Omron CIMR-L7Z DATASHEET

Cat. No. I62E-EN-01
English

Made to drive Lifts Model: CIMR-L7Z 200V Class 3-phase 3.7 to 55 kW 400V Class 3-phase 4.0 to 55 kW

Deutsch
Español
FrançaisItaliano
Português
Pyccкий
L7Z Quick Start Guide
Table of Contents
Warnings........................................................................EN-1
Safety Precautions and Instructions ............................................................. EN-2
EMC Compatibility ........................................................................................EN-3
Installation .....................................................................EN-5
Mechanical Installation ................................................................................. EN-5
Electrical Connection ....................................................................................EN-6
Keypad Operation .......................................................EN-11
Digital Operator Display (optional) ............................................................. EN-11
Power Up and Basic Parameter Setup......................EN-12
Start Up Procedure ..................................................................................... EN-12
Before Power Up ........................................................................................EN-13
Display after Power Up ...............................................................................EN-13
Control Mode Selection .............................................................................. EN-13
Autotuning...................................................................EN-14
Autotuning Mode Selection ........................................................................ EN-14
Autotuning Alarms and Faults ....................................................................EN-15
Autotuning Procedure with Induction Motors ............................................. EN-16
Autotuning Procedure for PM Motors ......................................................... EN-17
PM Motor Encoder Offset Tuning ............................................................... EN-18
Ride Profile and Sequence Setup..............................EN-19
Up and Down Commands and Speed Reference Selection .......................EN-19
Speed Selection Sequence Using Digital Inputs ........................................EN-19
Acceleration/Deceleration/Jerk Settings .....................................................EN-22
Brake Sequence .........................................................................................EN-22
Inertia Compensation (Feed Forward) .......................................................EN-22
Troubleshooting..........................................................EN-24
Fault and Alarm Detection .......................................................................... EN-24
Operator Programming Errors (OPE) .........................................................EN-26
Auto-tuning Faults .....................................................................................EN-27
Parameter Table ..........................................................EN-28

Warnings

Cables must not be connected or disconnected, nor signal tests carried out, while the power is switched on.
The Varispeed L7 DC bus capacitor remains charged even after the power has been switched off. To avoid an electric shock hazard, disconnect the frequency inverter from the mains before carrying out maintenance. Then wait for at least 5 minutes after all LEDs have gone out. Do not perform a withstand voltage test on any part of the inverter. It contains semiconductors, which are not designed for such high voltages.
Do not remove the digital operator while the mains supply is switched on. The printed circuit board must also not be touched while the inverter is connected to the power.
Never connect general LC/RC interference suppression filters, capacitors or overvoltage protection devices to the inverter input or output.
CAUTION
To avoid unnecessary over current faults, etc., being displayed, the signaling contacts of any contac­tor or switch fitted between inverter and motor must be integrated into the inverter control logic (e.g. baseblock).
This is absolutely imperative!
This manual must be read thoroughly before connecting and operating the inverter. All safety pre­cautions and instructions for use must be followed.
The inverter must be operated with the appropriate line filters, following the installation instructions in this manual and with all covers closed and terminals covered. Only then will adequate protection be provided. Please do not connect or operate any equipment with visible damage or missing parts. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
EN-1

Safety Precautions and Instructions

1. General
Please read these safety precautions and instructions for use thoroughly before installing and operating this inverter. Also read all of the warning signs on the inverter and ensure they are never damaged or removed.
Live and hot inverter components may be accessible during operation. Removal of housing components, the digital operator or terminal covers runs the risk of serious injuries or damage in the event of incorrect installa­tion or operation. The fact that frequency inverters control rotating mechanical machine components can give rise to other dangers.
The instructions in this manual must be followed. Installation, operation and maintenance may only be carried out by qualified personnel. For the purposes of the safety precautions, qualified personnel are defined as indi­viduals who are familiar with the installation, starting, operation and maintenance of frequency inverters and have the proper qualifications for this work. Safe operation of these units is only possible if they are used properly for their intended purpose.
The DC bus capacitors can remain live for about 5 minutes after the inverter is disconnected from the power. It is therefore necessary to wait for this time before opening its covers. All of the main circuit terminals may still carry dangerous voltages.
Children and other unauthorized persons must not be allowed access to these inverters.
Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all persons with any form of access to the inverters.
2. Intended Use
Frequency inverters are intended for installation in electrical systems or machinery.
Their installation in machinery and systems must conform to the following product standards of the Low Volt­age Directive:
EN 50178, 1997-10, Equipping of Power Systems with Electronic Devices
EN 60204-1, 1997-12 Machine Safety and Equipping with Electrical Devices
Part 1: General Requirements (IEC 60204-1:1997)/
Please note: Includes Corrigendum of September 1998
EN 61010-1, A2, 1995 Safety Requirements for Information Technology Equipment
(IEC 950, 1991 + A1, 1992 + A2, 1993 + A3, 1995 + A4, 1996, modified)
CE marking is carried out to EN 50178, using the line filters specified in this manual and following the appro­priate installation instructions.
3. Transportation and storage
The instructions for transportation, storage and proper handling must be followed in accordance with the tech­nical data.
4. Installation
Install and cool the inverters as specified in the documentation. The cooling air must flow in the specified direction. The inverter may therefore only be operated in the specified position (e.g. upright). Maintain the specified clearances. Protect the inverters against impermissible loads. Components must not be bent nor insu­lation clearances changed. To avoid damage being caused by static electricity, do not touch any electronic components or contacts.
EN-2
5. Electrical Connection
Carry out any work on live equipment in compliance with the national safety and accident prevention regula­tions. Carry out electrical installation in compliance with the relevant regulations. In particular, follow the installation instructions ensuring electromagnetic compatibility (EMC), e.g. shielding, grounding, filter arrangement and laying of cables. This also applies to equipment with the CE mark. It is the responsibility of the manufacturer of the system or machine to ensure conformity with EMC limits.
Contact your supplier or Omron-Yaskawa Motion Control representative when using leakage current circuit breaker in conjunction with frequency inverters.
In certain systems it may be necessary to use additional monitoring and safety devices in compliance with the relevant safety and accident prevention regulations. The frequency inverter hardware must not be modified.
If Permanent Magnet Motors are used:
If a PM motor is turned by any external force, high voltage is generated in the windings.
During wiring, maintenance or inspection make sure, that the motor is stopped and can not turn.
If the inverter is turned off and the motor must be turned, make sure that motor and inverter output are
electrically disconnected.
6. Inverter Setup
This L7 inverter can drive induction motors as well as permanent magnet motors. Always select the appropriate control mode:
For induction motors use V/f, Open Loop Vector or Closed Loop Vector control (A1-01 = 0, 2 or 3).
For permanent magnet motors use no other control mode than Closed Loop Vector for PM (A1-01 = 6).
A wrong control mode selection can damage the inverter and motor.
If a motor is exchanged or operated the first time, always set up the motor control relevant parameters using the nameplate data or perform autotuning. Do not change the parameters recklessly. To ensure a safe operation with PM motors always set the:
correct motor data
the PG open detection parameters
the speed deviation detection parameters
the over acceleration detection parameters
Wrong parameter settings can cause dangerous behavior or motor and inverter damage.
Refer to page 12, Start Up Procedure for details about the correct start up procedure.
7. Notes
The Varispeed L7 frequency inverters are certified to CE, UL, and c-UL.

EMC Compatibility

1. Introduction
This manual was compiled to help system manufacturers using Omron-Yaskawa Motion Control frequency inverters to design and install electrical switch gear. It also describes the measures necessary to comply with the EMC Directive. The manual's installation and wiring instructions must therefore be followed.
EN-3
Our products are tested by authorized bodies using the standards listed below.
Product standard: EN 61800-3:1996
EN 61800-3; A11:2000
2. Measures to Ensure Conformity of Omron-Yaskawa Motion Control Frequency
Inverters to the EMC Directive
Omron-Yaskawa Motion Control frequency inverters do not necessarily have to be installed in a switch cabi­net.
It is not possible to give detailed instructions for all of the possible types of installation. This manual therefore has to be limited to general guidelines.
All electrical equipment produces radio and line-borne interference at various frequencies. The cables pass this on to the environment like an aerial.
Connecting an item of electrical equipment (e.g. drive) to a supply without a line filter can therefore allow HF or LF interference to get into the mains.
The basic countermeasures are isolation of the wiring of control and power components, proper grounding and shielding of cables.
A large contact area is necessary for low-impedance grounding of HF interference. The use of grounding straps instead of cables is therefore definitely advisable.
Moreover, cable shields must be connected with purpose-made ground clips.
3. Laying Cables
Measures Against Line-Borne Interference:
Line filter and frequency inverter must be mounted on the same metal plate. Mount the two components as close to each other as possible, with cables kept as short as possible.
Use a power cable with well-grounded shield. Use a shielded motor cable not exceeding 20 meters in length. Arrange all grounds so as to maximize the area of the end of the lead in contact with the ground terminal (e.g. metal plate).
Shielded Cable:
Use a cable with braided shield.
Ground the maximum possible area of the shield. It is advisable to ground the shield by connecting the
cable to the ground plate with metal clips (see following figure).
Ground clip
The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and paint.
– Ground the cable shields at both ends.
– Ground the motor of the machine.
Ground plate
EN-4

Installation

Mechanical Installation

Unpacking the Inverter
Check the following items after unpacking the inverter.
Item Method
Has the correct model of Inverter been delivered? Check the model number on the nameplate on the side of the Inverter.
Is the Inverter damaged in any way?
Are any screws or other components loose? Use a screwdriver or other tools to check for tightness.
If you find any irregularities in the above items, contact the agency from which you purchased the Inverter or your Omron-Yaskawa Motion Control representative immediately.
Checking the Installation Site
Before installing the inverter check the following:
Make sure that the ambient temperature is not exceeded
Install the Inverter in a clean location which is free from oil mist and dust. It can be installed in a totally
enclosed panel that is completely shielded from floating dust.
When installing or operating the Inverter, always take special care so that metal powder, oil, water, or other
foreign matter does not get into the Inverter.
Do not install the Inverter on combustible material, such as wood.
Install the Inverter in a location free from radioactive materials and combustible materials.
Install the Inverter in a location free from harmful gasses and liquids.
Install the Inverter in a location without excessive oscillation.
Install the Inverter in a location free from chlorides.
Install the Inverter in a location free from direct sunlight.
Inspect the entire exterior of the Inverter to see if there are any scratches or other damage resulting from shipping.
Installation Orientation
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always pro­vide the following installation space to allow normal heat dissipation.
Air
A B
50 mm 120 mm
Air
50 mm min.
IMPORTANT
A
30 mm min.
30 mm min.
Horizontal Space
1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.
2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a panel. Always provide enough space for suspension eye bolts and the main circuit lines when installing an Inverter with an output of 22 kW or more in a panel.
B
120 mm min.
Vertical Space
EN-5

Electrical Connection

Installation of Inverters and EMC filters
PEL1L2
L3
Ground Bonds Remove any paint!
For an EMC rules compliant installation consider the following points:
Use a line filter.
Use shielded motor cables.
Mount the inverter and filter on a grounded conductive plate.
Remove any paint or dirt before mounting the parts in order to
reach the lowest possible grounding impedance.
Wiring Main Circuit Inputs
PE
Line
Filter
Load
Cable Length as short as possible
Grounded Metal Plate
GND
Ground Bonds Remove any paint!
Inverter
L2
U
L1
L3
V
M ~3
W
GND
Screened Motor cable
Consider the following precautions for the main circuit power sup­ply input.
If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3), ensure
that the circuit breaker is suitable for the Inverter.
If an earth leakage breaker is used, it should be able to detect all kinds of current should be used in order to
ensure a safe earth leakage current detection
A magnetic contactor or other switching device can be used at the inverter input. The inverter should not
be powered up more than once per hour.
The input phases (R/S/T) can be connected in any sequence.
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase advancing
capacitor is switched nearby, an excessive peak current could flow through the input power circuit, causing an inverter damage. As a countermeasure install an optional AC Reactor at the inverter input or a DC reac­tor at the DC reactor connection terminals.
Use a surge absorber or diode for inductive loads near the Inverter. Inductive loads include magnetic con-
tactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
Wiring the Output Side of the Main Circuit
The following precautions should be considered for the output circuit wiring.
Never connect any power source to the inverter output terminals. Otherwise the inverter can be damaged.
Never short or ground the output terminals. Otherwise the inverter can be damaged.
Do not use phase correction capacitors. Otherwise the inverter and capacitors can be damaged.
Check the control sequence to make sure, that the magnetic contactor (MC) between the Inverter and
motor is not turned ON or OFF during inverter operation. If the MC is turned ON during the Inverter is operation, a large inrush current will be created and the inverter’s over current protection may operate.
Ground Connection
The following precautions should be considered for the ground connection.
Do not share the ground wire with other devices, such as welding machines or power tools.
Always use a ground wire, that complies with technical standards on electrical equipment and minimize
the length of the ground wire.
EN-6
Leakage current is caused by the Inverter. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
When more than one Inverter is used, do not to loop the ground wire.
OK
NO
Fig 1 Ground Wiring
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2,
W/T3, , 1, 2, and 3, PO, NO) and other high-power lines.
Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, M4, M5, and M6 (contact out-
puts) from wiring to other control circuit terminals.
If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
Ground the cable shields with the maximum contact area of the shield and ground.
Cable shields have to be grounded on both cable ends.
Main Circuit Terminals
Main circuit terminal functions are summarized according to terminal symbols in Table 1. Wire the terminals correctly for the desired purposes.
Table 1 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Purpose Terminal Symbol
Main circuit power input
Inverter outputs U/T1, V/T2, W/T3 23P7 to 2055 43P7 to 4055 DC bus terminals Braking Resistor Unit connection B1, B2 23P7 to 2018 43P7 to 4018 DC reactor connection
Braking Unit connection Ground 23P7 to 2055 43P7 to 4055 Control Power Supply PO, NO 23P7 to 2055 43P7 to 4055
R/L1, S/L2, T/L3 23P7 to 2055 43P7 to 4055 R1/L11, S1/L21, T1/L31 2022 to 2055 4022 to 4055
1,
1, 2 3,
Model: CIMR-L7Z
200 V Class 400 V Class
23P7 to 2055 43P7 to 4055
23P7 to 2018 43P7 to 4018 2022 to 2055 4022 to 4055
EN-7
Control Circuit Terminals
Fig 2 shows the control terminal arrangement. The functions of the control circuit terminals are shown in Table 2. Use the appropriate terminals for the correct purposes.
E(G)
SC SC SC
S1
S2
BB
S3 S4
Fig 2 Control terminal arrangement
+V
A1 AC
S5 S6 S7 BB1
M5
M6
M3
MA MB MC
M4
M1
M2
E(G)
Table 2 Control Circuit Terminals with default settings
Type No. Signal Name Function Signal Level
S1 Forward run/stop command Forward run when ON; stopped when OFF. S2 Reverse run/stop command Reverse run when ON; stopped when OFF. S3 Nominal speed Nominal speed when ON.
Dig-
input
signals
S4 Inspection Run Inspection RUN when ON.
S5 Intermediate speed
ital
Intermediate speed when
ON. S6 Leveling speed Leveling speed when ON. S7 Not used
BB Hardware baseblock Both inputs must be enabled to enable the inverter
outputBB1 Hardware baseblock 1
SC Digital input common
Ana-
input
signals
Dig-
output
signals
+V
log
15 V power supply
A1 Frequency reference 0 to +10 V/100% 0 to +10 V(20 kΩ) AC Analog reference neutral
Shield wire, optional ground line
E(G)
connection point
M1
Brake command (1NO contact)
M2
M3
ital
*1. Do not use this power supply for supplying any external equipment. *2. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in Fig 3.
Contactor Control (1NO contact)
M4
M5
Inverter Ready (1NO contact)
M6
MA
Fault output signal (SPDT)
MB
(1 Change over contact)
MC
*1
15 V power supply for analog references
––
Brake command when ON.
Contactor Control when ON
Inverter Ready when ON.
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
Functions are selected by setting H1-01 to H1-05.
Multi-function con­tact outputs
24 VDC, 8 mA Photo-coupler
15 V (Max. current: 20 mA)
Relay contacts Contact capacity: 1 A max. at 250 VAC
1 A max. at 30 VDC
*2
Flywheel diode
The rating of the flywheel diode must
External power: 30 VDC max.
Coil
1 A max.
be at least as high as the circuit volt­age.
Fig 3 Flywheel Diode Connection
1. In Fig 4 the wiring of the digital inputs S1 to S7 and BB, BB1 is shown for the connection of contacts or NPN transistors (0V common and sinking mode). This is the default setting. For the connection of PNP transistors or for using a 24V external power supply, refer to Ta ble 3.
IMPORTANT
2. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when connecting a DC reactor.
Sinking/Sourcing Mode (NPN/PNP Selection)
The input terminal logic can be switched over between sinking mode (0-V common, NPN) and sourcing mode (+24V common, PNP) by using the jumper CN5. An external power supply is also supported, providing more freedom in signal input methods.
EN-8
Table 3 Sinking/Sourcing Mode and Input Signals
S1
S2
SC
IP24V
(+24V)
CN5
A1 A3
B1
B3B2
A2
S1
S2
SC
IP24V
(+24V)
CN5
A1 A3
B1
B3B2
A2
24 VDC
+
S1
S2
SC
IP24V
(+24V)
CN5
A1 A3
B1
B3B2
A2
24 VDC
-
Internal Power Supply – Sinking Mode (NPN)
Internal Power Supply – Sourcing Mode (PNP)
S1
S2
B1
SC
A1 A3
A2
B3B2
CN5
IP24V
(+24V)
External Power Supply – Sinking Mode (NPN)
External Power Supply – Sourcing Mode (PNP)
EN-9
Wiring the Inverter
3-phase power 380 to 480V 50/60Hz
Multi function Inputs (Factory setting)
Magnetic
Contactor
L1
L2
L3
PE
Forward run/stop
Reverse run/stop
Nominal Speed
Inspection Run
Intermediate Speed
Leveling Speed
Not used
Hardware Baseblock (note 3)
Line
Filter
DC reactor to improve input
power factor (optional)
Link
(+1) (+2)
L1(R)
L2(S)
L3(T)
S1
S2
S3
S4
S5
S6
S7
BB
BB1
SC
(-)
+24V, 8mA
IP24V (24V)
Braking Resistor unit (optional)
B1
U/T1
V/T2
W/T3
TA 1
PG-X2
(Optional)
TA 3
TA 2
B2
A Pulse
B Pulse
Z Pulse
Pulse Monitor Output RS-422 (100m or less)
Motor
IM/PM
P
P
PG
Voltage adjust­ment
Analog input
(Speed reference)
2kOhm
Optional control power
supply input for Rescue
Operation
Note: 1
. Main circuit terminals are indicatied with double circles and
control circuit terminals are indicatied with a single circles
2. The CN5 factory setting is NPN
3. To enable the inverter both inputs, BB and BB1 must be closed. If only one of the inputs is closed, “BB” will be displayed in the operator panel and the inverter will not start.
2kOhm
0 to 10 V
P
Input option cards
to terminal B1
to terminal -
CN5(NPN setting)
E(G)
+V
Analog input power supply +15V, 20mA
A1
Master speed reference 0 to 10V
AC
0 V
2CN
P0
Control Power
Supply Input
N0
Shielded wires
Fig 4 Wiring Diagram
MA
MB
MC
M1
M2
M3
M4
M5
M6
3CN
Twisted-pair wires
Fault contact output 250VAC, max. 1A 30VDC, max. 1A
Brake Command (Factory setting)
Contactor Control (Factory setting)
Inverter Ready (Factory setting)
Output option
cards
Multi-function contact output 250VAC, max. 1A 30VDC, max. 1A
EN-10

Keypad Operation

Digital Operator Display (optional)

The key names and functions of the Digital Operator are described below
Drive Status Indicators
FWD: Lights up when a forward run command is input. REV: Lights up when a reverse run command is input. SEQ: Lights up when any other run command source
REF: Lights up when any other frequency reference
ALARM:Lights up when an error or alarm has
Data Display
Displays monitor data, parameter numbers and param­eter settings.
Mode Display (displayed at the upper left of data display)
DRIVE: Lights up in Drive Mode. QUICK: Lights up in Quick Programming Mode. ADV: Lights up in Advanced Programming Mode. VERIFY: Lights up in Verify Mode. A. TUNE: Lights up in Autotuning Mode.
Keys
Execute operations such as setting parameters, moni­toring, jogging, and autotuning.
than the digital operator is selected
source than the digital operator is selected
occurred.
Digital Operator Keys
Key Name Function
LOCAL/REMOTE Key
MENU Key Selects menu items (modes).
ESC Key Returns to the status before the DATA/ENTER key was pressed.
JOG Key
FWD/REV Key
Shift/RESET Key
Increment Key
Decrement Key
DATA/ENTER Key Enters menus and parameters, and set validates parameter changes.
Switches between operation via the Digital Operator (LOCAL) and the settings in b1-01 and b1-02 (REMOTE). This key can be enabled or disabled by setting parameter o2-01.
Starts jog operation when the inverter is operated by the Digital Operator and d1-18 is set to 0.
Selects the rotation direction of the motor when the Inverter is operated by the Dig­ital Operator.
Sets the active digit when programming parameters. Also acts as the Reset key when a fault has occurred.
Selects menu items, sets parameter numbers, and increments set values. Used to move to the next item or data.
Selects menu items, sets parameter numbers, and decrements set values. Used to move to the previous item or data.
EN-11
RUN Key Starts the Inverter operation when the Inverter is controlled by the Digital Operator.
STOP Key
Note: Except in diagrams, Keys are referred to the key names listed in the above table.
Stops Inverter operation. This key can be enabled or disabled using parameter o2-02 when operating from a source different than the operator.

Power Up and Basic Parameter Setup

Start Up Procedure

START
Mechanical installation
Main and control circuit wiring
Check the encoder power supply selection
Select the control mode in parameter A1-02
Perform motor data / encoder offset auto tuning
* V/f control * Open Loop Vector Control * Closed Loop Vector Control * Closed Loop Vector Control for PM
Speed reference
source
Set up the analog/digital I/O’s in the H1-xx,
H2-xx and H3-xx parameters
* (Closed Loop only)
Switch on the power supply
page 16, Autotuning Procedure with Induction Motors
page 17, Autotuning Procedure for PM Motors
Digital operator (b1-02 = 0)
Analog Input
Select the control sequence in
paramerter d1-18
Set up the digital I/O’s in the H1-xx
and H2-xx parameters
* Acceleration / Deceleration times (C1-xx)
Set up the
* S-Curves (Jerk) (C2-x)
Make test runs
Fine Tuning * Brake sequence tuning * Special functions setup
FINISH
Fig 5 Basic Start Up Sequence
* Preset speed values (d1-xx)
Set up the
* Acceleration / Deceleration times (C1-xx) * S-Curves (Jerk) (C2-xx)
EN-12

Before Power Up

The following points should be checked carefully before the power is switched on.
Check if the power supply meets the inverter specification.
Check if the power supply cables are tightly connected to the right terminals (L1, L2, L3).
Check if the motor cables are tightly connected to the right terminals on the inverter side (U, V, W) as well
as on the motor side.
Check if the braking unit/braking resistor is connected correctly.
Check if the Inverter control circuit terminal and the control device are wired correctly.
Set all Inverter control circuit terminals to OFF.
When a PG card is used, check if it is wired correctly.

Display after Power Up

After normal power up without any problems the operator display shows the following messages
-DRIVE-
Display for normal operation The Baseblock message blinks.
Base Block
Rdy
BB
When a fault occurs or an alarm is active, a fault or alarm message will appear. In this case, refer to page 28,
Factory settings are in bold..
Display for fault operation
-DRIVE-
UV
Main Power Loss
A fault or alarm message is shown on the display. The example shows a low voltage alarm.

Control Mode Selection

As the first thing after power up one of the four control modes must be selected depending on the machine type. The Closed Loop Vector modes require PG feedback cards. Table 4 shows the required/possible PG cards for each mode.
Table 4 Control Mode Selection
Machine Type Control Mode
Induction motor without encoder
Induction motor with incremental encoder Closed Loop Vector Control 3 PG-B2/PG-X2 Permanent magnet motor with Hiperface
encoder
Yaskawa IPM motor with incremental encoder
y
or EnDat 2.1
Closed Loop Vector Control for
Closed Loop Vector Control for
V/f control 0 -
Open Loop Vector Control 2 -
PM motors
PM motors
A1-02 setting PG Card
6PG-F2
6 PG-X2
EN-13
CAUTION
• For Permanent Magnet motors do not use any other control mode than Closed Loop Vector for PM (A1-02 = 6). Using any other control mode can cause damage to the equipment or can cause dangerous behavior.

Autotuning

The motor data autotuning function sets the V/f pattern parameters (E1-), motor data parameters (E2-, E5-) and the encoder data (F1-01) automatically. The steps which have to be performed during the autotuning depend on the tuning mode selection.

Autotuning Mode Selection

The autotuning mode has to be selected according to selected control mode and the mechanical system (motor no load rotation possible or not). Tab l e 5 shows the selectable tuning mode for each control mode.
Table 5 Motor Data Autotuning Modes
Tuning
Autotuning Mode Function
Standard tuning with rotating motor Tunes all motor parameters. 0 No Yes Yes Yes IM tuning with not rotating motor Tunes the basic motor parameters. 1 No Yes Yes No
IM Line-to-line resistance tuning
Encoder offset tuning
Tunes the line-to-line resistance only Tunes the offset between the encoder and magnetic zero position.
Mode
Selection
(T1-01)
2YesYesYesNo
4NoNoNoYes
V/f
Control Mode
Open
Loop
Vector
Closed
Vector
Loop
Closed
Loop
Vector
(PM)
Autotuning Modes
Autotuning with Rotating Motor (T1-01 = 0)
This autotuning mode can be used in any Vector control mode. After the motor nameplate data have been input, the inverter will operate the motor for approximately 1~2 minutes and set the required motor parameters automatically.
Use this tuning mode only, if the motor can rotate freely which means that the ropes must be removed and the brake must be open. The gearbox can remain connected to the motor.
IMPORTANT
Autotuning with Not Rotating Motor (T1-01 = 1)
This autotuning mode can be used for Open Loop and Closed Loop Vector control for IM only. The inverter supplies power to the motor for approximately 1 minute and some of the motor parameters are set automati­cally while the motor does not turn. The motor no-load current and the rated slip value will automatically be fine tuned during the first time operation. Verify the rated slip value (E2-02) and the no-load current (E2-03) after the first run with nominal speed.
Autotuning for Line-to-Line Resistance (T1-01 = 2)
Non-rotating autotuning for line-to-line resistance can be used in V/f control, Open Loop Vector control and Closed loop Vector control. The Inverter supplies power to the motor for approximately 20 seconds to measure the motor line-to-line resistance and cable resistance. The motor does not turn during this tuning procedure.
Encoder Offset Tuning (T1-01=4)
This tuning mode is available in Closed Loop Vector control for PM motors only. It automatically sets the off­set between the magnetic pole and the encoder zero position. It can be used to retune the offset after an encoder change without changing the motor data settings.
EN-14
General Precautions:
1. Use rotating autotuning whenever high precision is required or for a motor that is not connected to a load.
2. Use not rotating autotuning whenever the load cannot be disconnected from the motor (e.g. the ropes can’t be
IMPORTANT
removed).
3. Make sure, that the mechanical brake is not open for not rotating autotuning.
4. During autotuning the motor contactors have to be closed.
5. For autotuning the BB and BB1 signals must be ON (Inverter must not be in base block condition).
6. Confirm, that the motor is mechanically fixed and can not move.
7. Power is supplied during auto tuning, even though the motor does not turn. Do not touch the motor until auto­tuning has been completed.
8. Remove the feather key from the motor shaft before performing a tuning with rotating motor with a stand alone motor (no traction sheave or gear mounted).
9. To cancel autotuning, press the STOP key on the Digital Operator.
Precautions for rotating and encoder offset autotuning:
1. The load should be disconnected which means, that the ropes have to be removed and the brake must be open.
2. If the load can’t be removed, the tuning can be done with a balanced car. The tuning result accuracy will be lower which can result in a performance loss.
3. Make sure that the brake is open during autotuning.
4. During autotuning the motor can be started and stopped repeatedly. When the tuning is finished, “END” will be displayed in the operator panel. Do not touch the motor until this display is shown and the motor has completely stopped.
Autotuning Alarms and Faults
Data Input Errors
The inverter will show a “Data Invalid” message and will not perform autotuning if:
the motor speed, rated frequency and pole pair number do not correspond.
Base Frequency · 60
Motor Speed
------------------
2 · Motor pole
the rated current does not correspond to the rated power value
The inverter calculates the motor power using the input current value and data from the internal motor data table. The calculated value must be between 50% and 150% of the input value for the rated power.
Other Alarms and Faults During Autotuning
For an overview of possible autotuning alarms or faults and corrective actions refer to page 27, Auto-tuning
Faults.
EN-15

Autotuning Procedure with Induction Motors

Fig 6 shows the autotuning procedure for an induction motor with or without encoder in V/f-, Open loop vec-
tor and Closed loop vector control.
START
Set the Base Block Inputs BB and
BB1
No
V/f Control ?
(A1-02 = 0)
(A1-02 = 2/3)
Yes
Enter auto tuning mode and
set parameter T1-01 = 2
Set:
T1-02 - Motor rated power
T1-04 - Motor rated current
Press the UP button until
“Tuning Ready” display appears
Can the motor
rotate freely ?
No
Enter auto tuning mode and
set parameter T1-01 = 1
T1-02 - Motor rated power T1-03 - Motor rated voltage T1-04 - Motor rated current T1-05 - Rated motor frequency T1-06 - Motor pole number T1-07 - Motor rated speed T1-08 - PG pulse number*
“Tuning Ready” display appears
Set:
(*CLV only)
Press the UP button until
Yes (ropes removed?)
“Tuning Ready” display appears
Enter auto tuning mode and
set parameter T1-01 = 0
T1-02 - Motor rated power T1-03 - Motor rated voltage T1-04 - Motor rated current T1-05 - Rated motor frequency T1-06 - Motor pole number T1-07 - Motor rated speed T1-08 - PG pulse number*
Set:
(*CLV only)
Press the UP button until
Open the brake
Refer to
page 27, Auto-tuning Faults
and eliminate the fault source
Close the motor contactor(s)
Press the RUN button
Tuning
No
(Fault code is
displayed)
Open the contactors, open the base
block inputs and close the brake if auto
tuning with rotating motor was performed
successful ?
(” Tuning successful”
is displayed)
FINISH
Fig 6 Autotuning for Induction Motors
Yes
EN-16

Autotuning Procedure for PM Motors

Fig 7 shows the autotuning procedure for permanent magnet motors. Before tuning make sure that the control
mode is set to PM Closed Loop Vector (A1-02 = 6).
START
* Remove the ropes so that the motor can rotate freely * Set the Base Block inputs BB and BB1
Switch ON the power supply if it is OFF
Does a OPE06 fault
occur?
No
Does a CPF24 fault
occur?
No
Does a OPE02 fault
occur?
No
S3-13 - Tracti on sheave diam eter S3-14 - Roping
turn the motor slowly in Forward direction*
Set mechanical constants:
Open the brake, close the motor contactor,
Does PGO (no
encoder feedback)
occur?
No
Yes
Yes
Yes
S3-15 - Gear r atio
1
and check monitor U1-05.
Yes
Check parameter
* F1-01
* n8-35
* Check parameter n8-35 * If EnDat / Hiperface is used
- check the encoder power supply
- check the CLOCK and DATA signal wiring * Switch off the power supply.
* Check if the correct PG constant (F1-01) and absolute encoder resolution (F1-21) has been set. * Refer to:
page 26, Operator Programming Errors (OPE)
Switch off the power supply
and check if the right PG card
is correctley installed
and eliminate the fault source
* Check the wi ring * Check/r eadjust the encoder power supply
EN-17
U1-05 value positive
T1- 01 = 0 - R otational Tuning T2-01 - Motor rated power T2- 02 - Mot or base fr equency T2-03 - Motor rated voltage
Pres s the UP button until the “ Tuning R eady” di splay appear s
Cl ose the motor c ontactor( s) and pr ess the R UN butt on
(”Tuning successful” is displayed)
Set the autotuning par ameter s:
Wai t until tuning is fi nsihed
Tuning successful?
Yes
Open the cont actors , open the basebloc k
inputs and close t he brake
Fig 7 Autotuning for Permanent Magnet Motors
Is the sign of the
(not -)?
Yes
FINISH
No
T2-04 - Motor rated current T2- 05 - Mot or pole num ber T2-09 - Encoder resolution T2- 10 - Mot or vol tage constant
No (Fault code is displayed)
* 1. Forward direction means:
* Check the enc oder wi ring * Change param eter F 1-05
Refer to
page 27, Auto-tuning Faults
and eli minate the faul t sourc e
The direction the motor turns with an UP command at terminal S1 (i.e. with a clockwise rotating 3 phase supply and U-U, V-V, W-W wiring between inverter and motor). Usually the direction is clockwise seen from the motor shaft (traction sheave) side. Refer to the motor instruction manual or consult the manufacturer for details about the rotation direction.

PM Motor Encoder Offset Tuning

Fig 8 shows the autotuning procedure for an encoder offset tuning. The procedure should be performed if the
encoder has been changed or has not been aligned correctly. Before tuning make sure that PM losed loop vec­tor control is selected (A1-02 = 6) and that the E1- and E5- parameters are set up correctly.
START
Is it possible to remove
the ropes ?
Yes
Remove the ropes.
Set the Base Block inputs BB and BB1
Switch ON the power supply if it is OFF
Does a OPE06 fault
occur?
No
Does a CPF24 fault
occur?
No
Does a OPE02 fault
occur?
No
Open the brake, close the motor contactor,
turn the motor slowly in Forward direction*
monitor U1-05.
No
Yes
Yes
Yes
1
and check
Balance the car so that it does not move
Check parameter
* F1-01
* n8-35
* Check parameter n8-35 * If EnDat / Hiperface is used
- check the encoder power supply
- check the CLOCK and DATA signal wiring * Switch off the power supply.
* Check if the correct PG constant (F1-01) and absolute encoder resolution (F1-21) has been set. * Refer to:
page 26, Operator Programming Errors (OPE)
and eliminate the fault source
with open brakes.
Note: The tuning accuracy will be lower
in this tuning mode
Switch off the power supply
and check if PG card is
correctly installed
Press the UP button until the “Tuning
(”Tuning successful”
display is shown)
Yes
Does PGO (no
encoder feedback)
occur?
No
Is the sign of the
U1-05 value positive
(not -)?
Yes
T1-01 = 4 - Encoder Offset Tuning
Close the motor contactor(s) and
Wait until the tuning is finished.
Open the contactors, open the base
block inputs and close the brake
Set:
Ready” display appears.
press the RUN key.
Tuning successful?
FINISH
Fig 8 Encoder Offset Autotuning
Yes
No
No (Fault code is displayed)
* C heck the wi ri ng * Chec k/readj ust the encoder power supply
* Chec k the encoder wir ing * C hange parameter F1- 05
Refer to
page 27, Auto-tuning Faults
and eliminate the fault source.
* 1. Forward direction means:
The direction the motor turns with an UP command at terminal S1 (i.e. with a clockwise rotating 3 phase supply and U-U, V-V, W-W wiring between inverter and motor). Usually the direction is clockwise seen from the motor shaft (traction sheave) side. Refer to the motor instruction manual or consult the manufacturer for details about the rotation direction.
EN-18

Ride Profile and Sequence Setup

Up and Down Commands and Speed Reference Selection

Up/Down Command Source Selection
The input source for the Up and Down signal can be selected in parameter b1-02. The factory setting is Up/ Down command by the terminals S1/S2 (b1-02 = 1).
Travel start in Up or Down direction
To start in the elevator in Up or Down direction the following conditions have to be fulfilled:
At least one speed reference must be selected if digital inputs are used for speed reference selection.
The hardware base block signal (Terminal BB and BB1) must be set (not base block condition).
The Up/Down signal must be set to start in the corresponding direction.
Travel stop
The inverter can be stopped as follows:
The direction command (UP or Down) signal is removed.
The speed reference selection signal is removed if digital inputs are used for speed reference selection.
If d1-18 is set to 3 and all speed inputs are removed
Speed Reference Source Selection
The speed reference source can be selected using parameter b1-01. The factory setting is the digital operator (b1-01 = 0), i.e. the speeds can be selected using digital inputs.

Speed Selection Sequence Using Digital Inputs

If the digital inputs are used for speed selection, the speed selection method and the speed priority depends on the setting of parameter d1-18 (Speed priority selection).
Multi-Step Speed Operation 1/2 (Binary Input) (d1-18=0/3)
If d1-18 = 0
8 preset speed steps (defined in the parameters d1-01 to d1-08) can be selected using 3 binary coded digital inputs. The Up/Down command starts the inverter. It stops when the Up/Down command is removed.
If d1-18 = 3
7 preset speed steps (defined in the parameters d1-02 to d1-08) can be selected using 3 binary coded digital inputs. The Up/Down command starts the inverter. It is stopped when the Up/Down command is removed or when no speed is selected (all D/Is off).
Multi-function Digital Input Settings (H1-01 to H1-05) (Example)
EN-19
Terminal
S4 H1-02 3 Multi-step speed command 1
S5 H1-03 4 Multi-step speed command 2 S6 H1-04 5 Multi-step speed command 3
Parameter
Number
Set Value Details
Speed Selection Table
The following table shows the combinations of the digital input and the according speed.
If b1-02 is set to “1”, frequency reference 1 is input as analog reference at terminal A1.
Multi-step
Speed
Speed Com-
mand 1
1 OFF OFF OFF Frequency reference 1 d1-01 Stop 2 ON OFF OFF Frequency reference 2 d1-02 Frequency reference 2 d1-02
3 OFF ON OFF Frequency reference 3 d1-03 Frequency reference 3 d1-03 4 ON ON OFF Frequency reference 4 d1-04 Frequency reference 4 d1-04 5 OFF OFF ON Frequency reference 5 d1-05 Frequency reference 5 d1-05
6 ON OFF ON Frequency reference 6 d1-06 Frequency reference 6 d1-06 7 OFF ON ON Frequency reference 7 d1-07 Frequency reference 7 d1-07 8 ON ON ON Frequency reference 8 d1-08 Frequency reference 8 d1-08
Multi-step
Speed Com-
mand 2
Multi-step
Speed Com-
mand 3
Selected Frequency
d1-18 = 0 d1-18 = 3
Separate Speed Selection Inputs, High Speed Has Priority (d1-18=1)
With this setting 6 different speeds (defined in the parameters d1-09 to d1-17) can be set and selected using four digital inputs.
Digital Input Factory Settings
Terminal
S3 H1-01 80 Nominal speed selection (d1-09) S4 H1-02 84 Inspection speed selection (d1-14) S5 H1-03 81 Intermediate speed selection (d1-10)
S6 H1-04 83 Leveling speed selection (d1-17)
Parameter
Number
Set Value Details
Higher Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
If d1-18 is set to 1 and one multi-function digital input is set to leveling speed selection (H1-=83), the inverter decelerates to the leveling speed (d1-17) when the selected speed signal is removed. Inspection Speed can not be selected as travel speed. The higher speed has priority over the leveling speed, i.e. as long as a higher speed is selected, the leveling signal is disregarded (see the fig. below)
The inverter stops when the leveling signal or the Up/Down signal is removed.
DC Injection/
zero servo
No effect Input is set
Speed
Hardware BB
Up/Donw
Leveling speed
Selected speed
DC Injection/
zero servo
Higher Speed Priority is Selected and a Leveling Speed Input is Not Selected (H1-K83)
When the leveling speed command is not selected for any digital input, the inverter decelerates to the leveling speed (d1-17) when the selected speed signal is removed. Inspection Speed can not be selected as travel speed To select the leveling speed as travel speed the frequency reference loss detection must be disabled (S3-09=0).
The inverter stops when the direction signal Up/Down is removed.
EN-20
When no speed selection input is set the leveling speed is taken as the speed reference.
Speed
Hardware BB
Up/Down
Selected speed
DC Injection/
zero servo
DC Injection/
zero servo
The inverter stops when the direction signal (UP or DOWN signal) is removed.
With this configuration the drive stops with a “FRL” (frequency reference loss fault) when no speed reference input is selected during the start.
IMPORTANT
To disable the FRL detection, set parameter S3-09 to “0”.
Separate Speed Selection Inputs, Leveling Speed Has Priority (d1-18=2)
The related parameters and the digital input pre-settings are the same as for the High Speed Priority setting (d1-18=1).
Leveling Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
If d1-18 is set to “2” and one multi-function digital input is set to leveling speed (H1-=83) the inverter decelerates to the leveling speed (d1-17) when the leveling speed selection input is activated. The leveling sig­nal has priority over the selected speed, i.e. the selected speed is disregarded. The selected travel speed must be different from inspection speed.
The inverter stops when the leveling speed command is removed.
Speed
Hardware BB
Up/Down
Leveling speed
Selected speed
DC Injection/
zero servo
DC Injection/
zero servo
Leveling speed has priority
Leveling Speed Priority is Selected and a Nominal Speed Input is Not Selected (H1-K80))
If d1-18 is set to “2” and no digital input is set to nominal speed selection, the speed reference with speed selection input set is nominal speed (d1-09). When the leveling speed signal is set, the inverter starts to decel­erate to the leveling speed. The leveling speed signal has priority over all other speed signals, i.e. the interme­diate speed 1 and 2 and the revelling signals are disregarded when leveling speed is selected.
The inverter can be stopped by removing the leveling speed signal or the Up/Down command.
CAUTION: This sequence can be risky if e.g. the speed selection doesn’t work for any reason (broken wire etc.).
Speed
Hardware BB
Up/Down
Leveling speed
DC Injection/
zero servo
DC Injection/
zero servo
EN-21

Acceleration/Deceleration/Jerk Settings

The acceleration time indicates the time to increase the speed from 0% to 100% of the maximum speed set in E1-04. The deceleration time indicates the time to decrease the speed from 100% to 0% of E1-04.
The standard acceleration/deceleration times are set in the parameters C1-01/02, the jerk settings (S-curve) are set in the C2- parameters as shown in Fig 9.
C2-02
Accel Time
C2-01
C1-01
Fig 9 Acceleration/Deceleration and Jerk (S-curve) settings

Brake Sequence

The figure below shows the standard brake sequence.
S1-04
Zero servo/
S1-16
DC Injection
at start
RUN delay time
Speed
S1-06
Delay time
Brake open
RUN
Inverter Hardware BB D/I
Brake Open Command
Decel Time
C1-02
C2-04
Selected Speed
C2-03
C2-05
Leveling Speed
Leveling Speed
S1-07
Brake close
delay time
S1-05
Zero servo/
DC inhection
at stop
S1-19
Contactor open delay
Fig 10 Timing chart of Brake sequence without torque compensation at start

Inertia Compensation (Feed Forward)

Feed Forward Control is used to eliminate the speed overshoot or undershoot by compensating inertia effects. It can be enabled by setting parameter n5-01 to 1. After that the motor acceleration time n5-05 must be tuned.
Motor Acceleration Time Auto Tuning (n5-05)
Before the n5-02 auto tuning is performed, the motor data autotuning and the general setup should have been finished. Do the tuning with the factory settings for the n5- parameters.
Use the following procedure:
1. Set n5-05 to “1” to enable the auto tuning and go back to the speed reference display.
2. Set the base block input.
3. Enable the inspection speed input. “FFCAL” will blink in the display to signalize that the calculation is active.
4. Set an UP command. The inverter will accelerate the motor up to the nominal speed. Release the UP com­mand a few seconds after the top speed has been reached.
EN-22
5. When the motor has stopped, apply a DOWN command. The inverter will accelerate the motor in the opposite direction to the nominal speed. Release the DOWN command a few seconds after the nominal speed has been reached.
To abort the tuning set parameter n5-05 to “0”.
1. The order of giving the UP or DOWN command has no influence.
2. n5-01 should not be changed from the factory value for the tuning.
3. After the run in both directions is finished, parameter n5-05 is automatically set back to “0”.
IMPORTANT
4. The autotuning will be performed only if the inspection speed input is set.
5. Do not change the mechanical constants (load, inertia) between the runs.
Feed Forward Compensation P-Gain Setup
Increase the gain to improve the responsiveness to the speed reference.
Decrease the gain if vibrations or oscillations occur.
EN-23

Troubleshooting

Fault and Alarm Detection

Faults and Alarms are functions that indicate unusual inverter/application conditions.
An alarm does not necessarily switch of the inverter but a message is displayed on the keypad and an alarm output is generated at the multi-function outputs (H2-01 to H2-03) if programmed. An alarm automatically disappears if the alarm condition is not present anymore.
A fault switches the inverter off immediately, a message is displayed on the keypad and the fault output is switched. The fault must be reset manually after the cause has been removed.
The following tables shows a list of faults and alarms with their corrective actions.
Display
BUS
Option Com Err
(flashing)
CF
Out of Control
CPF00 CPF01 COM-
ERR(OP&INV)
CPF02 - CPF 04
CPF24
Option Comm Err
DEV
Speed Deviation
DV3
DV4
DV6
Over Accelera-
tion
EF0
Opt External Flt
EF
Ext Fault S
EF
External Fault
(flashing)
Ext Run Active
Cannot Reset
Displayed as
Alarm Fault


Meaning Corrective Actions
Option Communications Alarm After initial communication was established, the con­nection was lost.
A torque limit was reached continuously for 3 sec­onds or longer during a deceleration stop in Open Loop Vector control.
• Digital Operator/LED Monitor Communication Fault 1/2
• Communication fault between Operator and inverter
• CPU External RAM Fault
• Baseblock circuit error
•EEPROM error
• CPU Internal A/D Converter Fault
Hiperface serial communication error Detected when no data were received from the encoder for 200 msec
F1-04 = 0, 1 or 2 and A1-02 = 3 or 6 The speed deviation is higher than the F1-10 value for the time F1-11 or longer.
F1-04 = 3 and A1-02 = 3 or 6 The speed deviation is higher than the F1-10 value for the time F1-11 or longer.
Wrong rotation direction Detected when the speed deviation is higher than 30% and the torque reference and acceleration have opposite signs.
Wrong rotation direction Detected when F1-19 is not 0, the speed reference and motor speed have opposite signs and the detec­tion threshold set in F1-19 is exceeded.
An over acceleration of the car was detected (A1-02 = 6 only)
External fault input from Communications Option Card
External fault at terminal S ( stands for terminals S3 to S7)
Forward/Reverse Run Commands Input Together Both the forward and the reverse run commands are input simultaneously for 500ms or more. This alarm stops the motor.
Fault reset was tried during run.
Check the connections and all user-side software con­figurations.
Check the motor parameters.
• Disconnect the Digital Operator/LED Monitor and then connect it again.
• Replace the Inverter.
• Cycle the Inverter power supply.
• Replace the Inverter.
• Perform an initialization to factory defaults.
• Cycle the Inverter power supply.
• Replace the Inverter.
Check the encoder connection or replace the encoder if necessary
• Reduce the load.
• Lengthen the acceleration time and deceleration time.
• Check the mechanical system.
• Check the settings of F1-10 and F1-11.
• Check the sequence and if the brake is opened when the inverter starts to increase the speed.
•Check the PG wiring
• Correct the wiring
• Verify the PG direction and execute an encoder off­set auto tuning
• Reduce the load and check the brake
• Verify the PG direction and execute an encoder off­set auto tuning
• Reduce the load and check the brake
• Reduce the load
• Check the PG direction, check F1-22 and perform an encoder offset tuning.
• Verify the settings of S3-13, S3-14 and S3-15.
• Adjust the acceleration and deceleration times.
• Check for an external fault condition.
• Verify the parameters.
• Verify communication signals
Eliminate the cause of the external fault condition.
Check external sequence logic, so that only one input is received at a time.
• Remove the direction signal and retry a fault reset.
• If a PLC handles the fault reset, check the sequence.
EN-24
Display
FF_CAL
FRL
Ref Missing
GF
Ground Fault
LF
Output Phase
Loss
OC
Over Current
OH
Heatsink Over-
temp
OH1
Heatsink Max
Tem p
OL1
Motor Overload
OL2
Inv Overload
OS
Motor Over speed
Det
OV
DC Bus Overvolt
PF
Input Phase Loss
PGO
PG Open
(PG Disconnec-
tion)
Displayed as
Alarm Fault
(only in
stop
condi-
tion)
Meaning Corrective Actions
Feed forward motor acceleration time active
No speed was selected before the inverter start. Check the speed selection/start sequence.
The ground current at the Inverter output exceeded 50% of the Inverter rated output current and L8-09=1
(Enabled).
An open-phase occurred at the Inverter output. The fault is detected when the output current falls
below 5% of the inverter rated current and L8-07=1
The Inverter’s output current exceeded the over cur-
rent detection level.
L8-03 = 0,1 or 2 and the temperature of the Inverter's cooling fin exceeded the L8-02 value.
Inverter's Cooling Fan Stopped L8-03 = 3 and the temperature of the Inverter's cool-
ing fin exceeded the L8-02 value. The temperature of the Inverter’s heatsink exceeded
105 °C.
Inverter’s Cooling Fan Stopped Detected when L1-01 is set to 1,2 or 3 and the
Inverter’s output current exceeded the motor over­load curve. The overload curve is adjustable using parameter E2-
01 (Motor Rated Current), L1-01 (Motor Protection Selection) and L2-02 (Motor Protection Time Con­stant)
The Inverter output current exceeded the Inverter’s
overload capability.
F1-03 = 0, 1 or 2 and A1-02 is set to 3 or 6. The motor speed feedback (U1-05) exceeded the F1-
08 value for the time F1-09.or longer. F1-03 = 3 and A1-02 is set to 3 or 6.
The motor speed feedback (U1-05) exceeded the F1­08 value for the time F1-09.or longer.
The DC bus voltage has exceeded the overvoltage detection level. Default detection levels are:
200 V class: 410 VDC 400 V class: 820 VDC
Too big DC bus voltage ripple.
Only detected when L8-05=1 (enabled) F1-02 = 0, 1 or 2 and A1-02 = 3 or 6
No PG (encoder) pulses are received for the time F1-
14 or longer. F1-02 = 3 and A1-02 = 3 or 6.
No PG (encoder) pulses are received for the time F1­14 or longer.
• Perform the complete tuning procedure
• Abort the tuning by setting n5-05 = 0.
• Remove the motor and run the Inverter without the motor.
• Check the motor for a phase to ground short.
• Check the output current with a clampmeter to ver­ify the DCCT reading.
• Check the control sequence for wrong motor contac­tor signals.
• Reset the fault after correcting its cause.
• Check the motor and Inverter capacity.
• Remove the motor and run the Inverter without the motor.
• Check the motor for a phase-to-phase short.
• Verify the accel/decel times
•(C1-).
• Check the Inverter for a phase-to-phase short at the output.
• Check for dirt build-up on the fans or heatsink.
• Reduce the ambient temperature around the drive.
• Replace the cooling fan(s).
• Check for dirt build-up on the fans or heatsink.
• Reduce the ambient temperature around the drive.
• Replace the cooling fan(s).
• Recheck the cycle time and the size of the load as well as the accel/decel times
•(C1-).
• Check the V/f characteristics (E1-).
• Check the setting of Motor Rated Current Setting (E2-01).
• Recheck the cycle time and the size of the load as well as the accel/decel times
•(C1-).
• Check the V/f characteristics (E1-).
• Check the setting of Motor Rated Current Setting (E2-01).
• Adjust the ASR settings in the C5 parameter group.
• Check the reference circuit and reference gain.
• Check the settings in F1-08 and F1-09.
• Increase the deceleration time (C1-02/04/06/08) or connect a braking option.
• Check the power supply and decrease the voltage to meet the inverter’s specifications.
• Check the braking chopper/resistor.
• Tighten the input terminal screws
• Check the power supply voltage
• Fix the broken/disconnected wiring.
• Fix the wiring.
• Supply power to the PG
•properly.
• Check the sequence and if the brake is opened when the inverter starts to increase the speed.
EN-25
Display
PUF
DC Bus Fuse
Open
RR
DynBrk Transistr
SE1
Sequence Error 1
SE2
Sequence Error 2
SE3
Sequence Error 3
SVE
Zero Servo Fault
UV1
DC Bus Under-
volt
UV2
CTL PS Under-
volt
Displayed as
Alarm Fault
(only in
condi-
tion)
stop
Meaning Corrective Actions
The fuse in the main circuit is blown. War ni ng: Never run the Inverter after replacing the DC bus fuse without checking for shorted components.
The built-in dynamic braking transistor failed.
No output contactor response S1-16 or longer. Check the output contactor.
The output current at start was below 25% of no-load current.
The output current during run was below 25% of no­load current.
The motor position moved during Zero Servo Opera­tion.
The DC bus voltage is below the under voltage Detection Level (L2-05). The default settings are: 200V class: 190 VDC 400 V class: 380 VDC
Main Circuit MC Operation Failure No MC response during Inverter operation.
Control Power Supply Undervoltage Undervoltage of the control circuit while the Inverter was running.
• Check the motor and the motor cables for short cir­cuits or insulation failures (phase-to-phase).
• Replace the inverter after correcting the fault.
• Cycle power to the Inverter.
• Replace the Inverter.
Check the output contactor.
Check the output contactor.
• Increase the torque limit.
• Decrease the load torque.
• Check for signal noise.
• Check the input voltage.
• Check the wiring of the input terminals.
• Check the input voltage and the wiring of the input terminals.
• Extend the settings in
• C1-01/03/05/07
Replace the Inverter.
• Remove all connection to the control terminals and cycle the power to the Inverter.
• Replace the Inverter.

Operator Programming Errors (OPE)

An Operator Programming Error (OPE) occurs when two or more parameter related to each other are set inap­propriate or an individual parameter setting is incorrect. The Inverter does not operate until the parameter set­ting is set correctly; however, no other alarm or fault outputs will occur. If an OPE occurs, change the related parameter by checking the cause shown in the table below. When an OPE error is displayed, press the ENTER key to see U1-34 (OPE Detected). This monitor displays the parameter that is causing the OPE error.
Display Meaning Corrective Actions
OPE01
kVA Selection
OPE02 Limit
OPE03
Ter mi nal
OPE05
Sequence Select
OPE06
PG Opt Missing
OPE08
Constant Selection
OPE10
V/f Ptrn Setting
Inverter kVA Setting Error Enter the correct kVA setting in o2-04.
Parameter Setting out of Range Hiperface selected (n8-35=4) and:
• F1-01 is different from 512 or 1024
• F1-21 is set to 2 EnDat selected (n8-35=5) and:
• F1-01 is different from 512 or 2048
• F1-21 is set to 0 or 1 Multi-function Input Selection Error (H1-01 to H1-05):
• Functions were selected duplicative.
• External Baseblock NO (8) and External Baseblock NC (9) were selected at the same time.
The Emergency Stop Command NO (15) and NC(17) are set simultaneously.
RUN/Reference Command Selection Error The Reference Source Selection b1-01 and/or the RUN Source Selection parameter b1-02 are set to 3 (option board) but no option board is installed.
Control method selection error/ PG-card missing
Function Selection Error Verify the control method and the function.
V/f Parameter Setting Error
Verify the parameter settings.
Verify the parameter settings in H1-
• Verify that the board is installed. Remove the power supply and re-install the option board again
• Recheck the setting of b1-01 and b1-02.
Verify the control method selection in parameter A1-02 and/or the installation of the PG option board.
Check parameters (E1-). A frequency/voltage value may be set higher than the maximum frequency/voltage.
EN-26

Auto-tuning Faults

Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the dig­ital operator and the motor coasts to stop. No fault or alarm outputs will be operated.
Display Meaning Corrective Actions
Acceleration error (detected during rotating autotuning
Accelerate
End - 1
V/f Over Setting
End - 2
Saturation
End - 3
Rated FLA Alm
Fault Motor data fault
I-det. Circuit
KE_ERR
(PM motor only)
LD_ERR
(PM motor only)
Leakage Induc-
tance Fault
Minor Fault
Motor Speed
No-Load Current No-Load Current Fault • Check the input data.
Resistance Line-to-Line Resistance Fault
Rated slip Rated Slip Fault
RS_ERR
(PM motor only)
STOP key STOP key input -
Z_SRCH_ERR
(PM motor only)
only) The motor did not accelerate in the specified time.
V/f Settings Alarm Displayed after auto-tuning is complete The torque reference exceeded 100% and the no-load cur­rent exceeded 70% during auto-tuning.
Motor Core Saturation Fault Displayed after auto-tuning is complete. Detected only for rotating autotuning
Rated Current Setting Alarm Displayed after auto-tuning is complete During auto-tuning, the measured value of motor rated current (E2-01) was higher than the set value.
Current detection error The current exceeded the motor rated current or any out­put phase is open
Voltage constant error Check the motor wiring
Inductance error Check the motor wiring
The leakage inductance measurement caused an error. The leakage inductance tuning current was too high or too low (Closed Loop Vector for PM only)
Any of the above listed alarms occured during autotuning or the inverter was in Base Block condition when the tun­ing was started.
Motor Speed Fault Detected only for rotating autotuning The torque reference exceeded 100% during acceleration. Detected only when A1-02 is set to 2 (Open Loop Vector control).
Line-to-line resistance error
All encoders: The motor speed exceeded 20 rpm at the auto tuning start. The magnetic pole position tuning could not be performed in the specified time.
Encoder with Z-pulse: The difference between two measurements of the magnet pole position was higher than 3°.
Serial encoders: The difference between two measurements of the magnet pole position was higher than 5° or an encoder serial com­munication error has occurred during the tuning.
• Increase C1-01 (Acceleration Time 1).
• Increase L7-01 and L7-02 (Torque Limits) if they are low.
• Remove the ropes and repeat the tuning.
• Check and correct the motor settings
• If the motor and the machine are connected, disconnect the motor from the machine.
• Check the input data.
• Check the motor wiring.
• If the motor and the machine are connected, disconnect the motor from the machine.
Check the motor rated current value.
• Check the input data.
• The motor and inverter capacity do not fit. Check the Inverter and motor capacity.
• Check the motor rated current and no-load current.
Check wiring of the Inverter and the mounting.
• Check the motor wiring.
• Check the motor rated current input value
• Reduce or increase the current level for leakage inductance tuning by changing parameter n8-46.
• Leave the tuning menu, check the alarm content and remove the cause as described in the alarm list above.
• Check the input data.
• Make sure that the inverter is not in Base Block condition during the tuning.
• If the motor is connected to the machine, disconnect it.
• Increase C1-01 (Acceleration Time 1).
• Check the input data (particularly the number of PG pulses and the number of motor poles).
• Perform not rotating auto tuning
• Check the motor wiring.
• If the motor is connected to the machine, disconnect it.
• If the setting of T1-03 is higher than the Inverter input power supply voltage (E1-01), change the input data.
• Check the motor wiring
• Check the motor input data
• Remove the ropes and repeat the tuning
• Check the encoder rotation direction and if necessary change F1-05.
• Check the encoder wiring (order, shield etc.)
• Check the encoder power supply.
Replace the encoder.
EN-27

Parameter Table

Note: Factory settings are in bold.
Param.
Num.
Name Description
Initialize Data
Language selection for Digital Opera-
A1-00
tor display (JVOP-160-OY only)
Parameter
A1-01
access level
Control method
A1-02
selection
A1-03 Initialize
0:English
1:Japanese 2:German 3:French 4:Italian 5:Spanish 6:Portuguese
0:Monitoring only (Monitoring drive
mode and setting A1-01 and A1-04.)
1:Used to select user parameters (Only
parameters set in A2-01 to A2-32 can be read and set.)
2:Advanced
(Parameters can be read and set in both, quick programming mode (Q) and advanced programming mode (A).)
0:V/f control
2: Open loop vector 3:Closed Loop Vector
6:Closed Loop Vector for PM motors
0: No initializing
1110:Initializes to user parameters 2220:.Initializes to the factory setting
Sequence/Reference Source
b1-01
b1-02
Reference source selection
RUN com­mand source selection
0:Digital Operator
1:Control circuit terminal (analog input) 3:Option Card
0:Digital Operator
1:Control circuit terminal (digital
multi function inputs)
3:Option Card
Acceleration/Deceleration Settings
Accel./Decel.
C1-

C2-

time 1 S-curve charac-
teristic
Refer to page 1-22
Set the S-curve times at speed changes to reduce the jerk. Refer to page 1-22
Slip Compensation
• Increase the value if slip compensation
C3-01
C3-02
Slip compensa­tion gain
Slip compensa­tion delay time
value is too low
• Decrease the value if slip is overcom­pensated
• Reduce the value if the slip compensa­tion responsiveness is low.
• When speed is not stable, increase the setting.
Automatic Speed Regulator (ASR)
ASR propor-
C5-01
tional (P) gain 1 ASR integral (I)
C5-02
time 1 ASR propor-
C5-03
tional (P) gain 2 ASR integral (I)
C5-04
time 2
C5-06 ASR delay time Sets the ASR output delay time.
ASR switching
C5-07
frequency
Set the proportional gain 1 and the inte­gral time 1 of the speed control loop (ASR) for the frequency C5-07.
Set the proportional gain 2 and the inte­gral time 2 of the speed control loop (ASR) for the minimum frequency. The setting is active only for acceleration.
Sets the frequency for switching between Proportion Gain 1, 2,3 and Integral Time 1, 2, 3.
Param.
Num.
C5-09
C5-10
Name Description
ASR propor­tional (P) gain 3
ASR integral (I) time 3
Set the proportional gain 3 and the inte­gral time 3 of the speed control loop (ASR) for the minimum frequency. The settings is active for deceleration only.
Carrier Frequency Setup
C6-02
C6-11
Carrier fre­quency selec­tion 1
Carrier fre­quency selec­tion 2
Selects the carrier frequency for Induc­tion motor control modes.
Selects the carrier frequency for PM motor control modes
Speed Settings
d1-01
Multi speed ref.
to
1 to 8
d1-08 d1-09 Nominal speed d1-10 Interm. speed 1 d1-11 Interm. speed 2 d1-12 Interm. speed 3 d1-13 Relevel. speed d1-14 Inspect. speed d1-17 Leveling Speed
Speed priority
d1-18
selection
Refer to page 19, Speed Selection
Sequence Using Digital Inputs
0:Use Multi-Speed ref. (d1-01 to d1-08) 1:High Speed reference has priority. 2:Leveling speed reference has priority. 3:Use multi-speed reference
With no speed selected, the up/ down signal is switched off
Refer to page 1-19
V/f Pattern Settings
E1-01
E1-04
E1-05
E1-06
E1-08
E1-10
E1-13
Input voltage setting
Max. output frequency (FMAX)
Max. output voltage (VMAX)
Base frequency (FA)
Mid. output fre­quency voltage (VB)
Min. output fre­quency voltage (VMIN)
Base voltage (VBASE)
This setting is used as a reference value for protection functions.
Output Voltage (V)
To set V/f characteristics in a straight line, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. Always ensure that the four frequencies are set in the following manner: E1-04 (FMAX) E1-06 (FA) > E1-07 (FB) E1-09 (FMIN)
Frequency (Hz)
EN-28
Loading...
+ 195 hidden pages