin input signal after origin
12 to 150Search direction: CW
Note“m” is the beginning DM word allocated when the unit number is set.
Origin Search Operation
The origin search operation is completed with the rising edge of the origin
input signal after the rising edge of the origin proximity input signal.
ORIGIN
SEARCH
Origin proximity
input signal
Origin input
signal
proximity input signal is received.
Pulse output
Busy Flag
Time
49
Connection Examples for Different Types of Motor DriverSection 3-6
Example 2: Mode 1 Connection
In this example, a Servo Drive is employed and the Z-phase of the encoder is
connected to the origin line driver input terminal and used as the origin input
signal. An OMRON G-Series Servo Drive is used.
Open Collector Output (CJ1W-NC113/NC213/NC413)
Position Control Unit
(open collector outputs
on the CJ1W-NC@13)
CW output
(with 1.6-kΩ
resistance)
CCW output
(with 1.6-kΩ
resistance)
Shield
A6
A8
OMRON R88D-GT@@@
Servo Drive
R88M-G@
+CW
3
−CW
4
+CCW
5
−CCW
6
Servomotor
24-V power supply
for output
24-V GND for
output
Error counter reset
output
Origin input
signal
Input common
Origin proximity
input signal
A1
A2
A9
A14
A12
A20
A17
+
24 VDC
FG
24 VDC
+
N.O. contact
N.O. contact
7
29
30
23
24
Shell
+24VIN
RUN
ECRST
+Z
−Z
FG
50
CCW limit
input signal
CW limit input
signal
Emergency stop
input signal
A19
A18
A16
N.C. contact
N.C. contact
N.C. contact
Connection Examples for Different Types of Motor DriverSection 3-6
Parameter Setting Example
This example is explained in terms of the X axis. For more details, refer to 4-4
Axis Parameter Area.
150
0 0 E 0
m+4
0 0 0 1
m+5
WordBitsSettingContents
m+4000CW/CCW output
01 to 030---
040Limit input: N.C. contact
051Origin proximity: N.O. contact
061Origin input signal: N.O. contact
071Pulse output stopped by emergency
08 to 150---
m+500 to 031Mode 1
04 to 070Reverse mode 1
08 to 110Takes origin input signal after rising
12 to 150Motor direction: CW
stop input signal; error counter reset
signal output.
and falling edge of origin proximity
signal.
Note“m” is the beginning DM word allocated when the unit number is set.
Origin Search Operation
The origin search operation stops on the rising edge of the first Z-phase signal after the origin proximity signal has turned from ON to OFF, and after
deceleration has ended.
ORIGIN SEARCH
Origin proximity
signal
Z-phase signal
Pulse output
Error counter
reset output
Approx. 20 ms
Busy Flag
Time
51
Connection Examples for Different Types of Motor DriverSection 3-6
Line Driver Output (CJ1W-NC133/NC233/NC433)
Position Control Unit
(line driver outputs on the CJ1W-NC@33)
5-V GND
for pulse
output
5-V power
supply for
pulse
output
CW (+)
output
CW (–)
output
CCW (+)
output
CCW (–)
output
24-V
power
supply for
output
24-V GND
for output
Error
counter
reset
output
Origin
input
signal
A3
A4
A5
A6
A7
A8
A1
A2
A9
A14
A12
5 VDC
+
24 VDC
Example:
OMRON R88D-GT@@@
Shield
+
Servo Drive
3
+CW
4
−CW
5
+CCW
6
−CCW
+24VIN
7
N.O. contact
RUN
29
ECRST
30
+Z
23
−Z
24
FG
Shell
FG
52
Connection Examples for Different Types of Motor DriverSection 3-6
Example 3: Mode 2 Connection
In this example, as in example 2, a Servo Drive is employed and the Z-phase
of the encoder is connected to the origin line driver input terminal and used as
the origin input signal.
In contrast to mode 1, the positioning completed signal (INP) of the Servo
Drive serves as both the origin search completed and the positioning completed signals.
Set the Servo Drive so that the positioning completed signal turns OFF during
motor operation and ON while the motor is stopped.
An origin search operation cannot be completed if the positioning completed
input signal from the Servo Drive is not properly connected or set.
W-series Servo Drive (CJ1W-NC113/NC213/NC413)
Position Control Unit
(open collector outputs
on the CJ1W-NC@13)
CW output
(with 1.6-kΩ
resistance)
CCW output
(with 1.6-kΩ
resistance)
24-V power
supply for
output
24-V GND
for output
A6
A8
A1
A2
24
VDC
Shield
N.O. contact
OMRON R88D-WT@@@@
Servo Drive
R88M-W
Servomotor
11
12
47
40
7
8
+CW
–CW
+CCW
–CCW
+24
VIN
RUN
Error counter
reset output
Origin input
signal
Positioning
completed
input signal
Input
common
Origin
proximity
input signal
CCW limit
input signal
CW limit
input signal
Emergency
stop input
signal
A10
A14
A12
A11
A20
A17
A19
A18
A16
FG
24 VDC
+
N.O. contact
N.C. contact
N.C. contact
N.C. contact
15
14
19
20
25
26
Shell
+ECRST
–ECRST
+Z
–Z
+INP
–INP
FG
53
Connection Examples for Different Types of Motor DriverSection 3-6
G-series Servo Drive (CJ1W-NC113/NC213/NC413)
Position Control Unit
(open collector outputs
on the CJ1W-NC@13)
CW output
(with 1.6-kΩ
A6
resistance)
CCW output
(with 1.6-kΩ
A8
resistance)
Shield
OMRON R88D-GT@@@
Servo Drive
R88M-G@
3
+CW
4
−CW
5
+CCW
6
−CCW
Servomotor
24-V power
supply for
output
24-V GND
for output
Error counter
reset output
Origin input
signal
Positioning
completed
input signal
Input
common
Origin
proximity
input signal
A1
A2
A9
A14
A12
A11
A20
A17
+
24 VDC
FG
24 VDC
+
N.O. contact
N.O. contact
+24VIN
7
RUN
29
30
ECRST
23
+Z
24
−Z
INP
3839INPCOM
FG
Shell
54
CCW limit
input signal
CW limit
input signal
Emergency
stop input
signal
A19
A18
A16
N.C. contact
N.C. contact
N.C. contact
Connection Examples for Different Types of Motor DriverSection 3-6
Connection to Line Driver (CJ1W-NC133/NC233/NC433)
Position Control Unit
(line driver outputs on the CJ1W-NC@33)
5-V GND
for pulse
output
5-V power
supply for
pulse
output
CW (+)
output
CW (–)
output
CCW (+)
output
CCW (–)
output
24-V
power
supply for
output
24-V GND
for output
Error
counter
reset
output
Origin
input
signal
A3
A4
A5
A6
A7
A8
A1
A2
A9
A14
A12
5 VDC
24 VDC
Example:
+
Shield
OMRON R88D-GT@@@
Servo Drive
R88M-G@
3
+CW
4
−CW
5
+CCW
6
−CCW
+24VIN
+
7
Servomotor
N.O. contact
RUN
29
30
ECRST
+Z
23
24
−Z
Positioning
completed
input signal
A11
FG
INP
3839INPCOM
FG
Shell
55
Connection Examples for Different Types of Motor DriverSection 3-6
Connection Examples for Different Types of Motor DriverSection 3-6
Connection to Line Driver (CJ1W-NC133/NC233/NC433)
Position Control Unit
(line driver outputs on the CJ1W-NC@33)
5-V GND
for pulse
output
5-V power
supply for
pulse
output
CW (+)
output
CW (–)
output
CCW (+)
output
CCW (–)
output
24-V
power
supply for
output
24-V GND
for output
Error
counter
reset
output
Origin input
signal
A3
A4
A5
A6
A7
A8
A1
A2
A9
A14
A12
+
5 VDC
+
24 VDC
Shield
N.O. contact
Example:
OMRON R7D-BP@@@
Servo Drive
R88M-G@
22
+CW
23
−CW
24
+CCW
25
−CCW
+24VIN
1
RUN
2
4
ECRST
+Z
19
20
−Z
Servomotor
Positioning
completed
input signal
A11
FG
INP
13100GND
FG
Shell
57
Connection Examples for Different Types of Motor DriverSection 3-6
Parameter Setting Example
This example is explained in terms of the X axis. For more details, refer to 4-4
Axis Parameter Area.
150
0 0 E 0
m+4
0 0 0 2
m+5
WordBitsSettingContents
m+4000CW/CCW output
01 to 030---
040Limit input: N.C. contact
051Origin proximity: N.O. contact
061Origin input signal: N.O. contact
071Pulse output stopped by emergency
08 to 150---
m+500 to 032Mode 2
04 to 070Reverse mode 1
08 to 110Takes origin input signal after rising
12 to 150Search direction: CW
stop input signal; error counter reset
signal output.
and falling edge of origin proximity
input signal.
Note“m” is the beginning DM word allocated when the unit number is set.
Origin Search Operation
The origin search operation stops on the rising edge of the first Z-phase signal after the origin proximity signal has turned from ON to OFF, and after
deceleration has ended. The Busy Flag turns OFF with the positioning completed input signal.
ORIGIN
SEARCH
Origin proximity
signal
Z phase signal
Pulse output
Error counter
reset output
Approx. 20 ms
Busy Flag
Positioning completed
input signal
Time
58
Connection Examples for Different Types of Motor DriverSection 3-6
Connection Examples for Different Types of Motor DriverSection 3-6
Connection to Line Driver (CJ1W-NC133/NC233/NC433)
Position Control Unit
(line driver outputs on the CJ1W-NC@33)
5-V GND
for pulse
output
5-V power
supply for
pulse
output
CW (+)
output
CW (–)
output
CCW (+)
output
CCW (–)
output
24-V
power
supply for
output
24-V GND
for output
Error
counter
reset
output
24-V origin
input
signal
A3
A4
A5
A6
A7
A8
A1
A2
A10
A13
A12
+
5 VDC
+
24 VDC
Shield
N.O.
contact
Example:
OMRON R7D-AP@@@
Servo Drive
R7M-A@
1
2
3
4
13
14
5
6
32
33
+CW
−CW
+CCW
−CCW
+24VIN
RUN
+ECRST
−ECRST
Z
ZCOM
Servomotor
Positioning
completed
input
signal
A11
FG
8
10
Shell
INP
0GND
FG
60
Connection of Unused AxesSection 3-7
3-7Connection of Unused Axes
This section provides connection examples for the CJ1W-NC213 and CJ1WNC233 in applications where not all axes are used.
3-7-1Using Only the X Axis and Not the Y Axis on the CJ1W-NC213/
NC233 (with Unit Version 2.3 or Later)
On PCUs with unit version 2.3 or later, wiring is not required for the CW/CCW
limit input signal and the emergency stop input signal for specified unused
axes.
The following figure, based on Example 2: Mode 1 Connection in 3-6 Connec-tion Examples for Different Types of Motor Driver, shows an example of connecting external I/O when only the X axis and not the Y axis is used on the
CJ1W-NC213/NC233. The limit input signal for the X axis is assumed to be
set as an N.C. connection.
Position Control Unit
Input
common
Origin
proximity
input
signal
CCW limit
input signal
CW limit
input signal
Emergency
stop input
signal
A20
X axis (used)
A17
Y axis
B17
(not used; no wiring required)
X axis (used)
A19
Y axis
B19
(not used; no wiring required)
X axis (used)
A18
Y axis
B18
(not used; no wiring required)
X axis (used)
A16
Y axis
B16
(not used; no wiring required)
24 VDC
N.O. contact
N.C. contact
N.C. contact
N.C. contact
To set only the X axis as the axis to be used, set the number of unused axes
to 01 in Axis Parameter Designation of 4-4 Common Parameter Area.
The following table shows the relation for each Unit between the number of
unused axes and the settings.
Setting1-axis Unit2-axis Unit4-axis Unit
0All axes used.All axes used.All axes used.
1Error 0013 occurs. Axis Y not used.Axis U not used.
2Error 0013 occurs.Error 0013 occurs.Axes Z and U not used.
3Error 0013 occurs.Error 0013 occurs.Axes Y, Z, and U not used.
Making this setting eliminates the need to perform wiring for the Y axis.
If other parameters are used in their default settings, the CW/CCW limit input
signal will be set to a N.C. contact input. Therefore, current will flow for the signal when the power supply for the inputs is connected.
61
Connection of Unused AxesSection 3-7
3-7-2Using Only the X Axis and Not the Y Axis on the CJ1W-NC213/
NC233 (Unit Versions Earlier Than 2.3)
On PCUs with a unit version earlier than 2.3, specified unused axes require
wiring only for the emergency stop input signal.
Based on Example 2: Mode 1 Connection on page 50, the following example
shows the connections for the CJ1W-NC213/NC233 when only the X axis
(and not the Y axis) is used. In this example, the limit input signals for both
axes are set to N.C. contacts. With the CJ1W-NC413/NC433, if the Z axis is
used and the U axis is not used, the connection will be the same with X and Y
replaced by Z and U respectively.
Position Control Unit
Input
common
Origin
proximity
input
signal
CCW limit
input signal
CW limit
input signal
Emergency
stop input
signal
A20
X axis (used)
A17
Y axis
(not used; no wiring required)
B17
X axis (used)
A19
Y axis (not used)
B19
X axis (used)
A18
Y axis (not used)
B18
X axis (used)
A16
Y axis (not used)
B16
24 VDC
N.O. contact
N.C. contact
N.C. contact
N.C. contact
When there is an unused axis, connect the emergency stop input signal (N.C.
contact) and the CW/CCW limit input signals (N.C./N.O. switchable) for that
axis so that they are ON. If the parameters are at their default settings, the
CW/CCW limit input signals are N.C. contact inputs and so connect an input
power supply and keep power ON.
If the emergency stop input signal and the CW/CCW limit input signals for an
unused axis are not ON, a sensor input error (error codes 6000, 6100, or
6101) will be generated for the axis, and the ERC indicator as well as the LED
indicator for the axis will light or flash. The used axis, however, will continue to
operate normally even if an error is generated for the unused axis.
62
NoteIf the CW/CCW limit input signals for the unused axis are set to N.O contacts
using the parameter settings, it is not necessary to wire the CW/CCW limit
inputs. For details, refer to 4-4 Axis Parameter Area.
Servo Relay UnitSection 3-8
3-8Servo Relay Unit
• Wiring requirements can be reduced by connecting Servo Drives and
PCUs via a Servo Relay Unit, which provide a connector and a terminal
block in one Unit.
• The connecting cable and the type of Servo Relay Unit required will
depend on the Servo Drive model connected. Refer to the tables under
Connection Compatibility given below.
• The cable length for PCU Connecting Cables is indicated in the “@@@”.
050: 0.5 m
100: 1 m
• The cable length for Servo Drive Connecting Cables is indicated in the
“@@@”.
100: 1 m
200: 2 m
• When using the CJ1W-NC413/433, 2 Servo Relay Units and 2 PCU Connecting Cables are required.
• When using in combination with the CJ1W-NC213/NC233 (2-axis control), 2 Servo Drive Connecting Cables are required.
• When using in combination with the CJ1W-NC413/NC433 (4-axis control), 4 Servo Drive Connecting Cables are required.
• To enable RS-422 communications with the R7D-AP@@@, an XW2Z@@@J-C1 Connecting Cable is required for RS-422 connection to Serial
Communications Boards or Units.
Servo Relay UnitCable connected to
Servo Relay Unit
XW2Z-@@@J-B4R88D-UT@@@
XW2Z-@@@J-B25R88D-GT@@@
XW2Z-@@@J-B29R7D-BP@@@
XW2Z-@@@J-B17R7D-ZP@@@
XW2Z-@@@J-B4R88D-UT@@@
XW2Z-@@@J-B25R88D-GT@@@
XW2Z-@@@J-B29R7D-BP@@@
XW2Z-@@@J-B17R7D-ZP@@@
Servo Drive
R88D-WT@@@@
R88D-WT@@@@
(when using RS-422)
64
SECTION 4
Data Areas
This section provides an overview of the parameter and data settings used in Position Control Unit operation and provides
information on memory allocation.
4-9-3Setting for Continuous Operation in the Same Direction for One Axis109
65
Overall StructureSection 4-1
4-1Overall Structure
The PCU is used by exchanging data with the CPU Unit as shown below.
CPU Unit
CIO Area
PCU
Special I/O Unit Area
Operating memory area
(output)
(input)
DM or EM Area
User-specified DM or EM words
(specified in common parameters)
Operating data area
(output)
(input)
DM Area words allocated
to Special I/O Units
Common parameter area
Axis parameter area
User-specified DM or EM words
(for data transfer)
Data transfer area
CX-Position
I/O refresh
Power up
or restart
(See note 1.)
Data transfer
Operating commands
Status (flags)
Operating data
Status data
Common parameters
Axis parameters
Memory operation data
Positioning
sequences
Speeds
Positions
Acceleration times
Deceleration times
Dwell times
Zones
Save data
Commands
Settings
Operating data
Result
Flash memory
Command
execution
66
PCU's internal memory
NoteThe user can select by means of a common parameters setting whether the
axis parameters set in the CPU Unit’s DM Area are to be transferred to the
PCU for use, or whether the axis parameters saved in the PCU’s flash memory are to be used.
Overall StructureSection 4-1
The data handled by the PCU can be classified in the way shown below.
Data nameContentsSetting areaEnable timing
Common parameter area
(Refer to 4-3 Common Parameter Area.)
Axis parameter area
(Refer to 4-4 Axis Param-eter Area.)
Operating memory area
(Refer to 4-5 Operating Memory Area.)
Operating data area
(Refer to 4-6 Operating Data Area.)
Memory operation data
(Refer to 4-7 Memory Operation Data.)
Zone data
(Refer to 4-8 Zone Data Area.)
This area contains the parameters for
settings related to basic PCU operation,
such as allocation of the operating memory area.
The common parameters must be set
when using the PCU.
This area contains the parameters for
settings related to axis operation, such
as pulse output type, logic for input signals, operation modes, and maximum
speed values.
Outputs for controlling PCU operation,
such as for direct operation, memory
operation, jogging, and origin search, are
allocated to this area. Information (see
note) relating to the status of the PCU,
such as busy flags, error flags, and external input are input to this area.
This area is for settings such as positions, speeds, and acceleration/deceleration times for direct operation, origin
searches and jogging, as well as positioning sequence numbers for memory
operation. It also contains PCU status
data (see note), such as present positions and the number of the currently
executed positioning sequence.
This area is for settings related to memory operation, such as operation
sequences, positions, speeds, and acceleration/deceleration times. The memory
operation area contains the following six
types of data:
• Positioning sequences
• Speeds
• Positions
• Acceleration times
• Deceleration times
• Dwell times
This data determines zones for the
present positions of axes controlled by
the PCU.
DM Area words in the
CPU Unit allocated to
Special I/O Units
DM Area words in the
CPU Unit allocated to
Special I/O Units
PCU’s flash memory
(See note on previous
page.)
CPU Unit’s Special I/O
Unit Area
CPU Unit’s DM or EM
area (determined by
common parameter setting)
PCU’s internal memory
(can be saved to PCU’s
flash memory)
PCU’s internal memory
(can be saved to PCU’s
flash memory)
The settings are transferred from the CPU Unit
to the PCU at power up
or restart and enabled.
These settings are transferred from the CPU
Unit’s DM Area or the
PCU’s flash memory to
the PCU’s internal memory at power up or
restart and enabled.
Operating commands
are sent from the CPU
Unit to the PCU and status data is sent from the
PCU to the CPU Unit
with every I/O refresh.
Data is updated with
every I/O refresh. The
set data is enabled and
used with the startup of
each operation.
Data is read from the
PCU’s flash memory to
the internal memory at
power up or restart. Settings are updated when
data is transferred. The
set data is enabled and
used with the startup of
each memory operation.
Data is read from the
PCU’s flash memory to
the internal memory at
power up or restart. Settings are updated when
data is transferred.
Note Error codes are input to the operating memory area.
Using these settings, the PCU executes operation (1) using the data/parameter areas specified in the common parameters and axis parameters (2)
according to the operating commands received from the operating memory
area and (3) based on operating data, memory operation data, and zone data.
The common parameters and axis parameters are basic settings for the PCU
and the axes to be controlled. It is necessary to make these settings when
using the PCU. Make settings for operating data, memory operation data, and
zone data according to the kind of operation required.
67
Data AreasSection 4-2
4-2Data Areas
The following tables give the addresses (bit/word addresses in the CPU Unit
and addresses in the PCU’s internal memory) for the parameters and data
handled by the PCU. For more details, refer to the relevant sections.
NoteDo not write to unused bits or words in the parameter and other data areas.
Doing so may result in malfunctions.
Common Parameter Area (refer to page 71)
Beginning word of common parameter area, m = D20000 + 100 × unit number.
Word (same for all models)NameData size
mOperating data area designation1 word
m+1Beginning word of operating data area1 word
m+2Axis parameter designation1 word
m+3Not used1 word
Axis Parameter Area (refer to page 75)
Word (address in PCU)NameData size
X axisY axisZ axisU axis
m+4 (0004)m+32 (0020)m+60 (003C)m+88 (0058)I/O settings1 word
m+5 (0005)m+33 (0021)m+61 (003D)m+89 (0059)Operation mode selection1 word
m+6 (0006)m+34 (0022)m+62 (003E)m+90 (005A)Maximum speed2 words
m+8 (0008)m+36 (0024)m+64 (0040)m+92 (005C)Initial speed2 words
m+10 (000A)m+38 (0026)m+66 (0042)m+94 (005E)Origin search high speed2 words
m+12 (000C)m+40 (0028)m+68 (0044)m+96 (0060)Origin search proximity speed2 words
m+14 (000E)m+42 (002A)m+70 (0046)m+98 (0062)Origin compensation2 words
m+16 (0010)m+44 (002C)m+72 (0048)m+100 (0064) Backlash compensation1 word
m+17 (0011)m+45 (002D)m+73 (0049)m+101 (0065) Backlash compensation speed2 words
Beginning word of operating data area, I = word specified in common parameters (m, m+1).
WordsNameData size
1 axis2 axes4 axes
X axisX axisY axisX axisY axisZ axisU axis
IIINumber of write
words
I+1I+1I+1Write source area1 word
I+2I+2I+2Write source word 1 word
I+3I+3I+3Write destination
address
I+4I+4I+4Number of read
words
I+5I+5I+5Read source
address
I+6I+6I+6Read destination
area
I+7I+7I+7Read destination
word
I+8I+8I+20I+8I+20I+32I+44Position2 words
I+10I+10I+22I+10I+22I+34I+46Speed2 words
I+12I+12I+24I+12I+24I+36I+48Acceleration time2 words
I+14I+14I+26I+14I+26I+38I+50Deceleration time2 words
I+16I+16I+28I+16I+28I+40I+52Positioning
sequence
I+17I+17I+29I+17I+29I+41I+53Override1 word
I+18I+18I+30I+18I+30I+42I+54Teaching address1 word
I+19I+19I+31I+19I+31I+43I+55Not used1 word
I+20I+32I+36I+56I+60I+64I+68Present position2 words
I+22I+34I+38I+58I+62I+66I+70Positioning
sequence
I+23I+35I+39I+59I+63I+67I+71Output code1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
70
Common Parameter AreaSection 4-3
Memory Operation Data (refer to page 101)
PCU internal addressNameData size
X axisY axisZ axisU axis
1000200030004000Positioning sequence numbers 0 to 993 words
112C212C312C412CSpeed numbers 0 to 992 words
11F421F431F441F4Position numbers 0 to 992 words
12BE22BE32BE42BEAcceleration time numbers 1 to 92 words
12D222D232D242D2Deceleration time numbers 1 to 92 words
12E522E532E542E5Dwell time numbers 1 to 191 word
Zone Data Area (refer to page 104)
PCU internal addressNameData size
X axisY axisZ axisU axis
12F822F832F842F8Zone 0, CCW2 words
12FA22FA32FA42FAZone 0, CW2 words
12FC22FC32FC42FCZone 1, CCW2 words
12FE22FE32FE42FEZone 1, CW2 words
1300230033004300Zone 2, CCW2 words
1302230233024302Zone 2, CW2 words
4-3Common Parameter Area
The common parameter settings determine the areas used to set the operating data (the operating data area) and axis parameters (the axis parameter
area) required for axis control. The common parameters must be set before
using the PCU.
4-3-1Outline
Memory from the area allocated to Special I/O Units in the CPU Unit’s DM
Area is allocated to the common parameters. The beginning word of the allocated area is determined by the unit number set for the PCU according to the
following equation.
Beginning word of common parameter area, m = D20000 + 100
ber.
After the common parameter settings have been made, they will go into effect
the next time the PCU is powered up or restarted.
The settings for the common parameters are explained below.
Word
(same for all
models)
mOperating data
m+1Beginning word
NameConfiguration/ExplanationPage
area designation
of operating
data area
Designate the memory area to which the operating data is to be set. Select
one from the following.
0000: DM Area words allocated to Special I/O Units (fixed)
000D: User-specified DM Area words
0X0E: User-specified EM Area words (X: bank number)
Designate the beginning word of the operating data area. If 000D (userspecified DM Area words) or 0X0E (user-specified EM Area words) is set for
the operating data area designation, specify the beginning word of the area
to be allocated as the operating data area in hexadecimal.
× unit num-
72
71
Common Parameter AreaSection 4-3
Word
(same for all
models)
m+2Axis parameter
m+3Not usedThis area is not used. Leave set to 0000.74
NameConfiguration/ExplanationPage
Designate the location of the data to be used as axis parameters. Select
designation
one from the following.
• Axis parameter data saved in the PCU’s flash memory.
• Axis parameter data set in the CPU Unit’s DM Area.
• PCU’s default setting.
• Settings for unused axes (supported on PCUs with unit version 2.3 or
later).
4-3-2Details
The details of the common parameters settings are given below.
Designation and Beginning Word of Operating Data Area
Word Address and Enable
Timing
The word addresses and enable timing for the beginning word of operating
data area and operating data area designation settings are shown below.
WordNameEnable timing
NC1@3NC2@3NC4@3
mOperating data area designationAt power up or
m+1Beginning word of operating data
area
restart
72
Bit ConfigurationThe bit configurations for the word addresses in the above table are shown
below.
150008 07
m
m+1
Bank designationArea designation
Beginning word of operating data area (Hex)
SettingsThe following settings are available.
Word m:0000, 000D, 0X0E (X = 0 to 9, A, B, or C)
Word m+1: 0000 to 7FXX Hex (settings possible for “XX” will depend on
the model)
ExplanationThe meanings of each of the settings are given below.
Area Designation (Word m, Bits 00 to 07)
Designate the area in CPU Unit memory to be used for setting operating data.
The following settings are available.
00: DM Area Words Allocated to Special I/O Units
Memory from the area allocated to Special I/O Units in the CPU Unit’s DM
Area will be allocated according to the unit number set for the PCU. The following words will be allocated consecutively to common parameters and axis
parameters.
NC1@3: m+32 to m+55
NC2@3: m+60 to m+99
NC4@3: m+116 to m+187
0D: User-specified DM Area Words
Words within the DM Area starting from the beginning word specified in word
m+1 will be allocated.
0E: User-specified EM Area Words
Words within the EM Area starting from the beginning word specified in word
72
Common Parameter AreaSection 4-3
m+1 will be allocated. Specify the bank number in the bank designation setting (word m, bits 08 to 15).
Bank Designation (Word m, Bits 08 to 15)
If user-specified EM Area words (0E) are designated as the location for the
operating data area using the area designation setting (word m, bits 00 to 07),
use this setting to designate a bank number. The following bank numbers can
be designated: 0 (00) to 9 (09), A (0A), B (0B), C (0C). Do not, however, select
a bank that is being used as PLC file memory. If the DM Area words allocated
to Special I/O Units (00) or user-specified DM Area words (0D) are designated as the location of the operating memory area, set the bank designation
to 0 (00). Any other setting will result in an operating data area specification
error (error code 0010).
NoteDo not set a bank number for a bank that is being used as PLC file memory. If
a bank that is being used as PLC file memory is set, the operating data area
settings will not be reflected in PCU operation and this will result in malfunction. When there are several PCUs mounted to the same PLC, be sure to set
the operating data areas for the PCUs so that they do not overlap with each
other. The PCU will not detect an error if operating data areas overlap, and
this may result in malfunction.
For details on the EM Area banks and how to use them as PLC file memory,
refer to the SYSMAC CS/CJ Series Programmable Controllers ProgrammingManual (W394).
Beginning Word of Operating Data Area (Word m+1)
If user-specified DM Area words (0D) or user-specified EM Area words (0E)
are designated as the location for the operating data area using the area designation setting (word m, bits 00 to 07), use this setting to designate the
beginning word of the operating data area. The beginning word is set in hexadecimal. The following settings are possible (varies with the model):
NC1@3: 0000 to 7FE8 Hex (0 to 32744)
NC2@3: 0000 to 7FD8 Hex (0 to 32728)
NC4@3: 0000 to 7FB8 Hex (0 to 32696)
If DM Area words allocated to Special I/O Units (00) are designated as the
location for the operating data area, this setting will not be used.
Example 1
0m00D
1
m+1
F40
The area in the CPU Unit’s DM Area beginning with word 1F40 Hex (8000) is
designated as the operating data area. The following words are allocated (varies with the model):
NC1@3:D8000 to D8023
NC2@3:D8000 to D8039
NC4@3:D8000 to D8071
Example 2
0m20E
m+1
3
98
A
The area in bank 2 of the CPU Unit’s EM Area beginning with word 3A98 Hex
(15000) is designated as the operating data area. The following words are
allocated (varies with the model):