TEMPERATURE CONTROLLER
N440
OPERANTING MANUAL - V1.1x
The N440 is a digital temperature controller in 1/16 DIN size with 2 ON/OFF outputs
for control and alarm. Its 3½ digit display is used for temperature indication as well as
for parameter configuration. Easy to configure, the N440 is intended for use in
furnaces, ovens, fryers, etc., delivering accurate temperature measurements with
excellent immunity to electromagnetic fields. Three sensor types are available (Pt100
and thermocouples J or K) with sensor offset correction.
SAFETY SUMMARY
The symbols below are used on the equipment and throughout this document to draw
the user’s attention to important operational and safety information.
CAUTION or WARNING:
Read complete instructions prior to
installation and operation of the unit.
All safety related instructions that appear in the manual must be observed to ensure
personal safety and to prevent damage to either the instrument or the system. If the
instrument is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
CAUTION or WARNING:
Electrical Shock Hazard
SPECIFICATIONS
Sensor Input: The sensor type is defined in the production process. Check the
instrument label to find out the input type of your particular model. The available
sensors options are:
Pt100; range: –50 °C to 530 °C (-58 to 986 °F); Accuracy: 1 °C (1.8 °F);
α=385. 3-wire connection. Excitation current: 0.170 mA;
Thermocouple J; 0 to 600 °C (32 to 999 °F); Accuracy: 2 °C (3.6 °F);
Thermocouple K; 0 to 1370 °C (32 to 2498 °F); Accuracy: 3 °C (5.4 °F);
Measurement resolution:
Pt100: 0,1 °C in the range –19.9 to 199.9 °C/°F, 1 °C/°F otherwise
Thermocouples: 1 °C/°F;
Output 1 (OUT1) (check instrument label for installed option)
Relay SPDT: 3 A / 250 Vac (3 A / 30 Vdc);
Output 2 (OUT2) (check instrument label for installed option)
Relay SPST-NO 1.5 A / 240 Vac (1.5 A / 30 Vdc);
Logic pulse: 5 Vdc, 15 mA max;
Power supply:
100 to 240 Vac/dc or 24 Vac/dc ± 10 % (check instrument label for installed option);
Frequency: 50/ 60 Hz; Power consumption: 2 VA
Environmental conditions: Temperature: 5 to 50 °C. Relative humidity (maximum): 80 %
up to 30 ºC. For temperatures above 30 ºC, decrease 3 % per ºC. Installation category II.
Pollution degree 2. Altitude < 2000 m.
EMC: EN 61326-1:1997 and EN 61326-1/A1:1998.
SAFETY: EN61010-1:1993 and EN61010-1/A2:1995
Warm-up time: 15 minutes;
Housing: Front panel: Polycarbonate UL94 V-2; Rear case: ABS+PC UL94 V-0
Dimensions: 48 x 48 x 110 mm. Panel cut-out: 45,5 x 45,5 mm; Weight: 150 g
OVER-TEMPERATURE PROTECTION
When designing any control system it is essential to consider what will happen if any
part of the system should fail. In temperature control applications the primary danger is
one in which the heating remains constantly on. In any application where physical
injury or destruction of equipment might occur, it is recommend to install an
independent protection equipment, with a separate temperature sensor, to disable the
heating circuit in case of overheating. Please note that the alarm relays within the
controller will not give protection under all failure conditions.
INSTALLATION
Panel mounting: Insert the unit into the panel cut-out and slide the mounting clamp
from the rear to a firm grip at the panel.
Electrical connections:
All electrical connections are made to the screw terminals at the rear of the controller.
They accept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be
tightened to a torque of 0.4 Nm (3.5 lb in).
Routing of wires
To minimize the pick-up of electrical noise, the low voltage DC connections and the
sensor input wiring should be routed away from high-current power conductors. If this
is impractical, use shielded cables. In general, keep cable lengths to a minimum.
It is strongly recommended to install RC filters (47 R and 100 nF, serial combination) at
contactor coils and other inductors.
WARNING: System failure should always be taken into account when designing a
control panel to avoid irreversible damage to equipment or people.
The figure below shows the N440 connections to mains, sensor and outputs.
Figure 1 – N440 back panel terminals
The installation must include a power isolating switch or circuit breaker
that disconnects all current carrying conductors. The device should be
mounted close to the controller, within easy reach of the operator and
marked as the disconnecting device for the instrument.
Wire sensor and outputs according to figure 1.
OPERATION
Before the controller is ready to be used in a given process, it requires some basic
configuration. The parameters are arranged in 4 levels:
Level Access Function
0 - Temperature measurement
1
2
3
4
After power-up, the controller will display the firmware version for 1 second. This
information is important for traceability and when contacting the manufacturer.
The instrument then shows the temperature measured by the sensor. This is the level
0 or temperature measurement level.
Pressing will lead to level 1, causing the display to alternate between the
messages “SP1
again.
To reach level 2, press for 2 seconds until the parameter “ sp2
Release the key to stay in this level. To go back to level 0, press again.
To enter level 3, press the key for 4 seconds and the parameter “Ac1
displayed. Release the key to stay in this level. Press to access other parameters
in this level. At the end of this cycle, the controller will return to level 0.
To enter the calibration level (level 4) press the key for 10 seconds.
To change a parameter setting, press the keys and until the desired value is
reached.
The new configuration value is saved in the controller by pressing the key (when
advancing to the next parameter in the level).
holding for 10 seconds
SP1” (set point 1) and the programmed value. To go back to level 0, press
SP1SP1
holding for 2 seconds
holding for 6 seconds
PROGRAM SECURITY
To avoid tampering, parameter “Prot
access to programming parameters.
With the jumper in the OFF position, all program levels are unprotected. The “ Pro t
parameter can only be changed with the jumper in the OFF position.
With the jumper in the ON position or removed, the protection level is defined by the
current value of the “Prot
0000 No protection. All parameters can be accessed;
1111 No access to the Calibration level;
2222 No access to Calibration and Configuration levels;
3
3 No access to Calibration, Configuration and SP2 levels;
33
4
4 Full protection.
44
Figure 2 – Protection Disabled Figure 3 – Protection Enabled
Prot” parameter:
ProtProt
OFF
Prot” and a hardware jumper can be used to disable
ProtProt
LEVEL 1 –OUT1 SET POINT
Parameter Description/Parameter function
SP1
SP1
SP1SP1
Set Point 1
Temperature set point associated to the OUT1 output. Possible
values are limited by the parameters SPL
Set point for output OUT1
Set point for output OUT2
Parameter configuration
SPL e S Pk
SPLSPL
Calibration
sp2” is displayed.
sp2sp2
ON
SPk in level 3
SPk SPk
Ac1” will be
Ac1Ac1
Prot”
ProtProt
LEVEL 2 –OUT2 SET POINT
(Available only on models with 2 outputs).
SP2
SP2
SP2SP2
Set Point 2
Temperature set point associated to the OUT1 output. Possible
values are limited by the parameters SPL
LEVEL 3 – PARAMETERS CONFIGURATION
Ac1
Ac1
Ac1Ac1
Action 1
OUT1 Functions:
0
0 Reverse action usually used for heating
00
1
1 Direct Action usually used for cooling.
11
2
2 Low temperature alarm
22
3
3 High temperature alarm
33
4
4 Low temperature alarm with initial blocking
44
5
5 High temperature alarm with initial blocking
55
6
6 Out of range alarm (differential).
66
7
7 In range alarm (differential).
77
8
8 Out of range alarm with initial blocking.
88
9
9 In range alarm with initial blocking.
99
See the following section for details.
Ac2
Ac2
Ac2Ac2
Action 2
OUT2 Functions:
0
0 Reverse action usually used for heating
00
1
1 Direct Action usually used for cooling.
11
2
2 Low temperature alarm
22
3
3 High temperature alarm
33
4
4 Low temperature alarm with initial blocking
44
5
5 High temperature alarm with initial blocking
55
6
6 Out of range alarm (differential).
66
7
7 In range alarm (differential).
77
8
8 Out of range alarm with initial blocking.
88
9
9 In range alarm with initial blocking.
99
See the following section for details.
ky1
ky1
ky1ky1
Histeresis 1
OUT1 Hysteresis: Defines the differential range between the
temperature value at which the alarm is turned on and the value at
which it is turned off (in engineering units - °C or °F). Adjustable in
the range 0.1 to 70.
ky2
ky2
ky2ky2
Histeresis 2
OUT2 Hysteresis: Defines the differential range between the
temperature value at which the alarm is turned on and the value at
which it is turned off (in engineering units - °C or °F). Adjustable in
the range 0.1 to 70.
ofs
ofs
ofsofs
Offset
spl
spl
splspl
SP Low Limit
spK
spK
spKspK
SP High Limit
Unt
Unt
UntUnt
Unit
prt
prt
prtprt
Protection
Offset value to be added to the measured temperature to
compensate sensor error. Default value: zero. Range: –15 to +15.
Set point Low Limit: sets the minimum value allowed for the set
points 1 and 2. Spl
Spl< s pK
spK
SplSpl
spKspK
Set point High Limit: sets the maximum value allowed for the set
points 1 and 2. Spx
Spx > spl
spl
Spx Spx
splspl
Selects the display indication to be in ºC or ºF.
0000 Temperature in degrees Celsius.
1111 Temperature in degrees Fahrenheit.
Configuration protection:
0 No protection
1 No access to the Calibration level;
2 No access to Calibration and Configuration levels;
3 No access to Calibration, Configuration and SP2 levels;
4 No access to Calibration, Configuration, SP2 and SP1 levels;
SPL e S Pk
SPk in level 3
SPLSPL
SPk SPk
LEVEL 4 – CALIBRATION
(al
(al
(al(al
CAlibration Low
(Ak
CAlibration High
(jl
Cold Junction Low
Calibration
INPUT LOW CALIBRATION: Sets the Process Variable low calibration
(offset). Several keystrokes at or might be necessary to
increment one digit. The displayed value corresponds to the actual
(calibrated) temperature as seen by the controller.
INPUT HIGH CALIBRATION: Adjusts the Process Variable span
calibration (gain).
COLD JUNCTION OFFSET CALIBRATION: Adjusts the offset of the
cold junction temperature. Valid for thermocouple inputs only.
USING THE CONTROLLER
When in the process, the N440 displays the temperature measured by the sensor
connected in the terminals named SENSOR INPUT.
The sensor is defined at the purchase. The user needs then to configure outputs OUT1
and OUT2 (OUT2 is optional) with the desired functionality. Parameters Ac 1
define the outputs working mode. OUT1 is normally used as the control output,
whereas OUT2 is used as the alarm output. Depending on output requirements (relay
or logic pulse), the outputs may be configured differently.
The OUT1 e OUT2 outputs can perform in the following ways:
0000- Reverse action usually used for heating.
Output turns on when temperature is bellow set point minus hysteresis. Output
turns off when temperature is above set point.
1111- Direct Action usually used for cooling.
Output turns on when temperature is above set point plus hysteresis Output turns
off when temperature is bellow set point.
2222- Low temperature alarm.
Output turns on when temperature is bellow set point. Output turns off when
temperature is above set point plus hysteresis.
3333- High temperature alarm.
Output turns on when temperature is above set point. Output turns off when
temperature is bellow set point minus hysteresis.
4444- Low temperature alarm with initial blocking.
Same as low temperature alarm, but with initial blocking as described next.
5555- Low temperature alarm with initial blocking.
Same as high temperature alarm, but with initial blocking as described next.
6666- In range alarm (differential).
Available only for OUT2. Output turns on when temperature is in the range from
(SP1
SP1 - SP2
SP2) to (S P1
SP1 + S P2
SP1SP1
SP2SP2
OUT
SP2
SP1
OUT1 programmed for in of range alarm OUT2 programmed for in of range alarm
SP1SP1
SP2
SP2).
SP2SP2
SP2 + SP1
SP1
SP2
7777- Out of range alarm (differential).
Available only for OUT2. Output turns on when temperature is out of the range from
(SP1
SP1 - SP2
SP2) to (S P1
SP1 + S P2
SP1 SP1
SP2SP2
OUTPUT ON
OUT
TEMPERATURE
SP2
SP1
OUT1 programmed for out of range alarm OUT2 programmed for out of range alarm
SP1SP1
SP2
SP2).
SP2SP2
SP2 + SP1
OUTPUT ON
OUTPUT ON
OUT
TEMPERATURA
SP1
SP2
OUTPUT ON
SP1
SP1
Ac1 and Ac2
Ac2
Ac1Ac1
Ac2 Ac2
SP1 + SP2
OUTPUT ON
SP1 + SP2
8888- In range alarm with initial blocking.
Same as in range alarm, but with initial blocking as described next.
9999- Out of range alarm with initial blocking.
Same as out of range alarm, but with initial blocking as described next.
Note 1: OUT1 and OUT2 outputs can’t be simultaneously configured for In Range and
Out of Range alarm.
Note 2: The initial blocking feature, when enabled, results in the controller ignoring
alarm conditions which exists when the controller is powered-on or started.
Alarms with initial blocking:
The initial blocking option inhibits the alarm from being recognized if an alarm condition
is present when the controller is first energized. The alarm will actuate only after the
occurrence of a non alarm condition followed by a new occurrence for the alarm.
In the front panel, OUT indicator will light on when OUT1 is active, and AL1 indicator
will light on when OUT2 is active.
Hysteresis parameters ky1
ky1 and ky2
ky1ky1
ky2 are associated to outputs OUT1 and OUT2,
ky2ky2
and defines the differential range between the temperature value at which the alarm is
turned on and the value at which it is turned off
Offset (ofs
ofs) parameter may be adjusted to correct temperature indication due to
ofsofs
sensor error. The adjusted value is added to the temperature read before indication.
Parameters write protection:
Write to parameters may be disabled for each parameter level by means of an internal
protection strap key which when ON will block access to configuration. The instrument
is not protected with the strap key in OFF position. By placing the strap at ON, access
will be limited as defined in the “Prt
The protection parameter “Prt
Prt’’ parameter description.
PrtPrt
Prt” must be defined with the strap key in place otherwise
PrtPrt
it cannot be changed.
PROBLEMS WITH THE CONTROLLER
Connection and configuration errors state for most of the problems in using the
controller. A final revision of parameters will save time and further losses. Error
messages are displayed to help the user to identify possible problems. If one of the
messages bellow is displayed, all outputs are turned off for safety.
• Temperature above high limit.
• Broken sensor. Pt100 badly connected
• Temperature bellow low limit.
• Pt100 short-circuited.
TECHNICAL ASSISTANCE
If you encounter a problem with your controller, review the configuration with regard to
inputs, outputs, alarms, etc. If the problem persists, contact your supplier or Novus at
info@novus.com.br.
ORDERING INFORMATION:
N440 - J R R - 24V
A B C D E
A. Series model: N440;
B. Input sensor: C (Pt100), J (type J thermocouple) or K (type K thermocouple);
C. Output 1: R (Relay);
D. Output 2: R (Relay) or P (Pulse);
E. Voltage rating: blank (100-240 Vac or 24V (24 Vac/dc);