Omega Products FSW-338 User Manual

K
K-38
The LVCN-300 Series is designed from an operator’s point of view, making any process and alarm points visible on the multi-colored display graph. They get everything they need at a glance! The LVCN-300 Series provides reliability with very flexible design options and a friendly face to tell you exactly what is going on inside your tank no matter where it is located. Everyone can easily see it from a distance or while walking the plant floor. It’s this simple to understand—if the green vertical bar (level) is between the orange and yellow line everything’s just fine. If it’s above or below the red marks, something is wrong. That is all there is to it. The LVCN-300 Series accepts all types of 4 to 20 mA sensors, such as pressure, ultrasonic, float type liquid level transmitters and capacitive transmitters. The sensor input is isolated and loop powered up to 24 Vdc, allowing data gathering devices to easily interface. Two models are available, the LVCN-301 or LVCN-302. The LVCN-301 is for Make Up applications and the LVCN­302 is for sump applications. A typical Make Up application is when the liquid in a tank is “lost” because it is being used in a manufacturing process or lost by evaporation and has to periodically be refilled or “made up”. To accomplish a Make Up operation the LVCN-301 controller uses a differential relay that is activated by a FALLING level in the tank. The same relay is going to turn the pump or valve ON and OFF. First you need to program the Make Up ON level where you want to begin refilling the tank with liquid.
When the level FALLS or DECREASES to this point, the controller will CLOSE or activate the relay and turn ON a pump or valve and begin refilling the tank. The LVCN-301 controller has internally “latched” the relay closed and will continue holding it closed until the Make Up OFF level that was programmed is reached and the tank stops filling. A typical Sump application is when the liquid in a tank is being collected and has to periodically be transferred or pumped out to prevent an overflow. A basement with a sump pump is doing the same type of operation. To accomplish this Sump Operation the LVCN-302 controller uses a differential relay that is activated by a RISING level in the tank. The same relay is going to turn the pump or valve ON and OFF. First you need to program the SUMP ON level where you want to begin draining the liquid in the tank. When the level RISES or INCREASES to this level the controller will CLOSE or activate the relay and turn on a pump or valve and begin draining the tank. The LVCN-302 controller has internally “latched” the relay closed and will continue holding it closed until the Sump OFF level you programmed is reached and the tank stops draining.
SPECIFICATIONS
Sensor Input: Isolated input accepts any
type of 4 to 20 mA process signal. Loop power available up to 24 Vdc @ 500µA for 2 wire device Input Power: 120 Vac/500mA; 24 Vdc or 24 Vac unregulated (optional) 750 mA
Security Levels:
3 levels of access protect data changes with DIP switch on back Control Circuits: Four Form C relays,
10.0 amp 125 Vac (noninductive)
Switching Mode: Selectable, NO or NC states
Output & Input Connections:
Terminal Connections are quick disconnect Phoenix type Programmed Memory: EEPROM-Loss of power will not affect existing programmed data Mounting Format: Flush mounted anodized steel enclosure with eight (8) 10/32 studs and sealing gasket; NEMA 4 (IP66) graphic front panel; steel back pan housing. Optional fiberglass enclosure is also rated NEMA 4 (IP66).
Overall Dimensions:
425 L x 250 W x 57 mm D (16.75 x 10.25 x 2.25") Weight: 4.5 kg (10 lb)
To Order
(Specify Model Number)
Model No. Price Description
LVCN-301 $2190 Make-up model LVCN-301-NEMA4 3034 LVCN-301 in NEMA 4 fiberglass enclosure 16 x 20 x 8" LVCN-302 2190 Sump model LVCN-302-NEMA4 3034 LVCN-302 in NEMA 4 fiberglass enclosure 16 x 20 x 8" LVR31 610 Float transmitter, 0.3 m (1') length PX439-005GI 579 Submersible pressure transmitter FSW-338 84 Reference Book: Advanced Resevoir Engineering
Comes with complete operator’s manual. For 24 Vdc power, add “-24VDC” to model number. For 24 Vac power, add “-24VAC” to model number. No additional charge. Ordering Example: LVCN-301, make up model, PX439-005GI, submersible pressure sensor, $2190 + 579 = $2769. LVCN-302-NEMA4, sump model with NEMA 4 (IP66) enclosure, $3034
LVCN-301
$
2190
PROCESS LEVEL CONTROLLER WITH MULTICOLORED BAR GRAPH
NEMA 4 (IP66) and
Optional NEMA 4 (IP66) Fiberglass Enclosure
Multi-Color Bar Graph
Process for Zooming in on Critical Range
Large Numeric Display4 to 20 mA Process InputEasy Front
Panel Programming
MOST POPULAR MODELS HIGHLIGHTED!
LVCN-301, $2190, shown with PX439-005GI, submersible pressure transmitter (sold separately), $579, shown smaller than actual size. For more information visit omega.com and search PX439.
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com
EPG05
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec)
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL 0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement Instruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level Measurement, Magnetic Flowmeters, Mass Flowmeters, Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen Instrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data Loggers Plug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, Pressure Reference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators, Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and Switching Devices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page