ALL-IN-ONE
90
(3.5)
100
(3.9)
110
(4.3)
120
(4.7)
130
(5.1)
8
(0.3)
85
(3.3)
Four, 4.5 (0.2) dia.
Weight:
610 g
(22 oz)
max
90
(3.5)
100
(3.9)
110
(4.3)
76
(3.0)
86
(3.4)
8
(0.3)
85
(3.3)
Four, 4.5 (0.2) dia.
Weight:
380 g
(13 oz)
max
CPU units with 14 or 20 I/O points
CPU units with 30 I/O points
PROGRAMMABLE LOGIC
CONTROLLERS (PLCs)
CP1L
Starts at
$
398
l Up to 18 Digital Inputs,
12 Relay Outputs
l Expandable to 150 I/O with
Expansion Modules
l Powerful Instruction Set
l 10K Program Steps
(32K Words Data Memory)
l Remote I/O Modules for Analog
I/O, Digital I/O, Thermocouples
and RTDs
CP1L-L20DR-A,
$475, shown smaller
than actual size.
The CP1L Series is an economical all-in-one
package-type PLC. A wide variety of built-in
functions expand application capabilities and
shorten the design time required for the
growing number and increasing complexity
of ladder programs.
With high-speed instruction processing
(550 nS for basic instructions), up to
150 I/O points including advanced
temperature and analog expansion
modules, and PID instructions with
on-demand auto-tuning, the CP1L Series
is ideal for continuous process control
applications at an affordable cost.
Equipped with a USB interface as standard
for programming and monitoring, the new
CPUs allow up to two serial ports to be
plugged in for communication with HMI or
field devices. And, of course, they provide
“Smart Platform” communication routing
over multiple network layers. Using CX-One,
programs can be created that enable the
user to build, configure and program
networks, PLCs, HMIs, motion-control
systems, drives, temperature controllers
and sensors.
The CP1L CPU Series has the same
architecture as the CS/CJ PLC Series, which
means programs are compatible for memory
allocations and instructions and support
Function Blocks and Structured Text in
addition to Ladder Logic.
A-1
Dimensions: mm (in)
CPU UNIT SPECIFICATIONS
ITEMS CP1L-XXXXX-A CP1L-XXXXX-D
POWER SUPPLY 100 to 240 Vac 50/60 Hz 24 Vdc
OPERATING VOLTAGE RANGE 85 to 264 Vac 21.6 to 26.4 Vdc
POWER CONSUMPTION 50 VA max 20 W max
INRUSH CURRENT 100 to 120 Vac inputs: 20 A max 8 ms max 30 A max 20 ms max
EXTERNAL POWER SUPPLY None 300 mA at 24 Vdc
INSULATION RESISTANCE 20 MΩ min (at 500 Vdc) between the 20 MΩ min (at 500 Vdc) between the
DIELECTRIC STRENGTH 2300 Vac at 50/60 Hz for 1 min between 1000 Vac at 50/60 Hz for 1 min between
NOISY IMMUNITY Conforming to IEC 61000-4-4. 2 kV (power supply line)
VIBRATION RESISTANCE Conforms to JIS C0040. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz,
SHOCK RESISTANCE Conforms to JIS C0041. 147 m/s
AMBIENT OPERATING 0 to 55°C (32 to 131ºF)
TEMPERATURE
AMBIENT HUMIDITY 10 to 90% (with no condensation)
AMBIENT OPERATING No corrosive gas
ENVIRONMENT
AMBIENT STORAGE -20 to 75°C (-4 to 167ºF) (excluding battery)
TEMPERATURE
POWER HOLDING TIME 10 ms min 2 ms min
DIMENSIONS 150 W x 90 H x 85 mm D (5.90 x 3.54 x 3.35")
WEIGHT 610 g (22 oz) max 610 g (22 oz) max
AC POWER SUPPLY MODELS: DC POWER SUPPLY MODELS:
200 to 240 Vac inputs: 40 A max 8 ms max
external AC terminals and GR terminals external DC terminals and GR terminals
the external AC and GR terminals, leakage the external DC and GR terminals,
current: 5 mA max leakage current: 5 mA max
2
acceleration: 9.8 m/s
in X, Y, and Z directions for 80 minutes each
(sweep time: 8 minutes x 10 sweeps = total time 80 minutes)
2
, three times each in X, Y, and Z directions
MODEL NO. CP1L-M60 CP1L-M40 CP1L-M30 CP1L-L20 CP1L-L14 CP1L-L10
POINTS 60 40 30 20 14 10
CONTROL METHOD Stored program method
I/O CONTROL METHOD Cyclic scan with immediate refreshing
PROGRAM LANGUAGE Ladder diagram
FUNCTION BLOCKS Maximum number of function block definitions: 128; maximum number of instances: 256;
languages usable in function block definitions: ladder diagrams, structured text (ST)
INSTRUCTION LENGTH 1 to 7 steps per instruction
INSTRUCTIONS Approx 500 (function codes: 3 digits)
INSTRUCTION Basic instructions: 0.55 µs min, special instructions: 4.1 µs min
EXECUTION TIME
COMMON 0.4 ms
PROCESSING TIME
PROGRAM CAPACITY 10K steps 5K steps
NUMBER OF TASKS 288 (32 cyclic tasks and 256 interrupt tasks)
SCHEDULED 1 (interrupt task No. 2, fixed)
INTERRUPT TASKS
INPUT INTERRUPT 6 (interrupt task No. 140 to 145, fixed) 4 (interrupt 2 (interrupt
TASKS task no. 140 task no.
to 143, fixed) 140 to
141, fixed)
Interrupt tasks can also be specified and executed for high-speed counter interrupts and executed
MAX SUBROUTINE NO. 256
MAX JUMP NO. 256
A-2