NOVUS NC400-6 User Manual

NC400-6 Counter
ELECTRONIC PROGRAMMABLE COUNTER – INSTRUCTIONS MANUAL – V1.2x A
SAFETY ALARMS
The following symbols appear in the device and throughout this manual to call the user’s attention as to important information related to safety and device use.
CAUTION:
Read manual carefully before installing and operating the device
All safety recommendations must be followed as to warrant the individual’s safety and prevent damage to the instrument or system. If the instrument is used in another way other than that specified in this manual, the equipment safety protections may not work properly.
Over Temperature Protection
When a system is designed, it is fundamental that one considers the consequence of any failure in any component of such system. In temperature control application, danger is even higher when heating remains constantly on. In applications where physical damage or device destruction may occur, the installation of an independent protection device is recommended, which has its own temperature sensor and can turn off the heating circuit in case of over heating. Note that the counter output relays of NC400-6 do not offer protection to all failure conditions.
CAUTION OR DANGER:
Risk of electrical shocks
DESCRIPTION
The NC400-6 counter and its configuration parameters are divided in the following blocks:
Inputs
Main counter
Batch counter
Each of these blocks has its own set of configuration parameters, which together determine how the device works. A summary of the operation of each block is presented below as well as their parameters.
INPUTS
NC400-6 has three inputs that can be configured to read contacts, NPN sensors, PNP sensors or voltage pulse connections. All inputs must receive the same type of input signal. Functions of each input are:
COUNT1: Main counting input
HOLD/COUNT2: Input to hold counting or second counting input. The
RESET: Input for external reset of counters and/or outputs.
Man 5001392
Totalizador counter
OUT1
OUT2
second counting input is required when the NC400­6 counter increases or decreases actions are determined by an external signal (quadrature signals, for example).
INTRODUCTION
NC400-6 is an advanced 6-digit counter that also performs batch and totalizer counting operations. It has two outputs with independent and configurable presets that can be triggered based on counting, batch or totalization values. Its 2 outputs allow for an independent timed triggering.
The counting input can be configured to read dry-contact, voltage pulse, NPN our PNP sensor connections. Sensors may be powered by an internal power supply.
Counting mode can be configured as progressive, regressive, quadrature, ADD or SUB. Several reset modes — automatic or manual — can be configured. Manual reset can be generated by a digital input or key from the front panel.
The following configuration parameters are directly related to the operation of inputs:
SEnS.tY
SEnS.tY
SEnS.tYSEnS.tY
Coun.tY
Coun.tY
Coun.tYCoun.tY
Coun.UP
Coun.UP
Coun.UPCoun.UP
MAIN COUNTER
It counts pulses from inputs, showing the value in the display after multiplying it by a configurable scaling factor. Manual or automatic reset. Two Set points can be defined (presets); when they are reached they produce configurable actions (enable output, increment batch counter, reset counter etc.) The following configuration parameters are directly related to the main counter operation.
FActor
FActor
FActorFActor
SP1 C
SP1 C
SP1 CSP1 C
SP2 C
SP2 C
SP2 CSP2 C
OPt.SP.C
OPt.SP.C
OPt.SP.COPt.SP.C
OFF.C
OFF.C
OFF.COFF.C
rES.C
rES.C
rES.CrES.C
Selection of type of signal (contact, pulse, NPN, PNP).
Selection of counting speed (slow or fast).
Progressive or regressive counting choice and use of COUNT2 input.
Factor that multiplies the number of input pulses (0.00001
0.00001 to 9.99999
0.000010.00001
Set point 1 for the main counter.
Set point 2 for the main counter.
Condition for Set point 1 reached (main counter higher or lower than Set point 1).
Initial value (Offset) for main counter.
Reset options in the main counter (input, key, Set point, output, etc.).
9.99999).
9.999999.99999
NOVUS AUTOMATION 1/8
Contador Eletrônico NC400-6
BATCH COUNTER
Counts the number of times that Set point 2 for the main counter was reached, with manual or automatic reset. When its Set point is exceeded (greater than or equals to) results in configurable actions (enable output or increment totalizer counter). It is always a progressive counter. The following configuration parameters are directly related to the batch counter operation.
SP bAt
SP bAt
SP bAtSP bAt
OFF.bAt
OFF.bAt
OFF.bAtOFF.bAt
rES.bAt
rES.bAt
rES.bAtrES.bAt
Batch counter Set point.
Initial value (Offset) for the batch counter.
Reset options for the batch counter (input, key, Set point, output, etc.).
TOTALIZER COUNTER
Totalizes the main counter or the number of times that the batch counter Set point was reached, with manual or automatic reset. When its Set point is reached (greater than or equals to) it can activate an output. The following configuration parameters are directly related to the totalizer operation.
Opt.tot
Opt.tot
Opt.totOpt.tot
Totalizer counting option (input pulse or batch)
SP tot
SP tot
SP totSP tot
OFF.t
OFF.t
OFF.tOFF.t
rES.tot
rES.tot
rES.totrES.tot
Totalizer Set point.
Initial value (Offset) for the totalizer.
Reset options for the totalizer (input, key, Set point, output, etc.).
OUT1
This output is always associated to the main counter, and it is activated when Set point 1 is reached, and disabled with time, reset, Set point 1 or when OUT2 is enabled. The following configuration parameters are directly related to the OUT1 operation.
Out1.t
Out1.t
Out1.tOut1.t
Time to deactivate OUT1 (0.00
0.00 to 9999.99
9999.99
0.000.00
9999.999999.99
s).
Out1.E
Out1.E
Out1.EOut1.E
Turn-off options of OUT1 (time, OUT2, reset, Set point 2).
Out1.OP
Out1.OP
Out1.OPOut1.OP
Freeze counting while OUT1 is activated (yes, no).
Out1.c
Out1.c
Out1.cOut1.c
OUT1 normal state open or closed.
OUT2
This output can be activated by Set point 2 of the main counter, by the batch counter Set point or by the totalizer Set point. It can be deactivated by time, reset, activation of OUT1 or Set point that activated it. The following configuration parameters are directly related to the OUT2 operation.
Out2.SE
Out2.SE
Out2.SEOut2.SE
OUT2 activation options (Set point 2, batches or totalizer).
Out2.t
Out2.t
Out2.tOut2.t
Time to deactivate OUT2 (0.00
0.00 to 9999.99
9999.99
0.000.00
9999.999999.99
s).
Out2.E
Out2.E
Out2.EOut2.E
Turn-off options of OUT2 (time, OUT1, reset).
Out2.OP
Out2.OP
Out2.OPOut2.OP
Freeze counting while OUT2 is activated (yes, no).
Out2.c
Out2.c
Out2.cOut2.c
OUT2 normal mode open or closed.
BLOCK DIAGRAM
Figure 1 illustrates associations among features and resources of
NC400-6:
Figure 1 – Diagram with features and resoucers of NC400-6
COUNTING MODES
The Coun.tY
Coun.tY parameter selects the counting mode as slow or fast.
Coun.tYCoun.tY
In the slow counting mode, a filter is applied to the counting signals, limiting the maximum pulse frequency, which is necessary to count the number of activations of electromechanical contacts. In the fast counting mode, NC400-6 operates up to the maximum frequency specified for the input signal. The frequency limits for each mode are defined in Item 5.
The Coun.UP
Coun.UP parameter defines the main counting direction (UP or
Coun.UPCoun.UP
DOWN) and the function of each input. Table 1 shows options for this parameter.
Code
0000 1111 4444 5555 6666 7777 8888 9999
12
12
1212 13
13
1313 14
14
1414 15
15
1515
Table 1 – Counting modes that can be selected with the Coun.UP
COUNT2/HOLD
Input
COUNT1 Input Main direction
HOLD SUB DOWN HOLD ADD UP
SUB SUB DOWN SUB ADD UP ADD SUB DOWN
ADD ADD UP Select ADD SUB or ADD DOWN Select SUB ADD or SUB UP
QUADRATURE DOWN
QUADRATURE UP QUADRATURE 2x DOWN QUADRATURE 2x UP
Coun.UP parameter.
Coun.UPCoun.UP
The main counting direction affects the main counter:
Main direction UP: Main counter count upstream, starting from
the Offset value defined (usually zero). Actions can be programmed to take place in Set point 1 and 2 values.
Main direction DOWN: The main counter count downstream,
starting from the Set point 2 value (SP2C
SP2C).
SP2CSP2C
The action programmed for this Set point will take place when the counter reaches the programmed Offset value.
The totalizer direction is always up.
You can select functions for COUNT1 and COUNT2/HOLD inputs:
ADD: Progressive counting input.
SUB: Regressive counting input.
Operation descriptions in this manual consider that the NC400-6 counter is operating in the UP direction. To operate in DOWN direction, refer to the explanation above.
HOLD: Stops the counting input for COUNT1.
NOVUS AUTOMATION
2
Contador Eletrônico NC400-6
Select ADD/SUB: COUNT2 input defines if COUNT1 input is
progressive or regressive.
QUADRATURE: Bidirectional counting mode that uses two
counting inputs to determine if counting is progressive or regressive. In this counting mode, the Coun.tY
Coun.tY parameter is ignored
Coun.tYCoun.tY
and the counting mode is always fast.
QUADRATURE 2X: The same as the QUADRATURE mode,
but it counts twice as fast, increasing resolution. In this counting mode, the
Coun.tY
Coun.tY parameter is ignored and the
Coun.tYCoun.tY
counting mode is always fast.
The counter is incremented or decremented whenever the voltage level in the counting inputs increases (rising edge) except in the fast counting mode (Coun.tY
Coun.tY = 1111) in COUNT1 input.
Coun.tYCoun.tY
The most representative counting modes are shown in Figures 2 to
5. Low and High levels in the following figures correspond to voltage
levels in these inputs with PNP sensor or Voltage pulse. For the case of NPN sensors or dry contact, signals will be reversed.
Figure 2 – Counting modes 1 and 5
Figure 3 – Counting modes 7 and 8
FEATURES
Signals compliant with the RS-485 standard. MODBUS (RTU)
protocol. 2 wire connection between 1 master and up to 31 (able to address up to 247) instruments in bus topology. Communication signals are electrically isolated from the rest of the device;
Maximum connection distance: 1000 meters;
NC400-6 disconnection time: Maximum 2 ms after the last byte;
Fixed communication speed (Baud Rate): 9600 bps;
Number of data bits: 8, no parity. Number of stop bits: 1;
Transmission onset and response time: maximum of 100 ms
after command.
RS-485 signals are:
D1 D D + B
D0
D - A
C
GND
CONFIGURATION OF SERIAL COMMUNICATION PARAMATERS
Bidirectional data line. Terminal 16
Reserved bidirectional data line. Terminal 17
Optimal connection that enhances the communication performance.
Parameter that must be configured when the serial communication used:
Addres
Addres
AddresAddres
OVERFLOW AND UNDERFLOW
NC400-6 counter communication adress.
If the counter is at 0000 and it receives a pulse to decrement, the counter will show 999.999 that the counter rolls to 999.999
999.999 and turn the OVFL flag on. This means
999.999999.999
999.999. If it increments beyond this, it will
999.999999.999
roll back to 0000, clearing OVFL flag. On a similar way, when the counter is at 999.999
999.999 and it is
999.999999.999
increased, it will roll to 0000 and turn the OVFL flag on. When it decreases again below 0000, it will turn the flag off and roll back to
999.999
999.999.
999.999999.999
Note: The setpoints and output control have no effect while OVFL flag is on, except those who are cleared by time.
Terminal 18
Figure 4 – Counting mode 13 (quadrature)
Figure 5 – Counting mode 15 (quadrature 2x)
SERIAL COMUNICATION (OPTIONAL)
Optionally, NC400-6 can be deliverd with an assynchronous master­slave serial communication interface RS-485 to communicate with a supervisor computer (master). The counter is always the slave. Communication always start with the master, which sends a command to the slave address with whom it wants to communicate. The addressed slave undertakes the command and sends the response to the master. NC400-6 also accepts broadcast commands.
INSTALATION
PANEL MOUNT
NC400-6 must be installed in a papel. To install, follow the steps below:
1. Make a panel cutout of 45.5 x 45.5 mm;
2. Remove the clips from NC400-6;
3. Insert NC400-6 in the frontal panel cutout;
4. Replace clips in NC400-6 and press them tightly to clamp the
counter to the panel.
INSTALLATION RECOMMENDATIONS
Input signal wires must be installed in grounded conduits and
away from power or contactor wires+
Instruments must be powered only by an exclusive power
supply.
System failure should always be taken into account when
designing a control panel to avoid irreversible damage to equipment or people. The output internal relay does not warrant total protection.
Installing RC filters (47 Ohms and 100 nF, serial) is strongly
recommended at contactor coils or any other inductors.
NOVUS AUTOMATION
3
Loading...
+ 5 hidden pages