Omega SBG25872, SBG41705, SBG25873, SBG22445 User Manual

SBG22445, SBG25872, SBG25873 (Non-Latching), SBG41705 (Latching) Solid-State Relays for Intrinsic Safety Use
Instruction Sheet M1773/0794
DESCRIPTION
®
The OMEGA State Relays are used as "intrinsically safe switching circuits in hazardous locations, with non-voltage- producing sensors. When installed in accor­dance with this manual, these field sensors are suitable for Class I, Division 1, 2, Groups A, B, C and D, and Class II, Division 2, Groups E, F and G as defined by Article 500 of the National Electric Code.
UNPACKING
Remove the Packing List and verify that you have received all equipment. If you have any questions about the shipment, please call the OMEGA Customer Service Department at 1-800-622-2378 or (203) 359-1660. When you receive the shipment, inspect the container and equipment for any signs of damage. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
NOTE
ASSOCIATED EQUIPMENT Caution: The intrinsically safe relays can be installed in panel assem-
blies in Class I, Div.2, Groups A, B, C and D or in a non-hazardous location. Only the sensor's terminals provide an intrinsically safe switch circuit (Fig. 1, 2). (Exia) means associated equipment "Appareilage connexe", located in safe area.
MOUNTING AND ENCLOSURE CONSIDERATION
Field wiring of intrinsically safe circuits is to be segregated from
non-intrinsically safe wiring by use of suitable barriers, separate wireways or trays (see Fig. 3).
Intrinsically safe and non-intrinsically safe connection points should
be located sufficiently apart to prevent any possibility of bypassing or miswiring during installation or servicing of equipment.
The enclosure shall contain a cautionary statement as follows:
"CAUTION: ANY SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY".
The mounting plate must be grounded to ensure intrinsic safety.
Resistance between the plate and earth ground should be less than one ohm. (See Figs. 4 and 5 for recommended selection of grounding hardware and refer to Article 250 of the National Electrical Code for methods and practice.)
INSTALLATION OF SENSOR SWITCH AND ASSOCIATED FIELD WIRING
The nature of the sensor switch must be that it is a non-voltage-
producing, essentially resistive termination or other device specifically examined and approved for use with the intrinsically safe solid-state relay.
The conductors of the intrinsically safe circuit should be sealed in a
rigid metal conduit at the point where the wiring enters the hazardous area. The wiring and sensor switch should be such that conductive dusts in the hazardous area will not close the circuit.
Hazardous area field wiring will store energy due to distributed
capacitance and inductance in proportion to its length. It is therefore recommended that the characteristics of the cable be known and judged against the length of run and atmosphere of exposure. The following chart is presented as a guideline in determining the limits of reactance for signal loops in the hazardous area wiring for the intrinsically safe solid-state relays.
SBG22445, SBG25872, SBG25873 and SBG41705 Solid-
Important: Read carefully and completely before installing or connecting the solid-state relays.
WARNING
3 mH 10mH 20mH
GROUP
A & B
C D
CAPACITANCE
0.1 µF
0.2 µF
0.3 µF
Product must be maintained and installed in strict accor­dance with the National Elec­trical Code. Failure to observe this warning could result in serious injuries or damages.
INDUCTANCE
Fuse F1
Input
VAC
Fuse
F1
Sensor Switch
Note: For 120V application, only one fuse is required in the ungrounded circuit of the input line.
Load
(EXIA)
Non-Hazardous Location
Hazardous Location
Fig. 1. Connection Diagram
(All Models Except SBG41705)
VAC
Sensor Switch
Load
AC
Latching Solid-State
Relay SBG41705
On
Off
C
LOAD
Non-Hazardous Location
Hazardous Location
Fig. 2. Connection Diagram: Model SBG41705
Earth
Ground
(2 Places)
Common
Earth-
Grounded
Mounting
Plate
Intrinsically Safe Wiring To Sensors
Note: All intrinsically safe wiring must be segregated from non-intrinsically safe wiring.
Resistance to ground must be from bracket to earthing member to insure integrity of system. (Must be below one ohm.)
Non-Intrinsically
Safe Wiring
Multiple
Units
Fig. 3. Multiple units grouped on a common, earth-grounded mounting plate.
Intrinsically Safe
Solid-State Relays
Example: Typical values of capacitance for a twisted pair of copper wires is between 20 and 60 pF per foot. Using the maximum value of 60pF/ft, Groups A & B could have a run of 1500+ feet with safety. Inductance of a typical twisted pair is between 0.10 and 0.20 µH/ ft, thus making a cable run in this example essentially determined by the capacitance.
Whenever possible, the actual measured parameters should be
used in making the determination of allowable length.
Shielded cable is not required, but if used in the application, the
shield must be returned to ground, the same point at mounting tab.
#10 Screw
#10 Lockwasher*
Mounting
Plate
*(Lockwashers to be internal or external tooth type)
#10 Lockwasher*
#10 Nut
Fig. 4. Unit Mounting Detail
Non-intrinsically safe wiring cannot be run in conduit or open
raceways together with intrinsically safe wiring.**
Refer to Fig 6 for detailed connection to terminal studs. All
hardware, including terminal lugs, is supplied with unit.
Fusing of the solid-state relays to be in accordance with
Fig. 1. Fuse F1 to be 6 amps slo-blo, 120 VAC for 120V line voltage; 250 VAC for 240 V application.
**
Note: All intrinsically safe wiring to intrinsically safe solid-state
relays must be segregated from non-intrinsically safe wiring.
Stud Cover
Terminals
Nylon
Stud Nuts
Stud
Cover
Terminals
Nylon
Stud Nuts
Mounting
Plate
Lockwasher*
Nut
Lockwasher*
Screw
Lockwasher*
Nut
Terminal Lug
Notes:
1. *(Lockwasher to be internal or external tooth type)
2. Grounding hardwre to be #8 or larger and S.S.
Fig. 5. Mounting Plate Grounding Detail
HEX Nut
Anti-Vibrational
Lockwasher
(Tighten assembly to between 3 and 5 in-lbs.)
Terminal Lug
(Closed Ring Type)
Terminal Stud
Fig. 6 Recommended method of connection to electrical terminals. All terminal hardware, including lug, supplied with unit.
Latching
Solid-State Relay
Non-Latching
Solid-State Relay
Fig. 7. Mounting of protective cover over sensor-connected terminals of unit.
7/32" Dia. (5.5 mm)
2-5/8"
(66.6 mm)
Mounting
Tab
3"
(76 mm)
1-5/8"
(41.3mm)
2-1/4"
(55mm)
3-1/8"
(79mm)
13/16"
(20.7mm)
Fig. 8.
Dimensions
Table 1. Specifications
Model
Number
SBG22445 SBG25872
SBG25873
SBG41705
Description
SSR for Intrinsic
Safety
Latching SSR
for Intrinsic
Safety
Line & Load
Voltage
Range
95 to
135 VAC
200 to
250 VAC
105 to
125 VAC
All AC voltage and current specifications are RMS values unless otherwise stated. Housing material is Polysulfone.
Load
Current
Max
5A
0.3 A
Steady
State
Turn-On
Sensitivity
(Typical)
< 400 K
< 25 K
Turn-Off
Sensitivity
(Typical)
1 meg.
1 meg.
Voltage
Loss
2 VAC
2 VAC
Operating
Temperature
Range
0° to +120°F
+32° to +120°F
Output
Leakage
Current Max.
6mA @
120 VAC 12 mA @
250 VAC
3 mA @
120 VAC
Switching Operation
SPST N.O. SPST N.C.
SPST N.O.
SPST N.O.
Weight
425g
425g
P/N 158350
Loading...