INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
Bathroom Exhaust
Fan/Fluorescent
Light Combination
MODEL: 770F
FOR BEST RESULTS
When installing the Exhaust Fan/Light in a new
construction site, install housing during the rough-in
construction of the building. The blower unit and grille should
be installed after the finished ceiling is in place.
To install the Exhaust Fan/Light in an existing finished
building see instructions page 4.
FIGURE 1
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE.
ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
B. Before servicing or cleaning unit, switch power off at
service panel and lock service panel to prevent power from
being switched on accidentally.
When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
CAUTION:
For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
INSTALLATION INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
B. Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent back drafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American Society
for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
C. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
D. Ducted fans must always be vented to the outdoors.
E. If this unit is to be installed over a tub or shower, it must be
marked as appropriate for the application.
F. NEVER place a switch where it can be reached from a tub
or shower.
•
The exhaust fan consists of the housing, power unit/blower
assembly (motor, wheel, mounting plate,) grille/lens
assembly, reflector/lamp plug assembly (lamps not
furnished) and duct collar.
•
WARNING: To reduce the risk of fire or electric shock,
do not use this fan with any solid-state speed control
device.
•
Not for use in kitchens.
•
For installation in sloped ceilings up to 12/12 pitch.
•
Ductwork must point up.
DUCT COLLAR
HOUSING
SLOTS
TABS
POWER UNIT/
BLOWER
ASSEMBLY
GRILLE
REFLECTOR
LENS
• SUITABLE FOR USE OVER A TUB OR
SHOWER WHEN INSTALLED IN A G.F.C.I.
PROTECTED BRANCH CIRCUIT .
PLANNING DUCTWORK AND WIRING
DUCTWORK
1. Use 4" round duct.
2. Plan to run duct from the fan's discharge opening to the
outside. For best fan performance, make duct run as short
as possible and use minimum number of elbows.
3. Use optional NuTone ducting accessories as needed (refer
to NuTone's catalog for a complete listing of optional
accessories).
WIRING
Plan to run 120vAC house wiring (with ground) from a
power source, through a standard wall switch or an optional
NuTone double FAN/LIGHT switch, to the junction box in the
Fan-Light's housing.
INSTALLATION IN A NEW
CONSTRUCTION SITE
PREPARATION
1. Unplug the power unit.
2. Refer to Figure 1. Remove power unit/blower assembly
from the housing. Remove screw and pull power unit
assembly tabs out of slots in housing. Set unit aside until
needed.
3. Remove one of the wiring knockouts from housing.
MOUNTING THE HOUSING
USING SIDE MOUNTING TABS
Refer to Figure 2.
1. Locate housing next to ceiling joist.
2. Use wood screws (not provided) to loosely attach housing
to ceiling joist through keyhole slots in mounting tabs.
3. Adjust housing so that it will be flush with the finished
ceiling.
4. When housing is properly adjusted, tighten screws in slots.
USING HANGER BARS
(Hanger bars sold separately, order model HB4)
Refer to Figure 3.
1. Insert hanger bars in slots provided in housing.
2. Locate fan housing between ceiling joists so that bottom of
fan housing is even with the planned finished ceiling.
3. Use screws or nails to secure mounting brackets to ceiling
joists.
INSTALLING DUCTWORK
1. Refer to Figure 1. Place duct collar over flanges at
discharge opening of fan. Secure collar by snapping tabs
into slots in flanges.
2. Refer to Figure 4. Run 4" round duct from outside to fan's
discharge opening.
3. Connect duct to duct collar.
FIGURE 2
FIGURE 3
FIGURE 4
WIRING
KNOCKOUTS
MOUNTING
TABS
ROOF CAP
90° ELBOW
4" DIAMETER
DUCT
WALL CAP
HANGER BARS
(SOLD SEPARATELY)
WIRING
Refer to Figures 5 and 6.
All wiring must comply with local codes and unit must
be properly grounded.
1. Run 120vAC house wiring (with ground) from wall switch
to fan location.
2. Insert and secure an approved box connector into wiring
entrance hole.
3. Pull wires through box connector and into junction box.
Tighten box connector.
4. If a single switch will be used to control both the fan and
the light, make wiring connections as shown in Figure 5.
If a double switch will be used for separate control of the
fan and light, make connections as shown in Figure 6.
NOTE: If a double switch is used, the wiring connections
determine which receptacle will b e used for the fan motor
plug and which receptacle will be used for the light plug.
Make note of this when making the wiring connections.
5. Connect the green (or bare) ground wire to the green
ground lead.
POWER/BLOWER UNIT INSTALLATION
Refer to Figure 7.
1. Place power/blower unit into housing so that mounting
plate's tabs insert into slots in housing.
2. Press other end of mounting plate down until it is firmly
seated over scroll and plug-in receptacles.
3. Secure mounting plate to housing with provided screw.
4. Insert motor plug into junction box receptacle.
COMPLETING INSTALLATION
Refer to Figure 8.
1. Remove wing nut from the threaded bolt on motor
mounting strap.
2. Place reflector into grille.
3. Align grille/reflector assembly with housing and insert light
plug into receptacle in junction box. (See figure 1 for
correct orientation)
4. Using wing nut, secure grille/reflector assembly to motor
mounting strap.
5. Install 26W fluorescent lamp (NEMA type
CFM26W/GX24D/827) into socket. (Lamp not provided)
6. Install lens by squeezing both sides and inserting lens tabs
into slots in grille.
FIGURE 6
FIGURE 7
FIGURE 5
FIGURE 8
SINGLE SWITCH
CONTROL
DOUBLE SWITCH
CONTROL
WHITE
WHITE
BLACK
120vAC
GROUND
GROUND
120vAC
BLACK
BLACK
SLOTS
MOUNTING
PLATE
MOTOR PLUG
INSERT TABS
INTO SLOTS
GRILLE
LAMP SOCKET
REFLECTOR
LIGHT PLUG
FAN PLUG
Product specifications subject to change without notice.
4820 Red Bank Road, Cincinnati, Ohio 45227
Printed in U.S.A., Rev. 5/02, Part No. 88731
PLANNING
Installing a bathroom exhaust fan-light in a finished house
requires at least a small accessible area (attic or crawl space)
above the planned installation location.
Review “INSTALLATION IN A NEW CONSTRUCTION
SITE” AND FOLLOW ALL INSTRUCTIONS WHICH APPLY
TO YOUR INSTALLATION.
LOCATION: Locate fan-light next to a ceiling joist.
WIRING AND DUCTING: Refer to Figures 5 and 6 for
wiring and to Figure 4 for ducting. Plan ducting and wiring
before proceeding with installation.
CAUTION: Check area above planned location to be sure
that:
(1) Ducting can be installed or that area is sufficient for
proper venting. The ceiling joists should run toward an
outside wall.
(2) Wiring can be run to the planned location.
(3) No wiring or other obstruction might interfere with
installation.
INSTALLATION
1. The fan light must be mounted to a ceiling joist. Decide
where you want to locate the fan-light and then determine
if there is a ceiling joist near.
LOCATING JOIST: Lightly tap the ceiling. A hollow sound
means no joists, a solid sound means a joist is present. To
be sure you have located a joist, drill a small hole (1/16")
and probe into the ceiling with a wire. Leave wire in hole to
help locate it in the attic or crawl space.
2. Locate hole in attic or crawl space. Make sure hole is
within 9" of joist.
3. From below, saw a line from hole to joist.
4. Using the housing as a template, mark the ceiling for the
cutout. Cutout dimensions:
91⁄
8
" x
9
1
⁄
8
". One side of cutout
must be right next to joist.
5. Make cutout along marked line.
6. In attic or crawl space, run 4" round duct from outside to
cutout location.
7. Run wiring to cutout location.
8. Place housing into cutout and secure housing to joist.
Make sure housing is flush with finished ceiling. Connect
duct.
9. From below, connect wiring. Install power/blower unit,
grille/reflector assembly, fluorescent lamp and lens.
INSTALLATION IN EXISTING CONSTRUCTION
One Year Limited Warranty
WARRANTY OWNER: NuTone warrants to the original consumer purchaser of its products that such products will be free from defects in materials or workmanship for a period
of one (1) year from the date of original purchase. THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During this one year period, NuTone will, at its option, repair or replace, without charge, any product or part which is found to be defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS OR TUBES, FILTERS, DUCT, ROOF CAPS, WALL CAPS AND OTHER ACCESSORIES
FOR DUCTING. This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse, negligence, accident,
improper maintenance or repair (other than by NuTone), faulty installation or installation contrary to recommended installation instructions.
The duration of any implied warranty is limited to the one year period as specified for the express warranty. Some states do not allow limitation on how long an implied warranty
lasts, so the above limitation may not apply to you.
NUTONE’S OBLIGATION TO REPAIR OR REPLACE, AT NUTONE’S OPTION, SHALL BE THE PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS
WARRANTY. NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH
PRODUCT USE OR PERFORMANCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may
not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. This warranty supersedes all prior warranties.
WARRANTY SERVICE: To qualify for warranty service, you must (a) notify NuTone at the address stated below or telephone 1/800-543-8687, (b) give the model
number and part identification and (c) describe the nature of any defect in the product or part. At the time of requesting warranty service, you must present
evidence of the original purchase date.
Date of Installation Builder or Installer
Model No. and Product Description
IF YOU NEED ASSISTANCE OR SERVICE:
For the location of your nearest NuTone Independent Authorized Service Center:
Residents of the contiguous United States Dial Free 1-800-543-8687
Please be prepared to provide:
Product model number • Date and Proof of purchase • The nature of the difficulty
Residents of Alaska or Hawaii should write to: NuTone Inc. Attn: Department of National Field Service, 4820 Red Bank Road, Cincinnati Ohio 45227-1599.
Residents of Canada should write to: Broan-NuTone Canada, 1140 Tristar Drive, Mississauga, Ontario, Canada L5T 1H9.
Rev. 03/2001