NOVUS N1500G User Manual

Alarm SP
PV
PV
AL SP + Deviation
AL SP
PV
AL SP +
Deviation
AL SP
PV
AL SP +
Deviation
Positive
Deviation
AL SP
AL SP -
Deviation
PV
AL SP - Deviation
Negative Deviation
AL SP AL SP + Deviat.
N1500G
UNIVERSAL INDICATOR - OPERATING MANUAL
1. PRESENTATION
N1500G is a universal process indicator which accepts a large variety of input signals and sensors.
Instrument configuration is achieved from the keyboard, without any hardware change.
The user should read this manual thoroughly before using the instrument. It is a fine electronic device and should be used accordingly for best results.
Some of the features of the basic version are:
Universal input: Pt100, thermocouples, 4-20 mA, 0-50 mV and 0-5
Vdc
24Vdc power supply for remote transmitters excitation
Maximum and minimum memory
Digital input with Hold Peak Tare and hold function
Process Variable retransmission in 0-20 mA or 4-20 mA
RS485 MODBUS RTU serial communication
Display: Shows process variable (PV) and the programming prompts.
ALM1 and ALM2: show alarm status.
INDEX key - This key is used to access the programming
menu and prompts. BACK key - This key is used to go back to the previously
reached prompt in the menu cycle. UP / MAX key and DOWN / MIN - Used to increase
and decrease parameters values, these keys are also used to display maximum and minimum values stored in memory..
Special FUNCTION key - This special function key is used for pre-programmed functions as explained in the SPECIAL FUNCTION KEY section of this manual.
2. PROCESS VARIABLE INPUT - PV
The Process Variable input type should be keyboard programmed by the user according to the codes shown on table 1 (refer to INPUT TYPE parameter "in.typ
All input types are factory calibrated and no additional calibration is required.
Thermocouples are calibrated to NBS standards. RTD’s are calibrated to DIN 43760 (α=0.00385).
TIPO CODE CARACTERÍSTICAS
J K T E N R S
B Pt100 Pt100
in.typ").
in.typin.typ
Range: -50 to 760 °C (-58 to 1400 °F)
Range: -90 to 1370 °C (-130 to 2498 °F)
Range: -100 to 400 °C (-148 to 752 °F)
Range: -35 to 720 °C (-31 to 1328 °F)
Range: -90 to 1300 °C (-130 to 2372 °F)
Range: 0 to 1760 °C (-32 to 3200 °F) Range: 0 to 1760 °C (-32 to 3200 °F)
Range: 150 to 1820 °C (302 to 3308 °F)
Range: -199.9 to 530.0 °C (-327.8 to 986.0 °F)
Range: -200 to 530 °C (-328 to 986 °F)
4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 0 -50 mV 4-20 mA
0 a 5 V
Linearizes J. Adjustable range: -110 to 760 °C
Linearizes K. Adjustable range.: -150 to 1370 °C
Linearizes T. Adjustable range.: -160 to 400 °C
Linearizes E. Adjustable range.: -90 to 720 °C
Linearizes N. Adjustable range -150 to 1300 °C
Linearizes R. Adjustable range 0 to 1760 °C
Linearizes S. Adjustable range.: 0 to 1760 °C
Linearizes B. Adjustable range.: 100 to 1820 °C
Linearizes Pt100. Adj. range.:-200.0 to 530.0 °C
Linearizes Pt100. Adj. range.: -200 to 530 °C
Linear. Adjustable range.: -1999 to 9999 Linear. Adjustable range.: -1999 to 9999 Linear. Adjustable range.: -1999 to 9999
Table 1 - Input type codes
3. ALARMS
The indicator features 2 alarm outputs in the basic version. Each alarm has a corresponding LED anunciator in the front panel to show alarm status.
TYPE PROMPT ACTION
Disabled
Sensor Break
(input Error)
Low Alarm
High Alarm
Diferential Low
Diferential High
Diferential
off
ierr
Lo
Ki
Dif.lo
Dif.ki
Dif
signal is out of range or Pt100 is shorted.
Table 2 - Alarm functions
3.1. ALARM FUNCTIONS
The alarms can set to operate in six different functions: Sensor break, Low Alarm, High Alarm, Differential Low, Differential High or Differential (Band). These functions are shown in table 2 and described as follows
3.1.1. Sensor break The alarm will go ON whenever the sensor breaks or is badly connected.
3.1.2. Low alarm The alarm relay will go ON whenever the measured value is below the alarm set point.
Alarm is inactive
Alarm will go ON if sensor breaks, input
Alarm SP
PV
NOVUS AUTOMATION 1/5
3.1.3. High alarm The alarm relay will be ON whenever the measured value is above the alarm set point.
3.1.4. Differential (Band) For differential alarm 2 parameters must be set: Differential Alarm Reference value (ALrEF) or alarm setpoint and Alarm Deviation (Band).
For a positive deviation the alarm will switch on whenever the measured value is out of the band defined as:
(ALrEF - Deviation) and (ALrEF + Deviation)
For a negative deviation the alarm will be switched on whenever the measured value is within the band defined above.
3.1.5. Differential Low The alarm relay will be ON whenever the measured value is below the band defined as:
(ALrEF - Deviation)
3.1.6. Differential High Alarm relay will be ON when the measured value is above the band defined as:
(ALrEF + Deviation)
3.2. ALARM INITIAL BLOCKING
The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is first energized. The alarm will actuate only after the occurrence of a non alarm condition followed by a new occurrence for the alarm.
The initial blocking is disabled for the sensor break alarm function.
3.3. ALARM TIMER
The alarms can be programmed to have timer functions where the user can set a delayed alarm action, just one pulse in an alarm event, or an oscillator function with sequential pulses.
Table 3 shows these advanced functions. Times T1 and T2 can be programmed from 0 to 6500 seconds (refer to item 8.2). Set 0 (zero) at the T1 and T2 prompt for a normal non-timer alarm operation.
The LEDs alarm anunciators will go ON whenever there is an alarm condition regardless of the present alarm status which may be temporarily off because of timer action.
Advanced
Function
Normal
Operation
Delayed 0 1s to 6500s
Pulse 1s to 6500s 0
Oscillator 1s to 6500s 1s to 6500s
T1 T2 ACTION
0 0
Table 3 - Timer Alarm Functions
Alarm
Output
Alarm
Output
Alarm
Output
Alarm
Output
Alarm Event
T2
Alarm Event
T1
Alarm Event
T1
Alarm Event
T2
T1
4. SPECIAL FUNCTIONS
4.1. MAXIMUM AND MINIMUM
The indicator memorizes the measured maximum and minimum values (peak and valley). These two values are shown by pressing either the MAX or MIN key. Pressing both keys simultaneously will clear the memory for a new peak and valley detection.
Indicator N1500G
4.2.1. Hold The hold function freezes the measured value in the display. Each
touch at the F key or closing the digital input alternates from hold to normal mode.
Whenever the indicator is in the hold mode a “HoLd” message is briefly displayed to show the operator that the displayed value is the frozen value and not the present reading.
4.2.2. Peak Hold The indicator turns automatically to Peak Hold mode whenever the F key or the digital input are programmed for “PHoLd
This operation mode makes the indicator display only the maximum reading value from the time the key was pressed of the digital input was activated.
Each activation of the F key or digital input triggers a new Peak Hold cycle and the display resets with a new peak value.
4.2.3. Reset (clears maximum and minimum) This function works the same way as the MAX and MIN keys pressed simultaneously, as explained in the 5.1 section.
If this “rESEt” function is programmed, for every touch of the F key or activation of the digital input the memory will be cleared and a new cycle of maximum and minimum will start.
4.2.4. AL.oFF - Alarm blocking This function allows the user to block or inhibit the alarm relays by pressing the F key or by activating the digital input. Each touch of the key or activation of the digital input will alternate the function from ON to OFF and vice-versa.
If an alarm situation occurs, the respective alarm status LEDs in the front panel will light regardless of the relay alarm blocking status.
4.2.5. Tare This function is used to zero the display. The tare residual values is subtracted or added to the total measured value. This function is generally used with load cells and strain gauges and applies to linear 4-20 mA, 0-50 mV and 0-5 V inputs.
4.3. PROCESS VARIABLE RETRANSMISSION
As an option, the indicator can be supplied with an isolated 0-20 mA or 4-20 mA analog output for Process Variable (PV) retransmission.
The PV values which define the range of the 0-20 mA or 4-20 mA retransmission can be programmed by the user in the high and low indication limits.
When available, this current output will be always active. For a voltage output signal an external shunt (calibrated resistor)
should be installed at the analog output terminals.
5. INSTALLATION
5.1. PANEL ASSEMBLY
The indicator is composed of two parts: the fixing base and the front part with main circuits. The base must be removed from the front and fixed onto a wall by means of four designed holes as shown in figure
2.
3X 12mm
90
4X 4mm
4.2. SPECIAL FUNCTION KEY AND DIGITAL INPUT
The F key and the optional digital input can execute special functions according to the user selection.
These functions can be chosen independently to the F key or to the digital input. Figure 10 shows how to activate the digital input. A
Figure 2 - Mounting the indicator in the panel cut-out.
The front part is only attached to the fixing base after all electrical wire connections are done.
266
closed contact or a short circuit at terminals 8 and 9 is recognized as activating the digital input.
The special functions for the F key and for the digital input are explained as follows.
NOVUS AUTOMATION 2/5
Loading...
+ 3 hidden pages