90
(3.5)
100
(3.9)
110
(4.3)
120
(4.7)
130
(5.1)
8
(0.3)
85
(3.3)
Four, 4.5 (0.2) dia.
Weight: 610 g (22 oz) max
90
(3.5)
100
(3.9)
110
(4.3)
76
(3.0)
86
(3.4)
8
(0.3)
85
(3.3)
Four, 4.5 (0.2) dia.
Weight: 380 g (13 oz) max
CPU units with 14 or 20 I/O points
CPU units with 30 I/O points
PROGRAMMABLE LOGIC CONTROLLERS (PLCs)
CP1L
Starts at
398
l Up to 18 Digital Inputs,
12 Relay Outputs
l Expandable to 150 I/O with
Expansion Modules
l Powerful Instruction Set l 10K Program Steps
(32K Words Data Memory)
l Remote I/O Modules for Analog
I/O, Digital I/O, Thermocouples and RTDs
CP1L-L20DR-A,
$475, shown smaller
than actual size.
The CP1L Series is an economical all-in-one package-type PLC. A wide variety of built-in functions expand application capabilities and shorten the design time required for the growing number and increasing complexity of ladder programs.
With high-speed instruction processing (550 nS for basic instructions), up to 150 I/O points including advanced temperature and analog expansion modules, and PID instructions with on-demand auto-tuning, the CP1L Series is ideal for continuous process control applications at an affordable cost.
Equipped with a USB interface as standard for programming and monitoring, the new CPUs allow up to two serial ports to be plugged in for communication with HMI or field devices. And, of course, they provide “Smart Platform” communication routing over multiple network layers. Using CX-One, programs can be created that enable the user to build, configure and program networks, PLCs, HMIs, motion-control systems, drives, temperature controllers and sensors.
The CP1L CPU Series has the same architecture as the CS/CJ PLC Series, which means programs are compatible for memory allocations and instructions and support Function Blocks and Structured Text in addition to Ladder Logic.
A-1
Dimensions: mm (in)
CPU UNIT SPECIFICATIONS
ITEMS CP1L-XXXXX-A CP1L-XXXXX-D POWER SUPPLY 100 to 240 Vac 50/60 Hz 24 Vdc OPERATING VOLTAGE RANGE 85 to 264 Vac 21.6 to 26.4 Vdc POWER CONSUMPTION 50 VA max 20 W max INRUSH CURRENT 100 to 120 Vac inputs: 20 A max 8 ms max 30 A max 20 ms max
EXTERNAL POWER SUPPLY None 300 mA at 24 Vdc INSULATION RESISTANCE 20 M min (at 500 Vdc) between the 20 M min (at 500 Vdc) between the
DIELECTRIC STRENGTH 2300 Vac at 50/60 Hz for 1 min between 1000 Vac at 50/60 Hz for 1 min between
NOISY IMMUNITY Conforming to IEC 61000-4-4. 2 kV (power supply line) VIBRATION RESISTANCE Conforms to JIS C0040. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz,
SHOCK RESISTANCE Conforms to JIS C0041. 147 m/s AMBIENT OPERATING 0 to 55°C (32 to 131ºF)
TEMPERATURE AMBIENT HUMIDITY 10 to 90% (with no condensation) AMBIENT OPERATING No corrosive gas
ENVIRONMENT AMBIENT STORAGE -20 to 75°C (-4 to 167ºF) (excluding battery)
TEMPERATURE POWER HOLDING TIME 10 ms min 2 ms min DIMENSIONS 150 W x 90 H x 85 mm D (5.90 x 3.54 x 3.35") WEIGHT 610 g (22 oz) max 610 g (22 oz) max
AC POWER SUPPLY MODELS: DC POWER SUPPLY MODELS:
200 to 240 Vac inputs: 40 A max 8 ms max
external AC terminals and GR terminals external DC terminals and GR terminals
the external AC and GR terminals, leakage the external DC and GR terminals, current: 5 mA max leakage current: 5 mA max
2
acceleration: 9.8 m/s
in X, Y, and Z directions for 80 minutes each
(sweep time: 8 minutes x 10 sweeps = total time 80 minutes)
2
, three times each in X, Y, and Z directions
MODEL NO. CP1L-M60 CP1L-M40 CP1L-M30 CP1L-L20 CP1L-L14 CP1L-L10 POINTS 60 40 30 20 14 10 CONTROL METHOD Stored program method I/O CONTROL METHOD Cyclic scan with immediate refreshing PROGRAM LANGUAGE Ladder diagram FUNCTION BLOCKS Maximum number of function block definitions: 128; maximum number of instances: 256;
languages usable in function block definitions: ladder diagrams, structured text (ST)
INSTRUCTION LENGTH 1 to 7 steps per instruction INSTRUCTIONS Approx 500 (function codes: 3 digits) INSTRUCTION Basic instructions: 0.55 µs min, special instructions: 4.1 µs min
EXECUTION TIME COMMON 0.4 ms
PROCESSING TIME PROGRAM CAPACITY 10K steps 5K steps NUMBER OF TASKS 288 (32 cyclic tasks and 256 interrupt tasks) SCHEDULED 1 (interrupt task No. 2, fixed)
INTERRUPT TASKS INPUT INTERRUPT 6 (interrupt task No. 140 to 145, fixed) 4 (interrupt 2 (interrupt
TASKS task no. 140 task no.
to 143, fixed) 140 to
141, fixed)
Interrupt tasks can also be specified and executed for high-speed counter interrupts and executed
MAX SUBROUTINE NO. 256 MAX JUMP NO. 256