Compact General Purpose Inverter
Model: CIMR-J7AZ
200V Class 3-phase 0.1 to 4.0kW
200V Class Single-phase 0.1 to 1.5kW
400V Class 3-phase 0.37 to 4.0kW
QUICK MANUAL
Manual No.
I39E-EN-01
EnglishDeutschEspañolFrançaisItalianoPortuguês
Pyccкий
General Precautions
z Some drawings in this manual are shown with protective covers or shields removed in
order to show detail with more clarity. Make sure all covers and shields are replaced
before operating the product.
z This manual may be modified when necessary because of improvements to the product,
modifications, or changes in specifications.
z To order a copy of this manual, or if your copy has been damaged or lost , contact your
OMRON YASKAWA Motion Control B. V. (Hereinafter called the OYMC) representatives.
z OYMC is not responsible for any modification of the product made by the user, since that
will void the guarantee.
Safety Information
The following conventions are used to indicate precautions in this document. Failure to heed precautions provided in this document can result in serious or possibly even fatal injury or damage to the
products or to related equipment and systems.
WARNING
CAUTION
Failure to heed a precaution classified as a caution can result in serious consequences depending on
the situation.
Indicates precautions that, if not heeded,
could possibly result in loss of life or serious injury.
Indicates precautions that, if not heeded,
could result in relatively serious or minor injury,
damage to the product, or faulty operation.
Precautions for UL/cUL Marking
· Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
· The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent
electric shock, disconnect all power before servicing the Inverter, and then wait at least one minute
after the power supply is disconnected. Confirm that all indicators are OFF before proceeding.
· Do not perform a withstand voltage test on any part of the Inverter. The Inverter is an electronic
device that uses semiconductors, and is thus vulnerable to high voltage.
· Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF.
Never touch the printed circuit board (PCB) while the power supply is turned ON.
· This Inverter is not suitable for use on a circuit capable of delivering more than 18,000RMS
symmetrical amperes, 250 volts maximum (200V class Inverters) or 480 volts maximum (400 V class
Inverters).
CAUTION
Use 75 °C copper wires or equivalent.
Low voltage wires shall be wired with Class I Wiring.
Precautions for CE Markings
· Only basic insulation to meet the requirements of protection class I and overvoltage category II is
provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to CE requirements.
· For 400 V class Inverters, make sure to ground the supply neutral to conform to CE requirements.
· For conformance to EMC directives, refer to section 3 in this document.
For details, refer to the following document.
Document No. EZZ008390 for English version.
· Our products are tested by authorized bodies using the standards listed below.
Product standard: EN61800-3 : 1996
EN61800-3 ; A11 : 2000
Receiving
CAUTION
Do not install or operate any Inverter that is damaged or has missing parts.
Failure to observe this caution may result in injury or equipment damage.
· Verify that the part numbers match your purchase order or packing slip.
· Check the unit for physical damage that may have occurred during shipping.
Warning Display
Japanese/French Warning Display
An English warning display is on the front panel of the inverter.
If you need Japanese or French warning display, use the stickers at the back of this manual.
Place it over the English warning display.
Checking the Name Plate
Example of 3-phase, 200VAC, 0.1kW (0.13HP)
Mounting
CAUTION
· Lift the cabinet by the heatsink. When moving the Inverter,
never lift it by the plastic case or the terminal covers.
Otherwise, the main unit may fall and be damaged.
· Mount the Inverter on nonflammable material (i.e., metal).
Failure to observe this caution may result in a fire.
· When mounting Inverters in an enclosure, install a fan or other cooling
device to keep the intake air temperature below 122°F (50°C)
for IP20 (open chassis type), or below 105°F(40°C) for NEMA1 (TYPE1).
Overheating may cause a fire or damage the Inverter.
· The VS mini generates heat. For effective cooling, mount it vertically.
Refer to the figure in Mounting Dimensions on section 3.
Wiring
WARNING
· Only begin wiring after verifying that the power supply is turned OFF.
Failure to observe this warning may result in an electric shock or a fire.
· Wiring should be performed only by qualified personnel.
Failure to observe this warning may result in an electric shock or a fire.
· When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning may result in injury.
· Always ground the ground terminal according to the local grounding code.
Failure to observe this warning may result in an electric shock or a fire.
· For 400V class, make sure to ground the supply neutral.
Failure to observe this warning may result in an electric shock or a fire.
· If the power supply is turned ON during the FWD(or REV) RUN command is given,
the motor will start automatically.
Turn the power supply ON after verifying that the RUN signal is OFF.
Failure to observe this warning may result in injury.
· When the 3-wire sequence is set, do not make the wiring unless the multi-function input
terminal parameter is set.
Failure to observe this warning may result in injury.
CAUTION
· Verify that the Inverter rated voltage coincides with the AC power supply voltage.
Failure to observe this caution may result in personal injury or a fire.
· Do not perform a withstand voltage test on the Inverter.
Performing withstand voltage tests may damage semiconductor elements.
· To connect a Braking Resistor, Braking Resistor Unit, or Braking Unit, follow the
Procedure described in this manual.
Improper connection may cause a fire.
· Always tighten terminal screws of the main circuit and the control circuits.
Failure to observe this caution may result in a malfunction, damage or a fire.
· Never connect the AC main circuit power supply to output ter minals U/T1, V/T2 or W/T3.
The Inverter will be damaged and the guarantee will be voided.
· Do not connect or disconnect wires or connectors while power is applied to the circuits.
Failure to observe this caution may result in injury.
· Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
Preautions for wiring
Wiring the control circuit terminalsScrewdriver blade width
Insert the wire into the lower part of the terminal block
and connect it tightly with a screwdriver.
Wire sheath strip length must be 5.5mm (0.22in).
Operation
WARNING
· Only turn ON the input power supply after confirming the Digital Operator
or blank cover(optional) are in place. Do not remove the Digital Operator or
the covers while current is flowing.
Failure to observe this warning may result in an electric shock.
· Never operate the Digital Operator or DIP the switches with wet hands.
Failure to observe this warning may result in an electric shock.
· Never touch the terminals while current is flowing, even if the Inverter is stopping.
Failure to observe this warning may result in an electric shock.
· When the fault retry function is selected, stand clear of the Inverter or the load.
The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the Inverter should restart.)
Failure to observe this warning may result in injury.
· When continuous operation after power recovery is selected, stand clear of the
Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the Inverter should restart.)
Failure to observe this warning may result in injury.
· The Digital Operator stop button can be disabled by a setting in the Inverter.
Install a separate emergency stop switch.
Failure to observe this warning may result in injury.
WARNING
· If an alarm is reset with the operation signal ON, the Inverter will restart automatically.
Reset an alarm only after verifying that the operation signal is OFF.
Failure to observe this warning may result in injury.
· When the 3-wire sequence is set, do not make the wiring unless the multi-function input
terminal parameter is set.
Failure to observe this warning may result in injury.
CAUTION
· Never touch the heatsinks, which can be extremely hot.
Failure to observe this caution may result in harmful burns to the body.
· It is easy to change operation speed from low to high. Verify the safe working
range of the motor and machine before operation.
Failure to observe this caution may result in injury and machine damage.
· Install a holding brake separately if necessary.
Failure to observe this caution may result in injury.
· If using an Inverter with an elevator, take safety measures on the elevator
to prevent the elevator from dropping.
Failure to observe this caution may result in injury.
· Do not perform signal checks during operation.
The machine or the Inver ter may be damaged.
· All the constants set in the Inverter have been preset at the factory.
Do not change the settings unnecessarily.
The Inverter may be damaged.
Maintenance and Inspection
WARNING
· Never touch high-voltage terminals on the Inverter.
Failure to observe this warning may result in an electrical shock.
· Disconnect all power before performing maintenance or inspection, and then wait at
least one minute after the power supply is disconnected. Confirm that all indicators are
OFF before proceeding.
If the indicators are not OFF, the capacitors are still charged and can be dangerous.
· Do not perform withstand voltage test on any part of the VS mini.
The Inverter is an electronic device that uses semiconductors, and is thus vulnerable to
high voltage.
· Only authorized personnel should be permitted to perform maintenance, inspections, or
parts replacement.
(Remove all metal objects (watches, bracelets, etc.) before starting work.)
Failure to observe these warnings may result in an electric shock.
CAUTION
· The control PCB board employs CMOS ICs. Do not touch the CMOS elements.
They are easily damaged by static electricity.
· Do not connect or disconnect wires, connectors, or the cooling fan while
power is applied to the circuit.
Failure to observe this caution may result in injury.
Periodical Inspection
Periodically inspect the inverter as described the following table to prevent accidents and to ensure
high performance with high-reliability.
Location to checkCheck forSolution
Terminals, unit mounting screws,
etc.
HeatsinkBuilt up durst, and debris
Printed circuit board
Power elements and
smoothing capacitor
Cooling fan
Connection hardware is proper ly
seated and securely tightened.
Accumulation of conductive
material or oil mist
Abnormal odor or discoloration Replace the inverter unit.
Abnormal noise or vibration
Cumulative operation time
Properly seat and tighten
hardware.
Blow with dry compressed air:
4
to 58.8 x 104 Pa,
39.2 x 10
57 to 85 psi (4 to 6kg / cm
pressure.
Blow with dry compressed air:
39.2 x 104 to 58.8 x 104 Pa,
57 to 85 psi (4 to 6kg / cm
pressure
If dust or oil cannot be removed,
replace the inverter unit.
Replace the cooling fan.
2
)
2
)
Part Replacement
Inverter’s maintenance periods are noted below. Keep them as reference.
Part Replacement Guidelines
PartStandard Replacement PeriodReplacement Method
Cooling fan2 to 3 yearsReplace with new part.
Smoothing capacitor5 years
Breaker relays–Determine need by inspection.
Replace with new part.
(Determine need by inspection.)
Fuses10 yearsReplace with new part.
Aluminium capacitors on PCBs 5 years
Note: Usage conditions are as follows:
· Ambient temperature: Yearly average of 30°C
· Load factor: 80% max.
· Operating rate: 12 hours max. per day
Replace with new part.
(Determine need by inspection.)
Others
WARNING
· Never modify the product.
Failure to observe this warning can result in an electric shock or injury
and will invalidate the guarantee.
CAUTION
· Do not subject the Inverter to halogen gases, such as fluorine, chlorine, bromine,
and iodine, at any time even during transportation or installation.
Otherwise, the Inverter can be damaged or interior parts burnt.
VS MINI J7
Quick Start Guide
1. Wiring
2. Control Circuit Terminals
3. Installation
4. Start up and Trial run
5. Quick Parameter List
6. Monitors
7. Faults and Alarms
ENGLISH
1. Wiring
3G3JV PFI @
Noise Filter
L1i
L1
L2
L3
3-phase 200 V AC
single-phase 200 V AC
(see note 1)
Note 1: Connect single-phase 200 V AC to terminals R/L1 and S/L2 of the J7AZB
Note 2: The braking resistor cannot be connected because no braking transistor is incorporated.
Ground terminal
Main circuit
output terminals
supply 20mA at +12V
Frequency reference input
Frequency reference common
R/L1
L2i
S/L2
L3i
T/L3
S1
S2
S3
S4
S5
SC
FS
FR
FC
Main circuit input
terminals
Control circuit
terminals
Ground
terminal
SHORT BAR
+1+2-
U/T1
V/T2
W/T3
Multi-function contact output
MA
NO
MB
NC
MC
Common
AM
Analog monitor output
AC
Analogue monitor output
common
Arrangement of Control Circuit Terminals
M
2. Control Circuit Terminals
SymbolNameFunctionSignal Level
InputS1 Forward/StopForward at ON/Stops at OFFPhotocoupler 8 mA
S2 Multi-function Input 1Set by parameter n36 (Reverse/Stop)
S3 Multi-function Input 2Set by parameter n37 (External Fault: NO)
S4 Multi-function Input 3Set by parameter n38 (Fault Reset)
S5 Multi-function Input 4Set by parameter n39
SC Sequence Input CommonCommon for S1 through S5
FS Frequency Reference Power Supply DC power supply for frequency reference use 20 mA at 12 V DC
FR Frequency Reference InputInput terminal for frequency reference use0 to 10 V DC (20 kΩ)
FC Frequency Reference CommonCommon for frequency reference use4 to 20 mA
Output MA MBMulti-function output: NO
*1 NPN is the setting for these terminals. No external power supply is required. Refer to connections shown below
*2 Functions in parentheses are default settings.
Multi-function output: NC
MC Multi-function output CommonCom mon for MA an d MB use
AM Analogue Monitor outputSet by parameter n44 (Output frequency)
AC Analogue Monitor output Common Common for AM use
(Multi-step reference 1)
Set by parameter n40 (during running)
*2
*2
*2
*2
*2
*2
*1
at 24 V DC
0 to 20 mA
Relay output 1 A
max. at 30 V DC and
250 V AC
12 mA max. at 0 to
10 V DC
Selecting Input Method
Switches SW7and SW8, both of
which are located above the control circuit terminals, are used for input method selection.
Remove the front cover and optional cover to use these switches.
PNP
NPN
SW7
SW7
V
OFF
Selecting Sequence Input Method
By using SW7, NPN or PNP input can be selected as shown below
Enter KeyEnters multi-function monitor numbers, parameter numl and
RUN KeyStarts the Inverter running when the 3G3JV is in operation
STP/RESET KeyStops the Inverter unless parameter nO6 is not set to
according to the sot parameteres is selectable while this
indicator is lit.
Note: The status of this indicator can be only monitored
while the Inverter is in operation. Any RUN command
input is ignored while this indicator is lit.
indicator is lit.
Note:
While the Inverter is in operation, the paramete can be
only monitored and only some parameti can be
changed. Any RUN command input is ignored while
this indicator is lit.
Parameter being set will be cancelled if this key is pressed
before entering the setting.
num-bers and parameter set values.
numbers and parameter sel values.
internal data values after they are set or changed.
with the Digital Operator.
disable the STOP Key.
The following seven steps describe the recommended minimum operations
to allow the J7 to control a connected motor in typical configuration, to allow
simple operation in the quickest time:
Step 1 – initial checks
1-1 Checkpoints before connecting the power supply.
Check that the power supply is as of the correct voltage.
CIMR-J7AZ2@@@: Three phase 200 to 230VAC
CIMR-J7AZB@@@: Single phase 200 to 240VAC (Wire R/L1 and S/L2)
CIMR-J7AZ4@@@: Three phase 380 to 460VAC
1-2 Make sure that the motor output terminals (U/T1, V/T2, W/T3) are connected to the motor.
1-3 Ensure that the control circuit terminals and the control device are wired correctly.
1-4 Make sure that all control terminals are turned off.
1-5 Set the motor to no-load status (i.e. not connected to the mechanical system)
Step 2 – Connecting the power supply and check the display status
2-1 After conducting the checks in step-1, connect the power supply.
2-2 If the display is normal when the power is connected it will read as follows;
RUN indicator: flashes
ALARM indicator: off
Setting/monitor indicators: FREF, FOUT or IOUT is lit.
Data display: displays the corresponding data for the indicator that is lit.
When fault has occurred, the details of the fault will be displayed. In that case, refer to user’s
manual and take necessary action.
Step 3 – Initializing parameters
To initialize the drive parameters to factory defaults, set parameter n01 = 8. This will set the J7 to
accept start/stop commands in what in termed “2-wire control”, i.e. 1 wire for a motor forward/stop
command, and 1 wire for a motor reverse/stop command.
Key
Sequence
In approximately
1s.
Indicator
Display
Explanation
example
Power On
Press the Mode Key repeatedly until the PRGM indicator is lit.
Press the Enter Key. The data of n01 will be displayed.
Use the Increment or Decrement Key to set n01 to 8. The display will
flash.
Press the Enter Key so that the set value will be entered and the data
display will be lit.
The parameter number will be displayed.
Step 4 – Set the motor rated current
This parameter is used for the electronic thermal function for motor overload detection (OL1). By correctly setting this, the J7 will protect an overloaded motor from burning out.
Read the rated current (in amps) on the motor nameplate, and enter this into parameter n32. The
example to the below shows entering a value of 1.8Amps.
Key
Sequence
Indicator
Display
Explanation
example
Displays the parameter number
Use the Increment or Decrement Key until n32 is displayed.
Press the Enter Key. The data of n32 will be displayed.
Use the Increment or Decrement Key to set the rated motor current. The
display will flash.
Press the Enter Key so that the set value will be entered and the data
display will be lit.
In approximately1s.The parameter number will be displayed.
Step 5 – Set the motor rated frequency
This is the maximum frequency the motor can run and allows the J7 to properly control the motor.
Read the rated frequency (in Hz) on the motor nameplate, and enter this into parameters n09 and n11
Step 6 – Set the operation command
This is the method for motor run and stop commands (i.e. how the inverter will start and stop the
motor). The two basic operations are for the RUN and STOP/RESET keys on the Digital Operator, or
for one of multi-function inputs through the control circuit terminals.
To set the operation command, enter the appropriate value into parameter n02:
0 = RUN and STOP/RESET keys on the Digital Operator are enabled.
1 = Multi-function inputs through the control circuit terminals.
The diagram to the below shows how to connect a switch to start/stop the motor in the forward direction in “2-wire control”. Set parameter n02=1. To enable a separate switch for reverse rotation on control terminal S2, set parameter n36=2 (this is actually the factory default setting for n36).
FWD RUN/STOP
REV RUN/STOP
Step 7 – Set the frequency reference
This is the method for selecting the source for the motor speed command. The factory default is for the
potentiometer on the digital Operator (FREF adjuster), in which case no setting is required.
Frequency reference can also come from an external potentiometer, an analog output from a PLC, or
up to 8 pre-programmed speeds held in the inverter and selected via the multi-function inputs.
For example, to accept frequency reference from an external potentiometer, or a 0-10V analog out
from a PLC, set parameter n03=2.
FS
( )
FREQUENCY
SETTING
MASTER SPEED
FREQUENCY
REFERENCE
(0 TO +10V)
POWER
+12V, 20mA
FR
FC(0V)
.
5. Quick Parameter List
Parameter No. DescriptionRangeDefault
n01Parameter access:
n02Run command selection:
n03Frequency reference selection:
n09Maximum output frequency50 to 400Hz
n10Maximum output voltage1 to 255V (200V class)
N11Maximum voltage output frequency50 to 400Hz
n16Acceleration time 10.0 to 999sec10sec
n17Deceleration time 20.0 to 999sec10sec
n21Frequency reference 10.0 to 400Hz50Hz
n22 - n28Frequency reference 2 - 80.0 to 400Hz0Hz
n32Motor rated currentDepending on model0 to 120% of inverter rated
n36 - n39Multi-function input (S2 -S5)0 to 35-n40Multi-function output (MA-MB-MC)0 to 181
n44Multi-function analog output (AM-AC):
n46Carrier frequency1 to 4 (2.5 - 10kHz)
n52DC injection braking current0 to 100%50%
n53DC injection braking at stop0 to 100%50%
n54DC injection braking at start0 to 100%50%
n55Stall prevention during deceleration:
Multi-function InputsMulti-function Outputs
Val ue*1FunctionVal ue*1Function
0: Digital operator
1: Control circuit terminal
2: Communication (option)
0: Digital operator (potentiometer)
1: Frequency reference 1 (n21)
2: Control circuit terminal (0 to 10V)
3: Control circuit terminal (4 to 20mA)
4: Control circuit terminal (0 to 20mA)
6: Communication (option)
0: Output frequency (10V/Max, freq.)
1: Output current (10V/Inverter rated current)
8Multi-step speed reference 315Undervoltage in progress
10Inching Command
12External base block (NO)
13External Base block (NC)0Otput frequency
17Local/Remote selection1Output current
*1 Refer to user’s manual for full set value
Analogue Output Functionsts
Val ue*1Function
Example of Parameter Settings
Cancels
Set Data
Key
Sequence
In approximately
1s.
Note 1: To cancel the set value, press the Mode Key instead, The parameter number will be
displayed.
2: There are parameters that cannot be changed while the Inverter is in operation. Refer to the
list of parameters. When attempting to change such parameters, the data display will not
change by pressing the Increment or Decrement Key.
In approximately 1s.
IndicatorDisplay example Explanation
Power On
Press the Mode Key repeatedly until the PRGM indicator
is lit.
Use the Increment or Decrement Key to set the parameter
number.
Press the Enter Key. The data of the selected parameter
number will be displayed.
Use the Increment or Decrement Key to set the data.
At that time, the display will flash.
Press the Enter Key so that the set value will be entered and the
data display will be lit (see note 1)
The parameter number will be displayed.
6. Monitors
The Vs mini J7 allows you to monitor various conditions, such as output current and status of multifunction inputs.
This monitoring is performed via the “U” parameters.
Key SecuenceIndicatorDisplay example Explanation
Constant No.NameDescription
U01Frequency Reference
U02Output frequency
U03Output Current
U04Output VoltageV Output voltage can be monitored
U05DC VoltageV Main circuit DC voltage can be monitored
U06Input Terminal Status-- Input terminal status of control circuit terminals can be monitored
U07Output Terminal Status-- Output terminal status of control circuit terminals can be monitored
U09Fault History-- Last four fault history is displayed
U10Software No.-- Software No. can be checked
U15Data Reception Error-- Contents of MEMOBUS communication data reception error can be
(FREF)
(FOUT)
(IOUT)
Power On
Press the Mode Key repeatedly until the MNTR indicator
is lit. U01 will be displayed.
Use the Increment or Decrement Key to select the monitor
item to be displayed..
Press the Enter Key so that the data of the selected
monitor item will be displayed.
The monitor number display will appear again by
pressing the mode key.
Hz Frequency reference can be moitored. (Same as FREF)
Hz Output frequency can be monitored. (Same as FOUT)
A Output current can be monitored. (Same as IOUT)
checked. (contents of transmission register No. 003DH are the same)
Input/Output terminal status
Input Terminal Status
1: Terminal S1 is “closed”
1: Terminal S2 is “closed”
1: Terminal S3 is “closed”
1: Terminal S4 is “closed”
1: Terminal S5 is “closed”
Output Terminal Status
Not Used
1: Terminal MA-MC is “closed”
Not Used
7. Faults and Alarms
Fault Display Fault name and meaningPossible cause and remedy
OCOvercurrent
OVO ver volta ge
uV1Main circuit undervoltage
OHUnit overheated
OL1Motor overload
EF
SER
(flashing)
bb
(flashing)
EF
(flashing)
*1 Refer to user’s manual for full fault code listings
Output current is higher than 250% of
inverter rated current.
DC bus voltage has exceeded
detection level.
DC bus voltage is below detection
level.
Temperature inside the inverter has
exceeded 110°C.
The inverter is protecting the motor
from overload based on an internal IT
calculation using n036 setting.
*1
External fault
An external fault has been input.
Sequence error
Sequence input when inverter
running.
External baseblock
An external baseblock command has
been input.
Sequence error has occuredForward and reverse run signal have been applied simultaneously.
Check output for short circuit or ground fault.
The Load is too large, reduce it ore use larger Inverter.
Check motor FLA rating compared to inverter and V/F setting.
Load inertia is too large and the motor is regenerating.
Increase deceleration time (n020 or n022).
Connect an external braking resistor and set n092 to 1.
Check braking resistor and wiring.
Check mains power supply voltage and connections.
Check correct supply for Inverter being used.
Monitor for mains dips or interruptions.
Refer to manual for installation guidelines and recommendations.
Check cooling fan (if fitted).
Check V/F characteristic ore reduce Carrier frequency.
Check and reduce the load.
Check V/F characteristic (V
Increase the running speed of the motor.
Increase acceleration/decelleration times.
Check your control terminal wiring.
A multi-functional digital input has been set to 3 or 4.
Run signal must be removed before this can be reset.
Inverter must be stopped when Local/Remote switching attempted.
Inverter must be stopped when Comms/Remote switching
attempted
Check your control terminal wiring.
A multi-functional digital input has been set to 12 or 13.
and F
).
max
max
VS MINI J7
Kurzanleitung
1. Anschlussplan
2. Steuerklemmen
3. Installation
4. Inbetriebnahme und Testlauf
5. Parameterübersicht
6. Überwachungsanzeige
7. Fehler und Alarme
DEUTSCH
1. Anschlussplan
3G3JV PFI @
Entstörfilter
L1
L2
L3
200 V AC (Drehstrom
oder Wechselstrom,
siehe Hinweis 1)
Externer
Frequenzeinsteller
(Potentiometer)
(2 kΩ min. 1/4 W)
Hinweis 1: 200 V Wechselspannung: Anschluss an die Klemmen R/L1 und S/L2.
Hinweis 2: Der Frequenzumrichter verfügt über keinen Bremstransistor, daher kann kein Bremswiderstand