Omega DRST-UR User Manual

Page 1
TM
Shop online at
omega.com
e-mail: info@omega.com
For latest product manuals:
www.omegamanual.info
Universal Transmitter with Relays
DRST-UR
Page 2
omega.com info@omega.com
Servicing North America:
U.S.A. Omega Engineering, Inc. Headquarters: Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only) Engineering Service: 1-800-872-9436 (USA & Canada only) Tel: (203) 359-1660 Fax: (203) 359-7700 e-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
Page 3
Table of
Contents
DRST-UR
Table of Contents
Section ........................................................................ Page
Section 1 Warning .......................................................................................... 5
Section 2 Symbol Identification .................................................................. 6
Section 2.2 Safety Instructions ....................................................... 6
Section 3 How to dismantle DRST-UR ...................................................... 8
Section 3.2 Front LED lights red/display shows AO.ER .......... 8
Section 4 Features ........................................................................................... 9
Section 4.1 Universal Transmitter DRST-UR .............................. 9
Section 4.2 Advanced features ...................................................... 9
Section 4.3 Application ................................................................... 9
Section 4.4 Technical characteristics ............................................. 9
Section 5 Display Characteristics ............................................................. 10
Section 5.1 Functionality .............................................................. 10
Section 5.2 Application ................................................................. 10
Section 5.3 Technical characteristics (display) .......................... 10
Section 5.4 Mounting/installation .............................................. 10
Section 6 Mounting / demounting ............................................................ 11
Section 7 Inputs Application ...................................................................... 12
Section 8 Order codes / Specifications ............................................... 13-16
Section 8.2 Electrical specifications ............................................ 13
Section 9 Visualisation in the DRSL-DISPLAY of sensor error detection 17
Section 10 Error Indications ......................................................................... 18
Section 11 Connections ................................................................................. 19
Section 12 Block Diagram ............................................................................. 20
Section 13 Configuration / operating the function keys ......................... 21
Section 14 Signal & Sensor error display ................................................... 22
3
Page 4
DRST-UR
Table of Contents
Section ........................................................................ Page
Section 15 Latch ............................................................................................... 23
Section 15.1 Manual deactivation of the latch .......................... 24
Section 15.2 Advanced functions ................................................ 24
Section 15.3 Display setup ........................................................... 24
Section 15.4 Two-point process calibration ............................... 24
Section 15.5 Process simulation function ................................... 24
Section 15.6 Password .................................................................. 24
Section 15.7 Language .................................................................. 24
Section 16 Auto Diagnosis ............................................................................ 25
Section 17 Units/safety/memory .................................................................. 26
Section 18 Routing diagram .................................................................... 27-32
Section 18.1 Routing Diagram ............................................... 27-30
Section 18.2 Advanced settings ................................................... 31
Section 18.3 Manual Deactivation .............................................. 32
Section 19 Scrolling help text in Display ................................................... 33
Section 20 Graphic Depication of Latch ..................................................... 34
Section 20.1 latch function setpoint ............................................ 35
Section 20.2 latch function window ........................................... 35
Section 20.3 Relay action setpoint ............................................... 36
Section 20.4 Relay action window .............................................. 36
Section 21 Displays .................................................................................. 37-38
Table of
Contents
Page 5
1
GENERAL
HAZARD OUS
VOLTAGE
Warning
WARNING
This device is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instructions of this manual must be observed and the guidelines followed. The specifications must not be exceeded, and the device must only be applied as described in the following. Prior to the commissioning of the device, this manual must be examined carefully. Only qualified personnel (technicians) should install this device. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
WARNING
Until the device is fixed, do not connect hazardous voltages to the device. The following operations should only be carried out on a disconnected device and under ESD safe conditions:
• Dismantlement of the device for setting of DIP-switches and jumpers.
• General mounting, connection and disconnection of wires. Troubleshooting the device.
INSTALLATION
Repair of the device and replacement of circuit breakers must be done by A/S only.
WARNING
To keep the safety distances, the relay contacts on the device must not be connected to both hazardous and non-hazard ous volt ages at the same time. SYSTEM 4000 must be mounted on a DIN rail according to DIN 46277.
WARNING
Do not open the front plate of the device as this will cause damage to the connector for the display/programming front Omega DRSL-DISPLAY. This device contains no DIP-switches or jumpers.
5
Page 6
2
Symbol Identification
Section 2.1 - Symbol Identification
Triangle with an exclamation mark: Warning/demand. Potentially lethal situations.
The CE mark proves the compliance of the device with the essential requirements of the directives.
The double insulation symbol shows that the device is protected by double or reinforced insulation.
Section 2.2 - Safety instructions
Definitions
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically correct and in
accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation.
Receipt and unpacking
Unpack the module without damaging it. The packing should always follow the module until this has been permanently mounted. Check at the receipt of the module whether the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. All devices fall under Installation Category II, Pollution Degree 1, and Insulation Class II.
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the device. Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
6
Page 7
Safety Instructions
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location. Descriptions of input / output and supply connections are shown in the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the device. The power switch should be marked with a label telling it will switch off the voltage to the device.
Year of manufacture can be taken from the first two digits in the serial number.
UL INSTALLATION REQUIREMENTS
Use 60/75°C copper conducters only For use only in pollution degree 2 or better
Max. ambient temperature ....... 60°C
Max. wire size ............................. AWG 26-14
UL file number ........................... E231911
2
Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use.
Normal operation
Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent that the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
7
Page 8
3
How to Dismantle DRST-UR
Section 3.1 - How to Dismantle DRST-UR
First, remember to demount the connectors with hazardous voltages. Picture 1: Detach the device from the DIN rail by lifting the bottom lock.
Section 3.2 - When front LED lights red / display shows AO.ER
Omega DRST-UR is designed as a SIL 2 device with a high safety level. Therefore, a continuous measurement of the outgoing current is carried out on a 4...20 mA and 20...4 mA output signal. If the current output signal is different from the internal calculated output value or the current output is 0 (due to e.g. an open circuit breakage), an error mode switches on the red front LED and disables the relays. This function is not a default option but must be actively selected via the programming menu (S4-20 & S20-4). The error mode can only be reset by switching off and then switching on the supply voltage to the device.
8
Page 9
Features
Section 4.1 - Universal Transmitter DRST-UR
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• FM-approved for installation in Div. 2
• Output for current, voltage and 2 relays
• Universal AC or DC supply
Section 4.2 - Advanced features
• Programmable via detachable display front (DRSL-DISPLAY), process calibration, signal and relay simulation, password protection, error diagnostics and selection of help text in several languages.
Section 4.3 - Application
• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analogue current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentio meter.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 pairs of potential-free relay contacts and analogue output.
• Galvanic separation of analogue signals and measurement of floating signals.
• The DRST-UR is designed according to strict safety requirements and is thus suit able for application in SIL 2 installations.
4
Section 4.4 - Technical characteristics
• When DRST-UR is used in combination with the DRSL-DISPLAY/programming front, all operational parameters can be modified to suit any application. As the DRST-UR is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP switches.
• A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 4-port 2.3 kVAC galvanic isolation.
9
Page 10
5
Display Characteristics
Section 5.1- Display / programming front
Functionality
The simple and easily understandable menu structure and the explanatory help texts guide you effortless ly and automatically through the configuration steps, thus making the product very easy to use. Functions and configuration options are described in the section ”Configuration / operating the function keys”.
Section 5.2 - Application
• Communications interface for modification of operational parameters in DRST-UR.
• Can be moved from one DRST-UR device to another and download the configuration of the first transmitter to subsequent transmitters.
• Fixed display for readout of process data and status.
Section 5.3 - Technical characteristics
• LCD display with 4 lines; Line 1 (H=5.57 mm) shows input signal, line 2 (H=3.33 mm) shows units, line 3 (H=3.33 mm) shows analogue output or tag no. and line 4 shows communication and relay status.
• Programming access can be blocked by assigning a password. The password is saved in the transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration.
Section 5.4 - Mounting / installation
• Click DRSL-DISPLAY onto the front of DRST-UR.
10
Page 11
Mounting/Demounting
Mounting / Demounting the DRSL-DISPLAY/DRST-UR
1: Insert the taps of DRSL-DISPLAY/DRST-CM into the holes at the top of the device.
2: Swing DRSL-DISPLAY/DRST-CM into place.
Demounting of DRSL-DISPLAY/DRST-UR
3: Push the release button on the bottom of DRSL-DISPLAY/DRST-UR and swing
DRSL-DISPLAY/DRST-UR up.
6
1
3
2
11
Page 12
7
Inputs Application
Input signals:
Volt -age
Current
Potentio meter
RTD and lin.R
Connect., wires
TC
44
+
-
Output signals:
+
-
*
-
+
Order separately: 5910 CJC connector. See the connection drawing on page 16.
43
42
41
Relays
12
14
13
11
+
-
10 V1V10 V
+
-
Analogue, 0/4...20 mA and voltage
+
-
1V
+
-
24
23
22
21
Supply:
21.6...253 VAC or
19.2...300 VDC
33
32
31
12
Page 13
Order codes / Specifications
Order codes
DRST-UR = Universal transmitter DRSL-DISPLAY = Display/programming front 5910 = CJC connector
Electrical specifications
Environmental conditions
Specifications range ....................... -20°C to +60°C
Calibration temperature ................ 20...28°C
Relative humidity ........................... < 95% RH (non-cond.)
Protection degree ........................... IP20
Mechanical specifications
Dimensions (HxBxD)...................... 109 x 23.5 x 104 mm
Dimensions, with DRSL-DISPLAY/DRST-CM (H x B x D), 109 x 23.5 x 116/131 mm
Weight .............................................. 170 g
Weight with DRSL-DISPLAY/DRST-CM 185 g / 270 g
Max. wire size ................................. 1 x 2.5 mm2 stranded wire
Screw terminal torque ................... 0.5 Nm
Vibration .......................................... IEC 60068-2-6 : 2007
2...13.2 Hz ..................................... ±1 mm
13.2...100 Hz ................................. ±0.7 g
Common specifications
Supply voltage, universal ............. 21.6...253 VAC, 50...60 Hz
or 19.2...300 VDC
Max. consumption ......................... 2.5 W
Fuse .................................................. 400 mA SB/250 VAC
Isolation voltage, test / operation 2.3 k VAC/250 VAC
Communications interface ............ Communication enabler DRST-CM
Programming front DRSL-DISPLAY
Signal / noise ratio ......................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input ..................... 1 s
mA / V input .............................. 400 ms
8
Accuracy, the greater of the general and basic values:
Input
type
All ±0.1% of span ±0.01% of span/°C
Absolute
accuracy
General values
Temperature
coefficient
13
Page 14
8
Order codes / Specifications
Section 8 - Inputs
Input
type
mA ±4 µA ±0.4 µA / °C
Volt ±20 µV ±2 µV / °C
Pt100 ±0.2°C ±0.01°C / °C
Linear resistance ±0.1 Ω ±0.01 Ω / °C
Potentiometer ±0.1 Ω ±0.01 Ω / °C
TC type:
E, J, K, L, N, T, U
TC type: R, S, W3, W5, LR
TC type: B
85...200°C
TC type: B
200...1820°C
Basic values
Basic
accuracy
±1°C
±2°C
±4°C
±2°C
Temperature
coefficient
±0.05°C / °C
±0.2°C / °C
±0.4°C / °C
±0.2°C / °C
EMC immunity influence ........ < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst ......... < ±1% of span
Auxiliary supplies: 2-wire supply (terminal 44...43) ... 25...16 VDC / 0...20 mA
RTD, linear resistance and potentiometer input
Input for RTD types: Pt10, Pt20, Pt50, Pt100, Pt200, PT250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
Input
type
Pt10...Pt1000 Ni50...Ni1000 Cu10...Cu100
Lin. R
Potentiometer
Cable resistance per wire (max.), RTD 50 Ω
Sensor current, RTD ....................... Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD ........................... < 0.002 Ω / Ω
Sensor error detection, RTD ......... Yes
Short circuit detection, RTD ......... < 15 Ω
Min.
value
-200°C
-60°C
-200°C 0 Ω
10 Ω
Max.
value
+850°C +250°C +260°C
10000 Ω
100 kΩ
Standard
IEC 60751
DIN 43760
α = 0,00427
-
-
14
Page 15
Section 8.2 - TC Input
Order codes / Specifications
8
Type
B E
J K L N R
S T U
W3 W5
LR
Cold junction compensation (CJC):
via external sensor in connector 5910 20...28°C ≤ ±1°C
-20...20°C / 28...70°C ≤±2°C
via internal CJC sensor ............... ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types: Yes Sensor error current:
when detecting ............................. Nom. 2 μA
else .................................................. 0 μA
Current input
Measurement range ....................... 0...20 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance .............................. Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA .................. Yes
Voltage input
Measurement range ....................... 0...12 VDC
Programmable measurement ranges 0...1 / 0.2...1 / 0...5 / 1...5 /
0...10 and 2...10 VDC
Input resistance .............................. Nom. 10 MΩ
Min.
value
0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C 0°C 0°C
-200°C
Max.
value
+1820°C +1000°C +1200°C +1372°C
+900°C +1300°C +1760°C +1760°C
+400°C
+600°C +2300°C +2300°C
+800°C
Standard
IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710 IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710
ASTM E988-90 ASTM E988-90
GOST 3044-84
15
Page 16
8
Order codes / Specifications
Current output
Signal range (span) ........................ 0...20 mA
Programmable signal ranges ........ 0...20 / 4...20 / 20...0 and 20...4 mA
Load (max.) ..................................... 20 mA / 800 Ω / 16 VDC
Load stability .................................. 0.01% of span / 100 Ω
Sensor error detection .................... 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale 23 mA / 3.5 mA Output limitation: on 4...20 and 20...4 mA signals .. 3.8...20.5 mA on 0...20 and 20...0 mA signals .. 0...20.5 mA
Current limit ................................... 28 mA
Voltage output
Signal range..................................... 0...10 VDC
Programmable signal ranges ........ 0...1 / 0.2...1 / 0...10 / 0...5 /
1...5 / 2...10 / 1...0 / 1...0.2 / 5...0 /
5...1 / 10...0 og 10...2 V
Load (min.) ...................................... 500 kΩ
Relay outputs
Relay functions ............................... Setpoint, Window, Sensor error,
Latch, Power and Off
Hysteresis ........................................ 0...100%
On and Off delay ............................ 0...3600 s
Sensor error detection .................... Break / Make / Hold
Max. voltage .................................... 250 VRMS
Max. current .................................... 2 A / AC or 1 A / DC
Max. AC power .............................. 500 VA
Ex / I.S. approval
FM, applicable in ............................ Class I, Div. 2, Group A, B, C, D
Class I, Div. 2, Group IIC Zone 2 Max. ambient temperature for T5 60°C
Marine approval
Det Norske Veritas, Ships & Offshore Standard for Certification No. 2.4
Observed authority requirements Standard
EMC 2004/108/EC ........................ EN 61326-1
LVD 2006/95/EC ........................... EN 61010-1
FM..................................................... 3600, 3611, 3810 and ISA 82.02.01
UL, Standard for Safety ................. UL 508
EAC TR-CU 020/2011 ................... EN 61326-1
of span = of the currently selected measurement range
16
Page 17
Visualisation in the DRSL-DISPLAY of sensor error detection
Section 9 - Visualisation in the DRSL-DISPLAY of sensor error detection and input signal outside range
Sensor error check:
Device: Configuration Sensor error detection:
R1, ERR.ACT=NONE - R2, ERR.
ACT=NONE,
DRST-UR
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input Range Readout Limit
0...1 V / 0.2...1 V
VOLT
0...10 V / 2...10 V
CURR 0...20 mA / 4...20 mA
0...800 Ω
LIN.R
0...10 kΩ
POTM -
TEMP TC / RTD
OUT.ERR=NONE.
Else: ON
IN.LO < -25 mV
IN.HI > 1.2 V
IN.LO < -25 mV
IN.HI > 12 V
IN.LO < -1.05 mA
IN.HI > 25.05 mA
IN.LO < 0 Ω
IN.HI > 1075 Ω
IN.LO < 0 Ω
IN.HI < 110 kΩ
IN.LO < -0.5 %
IN.HI > 100.5 %
IN.LO < temperature range -2°C
IN.HI > temperature range +2°C
OFF
9
Display readout below min.- / above max. (-1999, 9999):
Input Range Readout Limit
All All
-1999 Display readout <-1999
9999 Display readout >9999
Sensor error detection limits
Sensor error detection (SE.BR, SE.SH):
Input Range Readout Limit
CURR Loop break (4..20 mA) SE.BR <= 3.6 mA; > = 21 mA
POTM All, SE.BR on all 3-wire SE.BR > ca. 126 kΩ
LIN.R
TEMP
No SE.SH for Cuxx, Pt10, Pt20 and Pt50
0...800 Ω SE.BR > ca. 875 Ω
0...10 kΩ SE.BR > ca. 11 kΩ
TC SE.BR > ca. 750 kΩ / (1.25 V)
RTD, 2-, 3-, and 4-wire
SE.BR > ca. 15 kΩ SE.SH < ca. 15 Ω
17
Page 18
10
Error Indications
Section 10.1 - Error indications
Readout at hardware error
Error search Readout Error cause
Test of internal CJC sensor CJ.ER
Checksum test of the configuration in FLASH FL.ER Error in FLASH
Check measurement of analogue output current AO.ER
Communications test DRSL-DISPLAY/DRST-UR NO.CO Connection error Check that input signal matches input configuration IN.ER 1) Error levels on input Check that saved configuration in DRSL-DISPLAY matches device TY.ER Configuration is not DRST-UR
! Error indications in the display flash once per second. The help text explains the error.
1) The error is reset by switching off and then switching on the supply voltage to the device.
CJC sensor defect or temperature
outside range
1) No load on the current output (only S4...20/S20...4 mA)
18
Page 19
Connections
Section 11 - Connections
Supply:
31 32 33
Inputs:
TC, internal
RTD, 2-wire Resistance, 2-wire
41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44
RTD, 3- / 4-wire
CJC sensor
-+
11
Resistance,
3- / 4-wire
41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44
Voltage
41 42 43 44 41 42 CJC 44
- +
Potentiometer
*TC, CJC connector
-
+
- +
Tx
* Order separately:
CJC connector 5910
Current2-wire transmitter
- +
Outputs:
Voltage, 1 V Voltage, 10 VCurrent Relays
11 12 13 14 11 12 13 14 11 12 13 14
- + - + - +
mA
V V
21 22 23 24
R1 R2
19
Page 20
12
Block Diagram
Order separately: CJC connector 5910
2-wire transmitter
+
-
RTD og lin.R,
connection,
Voltage
Current
+
-
Potentiome ter
wires
TC
24 3
44
43
*
42
-
+
41
CJC
0.2 mA
MUX
V
loop
CPU
A / D
D / A
33
31
12
14
13
Supply
21.6...253 VAC or
19.2...300 VDC
Supply
I+
mA
10 V
1 V
mA
Safety
PTC
Red
Ω
50.0
l / min
VALVE 5
Green
20 Ω
21
EEPROM
DRST-UR
500
Yellow
Yellow
50 W
11
24
23
22
21
V V
I-
I + V Out.I Out.V Out.
Relay 2
Relay 2
Relay 1
Relay 1
20
Page 21
CONFIGURATION/OPERATING THE FUNCTION KEYS
13
Section 13.1 - Configuration / operating the function keys
Documentation for routing diagram.
In general
When configuring the DRST-UR, you will be guided through all parameters and you can choose the settings which fit
the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
will increase the numerical value or choose the next parameter
will decrease the numerical value or choose the previous parameter
OK
will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding will return to the previous menu or return to the default state (1.0) without saving the changed
values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) without saving the changed values or
parameters.
Further explanations
Fast setpoint adjustment and relay test: These menus allow you to make a quick setpoint change and relay test when
the FastSet menu is activated. This function can only be activated when the relays are set for setpoint function and are controlled by a setpoint.
Pressing and simultaneously will activate a relay test and change the state of the relay.
Pressing will save the setpoint change.
OK
Holding down for more than 1 second will return the unit to the default state without saving the setpoint change.
Password protection: Programming access can be blocked by assigning a password. The password is saved in the
transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration. Default password 2008 allows access to all configuration menus.
OK
OK
21
Page 22
13
Signal & sensor error display
Section 13.1 - Signal and sensor error info via display front DRSL-DISPLAY
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH (sensor short). Signals
outside the selected range (not sensor error, see table for limits) are displayed as IN.LO indicating low input signal or IN.HI indicating high input signal. The error indication is displayed in line 3 as text and at the same time the backlight flashes. Line 4 of the display is a status line which displays status of relay 1 and relay 2, COM (flashing bullet) indicating correct functioning of DRSL-DISPLAY and arrow up/down which indicates tendency readout of the input signal. If the figure 1 or figure 2 flashes, the unit has detected that the setpoint has been exceeded and that the relay is in “delay” mode. When the delay time has passed and the relay makes/breakes, the relay sign either displays or disappears.
Signal and sensor error indication without display front
Status of the unit can also be read from the red/green LED in the front of the device.
Green flashing LED 13 Hz indicates normal operation. Green flashing LED 1 Hz indicates sensor error. Steady red LED indicates internal error.
Relay functions
6 different settings of relay function can be selected.
Setpoint: The unit works as a single limit switch Window: The relay has a window that is defined by a low and a high
setpoint. On both sides of the window the relay has the same status. Error function: The relay is activated by sensor error.
Power: The relay is activated as long as the power is on. Off: The relay is deactivated. Latch: The relay is latched. Only valid for setpoint and window
function.
Increasing/decreasing: The relays can be set to activate at increasing or decreasing input signal. Delay: An ON and an OFF delay can be set on both relays in the range
0...3600 s.
Hysteresis: 0.0...100.0%.
22
Page 23
Latch
15
Latch
When the setpoint is exceeded the relay outputs enters an alarm state. The latch function of the DRST-UR will
hold the relays in this state until the function is deactivated manually. The latch function can be applied when the relay function setpoint or window is selected.
The latch function can be selected separately for each relay output. If the configuration is copied from one
device to another by way of the DRSL-DISPLAY, the latch function must be reconfigured.
The latch function activates and holds the relays when the input signal rises above or falls below the selected
setpoints and the relay action has been selected as increasing or decreasing. The window function is selected by choosing ”window” in the menu and defining a high and a low setpoint. It can be selected for each relay contact whether the contact is open or closed inside the window. This
selection is made in the menu R1.cont and R2.cont. The setpoint function is selected by choosing ”setpoint” in the menu and entering the desired limit. The
device then works as a single limit switch. An activated relay means that the contact is closed if the contact function ”normally open” is selected, and the
contact is open if the contact function ”normally closed” is selected. The delay time for activation and deactivation can be set independently of each other in the menus ON.DEL
and OFF DEL respectively. If the relay function ”Error” is active, the relay will latch when a sensor error occurs and will not be
deactivated automatically when the sensor error is rectified. The relay can only be deactivated by an operator and only when the normal conditions for deactivation are
met. If the input signal still has a value that will activate the relay, the relay will latch again. See the graphic depiction of the setpoint and window functions on pages 34 and 35.
23
Page 24
15
Latch
Section 15.1 - Manual deactivation of the latch function
If the relay outputs are activated and thereby latched, it will be indicated in the display. The backlight flashes and
the scrolling help text tells you how to deactivate the output. Manual deactivation is carried out by way of the front buttons on the DRSL-DISPLAY. Use and to navigate in the menu and to validate your selection. If the password protection has been activated, the password must be entered in order to access the deactivation menu. See the menu structure on page 29.
Section 15.2 - Advanced functions
The device gives access to a number of advanced functions which can be reached by answering “Yes” to the point
“adv.set”.
Section 15.3 - Display setup: Here you can adjust the brightness contrast and the backlight. Setup of TAG numbers with 6 alphanumerics.
Selection of functional readout in line 3 of the display - choose between readout of analogue output or tag no.
Section 15.4 - Two-point process calibration: The device can be process-calibrated in 2 points to fit a given input signal . A low input signal (not necessarily
0%) is applied and the actual value is entered via DRSL-DISPLAY. Then a high signal (not necessarily 100%) is applied and the actual value is entered via DRSL-DISPLAY. If you accept to use the calibration, the device will work according to this new adjustment. If you later reject this menu point or choose another type of input signal the device will return to factory calibration.
OK
Section 15.5 - Process simulation function: If you agree to the point “EN.SIM” it is possible to simulate an input signal by means of the arrow keys and thus
control the output signal up or down. When you finalise the point with , the device returns to normal mode.
OK
The following point allows you to activate relay 1 and relay 2 by means of the arrow-keys up/down. You must exit the menu by pressing (no time-out).
OK
Section 15.6 - Password: Here you can choose a password between 0000 and 9999 in order to protect the device against unauthorised
modifications to the configuration. The device is delivered default without password. If you have locked the device with a password by mistake, you can always open the menu by using the master password 2008.
Section 15.7 - Language: In the menu ”lang.setup” you can choose between 7 different language versions of help texts that will appear in the
menu. You can choose between UK, DE, FR, IT, ES, SE and DK.
24
Page 25
Auto Diagnosis
Section 16 - Auto diagnosis
The device performs an advanced auto diagnosis of the internal circuits.
The following possible errors can by displayed in the front unit DRSL-DISPLAY. CJ.ER - CJC sensor defect or CJC temperature outside range FL.ER - Flash error AO.ER - No load on the current output (only for S4...20 mA / S20...4 mA) NO.CO - Connection error IN.ER - Error levels on input TY.ER - Configuration in DRSL-DISPLAY does not match this product type
16
25
Page 26
17
Units/Safety/Memory
Section 17.1 - Selection of units
After choosing the input signal type you can choose which process units should be displayed in text line 2 (see
table). By selection of temperature input the process value is always displayed in Celsius or Fahrenheit. This is selected in the menu point after selection of temperature input.
Section 17.2 - Safety readback
When the device is delivered with default configuration, the SIL function is disabled. The safety readback
function (loop surveillance) can be selected in the menu O.RANGE, thus enabling the device to run in SIL mode. In order to enable the SIL functionality, the menu item S4...20 mA must be selected. Please note, however, that when safety readback is enabled, a sensor error will be indicated as an error on the analogue output signal.
Section 17.3 - CJC
In the CJC menu you can choose between CJC connector and internal cold junction compensation. The CJC
connecter (PR 5910) must be ordered separately.
Section 17.4 - Memory
In the memory menu you can save the configuration of the device in the DRSL-DISPLAY, and then move
the DRSL-DISPLAY onto another device of the same type and download the configuration in the new device.
26
Page 27
18
Routing Diagram
Power up
1.2
12.0
OK
%
0000 9999
50.0
1.0
50.0
RELAY1
Txt 57
75.0
RELAY2
Txt 57
NO YES
OK
OK
Fast setpoint adjustment
and relay test
Increase setpoint
Decrease setpoint
OK
Save and exit the menu
and simultaneously = change relay state
VOLT CURR POTM LIN.R TEMP
2-10 0-10
1-5 0-5
0.2-1 0-1
@C mA rpm
(69 units)
1111
111.1
11.11
1.111
999.9
-199.9
0000
PASSW.
Txt 1
1.1
1.0 = ...................................................
Default state Line 1 shows input signal. Line 2 shows UNIT. By pressing and simultaneously line 3 alternates between A.Out and TAG. Line 4 shows relay and communication status.
1.1 = ...................................................
Only if password­ protected.
1.2 = ...................................................
Only if FastSet is acti­ vated and the relay function is setpoint.
1.3 = ...................................................
Not valid for these input signals: 0...20 mA and voltage.
1.4 = ...................................................
Only if input signal is temperaure.
1.5 = ...................................................
The relay can only be deactivated by an ope­ rator and only if the normal conditions for deactivation are met. If the input signal still has a value that will activate the relay, the relay will latch again.
OK
NO
ADV.SET
Txt 2
OK
VOLT
IN TYPE
Txt 3
CURR
IN TYPE
Txt 3
POTM
IN TYPE
Txt 3
LIN.R
IN TYPE
Txt 3
TEMP
IN TYPE
Txt 3
OK
OK
OK
OK
OK
2-10
V.RANGE
Txt 4
0-20 4-20
4-20
I.RANGE
Txt 5
2W 3W 4W
3W
CONNEC.
Txt 6
OK
UNIT
Txt 11
OK
0...9999
OK
Cu Pt Ni TC
SENSOR
SENSOR
SENSOR
OK
%
OK
0
R 0% Txt 7
OK
Pt
Txt 10
OK
Ni
Txt 10
TC.B TC.E TC.J TC.K TC.L TC.N TC.R TC.S TC.T TC.U TC.W3 TC.W5 TC.Lr
OK
TC
Txt 10
111.1
DEC.P Txt 12
0...9999
2500
R 100%
Txt 8
10...1000
100
Pt TYPE
Txt 16
50...1000
100
Ni TYPE
Txt 17
TC.K
TC.TYPE
Txt 18
OK
OK
OK
OK
OK
0.0
DISP.LO
Txt 13
2W 3W 4W
3W
CONNEC.
Txt 6
2W 3W 4W
3W
CONNEC.
Txt 6
INT
CJC
Txt 63
Continued on the page Routing diagram ADV.SET
YES
ADV.SET
Txt 2
OK
Cu
SENSOR
Txt 10
10...100
OK
10
Cu TYPE
Txt 69
OK
2W 3W 4W
3W
CONNEC.
Txt 6
27
Page 28
Routing Diagram
Section 18.1 - Routing diagram
If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes.
Increase value / choose next parameter Decrease value / choose previous parameter Accept the chosen value and proceed to the next menu
OK
OK
Hold Back to previous menu / return to menu 1.0 without saving
SETP
WIND
ERR
999.9
-199.9
DISP
PERC
POW
OFF
N.O. N.C.
100.0
0.0
INCR DECR
100.0
0.0
18
1.0
Txt 23
100.0
0.0
1.0
Txt 30
OK
OK
Txt 15
OK
SETP
R1.FUNC
WIND
R1.FUNC
Txt 19
Txt 19
OK
N.O.
R1.CONT
OK
O.I.W
R1.CONT
OK
100.0
DISP.HI
Txt 14
OK
PERC
REL.UN
1.3
OK
ERR
R1.FUNC
Txt 19
OK
POW
R1.FUNC
Txt 19
OFF
R1.FUNC
OK
Txt 19
Selectable
@C
@F
% A
bar
cm
ft
ft/h
ft/min
ft/s
g
gal/h
gal/min
GW
hp
hPa
Hz
in
in/h
in/min
in/s
OK
1 2
@C @F
@C
UNIT
Txt 9
OK
OK
OPEN
ERR.ACT
OK
OK
UNITS:
Txt 20
O.I.W
C.I.W
Txt 27
CLOS OPEN
1 2
Txt 34
ips
K kA kg
kJ
kPa
kV
kW
kWh
l
l/h
l/min
l/s
m
m/h
m/min
m/s
m/s2
m3
m3/h
m3/min
OK
R1.SETP
100.0
OK
SETP.LO
OK
50.0
Txt 21
0.0
60.0
Txt 29
mA
mbar
mils min mm
mm/s
mol MPa
mV
MW
MWh
N
Ohm
Pa
pH
rpm
s S t
t/h
uA
OK
INCR
ACT.DIR
OK
SETP.HI
Txt 22
100.0
0.0
70.0
Txt 28
OK
R1.HYST
OK
R1.HYST
Continued on the next page
um
uS
V
W
Wh
yd
[blank]
28
Page 29
18
HOLD CLOS OPEN NONE
Routing Diagram
3600 0000
3600 0000
SETP
WIND
ERR
POW
OFF
N.O. N.C.
100.0
0.0
INCR DECR
100.0
0.0
1.3
1.3
NONE
ERR.ACT
Txt 24
HOLD CLOS OPEN NONE
NONE
ERR.ACT
Txt 31
OK
OK
0
ON.DEL
Txt 25
3600 0000
0
ON.DEL
Txt 32
OK
OK
0
OFF.DEL
Txt 26
3600 0000
0
OFF.DEL
Txt 33
OK
SETP
R2.FUNC
Txt 19
OK
WIND
R2.FUNC
Txt 19
N.O.
OK
R2.CONT
Txt 20
O.I.W C.I.W
OK
O.I.W
R2.CONT
Txt 27
CLOS OPEN
OK OK
OK OK
50.0
R2.SETP
Txt 21
100.0
0.0
60.0
SETP.LO
Txt 29
INCR
ACT.DIR
Txt 22
70.0
SETP.HI
Txt 28
100.0
OK
0.0
OK
1.0
R2.HYST
Txt 23
100.0
0.0
1.0
R2.HYST
Txt 30
1.3
ERR
R2.FUNC
Txt 19
POW
R2.FUNC
Txt 19
OK
OPEN
ERR.ACT
Txt 34
OK
OK
OFF
R2.FUNC
Txt 19
OK
29
Page 30
HOLD
CLOS OPEN NONE
3600 0000
3600 0000
VOLT CURR
S20-4
20-4 20-0
S4-20
4-20 0-20
Routing Diagram
23mA
0/3.5mA
NONE
850
-200
18
850
-200
NONE
OK
ERR.ACT
Txt 24
OK
0
ON.DEL
Txt 25
OK OK
0
OFF.DEL
Txt 26
CURR
ANA.OUT
Txt 36
OK
4-20
O.RANGE
Txt 37
1.3
HOLD
CLOS OPEN NONE
1 2
OK
NONE
ERR.ACT
Txt 31
OK
3600 0000
1 2
0
ON.DEL
Txt 32
3600 0000
1 2
OK
0
OFF.DEL
Txt 33
OK
10-2 10-0
5-1 5-0
1-0.2
1-0 2-10 0-10
1-5
0-5
0.2-1 0-1
OK
23mA
OUT.ERR
Txt 38
1.3
OK OK
0.0
OUT.LO
Txt 41
1.4 1.4
To default state 1.0
150.0
OUT.HI
Txt 42
OK
1.3
VOLT
ANA.OUT
Txt 36
OK OK
0-10
O.RANGE
Txt 39
30
Page 31
18
Routing Diagram
Section 18.2 - Advanced settings (Routing diagram)
Advanced settings (ADV.SET)
9
A
VALVE 5
Txt 47
YES NO
YES
CAL.HI
Txt 50
OK
OK
OK OK
NO
TAG
A.OUT
A.OUT
LINE 3
Txt 48
100.0
90.0
Txt 62
2.0 In the submenu simulation (SIM) you must press to return to the default state 1.0.
MEM
DISP CAL
SIM
PASS
LANG
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
CAL
SETUP
Txt 43
SAVE
LOAD
OK
SAVE
MEMORY
Txt 44
9 0
OK
OK OK
3
CONTRA
Txt 45
YES NO
YES
CAL.LO
Txt 49
OK
9 0
OK
LIGHT
Txt 46
100.0
2.0
Txt 61
NO
OK
9
0.0
OK
%
OK
0.0
%
YES NO
YES
USE.CAL
Txt 60
OK
SIM
SETUP
Txt 43
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
LATC
SETUP
YES NO
OK OK
YES
EN.SIM
Txt 51
2.0
YES NO
OK
YES
EN.PASS
Txt 54
DE, DK,
ES, FR,
IT, SE,
UK
OK
UK
LANGUA
Txt 59
YES
NO
OK
NO
R1.LATC
100.0
0.0
25.0
Txt 52
NO
9999 0000
OK
0000
NEW.PAS
Txt 55
NO
OK
YES NO
OK
NO
R2.LATC
OK
%
REL.SIM
Txt 53
YES
NO
OK
YES
EN.FAST
Txt 56
OK
OK
OK
To default state 1.0
31
Page 32
Routing Diagram
Section 18.3 - Manual deactivation (Routing diagram)
Manual deactivation of the latch function
YES
NO
To setup menu
40.0
Rx.LATC
Txt 65
OK
OK
NO
ENT.SET
Txt 67
OK
18
R1 reset
40.0
R1.LATC
Txt 65
R2 reset
40.0
R2.LATC
Txt 65
0000 9999
OK
40.0
R1.LATC
Txt 65
0000
PASSW
Txt 1
OK OK
YES
NO
NO
R1.RLSE
Txt 66
To default state 1.0
1.1 1.5
40.0
R2.LATC
Txt 65
1.1
0000 9999
0000
PASSW
Txt 1
OKOK
1.5
YES NO
NO
R2.RLSE
Txt 66
OK
32
Page 33
19
Scrolling Help Text in Display
Section 19 - Scrolling help text in display line 3
[01]
Set correct password
[02]
Enter advanced setup menu?
[03]
Select temperature input Select potentiometer input Select linear resistance input Select current input Select voltage input
[04]
Select 0.0-1 V input range Select 0.2-1 V input range Select 0-5 V input range Select 1-5 V input range Select 0-10 V input range Select 2-10 V input range
[05]
Select 0-20 mA input range Select 4-20 mA input range
[06]
Select 2-wire sensor connection Select 3-wire sensor connection Select 4-wire sensor connection
[07]
Set resistance value low
[08]
Set resistance value high
[09]
Select Celsius as temperature unit Select Fahrenheit as temperature unit
[10]
Select TC sensor type Select Ni sensor type Select Pt sensor type Select Cu sensor type
[11]
Select display unit
[12]
Select decimal point position
[13]
Set display range low
[14]
Set display range high
[15]
Set relays in % of input range Set relays in display units
[16]
Select Pt10 as sensor type Select Pt20 as sensor type Select Pt50 as sensor type Select Pt100 as sensor type Select Pt200 as sensor type Select Pt250 as sensor type Select Pt300 as sensor type Select Pt400 as sensor type Select Pt500 as sensor type Select Pt1000 as sensor type
[17]
Select Ni50 as sensor type Select Ni100 as sensor type Select Ni120 as sensor type Select Ni1000 as sensor type
[69]
Select Cu10 as sensor type Select Cu20 as sensor type Select Cu50 as sensor type Select Cu100 as sensor type
[18]
Select TC-B as sensor type Select TC-E as sensor type Select TC-J as sensor type Select TC-K as sensor type Select TC-L as sensor type Select TC-N as sensor type Select TC-R as sensor type Select TC-S as sensor type Select TC-T as sensor type Select TC-U as sensor type Select TC-W3 as sensor type Select TC-W5 as sensor type Select TC-Lr as sensor type
[19]
Select OFF function - relay is permanently off Select POWER function - relay indicates power status OK Select ERROR function - relay indicates sensor error only Select WINDOW function - relay controlled by 2 setpoints Select SETPOINT function - relay controlled by 1 setpoint
[20]
Select Normally Closed contact Select Normally Open contact
[21]
Set relay setpoint
[22]
Activate relay on decreasing signal Activate relay on increasing signal
[23]
Set relay hysteresis
[24]
No error action - undefined status at error Open relay contact at error Close relay contact at error Hold relay status at error
[25]
Set relay ON delay in seconds
[26]
Set relay OFF delay in seconds
[27]
Relay contact is Closed Inside Window Relay contact is Open Inside Window
[28]
Set relay window setpoint high
[29]
Set relay window setpoint low
[30]
Set relay window hysteresis
[31]
No error action - undefined status at error Open relay contact at error Close relay contact at error Hold relay status at error
[32]
Set relay ON delay in seconds
[33]
Set relay OFF delay in seconds
[34]
Open relay contact at error Close relay contact at error
[36]
Select current as analogue output type Select voltage as analogue output type
[37]
Select 0-20 mA output range Select 4-20 mA output range Select S4-20 mA with safety readback Select 20-0 mA output range Select 20-4 mA output range Select S20-4 mA with safety readback
[38]
Select no error action - output undefined at error Select downscale at error Select NAMUR NE43 downscale at error Select NAMUR NE43 upscale at error
[39]
Select 0.0-1 V output range Select 0.2-1 V output range Select 0-5 V output range Select 1-5 V output range Select 0-10 V output range Select 2-10 V output range Select 1-0.0 V output range Select 1-0.2 V output range Select 5-0 V output range Select 5-1 V output range Select 10-0 V output range Select 10-2 V output range
[41]
Set temperature for analogue output low
[42]
Set temperature for analogue output high
[43]
Enter password setup Enter simulation mode Perform process calibration Enter display setup Perform memory operations Enter relay latch setup
[44]
Load saved configuration into DRST-UR
[45]
Save DRST-UR configuration in DRSL-DISPLAY
[46]
Adjust LCD contrast
[47]
Adjust LCD backlight
[48]
Write a 6-character device TAG Analogue output value is shown in display line 3
[49]
Device TAG is shown in display line 3
[50]
Calibrate input low to process value?
[51]
Calibrate input high to process value?
[52]
Enable simulation mode?
[53]
Set the input simulation value
[54]
Relay simulation - use 1 and 2 to toggle relay 1 and 2
[55]
Enable password protection?
[56]
Set new password
[57]
Enable Fastset functionality?
[58]
Relay setpoint - press 3 to save
[59]
Relay setpoint - Read only
[60]
Select language
[61]
Use process calibration values?
[62]
Set value for low calibration point
[63]
Set value for high calibration point Select CJC connector (accessory)
[64]
Select internal temperature sensor
[65]
Enable relay latch function? Relay is latched - press 3 to acknowledge Relay 1 is latched - press 1 to release Relay 2 is latched - press 2 to release Relays are latched - press 1 or 2 tor release relay 1 or
[66]
relay 2
[67]
Release relay? (if conditions allow) Enter setup menu? (latched relays may release!)
33
Page 34
Graphic Depication of Latch
Section 20.1 - Graphic depiction of latch function setpoint
Input
Hysteresis
signal
Setpoint
(increasing)
ON delay
OFF delay
Time
20
Relay contact
(N.O.)
Closed
Open
Release not possible (setpoint still exceeded)
Release not possible (setpoint-hysteresis still exceeded)
Release not possible (OFF delay still exceeded)
Release possible (manual deactivation)
Relay latched
34
Page 35
20
Graphic Depication of Latch
Section 20.2 - Graphic depiction of latch function window
Hysteresis
Hysteresis
Setpoint high
Setpoint low
Closed
Relay contact (N.O.)
Release not possible (OFF delay still active)
Open
Release not possible (still inside window)
Release not possible (inside hysteresis)
Release possible
ON delay OFF- delay
Relay latched
ON delay OFF delay
Window
Time
Relay latched
35
Page 36
Graphic Depication of Latch
Section 20.3 - Graphic of relay action setpoint
20
100
90
80
70
60
50
40
Setpoint = 50
Hysteresis = 10
30
O N.O. O N.O.On N.O.
20
On N.C. On N.C.O N.C.
10
0 10 20 30 40 50 60 70 80 90 100
Relay action: Increasing Relay action: Decreasing
t
100
90
80
70
60
50
Hysteresis = 10
Setpoint = 50
40
30
20
10
O N.O. O N.O.On N.O.
On N.C. On N.C.
0 10 20 30 40 50 60 70 80 90 100
O N.C.
Section 20.4 - Graphic depiction of relay action window
Relay unitsRelay units
t
100
Relay units
90
80
70
60
Hysteresis = 5
Setpoint High = 60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for increasing signal)
Contact: Closed inside window = Contact: Open inside window =
Setpoint Low = 40
Hysteresis = 5
1 1
2 2
O OO
1
2
100
Relay units
90
80
70
60
Hysteresis = 5
Setpoint High = 60
50
40
30
20
OnOn On
t
10
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for decreasing signal)
Contact: Closed inside window = Contact: Open inside window =
Setpoint Low = 40
Hysteresis = 5
1 1
2 2
O OO
1
2
OnOn On
t
36
Page 37
21
Displays
Section 21.1 - Displays
Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearization, scaling, and difference measurement functions for programming via PReset software.
21.2 - EX Interfaces
Interfaces for analog and digital signals as well as HART frequency signals and control systems in Ex zone 0, 1 & 2 and for some devices in zone 20, 21 & 22.
®
signals between sensors/I/P converters /
21.3 - Isolation
Galvanic isolators for analog and digital signals as well as HART both loop powered and universal isolators featuring linearization, inversion, and scaling of output signals.
®
signals. A wide product range with
37
Page 38
21.4 - Temperature
A wide selection of transmitters for DIN form B mounting and DIN rail devices with analog and digital bus communication ranging from application­specific to universal transmitters.
21.5 - Universal
PC or front programmable devices with universal options for input, output and supply. This range offers a number of advanced features such as process calibration, linearization and auto-diagnosis.
Displays
21
38
Page 39
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a trademark of OMEGA ENGINEERING, INC. © Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
Page 40
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE
MU
Thermocouple, RTD & Thermistor Probes, Connectors,
Panels & Assemblies
MU
Wire: Thermocouple, RTD & Thermistor
MU
Calibrators & Ice Point References
MU
Recorders, Controllers & Process Monitors
MU
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
MU
Transducers & Strain Gages
MU
Load Cells & Pressure Gages
MU
Displacement Transducers
MU
Instrumentation & Accessories
FLOW/LEVEL
MU
Rotameters, Gas Mass Flowmeters & Flow Computers
MU
Air Velocity Indicators
MU
Turbine/Paddlewheel Systems
MU
Totalizers & Batch Controllers
pH/CONDUCTIVITY
MU
pH Electrodes, Testers & Accessories
MU
Benchtop/Laboratory Meters
MU
Controllers, Calibrators, Simulators & Pumps
MU
Industrial pH & Conductivity Equipment
DATA ACQUISITION
MU
Communications-Based Acquisition Systems
MU
Data Logging Systems
MU
Wireless Sensors, Transmitters, & Receivers
MU
Signal Conditioners
MU
Data Acquisition Software
HEATERS
MU
Heating Cable
MU
Cartridge & Strip Heaters
MU
Immersion & Band Heaters
MU
Flexible Heaters
MU
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
MU
Metering & Control Instrumentation
MU
Refractometers
MU
Pumps & Tubing
MU
Air, Soil & Water Monitors
MU
Industrial Water & Wastewater Treatment
MU
pH, Conductivity & Dissolved Oxygen Instruments
M5960/0918
Loading...