Ntron Sil02-LT Operating Manual

1 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
The
SIL O
2
User Operation Manual
Rev. 1.1
30/11/2018
2 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
3 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
Contents
1. Introduction .................................................................................................................................................... 6
1.1 The purpose of this User and Operation Manual................................................................................... 6
2. Installation and Operation ............................................................................................................................... 7
2.1 Notes for a safe installation ................................................................................................................... 7
2.2 Installation ........................................................................................................................................... 10
2.2.1 Mounting the SIL O2 Analyser....................................................................................................... 10
2.3 Electrical and Interface Connections ................................................................................................... 11
2.3.1 Sensor Input and Customer Interface Wiring.................................................................................. 11
2.3.2 Operational Settings and Wiring Configuration ............................................................................. 12
2.3.3 Typical Relay Configuration........................................................................................................... 13
2.3.4 Sensor Process Connection options ................................................................................................ 15
2.4 Operation ............................................................................................................................................. 16
2.4.1 Calibration Procedures .................................................................................................................... 16
2.4.2 Setting the Zero point. .................................................................................................................... 17
2.4.3 SPAN Calibration ........................................................................................................................... 18
.......................................................................................................................................................................... 18
3. Operational safety and maintenance instructions.......................................................................................... 19
3.1 Fault conditions ................................................................................................................................... 19
3.2 Wire break ........................................................................................................................................... 19
3.3 System faults ....................................................................................................................................... 19
3.4 Troubleshooting .................................................................................................................................. 20
Possible Faults and their solutions ........................................................................................................................ 20
3.4.1 Possible Sensor Faults .................................................................................................................... 21
3.5 General Maintenance .......................................................................................................................... 22
4. Specifications................................................................................................................................................ 23
5. Appendices ................................................................................................................................................... 26
5.1 SIL O2 Analyser and Sensor Connection Diagrams ........................................................................... 27
5.2 SIL O2 Analyser CE and ATEX Certificates ...................................................................................... 28
5.3 Sensor CE and ATEX Certificates ...................................................................................................... 29
4 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
Revision History
Revision No.
Change Description
Date
0
First Issue
19-10-2018
1
Note added for Non-ATEX Sensor usage
22-10-2018
1.1
Reference to 15% O2 in trouble shooting section removed.
30-11-2018
Calibration Span instruction amended and note added
5 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
6 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
1. Introduction
The Ntron SIL O2 Analyser is a ATEX approved SIL 2 rated Oxygen measuring instrument. It contains three programmable alarm settings, industry standard Analogue Output(active source) and a non-programmable safety trip relay. The range of operation is 0 to 25% Oxygen. The Reasolution is to 0.01%. Together with one of the range of Ntron ATEX approved Oxygen Sensors, it forms a SIL2 rated measurement unit which can operate on its own or as part of a larger installation.
Note. Non-Atex (Ex) Sensors variants of the models listed in the manual may also be used with the SIL O2 Analyser as long as they are installed in a Non-ATEX (Ex) or ‚Safe‘ area or zone.
The Alarm settings are typically factory set according to the end user’s requirements. Interface software and hardware is available for the user to perform such functions themselves. Contact Ntron for further details.
1.1 The purpose of this User and Operation Manual
This Manual is limited to providing the user with necessary details on installation, interface wiring, operation and maintenance of the SIL O2 Analyser and Oxygen Sensor, to ensure safe and reliable operation of this Analyser and Sensor unit.
Note: This manual does not cover the design or application of a safety Instrumented System (SIS) into which the SIL O2 Analyser unit may be incorporated. Further details of this can be obtained in the Ntron
SILO2 Technical and Safety Manual.
Increase (UP) and Decrease (Down) Pushbuttons. Pressing simultaneously enables entry into the calibration mode.
Power, Error/Fault and Alarm Level indicators
RS232
Communications
connection
The main user interface features
4-Digit LCD
Display/Readout
7 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2. Installation and Operation
Note: For system application information, consult the SIL O2 Analyzer Technical User Manual
2.1 Notes for a safe installation
Please do not short-circuit the + and -ve sensor cables while connecting to the SIL O2 Analyzer. This could damage the sensor.
This system can also be used in a non-Ex area application. In all applications, the SIL O2 Analyzer Din rail module is always located in the non-Ex area!
Assignment of the mounting rail housing terminals with intrinsically safe circuits and non-intrinsically safe circuits is indicated on the nameplate and is clearly indicated. In addition, the 4-pin terminals of intrinsically safe circuits follow the standard color protocol for intrinsically safe terminal connections and are coloured Blue. Connections for intrinsically safe external circuits are arranged in such a way that, in accordance with EN 60079-11, the exposed parts are at least 50 mm from the exposed connections and parts of the non-intrinsically safe circuits.
For safe operation, a protective ground/earth connection to terminal 13 or 15 should be made.
Assembly / disassembly, installation, operation and maintenance may only be performed by qualified personnel in accordance with regulatory requirements and the SIL O2 Oxygen Analysis Manual.
During installation, the technical data and the electrical values of the connected circuits must be respected.
Electrical supply. The SILO2 Analyser operates with an Extra low Voltage (ELV) supply. (See specification section in this manual)No special precautions are necessary but the ELV supply to the SIL O2, if generated from a Mains power source, that mains power source and associated wiring must be in accordance with IEC/EN standards and is the responsibilty of the user to provide and to ensure correct and safe installation of such.
When the SIL O2 analyzer is integrated into another system, also refer to the system manual for additional operational information.
The Ntron SILO2 Analyser is designed for use with a range of Ntron ATEX certified Oxygen Sensors to form a measurement system.These Sensor options are detailed in the Specification section of this manual.
If the SIL O2 Analyser has been supplied with a Sensor, the two units will have been calibrated at the Ntron factory prior to delivery. Otherwise, if a Sensor is supplied separately from the SIL O2 Analyser, a calibration will be required prior to putting the system into operational service.
8 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
The Ntron Sensors suitable for use with the SIL O2 analyser are listed in the Installationn section which follows.
9 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
The SIL O2 oxygen analyzer is an associated explosion-proof [Ex ia] IIC or [Ex ib] IIC electrical device and should always be used outside potentially explosive areas (in a safe area). Only electrical circuits, certified as intrinsically safe, can be connected to other intrinsically safe circuits in the Ex zone.
Before operation, the intrinsic safety must be verified for the SIL O2 oxygen analyzer circuit connected to the circuit of other equipment, including the interconnecting cabling. The data contained in the EC test certificate and the regulations of EN 60079-14: 2011-10 must be observed. The Sensors are ATEX rated devices and have certain conditions of use assigned.
Note. Non-Atex (Ex) Sensors variants of the models listed in the manual may also be used with the SIL O2 Analyser as long as they are installed in a Non-ATEX (Ex) or ‚Safe‘ area or zone.
For Acetal-bodies Sensors, the following instructions apply;
The Sensor should be installed in such a way that it is not subject to impact by other objects and should not be located close to additional heat sources. Note the ambient temperature range as it appears on the Sensor labelling.
Care must be taken when installing equipment with plastic enclosures or plastic parts of enclosures to ensure that the equipment is protected from any situations that could cause a build up of static charge. The equipment must not be installed into locations in which it could come into contact with, through normal or abnormal circumstances, fast moving dust laden air/gas or non-conductive fluids. The equipment must be cleaned only with a damp cloth.
10 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.2 Installation
The installation must be in accordance with the local electrical codes and taking into account the details in the Specification section of this manual.
The SIL O2 analyzer is designed for DIN rail mounting and can be supplied mounted in an additional enclosure or provided without an additional enclosure for customer mounting in a system enclosure or control panel.
The Sensor option chosen will determine the process connection/installation for that Sensor type. The Sensor types and related process connections are given below.
Sensor Type: Process Connection:
Model OC-25 Ntron Sensor base, Flow Through or Tri-Clamp
Model OC-26 KF40 Flange
Model OC-200’Oxyprobe‘ series Bushing insert or Extract* Probe Holder
The Sensor is typically supplied with a correcponding connection cable of either standard length or to a customer specified length.
*The Ntron OxyExtract Manual or Automatic probe insertion mechanism.
2.2.1 Mounting the SIL O2 Analyser
Mount the SIL O2 Analyser onto 35mm DIN rail as shown. Any Trunking/wireways above and below the Analyer when in situ, must be positioned so that there is a minimum of 30mm clearance between such trunking and the Analyser connection terminals.
115mm
100mm
67mm
11 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.3 Electrical and Interface Connections
2.3.1 Sensor Input and Customer Interface Wiring
The Ntron ATEX Sensor selected for use with the SIL O2 Analyser as listed in the Installation section previously, has intrinisically safe parameter values which match the Isolation Barrier output which is built into the SIL O2 Analyser. The Sensor connects to the Blue terminals as shown below.
The dark Grey terminals are for safe (Non-Ex area) customer interface connections. See the configuration section on the following page.
13 14 15 16
+ve -ve
Customer Clean
Earth
O2 Sensor
1 2 3 4
+ - 24 VDC
Relay 1
To customer Circuit
5 6 7 8
Relay 2 Transistor(DO)
To customer Circuit
9 10 11 12
Relay 3 4-20mA (AO)
To customer Circuits
12 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.3.2 Operational Settings and Wiring Configuration
The SIL O2 Analyser has two presettable alarm levels and associated Relays, referred to as RL1 and RL2. It also has a third presettable alarm level with an associate Transistor Digital Output (DO) The programmed setting of these outputs can vary depending on application. The Inspection and Calibration certificate supplied with each SIL O2 Analyser and Sensor unit will detail these settings. See the Ntron SIL O2 Technical and Safety manual for further details.
The SIL O2 Analyser has a main trip Relay referred to as RL3. This is not programmable and is normally open(contacts)/de-energised when the Analyser is not under power. The Relay energises and its associate contacts close when power is applied and the Analyser and Sensor are healthy and ready to operate.
The Analogue output is an industry standard 4-20mA active source output. The connected circuit should be of maximum resistance 420 ohm.
To meet the SIL 2 operational requirements as an Analyser and Sensor unit, the main trip Relay is required to be connected in series with other elements within the Analyser as shown in the diagrams below. For any other configurations, See the Ntron SIL O2 Technical and Safety manual for further details.
*Special case for use of the 4-20 mA analogue output within a safety system
When using the 4-20 mA analogue output from the SILO2 Oxygen Analyser within the safety system, this signal would typically be required to be processed by a safety PLC which would then activate the Final Trip Element. See the Ntron SIL O2 Technical and Safety manual for further
details.
Relay 3 Main Trip
Relay 1 or 2 Relay 3 Main Trip
Analogue Output 1/5
2/6 9
10 9 10
11
12
13 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.3.3 Typical Relay Configuration
Power to the Analyser
Relay
Contact 1
Relay Contact
2
Relay Contact
3
Comments
Power Off (All relay contacts in Fail Open condition)
Relays De-energised
Power on and system good/healthy
**
** All Relays
Energised
Power on and O2 alarm level(s) reached
* *
Relays 1 & 2 De-energised
Power on and System fault
**
** All Relays
De-energised
These relays are programmed to respond to the measured Oxygen level setpoints (Alarms), rising or falling in the range 0-25% Oxygen. These are pre-set to the customer’s requirements.
They operate in ‘Fail Safe’ mode which means that they are energized (under current), presenting a closed
contact to the customer/user when the SIL O2 module is under power and the status is healthy/good. When at a level setpoint (Alarm) or when the SIL O2 module is not-powered, the relays are de-energised (not
under current), presenting an open contact to the customer/user. This is also known as ‘Fail Open’ (FO)
condition.
Transisitor (DO)
This is an NPN device that can switch 24VDC and can be configured to be normally open or normally closed.
Analogue 4-20mA
This is an active output and requires connection to a passive external circuit suitable for proper operation.
It is set to the range 0-25% Oxygen / 4-20mA (0% Oxygen = 4mA, 25% Oxygen = 20mA.)
This range can not be adjusted.
If the 4-20 mA output is not used, the SIL O2 terminals T11 and T12 must be wired by the user. This output is internally connected in series with the SIL O2 Analyzer digital display, which will not work if the aforementioned terminals are in open circuit!
14 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
15 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.3.4 Sensor Process Connection options
The Sensors are suitable for mounting directly onto process Lines via a selection of process fittings. The electrical signal connectors are rated to IP67.
Tri-Clamp Sensor Base
Flow Through Sensor Base
OC-25 Sensor
OC-26 Sensor KF40 Process fitting
KF40 Process fitting onto pipeline
OC-200 Sensor with Screwed Bush Process
fitting
16 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.4 Operation
Before turning on the SIL O2 analyzer for the first time or after disconnecting the sensor for maintenance / replacement, make sure that a working sensor is connected. Otherwise, the SIL O2 analyzer will go into failure mode, with the red error indicator on and the RL3 relay disabled. As the fault circuit performs a cyclic check every 30 seconds or so. When the sensor is connected, resetting the red indicator and relay 3 occurs automatically, but it is advisable to power off the system to allow the sensor to be disconnected / reconnected under normal circumstances, if possible.
Turn on/apply power to the SIL O2 Analyser.
When operating under normal process/system conditions, the SIL O2 Analyser will give a digital readout of the measured Oxygen level (from the Sensor in the process).
This measurement is converted into a 4-20mA output signal proportional to the Oxygen being measured.
If an Alarm level even occurs, the relevant programmed output device will operate (Relay or Transistor) and the ineterface circuit to the user equipment will be interrupted. For further alarm or fault events and their conditions, please see the troubleshooting section at the end of this Manual.
2.4.1 Calibration Procedures
The SIL O2 Analyser and Sensor unit requires periodic calibrations performing, the timing between such calibrations being determined by the application and process requirements.
Typically, a periodic calibration check would reveal if any calibration adjustment is necessary. The SPAN calibration point of 20.9% O2 (Air) is the important setting and typically, if calibration adjustment is required, this is the value that would be adjusted. This adjustment can be made ussing ambient air as the calibration standard or, for greater accuracy, certified cylinder gas at 20.9% O2.
It is possible to also adjust the Zero point of the SIL O2 Analyser. Typically this would only be required when fitting a new/replacement Sensor. A Complete calibration procedure is given below.
Note: Calibration Adjustment procedure.
The displayed number change starts with the digit to the far right of the decimal point. Press and hold the Up or Down buttons to change the reading. This gives an accelerated adjustment. More accurate adjustment is achieved by pressing the Up or Down button at one press (press release, release of press, etc.). When the display reads 20.9%, the calibration of the range is complete
19.05
19.05
1, 2, 3….
6
6
1-
17 | P a g e R e v . 1 .1
I s s u e 3 0 - 11- 2018
2.4.2 Setting the Zero point.
This must be done each time a new sensor is installed before a span calibration is performed.
Subsequently, a zeroing can be performed periodically as needed.
A zeroing operation requires the application of a zero oxygen gas to the sensor, typically nitrogen (minimum quality <100 ppm). Note: Accessing the Zero function when the sensor is in ambient air (20.9% O2) will result in an error / fault condition.
Depending on the type of sensor installed, zero gas must be applied through a process fitting or calibration adapter, and be sure to leave a free exhaust at a suitable location so that the sensor does not become pressurized.
The sensors to be used with the SIL O2 unit will generally give a small output at zero oxygen levels. The zero adjustment function allows the user to adjust this small signal so that the SIL 2 analyzer displays 0.0 when no oxygen is present in the measured gas.
ZERO mode is activated after pressing the UP and DOWN button simultaneously for more than one
second. As an acknowledgment of receipt, the A3 LED flashes. An adjustment of the indicated value is made by pressing the UP or DOWN buttons individually as required.
The change starts with the digit to the right of the decimal point. (00.0) Press and hold the Up or Down
buttons to change the displayed reading. This allows an accelerated adjustment. Accurate adjustment is achieved by pressing the Up or Down button at one press (press release, release of press, etc.). When the display reads 0.0% O2, the setting is complete. By simultaneously pressing the two buttons or a delay of 20 seconds, the ZERO operating mode ends.
0.00
Loading...
+ 39 hidden pages