Page buttonPress to select a new list of parameters.
Scroll buttonPress to select a new parameter in a list.
Down buttonPress to decrease a value in the lower
Up buttonPress to increase a value in lower readout.
When lit, it indicates that output 1 is on. This
is normally the heating output.
When lit, it indicates that output 2 is on. This
is normally the cooling output.
When lit, this indicates that Setpoint 2 has
been selected.
When lit, this indicates that the PDLINK
remote Setpoint input has been selected.
‘REM’ is also used to indicate that user
comms is active.
When lit, it indicates that manual mode has
been selected
When lit, it indicates that Setpoint rate limit is
active.
readout.
Figure 1.2 Controller buttons and indicators
CN2216 Controller1-3
OperationInstallation and Operation Handbook
G
H
OP1
OP2
OP1
GETTING STARTED
Thank you for selecting the Omega CN2216 controller. This section shows the principle
of operation.
VIEWING THE PROCESS VALUE and SETPOINT
Install and wire up the controller in accordance with Chapter 2 and switch on. Following
a 3-second self-test sequence, this is the display you will see,
Output 1
Output 2
Fig. 1.3 The “Home Display”
NOTE
*
TO ADJUST THE SETPOINT
The display may flash an alarm message. Refer to the Parameter Tables later in
this chapter for a complete list and meaning of the messages.
140.0140.0
Press and hold to
decrease temperature
20.020.0
23.023.0
20.020.0
Actual Temperature (Process Value)
Required Temperature (Setpoint)
Press and hold to
increase temperature
Fig 1.4 The lower readout shows the setpoint
After 2 secs the lower readout will ‘blink’ indicating that the new value has been
accepted. For everyday use you may not need to do anymore than this.
1-4CN2216 Controller
Installation and Operation HandbookOperation
VIEWING THE DISPLAY UNITS
Display Units
oo
0.5 sec.
23.0 23.0
23.0 23.0
o o
CC
CC Degrees Centigrade
oo
FF Degrees Fahrenheit
oo
KK Degrees Kelvin
No units - Linear inputs
140.0140.0
Momentarily
press either
G
NOTE
*
USE OF THE “SCROLL” BUTTON
Pressing the scroll button will display the output power level. Continued pressing will
display further parameters in what is referred to as the operator scroll list.
If you get lost, pressing and together will return you to the Home
display
Fig. 1.5 Pressing or will flash the display units for 0.5 sec
2nd press
buttonG
OP OP
100.0100.0
m-A m-A
AutoAuto
Keep pressing to return to
Home display or select further
parameters (if available)
Fig. 1.6 Upper readout is parameter name. Lower is value
CN2216 Controller1-5
Output
Actual output level %
3rd press
Manual/Auto
Actual state
OperationInstallation and Operation Handbook
**
USE OF THE PAGE BUTTON
The “PAGE” button accesses parameter LISTS
Parameters are settings in the instrument which, generally, can be changed by the user to
suit the process. Examples are: Alarms, Self-Tune, etc. They are found under headings
called LISTS and a full set is given later in this chapter.
Fig 1.7 Press to choose a parameter list
0.5 sec.
23.023.0
oo
23.0 23.0
CC
140.0140.0
1st press
NOTE
23.023.0
14.0.014.0.0
2nd press
ALAL
LiSt LiSt
3rd press
Keep pressing to
select more list headings and
continue around a continuous loop
atunatun
LiStLiSt
The actual list headings may be longer or shorter than indicated above and you
can customize this for the operator’s convenience in EDIT level, Chapter 3.
1-6CN2216 Controller
Installation and Operation Handbook Operation
PARAMETER LISTS
Press to choose a LIST - “ALARMS” is a good one. This list allows you to set the
alarm trip levels. The parameters, which appear in the list, will vary according to the
configuration of your controller.
0.5 sec.
23.0 23.0
o o
23.0 23.0
140.0140.0
CC
1st press
G
Fig. 1.8a Choose a list
There are 4 alarms in
the controller. The first
character is the alarm
number. The following
three letters indicate
alarm type as follows:
-FSL-FSL Full S
-FSH-FSH Full Scale High
-dHi-dHi Deviation High
-dLo-dLo Deviation Low
-dEv-dEv Deviation Band
Disabled alarms will not
be displayed.
Chapter 7 gives a full
description of alarms.
Fig. 1.8b Press to select a parameter
cale Low
Alarm
List
2nd press
Keep pressing
1. to scroll through further parameters
2. to return to list header
ALAL
LiSt LiSt
1---1---
50.0 50.0
2---2---
200.0 200.0
Now press
the SCROLL
button
Alarm 1
or to
change trip level
2nd press
Alarm 2
or to
change trip level
NOTE
**
CN2216 Controller 1-7
If, at any time, no key is pressed within 45 seconds, the display will always
return to the “HOME” display.
Operation Installation and Operation Handbook
OPERATING MODES
The controller can be used in two modes:
Automatic mode - in which the output power is automatically adjusted to hold the
temperature at the required value. The controller normally operates in this mode.
Manual mode - in which the output is manually adjusted by the Operator. In this mode
the ‘MAN’ light will be on.
One other mode is available:
Remote setpoint - The setpoint is generated as an input signal from a master CN2216
series controller. In this mode the REM light is on.
AUTO or MANUAL SELECT
0.5 sec.
23.0 23.0
o o
CC
1st press
2nd press
ut
Outp
Actual output level %
140.0140.0
OP OP
100.0100.0
23.023.0
3rd press
m-A m-A
mAn mAn
Keep pressing
to return to “HOME”
display
1-8 CN2216 Controller
Manual/A
AutoAuto automatic mode
ManMan manual mode
Fig. 1.9 Auto/manual select
uto
or to select
Installation and Operation HandbookOperation
OP1
OP2
MAN
G
H
**
MANUAL ADJUSTMENT OF OUTPUT POWER
23.0 23.0
50.0 50.0
Press and hold to
decrease power
Fig. 1.10 The “Home Display” in manual mode
NOTE
SUMMARY
To step through list headers, press the Page button until the required header is
obtained
To step through parameters within a particular list, press the Scroll button until the
required parameter is obtained
Manual mode is generally used for test and commissioning purposes, take care
not to leave the controller in this mode since damage or personal injury could
occur.
Actual Temperature (Process Value)
Output Power Demand
Manual Indicator on
Press and hold to
increase power
To change the value (or state) of a parameter, press the Raise button or the Lower
button
The remainder of this chapter provides a complete list of all parameters available.
CN2216 Controller1-9
OperationInstallation and Operation Handbook
AtunAtun
(1)
List
2
2
2
2
3
3
3
NAVIGATION DIAGRAM (Part A)
Home
List
20.020.0
20.020.0
OP
100.0
AmPS
5
m-A
Auto
Alarm
AL AL
LiStLiSt
1---
100.0
2---
20.00
3---
Autotune
List
LiStLiSt
TunE
OFF
Adc
mAn
0
4---
0
Lbt
OFF
The navigation diagram shows a full
list of possible parameters.
However, some may not appear
because they are dependent upon
the particular controller variant.
PID
List
PidPid
LiStLiSt
Pb
50
Ti
300
td
50.0
RES
0.0
Lcb
Auto
Hcb
Auto
REL.C
1.00
Setpoint
List
SPSP
LiStLiSt
SSEL
SP 1
L-r
Loc
SP 1
20.0
SP 2
0.0
Rm.SP
0.0
Loc.t
0.0
SP1.L
3
Notes:
SP1.H
1. Either the PID list or the On/Off list will be
present depending upon the type of control in
use.
2. The last three characters depend upon the type
of alarm configured
SP2.L
100.0
SP2.H
3. Absolute setpoint limits are set in configuration,
see Chapter 5.
The shaded boxes are normally hidden in
Operator level. To see all the available
parameters you must select Full level. See
Loc.L
100.0
Loc.H
Chapter 3, Access Levels.
Figure 1.11a Navigation diagram
SPrr
OFF
1-10CN2216 Controller
0.0
0.0
Installation and Operation HandbookOperation
NAVIGATION DIAGRAM (PART B)
Input
List
IP
LiSt
FiLt
1.0
CAL
FACT
CAL.L
Adj.L
CAL.H
Adj.H
CJC
21.0
MV
1.17
no
no
Output
List
oP
LiSt
OP.Lo
100.0
OP.Hi
0.0
Sb.OP
100.0
4
CYC.C
5.0
On Off
(1)
List
OnOF
LiSt
hYS.H
1.0
hYS.C
1.0
HC.db
0.0
Comms
List
CmS
LiSt
Addr
Access
List
ACCS
LiSt
Return to
“HOME” Display
coDE
1
PASS
Goto
OPEr
ConF
0
Ont.C
1.0
4
CYC.H
20.0
Ont.H
1.0
Note:
4. Beware! Used for calibration. See Chapter 6.
The shaded boxes are normally hidden in
Operator level. To see all the available
parameters you must select Full level. See
Chapter 3, Access Levels.
Proportional band
Integral time
Derivative time
Manual reset (appears when ti set to OFF)
Cutback low
Cutback high
Relative cool gain (normally set to 1)
OFFOFFOFFON
MANMANMANCALC
20.00.09999
360OFF9999
60OFF9999
0.00.00100.0
Auto19999
Auto19999
1.000.019.99
as display
seconds
seconds
%
as display
as display
Select SP1 or SP2
Local or remote PDLINK setpoint select *
Setpoint 1 value
Setpoint 2 value
Remote setpoint
Local trim
Setpoint 1 low limit
Setpoint 1 high limit
Setpoint 2 low limit
Setpoint 2 high limit
Local setpoint trim low limit
Local setpoint trim high limit
Setpoint rate limit
SP1SP1SP2
LocLocrmt
25
25
0
0
0
1000
0
1000
-210
1200
OFF
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
•• Only appears if PDLINK fitted and configured in the HA comms slot
The next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.
CAL
FACt will re-instate factory settings and disable User Calibration. Default setting FACt
USEr will re-instate any previously set User Calibration offsets and make available User Calibration parameters as follows:
CAL.LUser low point calibration if YES allows access to next parameter. if no the next parameter is hidden
*
AdJ.L
Adjust low point to calibrated ref. source
CAL.HUser high point calibration if YES allows access to the next parameter if no the next parameter is hidden
*
AdJ.H
Adjust high point to calibrated ref. source
The following two parameters are always present in Full Access level but not in Operator level
o
CJC
mV
*
Do not make adjustments to the AdJ.L or AdJ.H parameters unless you wish to offset the controller calibration
Cold Junction compensation temperature
Millivolt input
oPoPOutput list Note; If On/Off control is configured only Sb.OP, ont.H and ont.C will appear in the following list
OP.Lo
OP.Hi
Sb.OP
CYC.H
CYC.C
ont.H
ont.C
Low (power) output limit
High (power) output limit
Output setting when in sensor break
Heat cycle time
Cool cycle time
This set of parameters only appear if On/Off control has been configured
hYS.H
hYS.C
HC.db
cmScmS
Addr
ACCSACCS
codE
GotoGoto level -OPEr,FuLL,Edit,or
ConF
1-16CN2216 Controller
On/off list
Heat hysteresis
Cool hysteresis
Heat/Cool dead band
C omms list
Communications address
Access list
Full and Edit level password
conF
Configuration level password
0009999
0009999
1109999
111254
1109999
OPErOPErOPErconF
2209999
as display
as display
as display
Installation and Operation Handbook Operation
SETTING ALARM LEVELS
Up to 4 Alarms may be configured. Each alarm is given a name to describe its function see table below: If an alarm is not used it does not appear in the list below.
In place of dashes,
letters indicate alarm
type as follows:
-FSL Full S
-FSH Full Scale High
-dHi Deviation High
-dLo Deviation Low
-dEv Deviation Band
cale Low
ALAL
LiSt LiSt
1---1---
100100
2---2---
200200
3---3---
00
4---4---
00
Alarm List
Alarm 1
or to change
2nd press
Alarm 2
or to change
3rd press
Alarm 3
or to change
4th press
Alarm 4
or to change
5th press
Lb tLb t
OFFOFF
Press to return
to list header
CN2216 Controller 1-17
Loop break time
or to change
OperationInstallation and Operation Handbook
Diagnostic alarms
These indicate that a fault exists in either the controller or the connected devices.
Table 1.1a Diagnostic alarms - continued on the next page
Display
shows
EE.Er
S.br
L.br
Ld.F
SSr.F
What it meansWhat to do about it
Electrically Erasable
Memory Error:
The value of an operator
or configuration
parameter has been
corrupted.
Sensor Break:
Input sensor is unreliable
or the input signal is out
of range.
Loop Break:
The feedback loop is
open circuit.
Load failure
Indication that there is a
fault in the heating circuit
or the solid state relay.
Solid state relay failure
Indication that there is a
fault in the solid state
relay
This fault will automatically take you into
configuration level. Check all of the
configuration parameters before returning to
operator level. Once in operator level, check
all of the operator parameters before
resuming normal operation. If the fault
persists or occurs frequently, contact Omega .
Check that the sensor is correctly connected.
Check that the heating and cooling circuits
are working properly.
This is an alarm generated by feedback from
a Omega SSC-TE10S solid state relay (SSR)
operating in PDLINK mode 1-see Electricalinstallation Chapter 2. It indicates either an
open or short circuit SSR, blown fuse, missing
supply or open circuit heater.
This is an alarm generated by feedback from
a Omega SSC-TE10S solid state relay (SSR)
operating in PDLINK mode 2 -see Electricalinstallation Chapter 2. It indicates either an
open or short circuit condition in the SSR.
Htr.F
HW.Er
1-18CN2216 Controller
Heater failure
Indication that there is a
fault in heating circuit
Hardware error
Indication that a module
is of the wrong type,
missing or faulty
This is an alarm generated by feedback from a
Omega SSC-TE10S solid state relay (SSR)
operating in PDLINK mode 2 -see Electricalinstallation Chapter 2. It indicates either a
blown fuse, missing supply or open circuit
heater.
Check that the correct modules are fitted.
Installation and Operation HandbookOperation
Diagnostic alarms continued
These indicate that a fault exists in either the controller or the connected devices.
Table 1.1b Diagnostic alarms
Display
shows
rmt.F
LLLL
HHHH
Err1
Err2
Err3
Err4
Err5
Pwr.F
What it meansWhat to do about it
Remote input failure. The
PDLINK input is open
circuit