NuTone 8663RLG User Manual

INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
Bathroom Exhaust Fan/Light Combination
Suitable for use in insulated ceilings. WARNING: To reduce the risk of fire or electrical shock, do not use these fans with any solid-state speed control device. Do not install in a ceiling insulated to a value greater than R-40.
IMPORTANT SAFETY INSTRUCTIONS
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at Service
Panel and lock Service Panel to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION:
For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
INSTALLATION INSTRUCTIONS
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards, including fire-rated construction.
B. Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
C. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities. D. Ducted fans must always be vented to the outdoors. E. If this unit is to be installed over a tub or shower, it must be
marked as appropriate for the application. F. NEVER place a switch where it can be reached from a tub or
shower.
MODEL: 8663RLG
Suitable for use over tub or shower enclosure when installed in a GFI protected branch circuit.
FOR BEST RESULTS
When installing the Exhaust Fan/Light in a new construction site, install housing during the rough-in construction of the building. The blower unit, reflector and grille should be installed after the finished ceiling is in place.
PLANNING DUCTWORK AND WIRING
1. Use 4" round duct.
2. Plan duct run from discharge opening of fan to the outside. For
best fan performance, make duct run as short as possible and use minimum number of elbows.
3. Use optional NuTone ducting accessories as needed.
IMPORTANT: Use wire suitable for 90°C.
Plan to run 120vAC house wiring (with ground) from power source, through wall switches, to junction box in fan. For separate control of fan, light, and night light three wall switches are required. See NuTone Catalog for accessory switches. For separate control of fan, light, and night light, five conductors are needed between the wall switch box and the fan's junction box.
Wiring Knockouts
FIGURE 1
Housing
Scroll
Slots
Power/Blower
Unit
Reflector Assembly
Night Light Socket
Wing Nut
Grille/Lens
Assembly
Mounting
Springs (2)
INSTALLATION IN A NEW CONSTRUCTION SITE
PREPARATION
1. Refer to Figure 1. Remove power unit/blower assembly from
housing. A. Unplug power unit. B. Remove screw (located next to plug-in receptacle) which holds
power/blower unit mounting plate in place. Save screw.
C. Lift mounting plate at end near the plug-in receptacle until
blower wheel clears the scroll.
D. Remove plate by pulling its tabs out of slots in housing. Set
power/blower unit aside until needed.
2. Remove one of the wiring knockouts from housing.
MOUNTING THE HOUSING
MOUNTING USING MOUNTING TABS Refer to Figure 2.
1. Locate fan housing next to ceiling joist.
2. Use wood screws (not provided) to loosely attach housing to ceiling joist through keyhole slots in mounting tabs.
3. Adjust housing so that it will be flush with finished ceiling. For the grille to fit properly, the housing's rim must not extend beyond finished ceiling surface.
4. When housing is properly adjusted, tighten screws in slots.
MOUNTING USING HANGER BARS Refer to Figure 3.
1. Insert hanger bars in slots provided in housing.
2. Locate fan housing between joists so that the bottom of the housing is even with the planned finished ceiling. Extend the hanger bars to the joists.
3. Use screws or nails (not provided) to secure hanger bars to ceiling joists.
INSTALLING DUCTWORK
1. Refer to Figure 1. Place duct collar over flanges at discharge opening of fan. Secure collar by snapping tabs into slots in flanges.
2. Run 4" round duct from fan's discharge opening to the outside and terminate.
WIRING
All wiring must comply with local codes and unit must be properly grounded. IMPORTANT: Use wire suitable for 90°C.
1. Run 120vAC house wiring from wall switches to fan location, neutral (white), ground (bare copper), and three switched hot leads. See Figure 4.
2. Insert and secure an approved box connector into wiring entrance hole.
3. Pull wires through box connector and into junction box. Tighten box connector.
4. Refer to Figure 4. Connect white wires from the fan and light receptacles to white (neutral) wire from the supply. Connect black wire to wire from fan switch. Connect red wire to wire from light switch. Connect yellow wire to wire from night light switch.
5. Connect the green (or bare) ground wire to the green ground lead.
POWER/BLOWER UNIT INSTALLATION
1. Refer to Figure 1. Place power/blower unit into housing so that mounting plate's tabs insert into slots in housing.
2. Press other end of mounting plate down until it is firmly seated over scroll and plug-in receptacles.
3. Secure mounting plate to housing with provided screw.
4. Insert motor plug into junction box receptacle.
FIGURE 2
FIGURE 3
FIGURE 4
WIRING
KNOCKOUTS
DUCT COLLAR
FLANGES
GROUND
LEAD
FAN RECEPTACLE
LIGHT RECEPTACLE
FAN SWITCH
LIGHT SWITCH
NIGHT LIGHT SWITCH
120 vAC
WHITE
Y E L L O
W
R E D
B L K
BOTTOM RIM
MOUNTING TABS
COMPLETING INSTALLATION
1. Insert lamp plug into junction box receptacle and secure reflector assembly to motor frame with wing nut provided.
2. Install lamps 100 watt (maximum) for light, and 7 watt (maximum) for night light.
3. Squeezing the grille assembly's mounting springs together, insert springs into slots on both sides of housing.
4. Press grille assembly firmly into place against ceiling.
INSTALLATION IN EXISTING CONSTRUCTION
Locate fan between ceiling joists. Plan ducting wiring before proceeding with installation. Refer to
Figure 4 for wiring and Figure 3 for ducting. CAUTION: Check area above planned location to be sure that:
1. Ducting can be installed or that area is sufficient for proper venting.
2. Wiring can be run to the planned location.
3. No wiring or other obstruction might interfere with installation.
INSTALLATION
1. The fan must be mounted between ceiling joists. Decide where you want to locate the fan, and then determine where the nearest joists are. Locating Joists – Lightly tap the ceiling. A hollow sound means no joist; a solid sound means a joist is present. To be sure you have located a joist, drill a small hole (1/16") and probe into the ceiling with a wire.
2. Locate the joists. Drill a starter hole in the ceiling between the joists.
3. To exactly locate the edge of joist, saw a line from hole to joist.
4. Refer to page 1. Remove power/blower unit from housing.
5. Use the housing pan as a template to mark cutout: place pan centered between joist and trace around pan.
6. Make cutout along outside of marked line.
7. Refer to Figure 5. Install 2 x 4 cleats to both ceiling joists. In some cases it may be necessary to use more than a single cleat on one side. The distance between cleats must be at least 9
1
8" but
not more than 10".
8. Remove side wiring knockout and insert and secure an approved box connector into the wiring entrance hole.
9. Use pliers to bend both mounting tabs as flush as possible to the side of the housing.
10. Install duct collar.
11. String wiring through box connector and connect 4" flexible duct
to duct collar.
12. Carefully push ductwork and wiring back into cutout. Place
housing into cutout.
13. Use wood screws to secure housing to cleats through four holes
in housing's pan. make sure pan is flush to finished ceiling.
14. Install Power/Blower Unit and complete installation.
CLEANING AND RELAMPING
1. Pull grille assembly away from ceiling.
2. Squeezing the grille assembly's mounting springs together, remove grille assembly from housing to expose socket for relamping.
3. Clean grille and lens of assembly using a mild soap and water solution. Assemblies with wood frames should not be immersed.
4. Replace grille assembly flat against ceiling after cleaning or relamping.
FIGURE 5
FIGURE 6
11-1/2"
9-1/8"-10"
Joist
2"
4"
5-3/4"
4" Flexible Duct
120vAC House Wiring
Duct Collar
Wiring Knockout
Bend Mounting Tabs Flush To Side of Housing
Mounting Holes
INSTRUCCIONES DE INSTALACION
¡
LEA Y GUARDE ESTAS INSTRUCCIONES!
Combinación de lámpara/ventilador aspirante para cuartos de baño
El ventilador aspirante consiste de la caja, el montaje de unidad de potencia/soplador (motor, ruede, placa de montaje), rejilla, conjunto del portalámparas de reflector/lámpara y collarín del conducto.
Todos los modelos están listados por U.L. para utilizarse en techos aislados.
ADVERTENCIA: Para reducir el riesgo de incendio o choque eléctrico, no utilice estos ventiladores con ningún dispositivo con control de la velocidad de estado sólido.
INSTRUCCIONES IMPORTANTES DE SEGURIDAD
ADVERTENCIA: PARA REDUCIR EL RIESGO DE INCENDIO, CHOQUE ELECTRICO O LESIONES A LAS PERSONAS, OBSERVE LO SIGUIENTE:
A. Utilice esta unidad solamente de la manera planeada por el
fabricante. Si tiene alguna pregunta, póngase en contacto con el fabricante.
B. Antes de reparar o limpiar la unidad, apague la corriente del panel
de servicio y cierre con llave el panel de servicio para evitar que la corriente se encienda accidentalmente.
PRECAUCION:
Solamente para ventilación general. No lo utilice para expulsar
materiales y vapores peligrosos o explosivos.
INSTRUCCIONES DE INSTALACION
ADVERTENCIA: PARA REDUCIR EL RIESGO DE INCENDIO, CHOQUE ELECTRICO O LESIONES A LAS PERSONAS, OBSERVE LO SIGUIENTE:
A. El trabajo de instalación y el cableado eléctrico deben ser
realizados por una(s) persona(s) calificada(s) de acuerdo con todos los códigos y estándares aplicables, incluyendo la construcción según los estándares contra incendios.
B. El flujo del aire de combustión necesario para el manejo seguro
del equipo quemador de combustible puede verse afectado por el funcionamiento de esta unidad. Siga las pautas y estándares de seguridad del fabricante para el equipo de calefacción como las publicadas por la Asociación Nacional de Protección contra Incendios (NFPA), por la Asociación Norteamericana de Ingenieros de Calefacción, Refrigeración y Aire Acondicionado (ASHRAE) y por las autoridades de códigos locales.
C. Cuando corto o taladre en la pared o el techo, no dañe el
cableado eléctrico ni otras utilidades escondidas.
D. Los ventiladores entubados siempre deben estar ventilados hacia
el exterior.
E. Si la unidad se va a instalar encima de una bañera o ducha,
aquélla debe estar señalada como apropiada para la aplicación.
F. No coloque NUNCA un interruptor donde pueda ser alcanzado
desde la bañera o ducha.
MODELO: 8663RLG
No se puede utilizar en recintos de ducha o bañera.
PARA OBTENER MEJORES RESULTADOS
Cuando instale la lámpara/ventilador aspirante en una construcción nueva, instale la caja durante la etapa de enterramiento de la instalación eléctrica de la construcción. La unidad de potencia, el reflector y la rejilla deben de instalarse después de que el techo acabado esté en su sitio.
Consulte las instrucciones de la página 7 para instalar la lámpara/ventilador aspirante en un edificio acabado existente.
PLANIFICACION DEL CODUCTO Y CABLEADO
1. Utilice un conducto redondo de 4".
2. Planee pasar el conducto desde la abertura de descarga del
ventilador al exterior. Para conseguir el mejor rendimiento del ventilador, haga el conducto lo más corto posible y utilice los menos codos posibles.
3. Utilice los accesorios opcionales de NuTone para conductos
si los necesita.
IMPORTANTE: Utilice cable apropiado para 90°C.
Planee pasar un cableado de la casa de 120v CA (puesto a tierra) desde la fuente de alimentación, a través de los interruptores de pared, a la caja de empalme en el ventilador. Para obtener el control separado del ventilador, la luz y la luz de noche se necesitan tres interuptores de pared. Consulte el Catálogo NuTone para ver los accesorios de interruptores. Para obtener el control separado del ventilador, la luz y la luz de noche se necesitan cinco conductores entre la caja del interruptor de pared y la caja de empalme del ventilador.
FIGURA 1
Agujeros Ciegos del Cableado
Caja
Espiral
Ranuras
Unidad de Potencia/Soplador
Conjunto del Relfector
Portalamparas de la Bombilla de Noche
Tuerca de Mariposa
Conjunto de Rejilla/Lente
Resortes de
Montar
Loading...
+ 8 hidden pages