NuTone ILF530, ILF360 User Manual

IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE. ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at service
• Suitable for use with solid state speed controls. CAUTION: For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
INSTALLATION INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction. B. Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment manufacturer's guideline
and safety standards such as those published by the National Fire
Protection Association (NFPA), and the American Society for
Heating, Refrigeration and Air Conditioning Engineers (ASHRAE),
and the local code authorities. C. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities. D. Ducted fans must always be vented to the outdoors. E. NEVER place a switch where it can be reached from a tub or shower.
FOR BEST RESULTS
When installing the Ventilator in a new construction site, install fan and ducting during the rough-in construction of the building. Inlet grille(s) should be installed after the finished ceiling is in place.
To install a ventilator in an existing building requires access to the attic area above the space to be ventilated.
INSTALLATION IN A NEW CONSTRUCTION SITE
MOUNTING
1. Select a mounting site; Identify a mounting location that offers accessibility with minimal duct run. Mount ventilator as far from the inlet grille as practical to minimize noise.
NOTE: If used for dryer boosting the ventilator must be mounted at
least 12 feet from the dryer outlet. For gas fired dryers the
ventilator capacity (CFM) must not exceed the dryer’s fan capacity.
2. Attach fan mounting bracket to the support joist using the wood
screws provided (Refer to Figure 1). For best performance vertical mounting is recommended, however any orientation is acceptable.
3. Attach fan to the mounting bracket using the self threading
screws provided (Refer to Figure 1). To ease attachment
1
16˝
pilot holes may be used for the mounting screws.
WIRING
1. Run 120v AC house power wiring through switch box to junction box in ventilator housing.
2. Remove ventilator junction box cover.
3. Refer to Figure 2. Connect the house power wire (black) to the
terminal marked LI. Connect the house neutral wire (white) to the terminal marked N. The fan housing is fully insulated and therefore no grounding is required.
4. Replace outlet box cover.
5. Connect house power wire to the wall switch.
NOTE: ALL WIRING MUST COMPLY WITH LOCAL
ELECTRICAL CODES.
DUCTING INSTALLATION
1. Refer to Figure 3. Attach duct to ventilator inlet and outlet using
clamps, fasteners and/or duct tape. Observe the following recommendations for best results; A. Always minimize duct lengths and turns. B. When flexible ducting is used be sure that the duct is fully stretched and free of kinks or sharp bends. C. Use insulated ducting when passing through unconditioned spaces. D. When insulated ducting is used clamp or tape the inner vinyl core to the inlet and outlet of the fan and tape the vapor barrier surrounding the duct insulation to the fan housing. E. Always install a damper at the inlet grilles.
INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
In-Line Fans
MODELS: ILF120, ILF130, ILF250,
ILF360, ILF 530
FIGURE 1
MOUNTING BRACKET
JOIST OR STUD
FAN MOUNTING
INSTALLATION IN EXISTING CONSTRUCTION
Installing in an existing building requires access to the attic or space
above the planned installation.
Carefully examine the installation area to be sure that;
1. Ducting can be installed.
2. Wiring can be run to the planned location.
3. No wiring or other obstructions might interfere with installation.
Install fan and ducting following the instructions in “Installation in a New Construction Site”.
CARE AND MAINTENANCE
1. No regular maintenance is required.
2. For dryer booster applications periodically check the fan and discharge vent for lint build up. Clean as needed.
Caution: Always disconnect power before inspecting.
FIGURE 3
CEILING JOIST
DAMPERED SLEEVE
INLET GRILLE
AIR FLOW
ROOF OR WALL CAP
DUCTING INSTALLATION
FIGURE 2
WIRING CONNECTIONS
(POWER)
BLACK
(NEUTRAL)
WHITE
LI
N
(TO CAPACITOR)
WHITE
(where applicable)
(TO CAPACITOR)
WHITE
(where applicable)
(MOTOR)
BLUE
(MOTOR)
BLACK
BROWN
Loading...
+ 3 hidden pages