Safety InformationInstallation and Operation Handbook
SAFETY and EMC INFORMATION
Please read this section before installing the controller
This controller meets the requirements of the European Directives on Safety and EMC, however it is the responsibility of the installer to
ensure the safety and EMC compliance of any particular installation.
Safety
This controller complies with the European Low Voltage Directive
73/23/EEC, amended by 93/68/EEC, by the application of the safety
standard EN 61010(93).
Electromagnetic compatibility
This controller conforms with the essential protection requirements
of the EMC Directive 89/336/EEC, amended by 93/68/EEC, by the
application of a technical construction file.
INSTALLATION REQUIREMENTS FOR EMC
To ensure compliance with the European EMC directive certain
installation precautions are necessary as follows:
• When using the relay output it may be necessary to fit a filter
suitable for suppressing the emissions. The filter requirements
will depend on the type of load.
iiCN2132 Controller
Routing of wires
To minimize the pick-up of electrical noise, the dc pulse wiring and
the sensor input wiring should be routed away from high-current
power cables. Where it is impractical to do this, use shielded cables
with the shield grounded at both ends.
SERVICE AND REPAIR
This controller has no user serviceable parts. Contact Omega
Engineering, Inc. for repair.
Installation and Operation HandbookSafety Information
TECHNICAL SPECIFICATION FOR SAFETY PURPOSES.
Equipment ratings
Supply voltage:100 to 240Vac -15%, +10%
Supply frequency:48 to 62Hz ac.
Power consumption:2.5 Watts maximum
Relay output:Maximum of 264Vac. Minimum 30Vac or dc. Maximum current, 2A resistive.
Leakage current:The leakage current through the relay contact suppression components is less than 2mA at 264Vac, 50Hz.
Over current protection:External over current protection devices are required that match the wiring of the installation. A minimum of 0.5mm
or 16awg wire is recommended. Use independent fuses for the instrument supply and the relay output. Suitable fuses
are T type, (IEC 127 time-lag type) as follows; Instrument supply: 85 to 264Vac, 2A, (T). Relay output: 2A (T).
Environmental ratings
Panel sealing:Instruments are intended to be panel mounted. The rating of panel sealing is defined by EN 60529: IP 65.
Operating temperature:0 to 55oC. Ensure the enclosure provides adequate ventilation.
Relative humidity:5 to 90%, non-condensing.
Atmosphere:The instrument is not suitable for use above 2000m or in explosive or corrosive atmospheres.
Electrical safety
Installation category II:Voltage transients on any mains power connected to the instrument must not exceed 2.5kV.
Pollution degree 2:Conductive pollution must be excluded from the cabinet in which the instrument is mounted.
Isolation:All inputs and outputs, have a reinforced isolation which provides protection against electric shock, except the dc pulse
output which is electrically connected to the main process variable input, (thermocouple etc.).
2
CN2132 Controlleriii
Safety InformationInstallation and Operation Handbook
INSTALLATION SAFETY REQUIREMENTS
Personnel
Installation must only be carried out by qualified personnel.
Enclosure of live parts
To prevent hands or metal tools touching parts that may be
electrically live, the controller must be installed in an enclosure.
Wiring
It is important to connect the controller in accordance with the wiring
data given in this handbook. Take particular care not to connect AC
supplies to the low voltage sensor input or the dc pulse output.
Wiring installations must comply with all local wiring regulations.
Isolation
The installation must include a power isolating switch or circuit
breaker. This device should be in close proximity to the controller,
within easy reach of the operator and marked as the disconnecting
device for the instrument.
Overcurrent protection
To protect the internal PCB tracking within the controller against
excess currents, the AC power supply to the controller and relay
output must be wired through the fuse or circuit breaker specified in
the technical specification.
Voltage rating
The maximum continuous voltage applied between any of the
following terminals must not exceed 264Vac:
• power supply to relay, dc pulse or sensor connections;
• relay output to logic or sensor connections;
The controller should not be wired to a three phase supply with an
unearthed star connection. Under fault conditions such a supply
could rise above 264Vac with respect to ground and the product
would not be safe.
Voltage transients across the power supply connections, and between
the power supply and ground, must not exceed 2.5kV. Where
occasional voltage transients over 2.5kV are expected or measured,
the power installation to both the instrument supply and load circuits
should include a transient limiting device. These units will typically
include gas discharge tubes and metal oxide varistors that limit and
control voltage transients on the supply line due to lightning strikes
or inductive load switching. Devices are available in a range of
energy ratings and should be selected to suit conditions at the
installation.
ivCN2132 Controller
Installation and Operation HandbookSafety Information
Conductive pollution
Conductive pollution must be excluded from the cabinet in which the
instrument is mounted. For example, carbon dust is a conducting
pollution. To secure a suitable atmosphere in conditions of
conductive pollution, fit an air filter to the air intake of the cabinet.
Where condensation is likely, for example in low temperatures,
include a thermostatically controlled heater in the cabinet.
Grounding
The dc pulse output is not isolated from the sensor input. Because of
this, two possible conditions need to be considered:
• The temperature sensor may be connected to the electrical
heating element and hence be at the heater supply voltage. The
controller is designed to operate under these conditions but the
logic output will also be at the heater potential. You must ensure
that this will not damage the power control device that is
connected to the dc pulse output and that someone servicing the
equipment does not touch the sensor connections or the dc pulse
output while they are live.
• In some installations it is a requirement to replace the
temperature sensor while the controller is still powered up.
Under these conditions, we recommend that the shield of the
temperature detector is grounded. Do not rely on grounding
through the framework of the machine.
Electrostatic discharge precautions
When the controller is removed from its sleeve, some of the exposed
electronic components are vulnerable to damage by electrostatic
discharge from someone handling the controller. To avoid this, when
handling the unplugged controller you should discharge yourself to
ground through a wrist strap with a 1MΩ series resistor.
Over-temperature protection
When designing any control system it is essential to consider what
will happen if any part of the system should fail. In temperature
control applications the primary danger is that the heating will remain
constantly on. Apart from spoiling the product, this could damage
any process machinery being controlled or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process;
• the controller failing with its heating output constantly on;
• an external valve or contactor sticking in the heating condition;
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a separate
over-temperature protection unit, with an independent temperature
sensor, which will isolate the heating circuit.
Please note that using the relay within the controller as an alarm
output will not give protection under all failure conditions.
CN2132 Controllerv
Installation and Operation HandbookInstallation
Chapter 1 INSTALLATION
The CN2132 controller is a compact 1/32 DIN (48x24mm) PID or
On/Off temperature controller with automatic tuning. It has a single
input, which is configurable on-site for either thermocouple,
resistance thermometer, linear millivolts, or linear milliamps. It has
two outputs: a relay output and a dc pulse output for operating a solid
state relay, either of which is configurable for heating, cooling, or
alarms.
This chapter consists of two parts:
• MECHANICAL INSTALLATION
• ELECTRICAL INSTALLATION.
Before proceeding please read Safety and EMC Information.
WARNING
You must ensure that the controller is correctly configured for your
application. Incorrect configuration could result in damage to the
process being controlled and/or personal injury. It is your
responsibility as the installer to ensure that the configuration is
correct. The controller may either have been configured when
ordered, or may now need configuring. See Chapter 5,
Configuration.
Upper panel retaining clip
Display screen
Latching ears
Ratchets
Panel sealing gasket
Figure 1-1 CN2132 1/32 DIN controller
Terminal covers
Label
Sleeve
Lower panel
retaining clip
CN2132 Controller1-1
InstallationInstallation and Operation Handbook
MECHANICAL INSTALLATION
48mm
(1.89in)
24mm
CN2132
(0.95in)
Figure 1-2 Outline dimensions
Panel cut-out and recommended minimum spacing of
controllers
22.2mm
X 45mm
-0.0 +0.3
–0.0 +0.6
-0.0 +0.1
0.88in
–0.0 +0.2
X 1.78in
10mm (0.2in)
103mm (4.06in)
Unplugging and plugging-in the controller
The electronic assembly of the controller plugs into a rigid plastic
sleeve, which in turn fits into the standard DIN size panel cut-out
shown in Figure 1-3. The controller can be unplugged from it’s
sleeve by easing the latching ears outwards and pulling it forward out
of the sleeve. When plugging the controller back into it’s sleeve,
ensure that the latching ears click into place in order to secure the
IP65 sealing.
To install the controller
1. Prepare the control panel cut-out to the size shown in Figure 1-3.
2. Insert the controller through the panel cut-out.
3. Spring the upper and lower retaining clips in place. Secure the
controller in position by holding it level and pushing both
retaining clips forward.
Note: If you subsequently need to remove the controller sleeve from
the control panel, unhook the retaining clips from the side with either
your fingers or a screwdriver.
Figure 1-3 Panel cut-outs and minimum spacing
1-2CN2132 Controller
Installation and Operation HandbookInstallation
Line
Line
Line
9Vdc @18mA
+
-
ELECTRICAL INSTALLATION
All electrical connections are made to the screw terminals at the rear
of the controller. Use crimp connectors that accept wire sizes from
0.5 to 1.5 mm
2
(16 to 22 awg).
Milliamp Inputs
If a milliamp input has been ordered a 2.5Ω sense resistor will be
supplied which must be wired across terminals V- and V+
Snubber
When switching inductive loads such as contactors and solenoid
valves, the 15nF/100Ω ‘snubber’ provided with the controller should
be wired across the relay terminals AA and AB to prolong contact life
and suppress interference.
WARNING
When the relay contact is open, the snubber circuit passes 0.6mA at
110vac and 1.2mA at 240vac. You must ensure that this current,
passing through the snubber, will not hold in low power electrical
loads. It is your responsibility as the installer to ensure that this does
not happen.
Electrical connections
SSC-TE10S
Solid state relay
Heating load
1B1A
dc pulse output
Input
V-V+ABAANL
Thermocouple
RTD/PT100
Heating, cooling,
or alarm contactor
Relay 2A, 264Vac
Unused
85 - 264Vac
50 - 60 Hz
Snubber
Heater Fuse
2A Fuse
2A
Neutral
Neutral
Neutral
CN2132 Controller1-3
Installation and Operation HandbookOperation
Output 2 on
Chapter 2 OPERATION
This chapter has six main topics:
• FRONT PANEL LAYOUT
• POWER ON
• PARAMETERS AND HOW TO ACCESS THEM
• PARAMETER NAVIGATION DIAGRAM
• OPERATOR PARAMETER TABLES
• TIMER FUNCTION
• ALARMS.
FRONT PANEL LAYOUT
Readout
Indicator
or button
OP1Output 1When lit, this indicates that the dc
OP2Output 2When lit, this indicates that the
NameFunction
pulse output is on.
relay output is on.
Page
button
Scroll
button
Press to select a new list of
parameters.
Press to select a new parameter in
a list.
CN2132
Output 1 on
OP1
OP2
25.0
Page
button
Figure 2-1 Front panel layout
CN2132 Controller2-1
Scroll
button
Down
button
Up
button
Down
button
Up
button
Figure 2-2 Indicators and buttons
Press and release to view the
setpoint or a selected parameter.
Keep pressed to decrease the
value.
Press and release to view the
setpoint or a selected parameter.
Keep pressed to increase the value
Operation Installation and Operation Handbook
POWER ON
Switch on the power to the controller. It runs through a self-test sequence for about three seconds and then displays the measured value. This is
called the Home display. It is the one you will use most often. From this display you can view and adjust the setpoint as shown below:
The Home display
The measured value is displayed.
Power on
OP1
25.025.0
OPOP
OP2
OP1
OP2
OP1
100.0100.0
OP2
x 2
x 2
OP1
OP2
^C^C
OP1
20.020.0
OP2
To view the setpoint, press and release either or .
To change the setpoint, keep pressing. Two seconds after releasing
the button, the new value will be accepted and the display will revert
to showing the measured value.
Press the Scroll button once.
Display units
The display units will be shown for 0.5 seconds after which the
display will revert to the Home display.
From the Home Display press the Scroll button twice.
Output power
To view the % output power, press and release or
This is a read-only value. You cannot change it.
Press and together to return to the Home display.
Other parameters
Pressing the Scroll button from the Output Power display may access
further parameters. If setpoint rate limit is enabled then the ‘w. SP’
display will enable the working setpoint to be accessed. Other
parameters may be in the scroll list if the ‘promote’ feature has been
used (see Edit Level, Chapter 3).
2-2 CN2132 Controller
Installation and Operation Handbook Operation
PARAMETERS AND HOW TO ACCESS THEM
Parameters are settings within the controller that determine how the
controller will operate. For example, alarm setpoints are parameters
that set the points at which alarms will occur. For ease of access, the
parameters are arranged in lists, as shown in the navigation diagram
(Figure 2-3). In each list the first item to be displayed is the name of
the list, called the list header. The lists are:
Home list
Alarm list
Autotune list
PID list
Setpoint list
Input list
To step through the list headers press the Page button .
You will eventually return to the Home display.
To step through the parameters within a particular list,
press the Scroll button .
When you reach the end of a parameter list you will return to the list
header. From within a list you can return to the list header at any time by
pressing the Page button.
To step to the next list header press the Page button once again.
Returning to the Home display
You can get back to the Home display at any time by pressing
and together.
Alternatively, you always get the Home display either if no button is
pressed for 45 seconds or when the power is first turned on.
Output list
On/Off list
Access list.
Parameter names
In the navigation diagram (Figure 2-3) each box depicts the display for
a selected list header or parameter within a list. The Operator
parameter tables later in this chapter list all the parameter names and
their meaning.
The navigation diagram shows all the parameters that potentially can
be present in the controller. In practice, only those associated with a
particular configuration will appear. For example, if no alarms are
configured no alarm parameters will be present and the alarm list will
not appear.
The shaded boxes in the diagram indicate parameters that are hidden
in normal operation. To see all the available parameters, you must
select Full access level. For more information about this, see Chapter
3, Access Levels.
To change the value of a parameter
First, select the required parameter. The parameter name will be
displayed.
To view the parameter value, press and release either or
To change the parameter value, press either
or
In this adjustment, pressing once changes the value by one digit.
Keeping the button pressed speeds up the rate of change.
Two seconds after releasing either button, the readout blinks to show
that the controller has accepted the new value.
CN2132 Controller 2-3
OperationInstallation and Operation Handbook
List
(1)
(2)
(2)
(2)
(1)
List
(3)
(4)
PARAMETER NAVIGATION DIAGRAM
Home
List
20.0
x2
Alarm
List
AL
Autotune
Atun
PID
List
PID
Setpoint
SP
Input
iP
List
Output
List
oP
On-Off
List
on.OF
Access
List
ACCS
x2
oP
ºC/F/k
w.SP
m - A ConF
???
1FSH
2FSL
3dEv
Lb t
tunE
AdC
Pb
ti
td
rES
Lcb
Hcb
rEL.C
SP L
SP H
SPrrCYC.H
dwell
FiLt
CAL
CAL.L
AdJ.L
CAL.H
Adj.H
CJC
mV
Figure 2-3 Operator parameters navigation diagram
OP.Lo
OP.Hi
CYC.C
ont.H
ont.C
hYS.H
hYS.C
HC.db
Notes:
1. Either the PID list or the On/Off list will be
present. This is dependent upon the
control type in use.
2. The last three characters depend upon the
type of alarm configured.
3. If setpoint rate limit is active ‘w.SP’ will be
displayed.
4. Other parameters may appear if the
‘promote’ feature has been used (see EditLevel, Chapter 3).
The shaded boxes are normally hidden in
Operator level
codE
Goto
Home
List
2-4CN2132 Controller
Loading...