The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
This device is designed for connection to hazardous electric
voltages.
Ignoring this warning can result in severe personal injury or mechanical
damage.
To avoid the risk of electric shock and fire, the safety instructions of this
manual must be observed and the guidelines fol lowed. The specifications
must not be exceeded, and the device must only be applied as described in
the following.
Prior to the commissioning of the device, this manual must be examined
carefully.
Only qualified personnel (technicians) should install this device. If the
equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
WARNING
Until the device is fixed, do not connect hazardous voltages to the device.
The following operations should only be carried out on a disconnected
device and under ESD safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the device.
1
INSTALLATION
Repair of the device and replacement of circuit breakers must be done by
PR electronics A/S only.
WARNING
DRST-UN must be mounted on a DIN rail according to DIN 46277.
WARNING
Do not open the front plate of the module as this will cause damage to
the connector for the display / programming front DRSL-DISPLAY.
This module contains no DIP-switches or jumpers.
1.2 - Symbol Identification
Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the device with the
essential requirements of the directives.
The double insulation symbol shows that the device is
protected by double or reinforced insulation.
5
Page 6
2
Instructions
Section 2 - Instructions
2.1 - Definitions
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000
Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the knobs
or potentiometers during normal operation.
2.2 - Receipt and Unpacking
Unpack the module without damaging it. The packing should always follow the module
until this has been permanently mounted.
Check at the receipt of the module whether the type corresponds to the one ordered.
2.3 - Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well
as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient
temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation Class II.
2.4 - Mounting
Only technicians who are familiar with the technical terms, warnings, and instruc tions in
the manual and who are able to follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please contact your
local distributor or, alternatively, Mounting and connection of the device should comply
with national legislation for mounting of electric materials, i.e. wire cross section,
protective fuse, and location. Descriptions of input / output and supply connections are
shown in the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it
should be easily accessible and close to the device. The power switch should be
marked with a label indicating that it will switch off the volt age to the device.
Year of manufacture can be taken from the first two digits in the serial number.
6
Page 7
Section 2.5 - UL Installation Requirements
Use 60/75°C copper conducters only
For use only in pollution degree 2 or better
Max. ambient temperature - 60°C
Max. wire size - AWG 26-14
UL file number - E231911
Section 2.6 - Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Section 2.7 - Normal Operation
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means there
is no electrical shock hazard, and the device is easily accessible.
Instructions
2
Section 2.8 - Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled
water.
Section 2.9 - Liability
To the extent that the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise exist
according to the concluded sales agreement.
7
Page 8
3
Demounting
Section 3.1 - How to demount DRST-UN
First, remember to demount the connectors with hazardous voltages.
Picture 1: Detach the device from the DIN rail by lifting the bottom lock.
When front LED lights red / display shows AO.ER
PR DRST-UN is designed as a SIL 2 device with a high safety level. Therefore, a
continuous measurement of the outgoing current is carried out on a 4...20 mA and
20...4 mA output signal. If the current output signal is different from the internal
calculated output value or the current output is 0 (due to e.g. an open circuit
breakage), an error mode switches on the red front LED.
This function is not a default option but must be actively selected via the
programming menu (S4-20 & S20-4).
The error mode can only be reset by switching off and then switching on the supply
voltage to the device.
8
Page 9
Section 4.1 - Universal Transmitter DRST-UN
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• Output for current and voltage
• Universal AC or DC supply
4.2 - Advanced Features
Programmable by way of detachable display front DRSL-DISPLAY, process
calibration, signal simulation, password protection, error diagnostics and help
text available in several languages.
4.3 - Application
• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analogue current /
voltage signal, i.e. from solenoids and butterfly valves or linear movements
with attached potentio meter.
Characteristics
4
• Power supply and signal isolator for 2-wire transmitters.
• Process control with standard analogue output.
• Galvanic separation of analogue signals and measurement of floating signals.
• The DRST-UN is designed according to strict safety requirements and is thus
suitable for application in SIL 2 installations.
4.4 - Technical characteristics
• When DRST-UN is used in combination with the DRSL-DISPLAY display/
programming front, all operational parameters can be modified to suit any
application. As the DRST-UN is designed with electronic hardware switches,
it is not necessary to open the device for setting of DIP-switches.
• A green / red front LED indicates normal operation and malfunction.
• Continuous check of vital stored data for safety reasons.
• 3-port 2.3 kVAC galvanic isolation.
9
Page 10
5
Display and Programming front
Section 5.1 - Functionality
explanatory help texts guide you effortless ly and automatically
through the configuration steps, thus making the product very
easy to use. Functions and configuration options are described in
the section ”Configuration / operating the function keys”.
5.2 - Application
• Communications interface for modification of operational
parameters in DRST-UN.
• Can be moved from one DRST-UN device to another and
download the configuration of the first transmitter to
subsequent transmitters.
• Fixed display for readout of process data and status.
5.3 - Technical characteristics
• LCD display with 4 lines; Line 1 (H=5.57 mm) shows input
signal, line 2 (H=3.33 mm) shows units, line 3 (H=3.33
mm) shows analogue output or tag no. and line 4 shows
communication status.
• Programming access can be blocked by assigning a password.
The password is saved in the transmitter in order to ensure a
high degree of protection against unauthorised modifications to
the configuration.
10
Page 11
Mounting and Demounting
Section 6.1 - Mounting and Installation
• Click DRSL-DISPLAY onto the front of DRST-UN.
Section 6.2 - Mounting/Demounting the DRSL-DISPLAY
1: Insert the taps of DRSL-DISPLAY into the holes at the top of the device.
2: Swing DRSL-DISPLAY into place.
Section 6.3 - Demounting of DRSL-DISPLAY
3: Push the release button on the bottom of DRSL-DISPLAY and swing
DRSL-DISPLAY up.
6
1
1
3
2
11
Page 12
7
Applications
Section - 7.1 - Inputs Signals
Current
Volt
age
+
-
+
-
Potentio-
meter
RTD and lin. RTC
Connect., wires
Section - 7.2 - Output Signals
44
*
-
+
43
42
41
Order separately: 5910 CJC connector.
See the connection drawing on page 15.
NAMUR NE 43 Upscale / Downscale 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals 3.8...20.5 mA
on 0...20 and 20...0 mA signals 0...20.5 mA
FM, applicable in ................. Class I, Div. 2, Group A, B, C, D
Class I, Div. 2, Group IIC
Zone 2
Max. ambient temperature for T5 60°C
Marine approval:
Det Norske Veritas, Ships & Offshore Standard for Certification No. 2.4
16
Page 17
Observed authority requirements Standard
EMC 2004/108/EC ............. EN 61326-1
LVD 2006/95/EC ................ EN 61010-1
UL, Standard for Safety ...... UL 508
EAC TR-CU 020/2011 ........ EN 61326-1
of span = of the currently selected measurement range
Display readout on the DRSL-DISPLAY of sensor error
detection and input signal outside range
Sensor error check:
Device:ConfigurationSensor error detection:
Specifications
8
DRST-UN
OUT.ERR=NONE.OFF
Else:ON
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
CURRLoop break (4..20 mA)SE.BR<= 3.6 mA; > = 21 mA
POTMAll, SE.BR on all 3-wireSE.BR> ca. 126 kΩ
0...800 ΩSE.BR> ca. 875 Ω
LIN.R
0...10 kΩSE.BR> ca. 11 kΩ
TCSE.BR> ca. 750 kΩ / (1.25 V)
TEMP
RTD, 2-, 3-, and 4-wire
No SE.SH for Cuxx, Pt10, Pt20 and Pt50
SE.BR> ca. 15 kΩ
SE.SH< ca. 15 Ω
Error indications
Readout at hardware error
Error searchReadoutError cause
Test of internal CJC sensorCJ.ER
CJC sensor defect or
temperature outside range
Checksum test of the configuration in FLASHFL.ERError in FLASH
1) No load on the current
Check measurement of analogue output currentAO.ER
output (only S4...20/S20...4
mA)
Communications test
DRSL-DISPLAY/DRST-UN
NO.COConnection error
Check that input signal matches input configurationIN.ER1) Error levels on input
Check that saved configuration in
matches device
! Error indications in the display flash once per second. The help text explains the error.
1) The error is reset by switching off and then switching on the supply voltage to the device.
DRSL-DISPLAY/
TY.ER
Configuration is not DRST-
UN
18
Page 19
Section 9.1 - Connections
Supply:
313233
Inputs
Diagrams
9
RTD, 3- / 4-wireRTD, 2-wireResistance, 2-wire
41424344414243444142434441424344
Resistance,
3- / 4-wire
41424344414243444142434441424344
Voltage
414243444142CJC 44
-+
Potentiometer
*TC, external
CJC connector
+
-
TC, internal
CJC sensor
+
* Order separately: CJC connector 5910
-
-+
Tx
Current2-wire transmitter
-+
111213141112131411121314
-+
mA
Voltage, 1 VVoltage, 10 VCurrent
-+
V
Outputs
19
-+
V
Page 20
9
Diagram
Section 9.2 - Block Diagram
Order separately: CJC connector 5910
RTD and lin. R,
connection,
2-wire transmitter
+
Current
Voltage
Potentiometer
wires
TC
243
44
0.2 mA
Supply
33
21.6...253 VAC or
V
loop
31
19.2...300 VDC
Supply
-
+
-
43
*
42
-
CJC
+
41
MUXA / D
PTC
CPU
SAFETY
D / A
I+
12
mA
10 V
14
mA
1 V
13
Green
Red
500 Ω
50 Ω
Gnd.
11
VV
I + V
Out.I Out.V Out.
50.0
l / min
VALVE 5
20 Ω
EEPROM
DRST-UN
20
Page 21
Section 9.3 - Routing Diagram
If no key is activated for 1 minute, the display will return to the default state 1.0
without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen value and proceed to the next menu
Hold 3 Back to previous menu / return to menu 1.0 without saving
Power up
ok
50.0
%
12.0
1.0
0000
9999
0000
PASSW.
Txt 1
okok
1.1
1.0 = Default state
Line 1 shows input
signal.
Line 2 shows
UNIT.
By pressing 1 and
2 simultaneously
line 3 alternates
between A.Out
and TAG.
Line 4 shows com munication status.
1.1 = Only if password protected.
1.2 = Not valid for these
input signals:
0...20 mA and
voltage.
1.3 = Only if input signal
is temperaure.
VO LT
CURR
LIN.R
POTM
NO
YES
NO
ADV.SET
Txt 2
TEMP
VO LT
IN TYPE
Txt 3
CURR
IN TYPE
Txt 3
POTM
IN TYPE
Txt 3
LIN.R
IN TYPE
Txt 3
TEMP
IN TYPE
Txt 3
Continued on the page
Routing diagram ADV.SET
ok
YES
ADV.SET
Txt 2
2-10
0-10
1-5
0-5
0.2-1
0-1
okokokokokokokokokok
2-10
V.RANGE
Txt 4
0-20 4-20
ok
4-20
I.RANGE
Txt 5
ok
2W 3W 4W
ok
3W
CONNEC.
Txt 6
ok
@C
mA
rpm
(69 units)
UNIT
Txt 11
ok
0...9999
ok
R 0%
Txt 7
Cu Pt Ni TC
SENSOR
Txt 10
SENSOR
Txt 10
TC
SENSOR
Txt 10
Cu
SENSOR
Txt 10
1111
111.1
11.11
1.111
111.1
DEC.P
%
Txt 12
0...9999
okok
0
2500
R 100%
10...1000
ok
Pt
100
Pt TYPE
Txt 16
50...1000
ok
Ni
100
Ni TYPE
Txt 17
TC.B TC.E TC.J TC.K TC.L
TC.N TC.R TC.S TC.T TC.U
TC.W3 TC.W5 TC.Lr
ok
TC.K
TC.TYPE
Txt 18
10...100
ok
Cu TYPE
Txt 69
Txt 8
10
-199.9
0.0
DISP.LO
Txt 13
2W 3W 4W
ok
3W
CONNEC.
2W 3W 4W
ok
3W
CONNEC.
ok
INT
2W 3W 4W
ok
3W
CONNEC.
999.9
Txt 6
Txt 6
CJC
Txt 63
Txt 6
VO LT
CURR
CURR
ANA.OUT
Txt 36
Volt
ANA.OUT
Txt 36
@C
UNIT
Txt 9
Selectable UNITS:
@C
ok
ok
ok
ok
999.9
-199.9
100.0
DISP.HI
Txt 14
@F
%
A
bar
cm
ft
ft/h
ft/min
ft/s
g
gal/h
gal/min
GW
hp
S20-4
20-4
20-0
S4-20
4-20
0-20
4-20
O.RANGE
Txt 37
10-2
10-0
5-1
5-0
1-0.2
1-0
2-10
0-10
1-5
0-5
0.2-1
0-1
ok
0-10
O.RANGE
Txt 39
ok
hPa
Hz
in
in/h
in/min
in/s
ips
K
kA
kg
kJ
kPa
kV
kW
kWh
23mA
0/3.5mA
NONE
23mA
OUT.ERR
Txt 38
1.2
ok
l/min
m/h
m/min
m/s
m/s2
m3/h
m3/min
mbar
mils
l
l/h
l/s
m
m3
mA
Diagram
4172
-328
ok
150.0
0.0
OUT.LO
Txt 41
1.31.3
To default state 1.0
min
mm
mm/s
mol
MPa
mV
MW
MWh
N
Ohm
Pa
pH
rpm
s
S
4172
-328
OUT.HI
Txt 42
9
t
t/h
uA
um
uS
V
W
Wh
yd
[blank]
21
Page 22
9
Diagram
Section 9.4 - Routing Diagram Advanced Settings
2.0 In the submenu simulation (SIM) you must press 3 to return to the default state 1.0.
MEM
DISP
CAL
SIM
PASS
LANG
MEM
SETUP
Txt 43
SAVE
LOAD
okok
SAVE
MEMORY
Txt 44
DISP
SETUP
Txt 43
CAL
SETUP
Txt 43
SIM
SETUP
Txt 43
PASS
SETUP
Txt 43
9
0
ok
3
CONTRA
Txt 45
YES
NO
ok
YES
CAL.LO
Txt 49
YES
NO
ok
YES
EN.SIM
Txt 51
2.0
YES
NO
ok
YES
EN.PASS
Txt 54
9
0
9
LIGHT
Txt 46
100.0
0.0
okokok
2.0
%
Txt 61
9
A
okok
VALVE 5
Txt 47
YES
NO
YES
CAL.HI
Txt 50
NO
100.0
0.0
ok
25.0
Txt 52
ok
%
NO
9999
0000
ok
0000
NEW.PAS
Txt 55
ok
TAG
A.OUT
ok
A.OUT
LINE 3
Txt 48
100.0
90.0
Txt 62
0.0
%
ok
YES
NO
okok
YES
USE.CAL
Txt 60
NO
To default state 1.0
NO
DE, DK,
ES, FR,
IT, SE,
UK
LANG
SETUP
Txt 43
okok
UK
LANGUA
Txt 59
22
Page 23
Section 10.1 - General
settings which fit the application. For each menu there is a scrolling help text which is
automatically shown in line 3 on the display.
Configuration is carried out by using the 3 function keys:
will increase the numerical value or choose the next parameter
will decrease the numerical value or choose the previous parameter
will accept the chosen value and proceed to the next menu
ok
When configuration is completed, the dispaly will return to the default state 1.0.
Pressing and holding will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0)
without saving the changed values or parameters.
ok
Section 10.2 - Password protection
Configuration / Operation
10
mitter in order to ensure a high degree of protection against unauthorised
modifications to the configuration. Default password 2008 allows acces to all
configuration menus
Section 10.3 - Signal and sensor error info (Display front
DRSL-DISPLAY)
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH
(sensor short). Signals outside the selected range (not sensor error, see table for limits)
are displayed as IN.LO indicating low input signal or IN.HI indicating high input
signal. The error indication is displayed in line 3 as text and at the same time the
backlight flashes. Line 4 of the display is a status line which displays COM (flashing
bullet) indicating correct functioning of DRSL-DISPLAY, and arrow up/down which
indicates tendency readout of the input signal.
23
Page 24
10
Configuration / operation
Section 10.4 - Signal and sensor error info (no display)
Status of the unit can also be read from the red/green LED in the front of the device.
Green flashing LED 13 Hz indicates normal operation.
Green flashing LED 1 Hz indicates sensor error.
Steady green LED indicates internal error.
Steady red LED indicates fatal error.
Section 10.5 - Advanced Functions
The unit gives access to a number of advanced functions which can be reached by
answering “Yes” to the point “adv.set”.
Section 10.6 - Display setup
Here you can adjust the brightness contrast and the backlight. Setup of TAG number
with 6 alphanumerics. Selection of functional readout in line 3 of the display - choose
between readout of analogue output or TAG number.
Section 10.7 - Two-point process calibration
The unit can be process-calibrated in 2 points to fit a given input signal. A low input
signal (not necessarily 0%) is applied and the actual value is entered via DRSLDISPLAY. Then a high signal (not necessarily 100%) is applied and the actual value
is entered via DRSL-DISPLAY. If you accept to use the calibration, the unit will work
according to this new adjustment. If you later reject this menu point or choose another
type of input signal the unit will return to factory calibration.
24
Page 25
Section 10.8 - Process simulation function
If you say ”yes” to the point “EN.SIM” it is possible to simulate an input signal by
means of the arrow keys and thus control the output signal up or down. When you
finalise the point with , the unit returns to normal mode.
ok
Section 10.9 - Password
Here you can choose a password between 0000 and 9999 in order to protect the unit
against unauthorised modifications to the configuration. The unit is delivered default
without password. If you have locked the unit with a password by mistake, you can
always open the menu by using the master password 2008.
Configuration / operation
10
Section 10.10 - Language
In the menu ”lang.setup” you can choose between 7 different language versions of
help texts that will appear in the menu. You can choose between UK, DE, FR, IT, ES,
SE and DK.
25
Page 26
10
Configuration / operation
Section 10.11 - Auto diagnosis
The unit performs an advanced auto diagnosis of the internal circuits.
The following possible errors can by display in the front unit DRSL-DISPLAY.
CJ.ER - CJC sensor defect or CJC temperature outside range
FL.ER - Flash error
AO.ER - No load on the current output (only for S4...20 mA/S20...4 mA)
NO.CO - Connection error
IN.ER - Error levels on input
TY.ER - Configuration in DRSL-DISPLAY/DRST-CM does not match this
product type
Section 10.12 - Selection of units
After choosing the input signal type you can choose the process units which will be
displayed in text line 2 (see table). By selection of temperature input the process value
is always displayed in Celsius or Fahrenheit. This is selected in the menu point after
selection of temperature input.
Section 10.13 - Safety readback
When the device is delivered with default configuration, the SIL function is disabled.
The safety readback function (loop surveillance) can be selected in the menu
O.RANGE, thus enabling the device to run in SIL mode. In order to enable the SIL
functionality, the menu item S4...20 mA must be selected. Please note, however, that
when safety readback is enabled, a sensor error will be indicated as an error on the
analogue output signal.
26
Page 27
Section 10.14 - CJC
In the CJC menu you can choose between external CJC connector and internal cold
junction compensation. The external CJC connector (5910) must be ordered separately.
Section 10.15 - Memory
In the memory menu you can save the configuration of the device in the
DRSL-DISPLAY, and then move the DRSL-DISPLAY onto another device of
the same type and download the configuration in the new device.
Configuration / operation
10
27
Page 28
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal one (1) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for
any damages that result from the use of its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE contacting
OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have
the following information available BEFORE
contacting OMEGA:
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.