Important: Read and save these instructions. This guide to be left with equipment.
Nortec
SE-Series
Installation and
Operation Manual
Includes installation, operation,
maintenance, and troubleshooting
information for your indoor
Nortec SETC B+ and Nortec SEP
steam exchange humidifier
2552940-D | 23/11/2018
Thank you for choosing Condair.
SERIAL #
MODEL #
INSTALLATION DATE (MM/DD/YYYY)
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair LTD. Neither this
document nor the information contained herein shall be reproduced used, or disclosed to others without the
written authorization of Condair LTD., except to the extent required for installation or maintenance of
recipient’s equipment. All references to the Condair name should be taken as referring to Condair LTD.
Liability Notice
Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel
or the use of parts/components/equipment that are not authorized or approved by Condair.
Copyright Notice
Copyright 2018, Condair LTD. All rights reserved.
Contents
1
Introduction
43
Operation
2 Receiving and Unpacking
3 Humidifier Components
5 Nortec SETC/P Models
6 Options and Accessories
44 Nortec SEP LED Status Lights
45 How the Humidifier Works
49 Nortec SETC Humidifier Configuration
60 Nortec SEP Humidifier Configuration
63
Maintenance and
Servicing
64 Required Maintenance
65 Maintenance Schedule
69 Maintenance Shutdown and
Extended Shutdown
70 Maintenance Checklist
71
Troubleshooting
73 General Troubleshooting
23 External Controls
32 Options and Accessories
33
Start Up
34 Installation Check
35 Nortec SETC User Interface
36 Start Up Procedure
37 Status Screens
39 Digital Controls
41 Start Up Checklists
76 Nortec SETC Warnings and Faults
82 SEP Faults
83 Wiring Diagrams
85
96
Spare Parts
Warranty
1 | Introduction
Introduction
CAUTION: Servicing
Disconnect main power before any servicing.
Shut off pressurized steam supply and ensure steam pressure is safely relieved
before any servicing of pressurized steam components.
The electrical compartment contains high voltage components and wiring. Access
should be limited to authorized personnel only.
During and following operation of the humidifier, the steam and components in
contact with the steam such as the tank, blower pack, steam lines, steam
distributors, and condensate lines can become hot and can burn if touched.
Condair does not accept any liability for installations of humidity equipment
installed by unqualified personnel or the use of parts/components/equipment
that are not authorized or approved by Condair.
CAUTION: Electrical
All electrical work should be done according to local electrical code.
Electrical connection to be performed by a licensed electrician.
CAUTION: Plumbing / Steam Lines
Plumbing to be performed by a licensed plumber.
Pressurized steam line installation to be performed by a qualified installer.
Drain water from humidifier can be very hot. Do not drain to public sink.
All plumbing and pressurized steam supply line work should be done according to
local plumbing code.
CAUTION: Installation
Do not mount on hot surfaces
Do not mount in area where freezing can occur
Do not mount on vibrating surface
The Nortec SETC/P produces steam at atmospheric pressure no devices which
could block steam output should be connected to the steam outlet.
Steam output lines must be installed so that no restriction can produce
backpressure in the humidifier.
Regardless of selecting On/Off or modulating control method, Condair humidifiers
must have a closed circuit across its On/Off security loop control terminal to
operate. Condair highly recommends the use of a high limit humidistat and an air
proving switch in series for this function.
Unit damage caused by water quality outside of the specified ranges is not
covered under warranty.
Introduction | 2
Receiving and Unpacking
Note: A steam valve, actuator, and wye strainer are shipped along with the SETC/P
humidifier but in separate small boxes.
1 Check packing slip to ensure ALL material has been delivered.
2 All material shortages are to be reported to Condair within 48 hours from receipt of goods.
Condair assumes no responsibility for any material shortages beyond this period.
3 Inspect shipment for damage and note damages on shipping waybill accordingly.
4 After unpacking, inspect equipment for damage and if damage is found, notify the shipper
promptly.
5 All Condair products are shipped on an FOB factory basis. Any and all damage, breakage
or loss claims are to be made directly to the shipping company.
Before Installation
1 Ensure that available voltage and phase corresponds with humidifier voltage and phase as
indicated on humidifier’s specification label.
2 If steam supply is from a Medium or High Pressure boiler ensure supply steam line includes
a relief valve to prevent supply pressure from exceeding 15 psig.
3 Ensure means for returning boiler steam condensate to boiler at atmospheric pressure are
available.
4 Ensure sufficient clearances will be available as described in Location on page 11.
5 Ensure steam lines can be routed to distributor SAM-e manifold or blower pack as described
in Steam Lines and Condensate Returns on page 17.
6 Report any discrepancy immediately to the site engineer.
Figure 1: Specification Label Location
3 | Introduction
Humidifier Components
Tank
Clean Out
Port
Heat
Exchanger
Gasket
Base
Total Controller
Manual Drain Switch
Float Chamber
Heat
Exchangers
(Faceplate)
Display and Keypad
Steam Outlet
Transformer
Fill Box
Vacuum Break
Steam Inlet
(Boiler Steam)
Control Terminal Strip
On/Off Switch
Remote Relay
Board
Driver Board
High Voltage
Terminal Block
Actuator
Wye Strainer
Steam Trap
Drain Pump
Mixing Box
Figure 2: Nortec SETC Humidifier Components
CV Valve
Fill Valve
Drain Outlet
P Trap
Condensate Drain
(Boiler Steam)
Auxiliary Drain
Outlet
Introduction | 4
Description of Components
Component
Function of Component
Actuator
Opens and closes the CV valve in proportion to demand for steam.
Auxiliary Drain
Outlet
Drains water from tank in case of pump failure.
Base
Provides an integrated floor support for the humidifier.
Clean Out Port
Provides access to clean scale from the tank and heat exchanger.
Condensate Drain
Drains condensate formed from boiler steam in the heat exchanger(s)
Control Terminal
Strip
Terminal strip for connecting external controls and blower pack to
humidifier.
CV Valve
Controls the amount of steam allowed into the heat exchanger which in
turn controls the output of the humidifier.
Display and Keypad
User interface for configuring the humidifier.
Drain Outlet
Drain port used for draining water from the humidifier tank.
Drain Pump
Drains water from humidifier.
Driver Board
Provides input and output connections to humidifier components.
Fill Box
Provides an air gap for backflow prevention.
Fill Valve
Controls flow of water into humidifier.
Float Chamber
Measures water level in the humidifier tank.
Gasket
Seals heat exchanger face plate and clean out port cover to tank.
Heat Exchanger(s)
Exchanges energy from boiler steam to the tank water to produce steam
for humidification. The faceplate mounts the heat exchanger to the tank.
High Voltage
Terminal Block
Primary power connection from remote disconnect to humidifier.
Manual Drain Switch
Manually activates pump to drain water from the tank.
Mixing Box
Blends hot tank water with cool fill water to provide drain water cooling.
On/Off Switch
Turns power On/Off to humidifier controller. Note: Turn off humidifier
disconnect to shut off primary power to the humidifier.
P Trap
Prevents steam from flowing out the drain outlet.
Remote Relay
Board
Provides a terminal strip to dry contacts which open/close to indicate the
humidifier is on, humidifying, needs service, or is in a fault condition.
Steam Inlet
Connection for boiler steam, it is connected to the heat exchangers.
Steam Outlet
Connect to steam line with steam hose.
Steam Trap
Drains condensate from the heat exchanger without letting boiler steam
escape to drain.
Tank
Holds the water used to generate clean steam for humidification.
Total Controller
Controls all functions of the humidifier’s operation and provides user
interface for configuration of the humidifier.
Transformer
Steps primary voltage down to 24 VAC for the controller and internal
components such as the fill valve and drain valve.
Vacuum Break
Prevents a siphon from occurring when the drain pump is stopped.
Wye Strainer
Protects CV valve and other system components from dirt and rust in the
piping system.
Table 1: Humidifier Components
5 | Introduction
Nortec SETC/P Models
SETC5 0
Note:
SE 750 has
2 steam outlets
SE 525-750
SE 100-175
SE 1050
SE 250-375
The Nortec SETC with its Total Controller and state-of-the-art features and options is the most
advanced steam exchange humidifier available. The base model Nortec SEP provides steady
and reliable humidification using the same proven heat exchanger technology as the
Nortec SETC. The Nortec SETC/P is available in capacities ranging from 50 lb/hr (23 kg/hr) to
1050 lb/hr (475 kg/hr). Nortec SETC/P humidifiers are packaged in five different cabinets
depending on their capacity. Figure 3: Nortec SETC/P Models shows the configuration and
relative size of the five different cabinets. Table 3 provides specifications for the
Nortec SETC/P product line.
The Nortec SE 50, 100, 175, 250, and 375 all have a single heat exchanger. The Nortec SE
525 and 750 have two heat exchangers. The Nortec SE 1050 has three heat exchangers. All
models have a single pressurized steam inlet and condensate drain with internal manifold
connecting separate heat exchangers if they are present.
Figure 3: Nortec SETC/P Models
Introduction | 6
Outdoor Model (Nortec SETC Only)
Option / Accessory
Used For
Freeze Protection Package
(Nortec SETC Only)
Emptying the tank in case of fault or power failure to prevent
freezing. (Factory installed)
Floor Stand
Supporting the humidifier 27 inches above the floor (height can be
reduced by cutting legs of floor stand). (field assembled)
Ceiling Mounting Kit (Nortec SE50 Only)
Providing a drain pan and support brackets for mounting an
Nortec SE50 unit from the ceiling.
Steam Distributors
Adding steam into air ducts
Remote Blower Pack
Adding steam into a space remote from the humidifier.
SAM-e Steam Distribution Manifold
Adding steam into air ducts where short absorption is required.
Digital or Analog Control Humidistats
Controlling the output of the humidifier based on sensed RH (can
be mounted in the space being humidified or in the duct).
Digital RH Transducers
Communicating RH in a space or duct to the humidifier
Digital or Analog High Limit Humidistats
Preventing over humidification in a duct by shutting down or
throttling down the humidifier when duct RH gets high.
Air Proving Switches
Insuring humidification only occurs when air is moving in a duct.
Condair LINKS 2 (Nortec SETC Only)
Connecting the humidifier to a building management interface.
hardware allows control of the humidifier via BACnet, Lonworks,
Johnson N2, or Modbus.
Condair OnLine (Nortec SETC Only)
User and factory monitoring and configuration of the humidifier via
the internet.
The outdoor model of the Nortec SETC provides a weatherproof enclosure that allows the Nortec
SETC to be installed on rooftops in moderately cool climates. Refer to the Nortec SETC
installation manual that is provided with the outdoor model to insure proper installation.
Options and Accessories
Condair provides a complete line of options and accessories for every humidification application.
The following options and accessories are available and may have been delivered with your
Nortec SETC/P humidifier. Refer to the installation instructions that came with the accessories
for their proper installation and operation.
Table 2: Options and Accessories
9 | Installation
Nortec
Model
SETC
Part No
SEP
Part No.
CV
Valve
CV Valve,
Steam
Inlet, Wye
Port (NPT)
Condensate
Port
(NPT)
Net/Full
Weight
lb (kg)
Required
fill line
flow
gal (l)
/min
Required
Drain
capacity
gal (l)
/min
Electrical
50
2552765
2520383
2.8
1/2
3/4
125/180
(57/82)
2.6 (10)
5.2 (20)
Voltage
110-120
100
2550073
2525132
5.5
3/4
3/4
267/423
Phase
1
175
2550074
2525133
10 1 3/4
(121/192)
250
2550075
2525134
12 1 3/4
355/599
Amps
(161/272)
1.25 A
375
2550076
2525135
20
1 1/4
3/4
Power
525
2550077
2553312
28
1 1/2
1
529/992
0.15 KW
750
2550078
2553313
40 2 1
(240/450)
4.5 (17)
8 (29)
Max
1050
2550080
2525139
77 2, 2 1/2,
2 1/2
1 1/4
703/1384
(318/628)
Disconnect
15 A
Nortec
Model
*Supply
Steam
Pressure
(psig)
*Max Output
lb/hr (kg/hr)
Approximate
Boiler Steam
Consumption
lb/hr (kg/hr)
**Water
Consumption
gal (l) /hr
**Drain Volume
gal (l) /hr
50
5
13 (6)
15 (7)
2.3 (9)
0.8 (3)
10
32 (14)
36 (16)
5.7 (21)
1.9 (7)
15
50 (23)
58 (26)
9.0 (34)
3.0 (11)
100
5
26 (12)
30 (14)
4.7 (18)
1.6 (6)
10
63 (29)
72 (33)
11.3 (43)
3.8 (14)
15
100 (45)
115 (52)
18.0 (68)
6.0 (23)
175
5
46 (21)
52 (24)
8.2 (31)
2.7 (10)
10
110 (50)
127 (58)
19.8 (75)
6.6 (25)
15
175 (80)
201 (91)
31.5 (119)
10.5 (40)
250
5
65 (30)
75 (34)
11.7 (44)
3.9 (15)
10
158 (72)
181 (82)
28.3 (107)
9.4 (36)
15
250 (114)
288 (131)
44.9 (170)
15.0 (57)
375
5
98 (44)
112 (51)
17.5 (66)
5.8 (22)
10
236 (107)
272 (123)
42.5 (161)
14.2 (54)
15
375 (170)
431 (196)
67.4 (255)
22.5 (85)
525
5
137 (62)
157 (71)
24.5 (93)
8.2 (31)
10
331 (150)
380 (173)
59.5 (225)
19.8 (75)
15
525 (239)
604 (274)
94.4 (357)
31.5 (119)
750
5
195 (89)
224 (102)
35.1 (133)
11.7 (44)
10
473 (215)
543 (247)
84.9 (321)
28.3 (107)
15
750 (341)
863 (392)
134.8 (510)
44.9 (170)
1050
5
273 (124)
314 (143)
49.1 (186)
16.4 (62)
10
662 (301)
761 (346)
118.9 (450)
39.6 (150)
15
1050 (477)
1208 (549)
188.7 (714)
62.9 (238)
Table 4: Nortec SETC/P Capacities and Water Consumption
Table 3: Nortec SETC/P Specifications
* Supply steam pressure must be present at the CV valve to achieve rated output
** At maximum output , 25% blow down, and with drain water cooling activated
Installation | 8
Nortec
Nortec
Nortec
9 | Installation
Installation
10 Typical Humidifier Installation
11 Location
12 Mounting on Optional Stand
13 Ceiling Mounting (Nortec SE50 Only)
14 Plumbing
15 Boiler Steam and Boiler Condensate
Return
17
Steam Lines and Condensate Returns
22 Electrical
23 External Controls
23 Control Wiring
23 Control Location
24 On/Off Control Wiring
25 Modulating Control Wiring
Note:. Condensate drain line must be sloped downward to boiler condensate return.
Use pump (by others) or stand (optional) if necessary.
The Nortec SE series humidifiers are designed to be either floor mounted or stand mounted
(stand optional). Nortec SE 50 models can also be ceiling mounted with the optional ceiling
installation kit, part number 2520345.
Install only in areas with ambient temperature 41-104 °F (5 – 40 °C) relative humidity 5 -
95% (non condensing).
Ensure mounting surface is strong enough to support the full weight of the humidifier and
accessories (see Table 3: Nortec SETC/P Specifications).
Install in location where electrical power, boiler steam, and drain can be connected to the
humidifier.
When possible install below the steam distributor. If mounted above the steam distributor
take care to provide proper steam line routing and proper condensate traps.
DO NOT locate the humidifier any further then absolutely necessary from the steam
distributor location as net output will be reduced as a result of heat loss through the steam
line.
Condensate drain is located close to the bottom of the humidifier. Locate the unit so that
condensate line slopes down to boiler or use pump (by others) to lift to boiler. Use stand if
necessary.
Avoid mounting humidifier on combustible surfaces including (but not limited to) carpet, tile,
or certain insulating materials.
Clearance dimensions shown are for reference only and are the minimum required for
maintenance of the humidifier. Consult local and national codes before final location and
installation. Condair does not accept responsibility for installation code violations.
Figure 6: Installation Location / Clearance
Installation | 12
Mounting on Optional Stand
Fasten Nortec SE humidifier
to stand with bolts, lock
washers, and nuts provided.
Tighten
to 200 in-lb (22.6 Nm).
Note: Center support only
present on Nortec SE
525 and larger.
Secure stand to floor
four places. (hardware by
others)
Note: The humidifier must be secured to the stand (hardware provided) and the stand
must be secured to the floor (hardware by others).
The optional Nortec SE floor stand positions the Nortec SE humidifier at a convenient working
height and provides additional clearances for sloping drains. The stand must be assembled
at site.
Assemble the stand according to the instructions that are provided with it.
Ensure the stand and humidifier are installed on a level surface
Permanently secure the stand to the floor via the holes in the leg support plates following
any local codes or regulations.
Mount stand on level surface
Ensure humidifier is Level
Figure 7: Mounting on Optional Stand
13 | Installation
Note:. The Nortec SE50 requires regular maintenance including removal of scale
from the heat exchanger and tank. Make sure it is installed in a location where
the maintenance can be performed.
Ceiling Mounting (Nortec SE50 Only)
12.8 in.
Anchor 3/8 in (M10)
support rods to ceiling
(by others)
Support rods and hardware
(by others) must not extend
below support bracket flange.
Figure 8: Ceiling Mounting the Nortec SE50
(32.6 cm)
Sloped drain
1/2 in. pipe
(by others)
Condair offers an optional ceiling mounting kit (part number 2520345) which allows the Nortec
SE50 to be ceiling mounted with zero clearance to the ceiling. Follow the following guidelines
for installation.
Follow the instructions provided with the ceiling mounting kit.
Install in a location where regular maintenance can be performed. Provide clearance as
The Nortec SE50 weighs 180 lb (82 kg) when filled with water and without any
The humidifier cannot be used as a structural member. All piping connected to the unit
A drain line emptying into an open drain must be connected to the ceiling kit drain pan.
shown in Figure 6: Installation Location / Clearance.
accessories or piping. It is the installer’s responsibility to calculate the total weight
which must be supported, to ensure the ceiling structure is adequate, and to install
support rods and to connect drain pan per local codes and regulations.
must be supported independently.
Condair recommends a 1/2 in. pipe with sufficient slope to ensure any water collected in
the pan will drain from it.
Installation | 14
Plumbing
Note:
Drain Water is very hot, do not use plastic pipe for drain or condensate lines, do not
drain to public sink. Route to floor drain or equivalent.
Supply cold potable water, deionized water or reverse osmosis water at 30 - 80 PSIG.
Hardness 5-7 grain or 90 – 120 mg/l (as Ca
+2
as CaCO3)
Total Dissolved Solvents (TDS) 0.5-3 mg/l or Conductivity 1 to 70 mho/cm
Chlorides 0-25 ppm PH 7.2-8.5 Alkalinity 30-130 mg/l (as CaCO3)
0.75 in. (19 mm). OD
un-threaded drain outlet
Connect with hose cuff
and hose clamps.
*Pipe, unions, and water shut-off valve not supplied by Condair.
All water supply and drain line connections must be installed in accordance with local
plumbing codes.
1/2 in. NPT
Use union to connect
supply pipe to unit.
Always install a water
shut-off valve.
Air gap required.
2 1/2 in. to 1 1/4 in. copper
reducer is ideal.
Hose/line must not touch
the bottom of the funnel.
Min. 1 1/4 in. OD drain line.
Slope down. Increase size
if combining multiple drains.
Axillary drain, 1/2 in. female NPT
For draining tank without pump. Leave
valve closed except if freeze protection is installed.
Figure 9: Water Supply and Drain Connection
See Table 3 and Table 4 on page 7 for supply water flow requirements.
Install water shut off valve and union before humidifier to facilitate servicing.
Insure drain line is adequately sized to provide free and easy draining and that an air gap is
installed as shown. See Table 3 and Table 4 on page 7 for flow requirements.
Auxiliary drain connection with manual shut off valve is recommended for all units. Valve to
be left closed on units without freeze protection option installed. Valve to be left open on
units with freeze protection option installed except during servicing.
High hardness or silica content supply water may require increased maintenance.
Unit damage caused by water quality outside of the specified ranges is not covered under
warranty.
15 | Installation
6 in.
(15 cm)
Max
Boiler steam supply
line. Max 15 psi, Min 5 psi
measured at CV Valve
Boiler steam
Actuator
inlet port location
on Nortec SE 1050
CV Valve
(see table 3)
Pressure
gauge (optional)
F&T Trap
Wye Strainer
Isolation Valve
Boiler steam
inlet port
(see table 3)
Condensate Drain
Port (see table 3)
Condensate drain line.
Gravity feed to boiler.
Use pump if condensate
must be lifted.
Boiler Steam and Boiler Condensate Return
Note:.
Pressurized steam line installation to be performed by a qualified installer.
Damage to Nortec SE heat exchanger will occur if it is exposed to pressure above
20 psi.. A safety relief valve must be installed to prevent the Nortec SE from being
exposed to pressure in excess of 15 psi when the Nortec SE is connected to a
medium or high pressure boiler via a pressure reducing valve.
The steam supply line must be designed to provide design pressure at the CV valve
when there is 100 % demand (CV valve completely open). Pressure losses in the
steam supply line will reduce Nortec SE output.
Condensate must be drained to a non-pressurized boiler condensate return line.
Note: Condair supplies CV valve,
actuator and wye strainer. All other
components and fittings by others.
Not pressurized
condensate header
(slope down)
Pressurized condensate
header
Figure 10: Nortec SE Boiler Steam and Condensate Connection
Installation | 16
Condair supplies a CV valve, actuator and wye strainer with each Nortec SE humidifier. The port
Caution: Condensate leaves the steam traps inside the Nortec SE under slight pressure.
Steam flash could occur in the condensate drain line.
sizes of the CV valve, boiler steam inlet port, and condensate drain port are given in Table
3: Nortec SETC/P Specifications on page 7. Follow the following guidelines for installation.
All steam line connections must be installed in accordance with local codes.
Install the CV valve actuator following the procedure in Figure 11: CV Valve Actuator
Installation after the CV valve is installed on the steam line. Wire the actuator as described
in CV Valve Actuator Wiring on page 29.
Boiler steam supply line design is the responsibility of the installer. The boiler steam supply
line must be designed so that that design pressure is present at the CV valve when the CV
valve is completely open (100% demand). The diameter of the supply line up to the wye
strainer may have to be oversized to insure proper steam pressure.
The Nortec SE will operate on supply steam pressures between 5 and 15 psi measured at
the CV valve. Lower steam supply pressures will result in lower output. See Table
4: Nortec SETC/P Capacities and Water Consumption on page 7 for capacities at different
supply pressures.
If condensate cannot be gravity fed to the boiler then a pump must be used to lift the
condensate. See Spirax Sarco (www.spiraxsarco.com) and others for pumps and additional
information on condensate management.
The boiler steam and condensate connections are independent. Boiler steam condensate
should be returned to the boiler and should not be mixed with water from the tank drain.
The steam supply pressure can be entered into the Nortec SETC control software to provide
display of unit output. See Pressure Based on page 56.
Install jam nut
and lock washer
Turn stem
extension
until holes
line up
1/2 in. (1.2 cm)
CV Valve
Install stem
extension
min.
Figure 11: CV Valve Actuator Installation
Insert
connecting
pin
Actuator
Raise valve
stem to full up
2 turns then
push in and
1/8 turn to lock
Tighten jam nut
against stem extension
Install and
tighten
mounting nut
17 | Installation
St
eam
Dire
ction
Steam Line
Material
Lb/hr (kg/hr)
Steam Line Length
ft
m
Steam Line Description
Copper Tube
0-100 (0-45)
0-90
0-27
1 1/2 in. MED-L Tubing (1.625 in. OD)
101-250 (46-113)
0-180
0-54
3 in. MED-L Tubing (3.125 in. OD)
251-650 (114-295)
0-260
0-79
**4 in. MED-L Tubing (4.125 in. OD)
*Stainless Steel
Tube
0-100 (0-45)
0-90
0-27
1.75 inch Tube x 0.065 inch thick wall
101-250 (46-113)
0-180
0-54
3 inch Tube x 0.065 inch thick wall
251-650 (114-295)
0-260
0-79
**4 inch Tube x 0.065 inch thick wall
Condair Hose
31-100 (14-45)**
<15
<4.5
***Part Number 1328820 (1 3/4”)
10 Degrees
2 in.
(5 cm)
1 ft (30 cm)
MAIN RULES FOR ATMOSPHERIC STEAM LINES
Slope the steam lines.
Trap condensate (Use full size ‘T’ for Traps).
Steam lines must not have any restrictions which could cause back pressure.
Insulate with 1.0 in. (2.5 cm) pipe insulation.
Follow recommended materials, size and length see tables.
Steam Hose Odour: Condair hose may generate a slight odour during initial use.
This odour is temporary and will disappear after a short period of time.
Steam Lines and Condensate Returns
Use Appropriate Slope Insulate Pipe
2 Degrees
0.5 in.
(12 mm)
1ft (30 cm)
Figure 12: Main Steam Line Requirements
1 in. (2.5 cm) pipe
insulation
Note: * Use only stainless steel tube for reverse osmosis and deionized water applications.
** Use 2 x 4 in. steam lines for steam capacities higher than 750 lb/hr (307 kg/hr)
*** Use one steam hose per 100 lb/hr (45 kg/hr) of output.
Table 5: Recommended Steam Line Material
Installation | 18
48(2.4)4(
Figure
1.2)15(4.5)
1.6
13:CondensateTraps
Table 6: Maximum Recommended Length of Steam Line
Note: Condensate should not be routed to a sink used frequently by personnel. Route to
a floor drain or equivalent. Condensate normally cools in traps but is still hot. A SAM-e or
larger steam line generates more condensate and water may not cool in the trap. A drain
water cooler option may be installed if required by code.
as steam line
Unit Size
Steam Output
lb/hr (kg/hr)
Steam Outlet
and Line Size
copper (SST)
Maximum
Length
ft (m)
Possible Loss
lb/hr/ft (kg/hr/m)
Possible Loss at
Max. Length
lb/hr (kg/hr)
50
50
(23)
1 1/2 (1 3/4)
37 (11)
0.11 (0.16)
4 (2)
100
100
(45)
1 1/2 (1 3/4)
90 (27)
0.11 (0.16)
10 (4.5)
175
175
(80)
3 (3)
90 (27)
0.16 (0.24)
14 (6.5)
250
250
(114)
3 (3)
180 (55)
0.16 (0.24)
28 (13)
375
375
(170)
4 (4)
180 (55)
0.22 (0.33)
39 (18)
525
525
(239)
4 (4)
220 (67)
0.22 (0.33)
48 (22)
750
750
(341)
2X 4 (4)
260 (79)
0.44 (0.66)
114 (52)
1050
1050
(477)
2X 4 (4)
260 (79)
0.44 (0.66)
114 (52)
Tube Diameter
in.
90 Degree
Elbow ft (m)
45 Degree Elbow
ft (m)
Side Outlet Tee
ft (m)
Gate Valve
ft (m)
Control Valve
ft (m)
1 1/2 or 1 3/4
3.5 (1)
1.75 (0.5)
7 (2.1)
0.8 (2.4)
34 (10)
3
5 (1.5)
2.5 (0.75)
11 (3.3)
1.1 (3.1)
54 (16)
4
8 (2.4)
4 (1.2)
15 (4.5)
1.6 (0.5)
80 (24)
NOTE:
12 in. (30 cm)
min drop to
top of ‘P’ Trap
plus duct
static pressure
See Table 7 for equivalent length of common fittings.
Table 7: Equivalent Length of Some Common Fittings
Tee is same size
P Trap
min 8 in.
(20 cm)
Use a full size tee, not a 90
degree elbow for vertical
to horizontal transitions.
‘P’ Traps Use:
-
Condair 0.375 in condensate hose .
-
1/4 in Med-L copper tubing, or
-
0.375 in stainless steel tubing
Condensate drains must be sloped down.
Route to humidifier fill cup if possible.
PossibleLoss at
Max.length
lb/hr
(kg/hr)
Globe Valve
ft(m)
19 | Installation
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
2 x duct
height min.
2/3 Duct
height
12 in.
(30 cm)
min.
Mount distributor
to side of duct
Figure 14: Distributor Location in Duct
Note:
Refer to distributor or SAM-e installation manuals for detailed installation instructions.
Insulated copper
steam line. Support
so weight is not on
steam outlet.
1 ft (30 cm)
min. before
Figure 15: SAM-e/Steam Distributor Above Humidifier (Copper Steam Line Shown)
anybend
with clamps
2 in. (5 cm)
min.
Hose cuff
1 ft (30 cm)
Condensate line
‘P’ Trap
To drain
Use steam hose between
steam outlet and steam line.
Installation | 20
1 ft (30 cm)
0.5 in. (1.2 cm) min.
1ft (30 cm)
min. before
any bend
Obstruction
1 ft (30 cm)
min.
Use full size condensate tee
at low point. Slope lines up
to “T” and immediately after it.
‘P’ Trap
To drain
‘P’ Trap
To drain
Hose will soften
over time
proper support
Is necessary
Figure 17: Steam Under Obstruction (Copper Steam Line Shown)
21 | Installation
Method for Longer Runs With Limited Vertical Space
1 ft (30 cm)
min before turn
Condensate
tee every
15-20 ft
(4.5 - 6 m)
Install condensate tee
before distributor
Condensate
tee at low
points
Individually trap multiple condensate
returns before joining on common line.
1 ft (30 cm)
min.
To Drain
Figure 18: Long Steam Run
Installation | 22
Caution:
Wiring to be performed by a licensed Electrician.
All SE humidifiers operate on 120 VAC, single phase, 60 HZ power. Refer to
specification label for power requirements.
Electrical
Knockouts provided
in top and bottom panels.
Install strain relief (by others)
High voltage
terminal block
Note:
1 Dedicated external fused
disconnect must be installed.
Fusing must not exceed max
circuit protection as indicated
on the specification label.
2 Ensure that adequate power is
available to carry full humidifier
amp draw as indicated on the
specification label.
3 All wiring to be in accordance
with national and local electrical
codes.
Figure 19: Primary Power Connection
Single Phase Supply
Ground
L1
Neutral
Nortec SETC / P Primary Power
Dedicated circuit
breaker or fused
disconect.
Ground
L1
Neutral
E I
X N
T T
23 | Installation
Figure20:ControlLocation
External Controls
Note: Regardless of selecting on/off or modulating control method, Condair humidifiers
must have a closed circuit across their on/off security loop control terminal to operate.
Condair highly recommends the use of a high limit humidistat and an air
proving switch in series for this function.
Caution: Failure to wire the humidifier in accordance with the wiring instructions could
cause permanent damage. Such errors will void the warranty.
Control Wiring
Controls are available from Condair as accessories. If controls were not ordered with humidifier
they must be supplied by others. The following information is relevant to all controls, factory
supplied or otherwise. For wiring use minimum of 18 AWG and keep as short as possible.
The Nortec SETC humidifier can be operated with two modulating inputs. The Nortec SEP has one
modulating input which can be used for a duct high limit or humidity control. Both the
Nortec SETC and Nortec SEP can be operated as On/Off. See Control Setting on page 53 for
Nortec SETC configuration and On/Off or Modulating Control (J10) on page 61 for Nortec SEP
configuration.
Control Location
10 ft min.
1
Air
Proving
Switch
1Air Proving Switch
2
Duct High
Limit
3
Humidity
Control
(return air
duct or
in room)
Locate so that it can sense air flow or lack of it. 2Duct High Limit
Nortec SETC can be modulating, On/Off, or a humidity sensor. Nortec SEP can be modulating or On/Off.
Locate at least 10 feet from steam distributor or far enough that under normal conditions
3 Humidity Control
Nortec SETC can be Modulating, On/Off, or a Humidity Sensor. Nortec SEP can be modulating or On/Off.
Can be located either in return air duct (preferred) or in room being humidified.
Mount in area representative of room humidity (draft, doorways, sunlight, or overhang such
steam is fully absorbed.
as a shelf can affect reading). Avoid placing near discharge diffuser of humidified air.
Installation | 24
On/Off Control Wiring
Connect 24 VAC ,
term inal 1 of hum id ifie r to
term inal 2 of controllers.
Com N/O
1 -
Groun
d
2 -
24
VAC
3 -
Common
4
-
Digital
Out
5
-
Fan
Relay
6
-
Fan
Relay
7
-
NTC
Sensor
8
-
NTC
Sensor
1 -
Groun
d
2 -
24
VAC
3 -
Common
4
-
Digital
Out
5
-
Fan
Relay
6
-
Fan
Relay
7
-
NTC
Sensor
8
-
NTC
Sensor
Humidifier Terminal Strip
Air Proving Switch
Wire to make when
sensing air flow
Air Proving
Switch
Duct High Limit
2548732 - On/Off
Duct Humidistat
Knockouts provided
in top and bottom panels.
Install strain relief (by others)
Figure 21: On/Off Controls
Duct High Limit
2548732 - On/Off Duct Humidistat
Wire to make on drop in humidity
Humidity Control
2548731 - On/Off
Wall Humidistat
Note: 1 Humidifier will run when circuit between
terminal 1 and 2 on humidifier is closed.
2
Terminal 1 is 24VAC Hot, turn unit off to
avoid shorting while wiring.
3
Digital Humidistats require 24 VAC power
from terminals 1 and 3 of humidifier.
4
Humidity Control can be wall mounted
as shown or return air duct mounted.
Humidity Control
2548731 - On/Off Wall Humidistat or,
2548732 - On/Off Duct Humidistat
OR
E S
X E
T
1- 24 VAC
2 - On/Off Loop
3 - Ground
4 - Control Signal
5 - Limit Signal (SETC only)
6 - 5 VDC
7 - Ground
8 - Full Tank Blow Down
9 - Ground
10 - Actuator power
11 - Actuator power
12 - 0-10 VDC Out
Figure 22: Digital On/Off
25 | Installation
Modulating Control Wiring
1 - Ground 2 - 24 VAC
6 - Analog
Out
7 - Analog
In
8 - Temperature
1 - Ground
2 - 24 VAC
6 - Analog
Out
8 - Temperature
Air Proving
Switch
Humidifier Terminal Strip
2520266 - Digital Duct Humidistat
Package
High Limit Humidistat
Note: 1
Install On/Off controls or jumper between
terminal 1 and 2 of humidifier in order to run.
2
Terminal 1 is 24 VAC Hot, turn unit off to
avoid shorting while wiring.
3
High Limit Humidistat must be duct mounted.
It can be On/Off or modulating.
4
Control Humidistat can be mounted in space
or in return air duct and can be On/Off or
modulating.
5
The Nortec SEP can only accept one
modulating signal.
Knockouts provided
in top and bottom panels.
Install strain relief (by others)
Figure 23: Modulating Controls
1510142 - Digital Wall Humidistat
Control Humidistat
Analog Out - 3
24 VAC - 2
Ground - 1
Connect 24 VAC, terminal 1 of
Nortec SETC/P to terminal
2 of controllers.
Figure 24: Digital Modulating Humidistats
Insert On/Off
controls or jumper
between 1 and 2
E
S
X
T E
1- 24 VAC
2 - On/Off Loop
3 - Ground
4 - Control Signal
5 - Limit Signal (SETC only)
6 - 5 VDC
7 - Ground
8 - Full Tank Blow Down
9 - Ground
10 - Actuator power
11 - Actuator power
12 - 0-10 VDC Out
Installation | 26
1 - Ground 2 - 24 VAC
6 - Analog
Out
7 - Analog
In
8 - Temperature
1 - Ground 2 - 24 VAC
6 - Analog
Out
Connect 24 VAC, terminal
1 of SETC/P to terminal
2 of controllers.
1- 24 VAC
2 - On/Off Loop
3 - Ground
4
- Control Signal
5
- Limit Signal (SETC only)
6
- 5 VDC
7
- Ground
8
- Full Tank Blow Down
9 - Ground
10 - Actuator power
11 - Actuator power
12 - 0-10 VDC Out
Air Proving
Switch
Duct High
Limit
2520261 - Digital
Wall W/O Sensor
1509858 - Wall
Sensor
Humidifier Terminal Strip
2520261 - Digital Wall W/O Sensor
+
1509858 - Wall Sensor
Wire wall sensor to digital display as shown
below, wire digital display to humidifier as shown
for 1510142 - Digital Wall Humidistat.
Knockouts provided
in top and bottom panels.
Install strain relief (by others)
Figure 25: Digital Wall Humidistat – Remote Wall Sensor
2520261 - Digital
Wall W/O Sensor
1509858 - Wall
Sensor
Figure 26: Remote Wall Sensor Wiring
27 | Installation
1 - Ground 2 - 24 VAC 3 - Analog
Out
Transducer Control Wiring (Nortec SETC Only)
Connect 24 VAC ,
terminal 1 of SETC to
terminal 2 of controllers
1 - Ground 2 - 24 VAC
6 - Analog
Out
E
Figure 27: Transducers
1509857 - 2-10V Duct Humidity
Humidifier Terminal Strip
Transducer
Air Proving
Switch
1509858 - 2-10V Wall Humidity
Figure 28: Digital
Duct High Limit
1509857 - 2-10V
Duct Humidity
Transducer
Note: 1
Knockouts provided
in top and bottom panels.
Install strain relief (by others)
Install On/Off controls or jumper between
terminal 1 and 2 of humidifier .
2
Terminal 1 is 24 VAC Hot, turn unit off to
avoid shorting while wiring.
3
Duct High limit can be duct humidity
transducer as shown or duct On/Off
humidistat.
4
Humidity Control can be wall humidity
transducer as shown, duct humidity
transducer, or On/Off humidistat.
Transducer
E
X
T
Humidity Control
1509858 - 2-10V Wall
Humidity Transducer
Insert On/Off
controls or jumper
between 1 and 2
S
1- 24 VAC
2 - On/Off Loop
3 - Ground
4
- Control Signal
5
- Limit Signal (SETC only)
6 - 5 VDC
7
- Ground
8
- Full Tank Blow Down
9 - Ground
10 - Actuator power
11 - Actuator power
12 - 0-10 VDC Out
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.