4 DIN Compact Temperature
Controller
CN2110 Series
Starts at
$
340
Compact 1⁄4 DIN Design
102 mm (4") Depth
On/Off or
Proportional Control
20 A Mechanical
Plug-In Output ModulesJ, K Thermocouple or
RTD Inputs, °F and °C Indication, Switch Selectable
Alarm Relay
Output Option
NEMA 4X (IP65)
Front Panel
P
a
n
e
l
p
u
n
c
h
e
a
v
a
i
l
a
b
o
m
e
g
a
p
a
n
e
l
p
u
s
l
e
,
v
i
s
i
t
.
c
o
m
/
n
c
h
e
s
The CN2110 temperature controller offers simple setup, flexibility and control features in an attractive, compact design that both OEMs and users will find cost-effective. The CN2110 is housed in a rugged, plastic 1⁄4 DIN package that only requires 4" behind the mounting surface. Straightforward operation and easy-to-use control features are major strengths of the CN2110 controller.
Full Feature Outputs
A total of 6 output types further extend the applications flexibility of the CN2110 controller:
• 1 A relay
• 20 A relay
• 1 A solid state relay
• 5 A solid state relay
• 10 A solid state relay
• DC pulse, SSR drive
The CN2110 features a variety of output modules including high­current options of a 10 A solid state relay or 20 A mechanical relay. These outputs can directly control many cartridge or strip heaters, eliminating the need for a remote contactor or solid state relay. For larger, 3-phase loads, the CN2110 can drive a remote device with the pilot duty relay or solid state relay drive outputs.
CN2110-DC, $340, shown actual size.
The optional alarm output gives the user a non-latching, normally de-energized, 5 A relay output for over- or under-temperature protection of critical process temperatures.
Packaging with the User in Mind
The CN2110 features a NEMA 4X (IP65) front panel with tactile feedback push buttons. Large, bright LED’s provide an easy-to-read interface at a distance.
Flexibility and Simplicity
Outputs are plug-in modules that are field replaceable. The switch­selectable control modes include on/off or proportional-integral (PI). Sensor Types J, K, RTD are also switch selectable. No programming necessary.
Features High-Current Switching
The CN2110 features high-current output switching (relay and solid state relay), eliminating the need for an external power switching device and reducing installation cost. Single-phase loads up to 20 A may be directly connected to the CN2110, eliminating the need
P-67
for a remote contactor or solid state relay. The internal relay option can switch up to 20 A or the internal solid state relay option can switch up to 10 A. The CN2110 automatically detects the output type and adjusts the controllers setting for optimal control.
Control Modes
The CN2110 provides precise, solid state proportion control with automatic reset (PI) that will control most heating applications. On/off control may be selected for applications where maximum output life (load switching) is needed.
OMEGACARESMextended warranty program is available for models shown on this page. Ask your sales representative for full details when placing an order. OMEGACARE labor and equivalent loaners.
SM
covers parts,
Load
A
larm
°F
°
C
Temp
S
et
Point
Set Point
101.6 (4.0)
101.6 (4.0)
102
(4.0)
92
(3.6)
90
(3.55)
10
(0.4)
12.7 (0.5)
*
92
(3.6)
92
(3.6)
P
anel
Cutout
Specifications
Control Modes: On/off, PI-proportional
with integral
Control Adjustments
Proportional Band: Sensor range Automatic Reset:
0.0 to 99.9 repeats/min
Cycle Time: 0.1 to 60.0 sec
n/Off Deadband: 1° to 100°F or °C
O Setpoint Upper Limit: Sensor range
°F or °C Setpoint Lower Limit: Sensor range °F or °C
Output Limit: 0 to 100%
Alarm Adjustments:
Type: Absolute, high or low Setpoint: Sensor range °F or °C Alarm Dead Band: 0 to 100°F or °C
Control/Alarm Outputs:
Relay (-R1): 1 A form A, 120/240 Vac Relay (-R20): Form A, 120/240 Vac
resistive loads at 30 s cycle time; 20 A, 500,000 operations; 15 A, 1 million operations; 5 A, 5 million operations
Solid State Relay Drive (-DC):
24 Vdc at 40 mA
Solid State Relay (-T1):
1 A, up to 240 Vac
Solid State Relay (-T5):
5 A, up to 240 Vac at 40°C
Solid State Relay (-T10):
10 A, up to 240 Vac at 40°C
Alarm: Form C, relay 5 A@ 120 Vac,
2.5 A at 240 Vac Sensor Input: Switch selectable J, K
thermocouple or RTD
Input Update Rate: 4 samples/s Readout Stability:
J and K Thermocouple: ±1°F per
10°F change in ambient temperature RTD: ±0.5 per 10°F change in
ambient temperature
Open Sensor and Out-of-Range:
Conditions: Displays “SEnS”, control
output 0%
Instrument Power: 90 to 260 Vac ,<10 Va Operating Environment: 0° to 65°C
(32°to 150°F) Enclosure Material: High-temperature ABS plastic rated for 0° to 175°F
Front Panel:
NEMA 4X (IP65) construction
Influence of Line Voltage Variation:
±0.1% of sensor span per 10% change in nominal line voltage
Noise Rejection:
Common Mode Noise: <2°F with
230 Vac, 60 Hz applied from sensor input to earth ground Series Mode Noise: <2°F with 100 mV, peak-to-peak series mode noise
RFI: Typically <0.5% of sensor span at distance of 1 m (3.1') from a transmitter of 4 W at 464 MHz
Sensor Leadwire Effect:
RTD: ±0.1% of sensor span per
20 Ω balanced leadwire resistance
* With alarm option or S2 output
Dimensions: mm (in)
Input Specifications
Input Accuracy at Specifications Range °F Range °C 77°F ambient
Iron-Constantan -100 to 1400°F -73 to 760°C 0.2% span ±1 LSD CHROMEGA®-
ALOMEGA
®
-300 to 2400°F -184 to 1316°C 0.2% span ±1 LSD
100Ω Pt, 3-wire -200 to 1000°F -128 to 538°C 0.2% span ±1 LSD
MOST POPULAR MODELS HIGHLIGHTED!
To Order (Specify Model Number)
Model No. Price Description CN2110-R1 $345 Relay, 1 A CN2110-R20 350 Relay, 20 A CN2110-DC 340 DC pulse 24 Vdc CN2110-T1 345 AC SSR, 1 A CN2110-T5 365 AC SSR, 5 A CN2110-T10 390 AC SSR, 10 A
Comes complete with operator’s manual.
Ordering Examples: CN2110-R20, controller with a 20 A relay, $350. OCW-3, OMEGACARE
$350 + 87 = $437. CN2110-T10, controller with a 10 A ac SSR, $390
Option
Order Suffix Add’l Price Description
-AL $25 Alarm
Accessories* (Field Installable)
Model No. Price Description 2110X-R1 $55 1 A relay output module 2110X-R20 55 20 A relay output module 2110X-DC 45 DC pulse output module 2110X-T1 55 1 A, AC SSR output module 2110X-T5 110 5 A, AC SSR output module 2110X-T10 110 10 A, AC SSR output module 2110X-R1-AL 70 1 A relay output module, with alarm 2110X-R20-AL 80 20 A relay output module, with alarm 2110X-DC-AL 70 DC pulse output module, with alarm 2110X-T1-AL 70 1 A, AC SSR output module, with alarm 2110X-T5-AL 150 5 A, AC SSR output module, with alarm 2110X-T10-AL 150 10 A, AC SSR output module, with alarm CNQUENCHARC 8 Noise suppression RC snubber (2 leads),
Alarm relay built into output module. If ordering a replacement module for existing controller
*
with alarm, must specify accessory module with “-AL” suffix.
SM
extends standard 1-year warranty to a total of 4 years ($87),
110 to 230 Vac
P-68
P
Loading...
+ 1 hidden pages