Step 17. Enter Alarm 1 Enable/Disable Submenu
Press dto display flashing
DSBL/ ENBL
.
Step 18. Enable Alarm 1 Submenu
If flashing
ENBL
is displayed, press a, if
DSBL
is displayed,
press buntil
ENBL
is displayed, then press dto store and
go to the next menu item.
Step 19. Select the Deviation Control Type Submenu
Press d. If flashing
_DEV
Deviation is displayed press a,
otherwise press buntil flashing
_DEV
is shown. Now
press dto store and go to next menu item.
Step 20. Select the Latched Type Submenu
Press d. If flashing
UNLT
Unlatched is displayed press a,
otherwise press buntil
UNLT
is displayed.
Press dto store and advance to next menu item.
Step 21. Select the Normally Open Type of Contact
Closure Submenu
Press d. If flashing
N.o.
Normally Open is displayed,
press a, otherwise press buntil
N.o.
is displayed. Press
d
to store and advance to next menu item.
Step 22. Select the Above Type of Active Submenu
Press d. If flashing
ABoV
Above is displayed, press a,
otherwise press b until
ABoV
is displayed. Press d to store
and advance to next menu item.
Step 23. Enable Alarm 1 at Power On
(
A.P.oN
)
Press d. If flashing
ENBL
is displayed, press a, otherwise
press buntil
ENBL
is displayed. Press dto store and
advance to next menu item.
Step 24. Enter Alarm 1 High Submenu
Press atwice to skip
ALR.L
Alarm 1 Low value.
ALR.L
is
for below &
ALR.H
for above.
Step 25. Set the Alarm 1 High value
(
ALR.H
)
Press d. Press bor cuntil value to set the display to
002.0
. Press dto save.
Step 26. Enter the Alarm 2 Menu
The display will show
ALR2
the top menu for Alarm 2.
Repeat steps from 17 to 25 to set for Alarm 2 the same
conditions as for Alarm 1.
Step 27. Skip the Loop Break Time Menu
(
LOOP
)
Press ato go to the
OUT1
Output 1 Menu item.
Step 28. Configuration the Output 1 Menu
Set Alarm 1 Disabled (Step 18) to be able to Enable
Output 1.
Step 29. Configuration of Display Color Selection
Press auntil the
COLR
Display Color Selection Menu
appears on the Display. Configure
COLR
as
N.CLR/GRN
(green),
1.CLR/ RED
(red),
2.CLR/AMBR
(amber). Please
refer to the operator’s manual if needed.
For color change on Setpoints refer to Owners
Manual Section 2.
OPERATION
Step 1. Apply Power to the Instrument
When your device is first powered up it will display the
ambient temperature (assume 75°F).
Step 2. Enter Setpoint 1 Menu
Press aone time from run mode to get to
SP1
Setpoint 1.
Step 3. Enter the Setpoint 1 Value Submenu
Press d. Display shows the previous selection of Setpoint 1.
Step 4. Change the Setpoint 1 Value
Press bor cuntil desired value is displayed.
Step 5. Store the Setpoint 1 Value
Set the Setpoint 1 to 10 degree higher than Process value
(SP1 = 85) and press dto store, display flashes
STRD
message and advances to
SP2
Setpoint 2 Menu.
Step 6. Store the Setpoint 2 Value
Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher
than Process value (SP2 = 80) and press dto store,
display flashes
STRD
message and advances to
CNFG
Configuration Menu.
Step 7. Enter the Reading Config Menu
Press dto enter
RDG
Reading Config Menu.
Step 8. Enter the submenu items of Rdg Config Menu
Press dto display
SNSR
Sensor submenu: Sensor selection
for Autotune, Loop, or Ramp and Soak
°F.°C
is for
temperature and
DRRh
is for Humidity
Step 9. Enter the submenu items of Rdg Config Menu
Press dto display Temp Unit submenu:
Step 10 Scroll thru selection for Temp Unit submenu
Press bto Scroll though the available selections of the
Temperature Unit of your choice: °For °C.
Step 11. Store the Temperature Unit
Press d, display momentarily shows
STRD
the Unit has
been stored and the instrument will go automatically to the
next menu item.
Step 12. Enter the Filter Constant Submenu
Display shows
FLTR
Filter Constant Submenu.
Step 13. Display the Filter Constant Value Submenu
Press dto display the flashing, previously selected Filter
Constant.
Step 14. Scroll through available Filter Constants
Press bto sequence thru Filter Constants
0001, 0002
,
0004, 0008, 0016, 0032, 0064
and
0128
.
Step 15. Store the Filter Constant
Press dmomentarily to store
0004
Filter Constant and the
instrument will automatically go to the next menu item.
Step 16. Enter Alarm 1 Menu
The display will show
ALR1
the top menu for Alarm 1. In the
following steps we are going to enable Alarm 1, Deviation,
Unlatch, Normally Open, Active Above, Enable at power-on
and +2°F High Alarm i.e. Process Value > Setpoint 1 Value
+2°F will activate Alarm 1.
• If Analog Output Option is installed and enabled,
the controller will skip Alarm 1 Menu item to Analog
Output.
• Alarm must be DISABLED if Ramp is ENABLED.
• Alarm1 will only work for Humidity, not
Temperature.
MQS4007/0411
SPECIFICATION
SENSOR SPECIFICATIONS
Relative Humidity Accuracy/Range:
±2% for 10 to 90%
±3% for 5 to 10% and 90 to 95%
±4% for 0 to 5% and 95 to 100%
Non-linearity: ±3%
Hysteresis: ±1% RH
Response Time:
8 sec, tau 63%
Repeatability: ±0.1%
Resolution: 0.1%, 12bit
Temperature Accuracy/Range*:
±0.5°C for 5 to 45°C (±1°F for 41 to 113°F);
up to ±1.5°C for -40 to 5°C and 45 to 124°C
(up to ±2.7°F for -40 to 41°F and 113 to 257°F)
*NOTE: extended temp range is for Probe only, the
Controller’s operating temp is 0-50°C
Response Time:
5 to 30 sec, tau 63%
Repeatability: ±0.1°C
Resolution: 0.1°C, 14 bit
METER SPECIFICATIONS
Display:
4-digit, 9-segment LED,
• 10.2 mm (0.40")
Red, green, and amber programmable
colors for setpoint and temperature units.
Output 1
†
:
Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse
Output 2†:
Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse
†
Only with -AL Limit Alarm option
Options: Communication
RS-232 / RS-485
or
Excitation:
24 Vdc
@ 25 mA
Exc. not available for Low Power Option
Line Voltage/Power:
90 - 240 Vac ±10%,
50 - 400 Hz*,
or 110 - 375 Vdc, 4 W
* No CE compliance above 60 Hz
Low Voltage Power Option:
12 - 36 Vdc or 24 Vac**
±10%
, 3 W
** Units can be powered safely with 24 Vac
but No Certification for CE/UL are claimed.
Dimensions:
25.4 H x 48 W x 126.3 D mm
(1.0 x 1.89 x 5")
Weight:
127 g (0.28 lb)
Approvals:
CE per EN61010-1:2001
Alarm 1 is designed to monitor the humidity value
around Setpoint 1 and Alarm 2 is designed to monitor
the temperature value around Setpoint 2.
DPiTH-i32 Monitor
CNiTH-i32-AL Limit Alarm
Humidity + Temperature
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is
returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will
issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA,
if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply
to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit
shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive
corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to
contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA
warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO
OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or
otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event
shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications
or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic
WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless
from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY
RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
FOR NON-WARRANTY
REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the
repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2011 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without
the prior written consent of OMEGA ENGINEERING, INC.
PATENT AND TRADEMARK NOTICE: This product is covered by one or more of the following patents: U.S. Pat.
No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / GERMANY DE
41 34398 C2 / SPAIN 2039150; 2048066 / UK Patent No. GB2 249 837; GB2 248 954 / FRANCE BREVET NO. 91
12756. The “Meter Bezel Design” is a trademark of Newport Electronics, Inc. USED UNDER LICENSE. Other U.S.
and International Patents pending or applied for.
This device is marked with the international caution symbol. It is important to read the
Setup Guide before installing or commissioning this device, as the guide contains important
information relating to safety and EMC.
WARNING: These products are not designed for use in, and should not be used for, patientconnected applications.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OEMGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc.
accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:
®
,
omega.com
®
, , and ®are Trademarks of
OMEGA ENGINEERING, INC.