Pt100 6 range: -199.9 to 530.0 °C ( -328.0 to 986.0 ºF)
7
4-20 mA
8
J linearization. Programmable range: -110 to 760 °C
4-20 mA
9
K linearization. P rogrammable range: -150 to 1370 °C
4-20 mA
10
T linearization. Programmable range: -160 to 400 °C
4-20 mA
11
N Linearization. Programmable range: -90 a 1370 °C
4-20 mA
12
R Linearization. Programmable range: 0 a 1760 °C
4-20 mA
13
S linearization. P rogrammable range: 0 to 1760 °C
4-20 mA
14
Pt100 linearization. Prog. Range:-200.0 to 530.0 °C
4-20 mA
15
Pt100 linearization Prog. Range:-200 to 530 °C
0 to 50 mV
16
Linear. Programmable i ndication -1999 to 9999
4-20 mA
17
Linear. Programmable i ndication -1999 to 9999
0 to 5 Vdc
18
Linear. Programmable i ndication -1999 to 9999
4 to 20 mA
19
Square Root Extraction
N3000
AL PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V2.1x C
SAFETY SUMMARY
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION OR WARNING:
Read complete instructions prior to
unit.
CAUTION OR WARNING:
Electrical S hock Hazard
All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the i nstrument is used in a manner
not specified by the manufacturer, the protection provided by the
equipment may be impaired.
INTRODUCTION
The N3000 is a proc ess controller incorporating a P ID algorithm and
universal inputs (sensor and standard si gnals) and outputs (logical,
relay and analog outputs). It holds in one single instrument all de
main features that are needed for the vast majority of industrial
processes.
CONFIGURATION
INPUT TYPE SELECTION
Select the input type (in parameter “
Pt100
range: -200 to 530 °C (-328 to 986 ºF)
”) from Table 1 below.
OVER-TEMPERATURE PROTECTION
When designing any control system it is essential to consider what
will happen if any part of the system should fail. In temperature
control applications the primary danger is one in which the heating
remains constantly on. In any application where physical injury or
destruction of equipment might occur, it is recommend to install an
independent protection equipment, with a separate temperature
sensor, to disable the heating c ircuit in case of overheating. Please
note that the alarm relays within the controller wil l not give protection
under all failure conditions.
NOVUS AUTOMATION 1/9
Table 1 - Input Types
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input/output c hannels can assume multiple functions,
depending on configuration: control output, alarm output, digital
output, digital input, and PV or SV analog retransmission. These
channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6.
The basic controller model comes loaded with:
• I/O1 and I/O2 - SPDT relay output;
• I/O3 and I/O4 – SPST relay output;
• I/O5 - analog output (0-20 or 4-20 mA), pulse 10 V max, digital I/O;
• I/O6 – Digital Input;
The function code of each I/O can be selec ted among the options on
Table 2. Only valid function codes are displayed for each I/O (for
example, I/O1, which is a relay , can be confi gured with functi ons 0 to
5 only; on the other hand, I/05 can perform all 16 functions).
The description for the functions follows:
•CODE 0 - No function. The I/O channel programmed with code 0
will not be used by the controller. It is available to be used by serial
communication as digital output.
•CODES 1 to 4 - Alarm output - Available for all I/O channels
(except I/O6). The selected channel can be used as output to
Alarms 1 to 4.
• CODE 6 - Digital input - Standard for I/O5 and I/O6.
Closed: Manual control
Opened: Automatic control
Controller N3000
rvn
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
off
No active alarm. This output can be used as a digital
output to be set by t he serial communication.
(input Error)
ierr
Alarm will be ON if P V sensor breaks, input signal is
Event Alarm
Soak)
rs
Can be activated at a specific segment of ramp and
resistance f ail
rfail
lo
SPAn
PV
ki
SPAn
PV
difl
SV
PV
SV - SPAn
SV
PV
SV - SPAn
difk
SV
PV
SV + SPAn
SV
PV
SV + SPAn
dif
SV
PV
SV + SPAn
SV - SPAn
SV
PV
SV - SPAn
SV + SPAn
SPA1
SPA2
A1t1
A1t2
A2t1
A2t2
•CODE 7 - Digital input - Standard for I/O5, I/O6 and key.
Start/Stop input (“
”: YES / no).
Closed: outputs enabled
Opened: outputs disabled
•CODE 8 - Digital input - Standard for I/O5, I/O6 and
key.
Closed: remote SP (4-20 mA in remote SP input)
Opened: main SP (internal programmed SV)
•CODE 9 - Digital input - Standard for I/O5, I/O6 and key.
Opened: enables R&S program
Closed: holds R&S program (the program resumes when the
contact is opened again)
CODE I/O TYPE I/O FUNCTION
Digital Output Digital Output to be set by the serial comm.
Digital Output Alarm 1 Output
Digital Output Alarm 2 Output
Digital Output Alarm 3 Output
Digital Output Alarm 4 Output
Digital Output PWM Control Output
Digital Input Automatic/Manual mode change
Digital Input Run/Stop mode change
Digital Input Select Remote Set Point Input
Digital Input Executes/Holds selected ramp and soak profile
Digital Input Enable/Disable R&S profile 1 selection
Analog Output 0 to 20mA Analog control out put
Analog Output 4 to 20mA Analog control output
Analog Output 0 to 20mA PV retransmission
Analog Output 4 to 20mA PV retransmission
Analog Output 0 to 20mA SP retransmission
Analog Output 4 to 20mA SP retransmission
Table 2 - I/O channel f unctions
•CODE 10 - Digital input - Standard for I/O5, I/O6 and key.
Selects R&S program 1. Used to alternate between the main
Setpoint and a second Setpoint defined by the R&S program 1.
Closed: selects program 1
Opened: uses main Setpoint
•CODE 11 - Analog control output - I/O5 only. 0-20 mA control
output.
•CODE 12 - Analog control output - I/O5 only. 4-20 mA control
output.
•CODES 13 to 16 - Analog retransmission. I/O5 only. Configures
I/O5 to output a 0-20 mA or 4-20 mA analog signal proportional to
PV or SP.
REMOTE SETPOINT
The remote Setpoint (SP) is enabled by an external digi tal signal in
either I/O5 or I/O6, when programmed with the code 8 (Select remote
SP input).
An external resistor shunt of 100 Ω is required between the terminals
7 and 8.
ALARMS FUNCTION
The controller has 4 alarms. The alarms can the configured to
operate in any of the nine functions listed on Table 3.
• Open sensor
It is activated whenever the input sensor is broken or disconnected.
• Event alarm
It activates alarm(s) in specifi c segments of the program. See item
7.2 in this manual.
• Event alarm
Detects a heater broken condition, by monitoring the load current
when the control output is ac tivated. This alarm functi on requires an
optional device (option 3). Details of the "resis tance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.
TYPE PROMPT
Disabled
Sensor Break
(ramp and
Detection
Low Alarm
High Alarm
LOW
Differential
HIGH
Differential
Differential
out of range or Pt100 is shorted.
Detects a heater br oken condition
positive SPAn
positive SPAn
positive SPAn
Table 3 - Alarm functions
ACTION
soak program.
negative SPAn
negative SPAn
negative SPAn
Where SPAn means “SPA1”, “SPA2”, “SPA2” and “SPA4”.
• Minimum value
It is activated when the measured value i s below the v alue defined i n
the alarm Setpoint.
• Maximum value
It is activated when the meas ured val ue is above t he val ue defi ned in
the alarm Setpoint.
• Differential (or Band)
In this function, the parameters “
”, “
” represent the PV
deviation as compared to the main SP.
In a positive deviation, the di fferential alarm will be triggered when
the measured value is out of the range defined in:
( SP – Deviation) and (SP + Deviation)
In a negative deviation, the differenti al alarm will be triggered when
the measured value is within the range defined above.
• Minimum differential
It is activated when the measured value is below the value defined in.
(SP - Deviation)
• Maximum differential
It is activated when the measured value is above the value defined in:
(SP + Deviation)
ALARM TIMER FUNCTIONS
Alarms 1 and 2 can be programmed to have timer functions. The 3
modes of operation are:
1- Pulse 2- delayed actuation 3- Oscillator
The desired function can be achieved programming the parameters
”, “
”, “
” and “
“
” (see Table 4).
The LEDs associated to the alarms will light when the alarm condition
is recognized, not following the actual state of the output, which may
be temporarily OFF because of the temporization.
NOVUS AUTOMATION 2/9
Alarm Function
T1 T2 ACTION
Alarm Event
Alarm
Output
Alarm Event
Alarm
Output
T2
Alarm Event
Alarm
Output
T1
Alarm Event
Alarm
Output
T1
T2
T1
SPLL
SPkL
SfSt
ovLL
ovkL
irreversible damage
will occur
Figure 2 – High and Low Voltage AC power w iring
wiring
three conductors
Figura 5 – connection of 4-20 mA
Figura 6 – Connection of 5 Vdc
Normal 0 0
Delayed 0 1s to 6500s
Controller N3000
Pulse 1s to
6500s
Oscillator 1s to
6500s
Table 4 - Advanced Timer A larm (for alarms 1 or 2)
0
1s to 6500s
ALARM INITIAL BLOCKING
The initial blocking opti on inhibits the alarm from being recognized if
an alarm condition is present when the controll er is first energized.
The alarm will actuate only after the occurrence of a non alarm
condition followed by a new occurrence for the alarm.
The initial blocking is disabled for the sensor break alarm function.
SQUARE ROOT EXTRACTION
Available when input type 19 is sel ected. The indicator displays the
square root of the current signal input applied to terminals 22 and 24.
ANALOG RETRANSMISSION OF PV AND SP
The analog output, when not used for control purposes, is available
for retransmitting the SV and SP values in 0-20 or 4-20 mA. Thi s
analog output is electrically isolated from other inputs and outputs.
The analog output signal is scaleable, with the output range
determined by the values programmed in the parameters “
”. To obtain a voltage output, connect a resistor shunt to the
“
” and
current output terminals (terminal 1 and 2).
Figure 1 – Back panel terminals
POWER WIRING
If high voltage is
applied to a low
voltage input,
INPUT CONNECTIONS
• Thermocouple and Voltage (Volts and mV) input connect as i n
Figure 3.
SOFT START
Defines the time i nterval for the output to reach its maximum value
(100 %). The soft start value is programmed in “
parameters “
” and “
INSTALLATION / CONNECTION
Insert the unit into the panel cut-out and slide the mounting clamp
from the rear to a firm grip at the panel.
All electrical connecti ons are made to the screw terminals at t he rear
of the controller. They accept wire siz es from 0.5 to 1.5 mm2 (16 to
22 AWG). The terminals should be tightened to a torque of 0.4 Nm
(3.5 lb in).
To minimize the pick-up of electrical noise, the low voltage DC
connections and the sensor input wiring s hould be routed away from
high-current power conductors. If this is impractical, use shielded
cables. In general, keep cable lengths to a minimum.
RECOMMENDATIONS FOR INSTALLATION
• Input signal wires s hould be laid out away from power lines and
preferably inside grounded conduits.
• Instrument mains (line) supply should be suitabl e for this purpose
and should not be shared.
• In controlling and monitoring applicati ons, possible consequences
of any system failure mus t be considered in advanc e. The internal
alarm relay does not warrant total protection.
• Use of RC filters (47 R and 100 nF, serial) are highly
recommended when driving solenoids, contactor coils or other
inductive loads.
NOVUS AUTOMATION 3/9
”. See also
Figure 3 – T/C and Voltage
Figura 4 – Pt100 wiring wi th
”.
• RTD (Pt100)
Figure 4 shows the Pt100 wiring, for 3 conductors. Terminals 10, 11 and 12
must have the same wire resistance for proper cable length compensation.
For 2 wire Pt100, shor t circuit t erminals 10 and 11.
•4-20 mA:
Refer to Figure 5. (The controller provides an internal electronic
shunt for the input current. No changes in the circuit are necessary).
•Alarm and output connection
When I/O channels are set up as output channels, they must have
their capacity respected, according do specifications.
• Remote setpoint:
The remote Setpoint (SP) is enabled by an external digi tal signal in
either I/O5 or I/O6, when programmed with the code 8 (Select remote
SP input).An external resistor shunt of 100 is required between the
terminals 7 and 8.
DIGITAL INPUT
Loading...
+ 6 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.