Omega Products CN3251-DT User Manual

1
4 DIN Ramp/Soak Temperature/
Process Controller with Fuzzy Logic
CN3251
U Dual PID + Fuzzy
Logic Control
U Up to 5 Outputs–
Control, Alarm or Event
Supply 100 to 240 Vac or Optional 12 to 24 Vac/Vdc
U 16-Segment
Ramp/Soak Program
U Optional RS232,
RS422, RS485 Digital Communications
U Programmable Remote
Setpoint Input (Standard)
CN3251 1⁄4 DIN
Panel punches
available, visit
omega.com/
panelpunches
The CN3251 1⁄4 DIN temperature and process controller is a cost effective, high-performance, single loop controller that can be used for temperature, flow, pressure and level control applications. With universal sensor inputs and front panel operator setup, one CN3251 controller can be easily field configured for a wide variety of applications, and simply reconfigured as application needs change. This makes it an exceptional choice for applications requiring multiple control needs, manufacturing facilities, testing facilities and testing applications.
Features 5 Possible Outputs for single output or
heat/cool control, plus up to 3 alarms or event outputs
Universal Sensor Input accepts thermocouple, RTD or analog signals; 24 Vdc output for loop power
Self-Tuning with Fuzzy Logic optimizes PID control and minimizes overshoot
Digital Input for remote switching of 1 of the following:
U PID1/PID2 U Remote/local setpoint U Main/auxiliary setpoint U Ramp/soak operation U Manual/auto control U Alarm reset for latching alarms
16-Interval Ramp/Soak Program with guaranteed soak, event outputs and looping
U Optional programmable analog U Programmable remote setpoint input
(standard on all products)
AUX Pushbutton and LED for front panel switching of:
U PID1/PID2 U Remote/local setpoint U Main/auxiliary setpoint U Ramp/soak operation U Manual/suto control
P-71
Security Code Protection prevents
unauthorized access Setpoint Ramp Rate provides soft start
at power-up, or on setpoint changes, to prevent uneven heating and overshoot
Control Loop Protection provides process protection from:
U Open sensor U Shorted sensor U Sensor reversed U Control output open or shorted U Power control device open or shorted U Load power missing and
self-diagnostics
Operating Ambient up to 65°C (150°F)
OMEGACARESM extended
SM
warranty program is available for models shown on this page. Ask your sales representative for full
Extended Warranty
Program
details when placing an order. OMEGACARE labor and equivalent loaners.
SM
covers parts,
Specifications
Control Modes: Automatic: On/off, proportional, PID,
PI, PD, PID + fuzzy logic, heat/cool (dual PID)
Control Adjustments: Control Setpoint: Sensor range Setpoint Limits: Sensor range Deadband: 1 to 100°F Proportional Band: Sensor range Manual Reset: –99.9 to 99.9 Automatic Reset: 0.00 to 99.99
repeats per minute
Rate: 0 to 500 seconds Output Cycle Time: 0.1 to
60.0 seconds
Output Limit: 0.0 to 100.0% Open Sensor/Out of Range Output Command: 0.0 to 100.0% Display Offset: –100 to 100°F Heat/Cool Adjustments: Output Offsets: 0 to 100% of
proportional band
Cooling Medium: Air, water or oil Alarm Adjustments: Setpoints: High and low settings for
each alarm output Alarm Types: Absolute: High, low and high/low, Tracking: +deviation, –deviation, and ±deviation Relay Action: Latching or non­latching, energized or de-energized Alarm Deadband: Adjustable,
-18 to 38°C (0 to 100°F) Alarm Inhibit: On power-up, enabled or disabled Control/Alarm Outputs: Total of 5 control/alarm outputs possible Relay: Form A contacts, 1.0 A at 120/230 Vac (resistive load) Solid State Relay Drive: 24 Vdc nominal at 40 mA Triac: 1 A continuous, 10 A in-rush @ 120 or 230 Vac Current/Voltage: 4 to 20 mA into 0 to 800 Ω, field-changeable to 1 to 5 Vdc
Output #5 (Optional): Relay: N.O. form “C” contact,
5 A @ 120 or 2.5 A 230 Vac Sensor Input: Field-selectable thermocouple, RTD, current or voltage
Input Update Rate: 2 samples/s Ramp/Soak Programming: Intervals: 16 Loops: 1 loop, 0 to 255 times
or continuous
Event Outputs: Up to 3 Guaranteed Soak Differential: Off,
1°F to sensor span Time Units: Seconds, minutes, hours (1 s to 99.99 hours/segment) Ramp to Setpoint: 1 to 9999°/hour on power-up
Open Sensor and Out-of-Range Condition: Programmable control
action with display indicating condition “OPEN SENS”
Front Panel
Yellow LED’s
indicate control
output #1 or #2 on.
Yellow LED’s
indicate alarm or
event output on.
- Process variable display in operation mode.
- Alphanumeric menu display in setup mode.
(4 Red, 7-Segment LED’s)
RESET
Pushbutton
- Alarm reset.
- Hold for more than 3 seconds to enter or exit setup mode.
- Scrolls through menu in setup mode.
AUX
Programmable
Pushbutton
- PID1/PID2 toggle switch.
- Auxiliary setpoint enable.
- Remote setpoint enable.
- Output disable.
- Ramp/soak operations.
- Auto/manual selector.
Remote Setpoint Input: Input Signal: 4 to 20 mA, 250 Ω input
impedance, 1 to 5 Vdc, 110 KΩ input impedance, voltage or current field­selectable via switch Range: Programmable over-selected sensor span Accuracy: ±0.3% of sensor span (initial accuracy) at 24°C (75°F) ambient temperature and rated line voltage, field calibrate to ±0.2% of sensor span
Digital Input: Accepts dry-contact closure Analog Output Option: Assignable Functions: Process
variable, output #1 command, active setpoint, output #2 command Output Signal: 4 to 20 mA into 0 to 800 Ω load, 1 to 5 Vdc into 100 KΩ or greater load selectable via DIP switch Range: Programmable over selected sensor span for retransmission of process variable and active setpoint, fixed to 0 to 100% for transmission of output commands Accuracy: ±0.2% of programmed span, ±1 LSD
Digital Communications (Optional): RS232: Single-drop, isolated RS422/485: Multi-drop, isolated, field
selectable by switch
Lower Display
(4 Green 7-Segment LED’s)
- Active setpoint display in operation mode.
- Menu value display in setup mode.
Upper Display
Baud Rates: 1200, 2400, 4800,
9600, 19.2 K Protocols: ASCII line, computer interface Instrument Power: 100 to 240 Vac, 10%, -15%; 12 to 24 Vac/Vdc, ±10%; 50 to 60 Hz Operating Environment: 0 to 65°C (32 to 150°F) ambient temperature, relative humidity <95%, non-condensing
Dimensions: Overall: 97 H x 97 W x 97 mm D
(3.8 x 3.8 x 3.8")
Depth Behind Panel: 97 mm (3.8") Front Panel Projection: 20 mm (0.8") Panel Cutout: 91 x 91 mm (3.6 x 3.6") Weight: 454 g (1 lb) Case Material: High-impact, black
ABS plastic
Influence of Line Voltage Variation:
±0.1% of sensor span/10% change in nominal line voltage
Noise Rejection: Common Mode Noise:
140 dB at 60 Hz Series Mode Noise: ±0.1% of sensor span with 300 mV peak-to-peak, 50 or 60 Hz series mode noise RFI: Typically less than 0.5% of sensor span at a distance of 1 m (3.1') from transmitter (4 W, 464 MHz)
Front Panel
Setup of all control
parameters
and selections.
Green LED’s
indicate °C or
°F selected for process
variable.
Yellow LED
indicates
an auxiliary
function
is active.
- In operation mode, pushbuttons adjust setpoint.
- In setup mode, pushbuttons increase/decrease menu values.
- While holding reset pushbutton, increase/decrease page.
P
P-72