Section 1 - Introduction
The FMA900A series measures air velocities up to 12,000 FPM (60.9 m/sec). It
provides either a 0 to 5 Vdc or 4/20 mA analog output corresponding to the air
flow range and one SPST relay contact closure corresponding to high alarm set
point. The alarm set point is adjustable from 0 to 100% of the air flow range. This
unit can be used in HVAC applications, R&D labs, exhaust/ ventilation hoods
and other manufacturing processes.
The sensor is designed based on RTD elements. The air velocity is measured by
the heat loss from the RTD sensor as it cools down by the air flow. The sensor is
housed in a 1/4" OD x 12" long 304 Stainless Steel tube with inch marks for ease
of insertion depths. The sensor probe comes in three configurations:
• Fixed mount probe
• 12" long remote probe connected via 15 feet of shielded cable
• 3.75" Short Probe
The following table shows all the models of this product.
Model No. Range FPM (m/sec) Description
FMA901A-*-** 0 to 500 (0 to 2.54) Air velocity transmitter, relay output, fixed probe
FMA901R-*-** 0 to 500 (0 to 2.54) Air velocity transmitter, relay output, remote probe
FMA902A-*-** 0 to 1000 (0 to 5.08) Air velocity transmitter, relay output, fixed probe
FMA902R-*-** 0 to 1000 (0 to 5.08) Air velocity transmitter, relay output, remote probe
FMA903A-*-** 0 to 2000 (0 to 10.16) Air velocity transmitter, relay output, fixed probe
FMA903R-*-** 0 to 2000 (0 to 10.16) Air velocity transmitter, relay output, remote probe
FMA904A-*-** 0 to 5000 (0 to 25.4) Air velocity transmitter, relay output, fixed probe
FMA904R-*-** 0 to 5000 (0 to 25.4) Air velocity transmitter, relay output, remote probe
FMA905A-*-** 0 to 10,000 (0 to 50.8) Air velocity transmitter, relay output, fixed probe
FMA905R-*-** 0 to 10,000 (0 to 50.8) Air velocity transmitter, relay output, remote probe
FMA906A-*-** 0 to 12,000 (0 to 60.9) Air velocity transmitter, relay output, fixed probe
FMA906R-*-** 0 to 12,000 (0 to 60.9) Air velocity transmitter, relay output, remote probe
Where,
*- Specify output type, add suffix “V1” for 0 to 5 Vdc, “MA” for 4 to 20 mA
**- Add suffix “S” for 95mm (3.75”) short probe
1-1
Introduction