Nortec SETC 50, SETC 250, SETC 100, SETC 175, SETC 375 Installation And Operation Manual

...
Important: Read and save these instructions. This guide to be left with equipment.
Nortec
SE-Series
Installation and
Operation Manual
Includes installation, operation,
information for your indoor
Nortec SETC B+ and Nortec SEP
steam exchange humidifier
2552940-D | 23/11/2018
Thank you for choosing Condair.
SERIAL #
MODEL #
INSTALLATION DATE (MM/DD/YYYY)
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of Condair LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the Condair name should be taken as referring to Condair LTD.
Liability Notice
Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Condair.
Copyright Notice
Copyright 2018, Condair LTD. All rights reserved.
Contents
1
Introduction
43
Operation
2 Receiving and Unpacking 3 Humidifier Components 5 Nortec SETC/P Models 6 Options and Accessories
9
Installation
10 Typical Humidifier Installation 11 Location 12 Mounting 14 Plumbing 15 Boiler Steam and Boiler
Condensate Return
17 Steam Lines and Condensate
Returns
22 Electrical
44 Nortec SETC LED Status Lights
44 Nortec SEP LED Status Lights 45 How the Humidifier Works
49 Nortec SETC Humidifier Configuration
60 Nortec SEP Humidifier Configuration
63
Maintenance and Servicing
64 Required Maintenance 65 Maintenance Schedule 69 Maintenance Shutdown and
Extended Shutdown
70 Maintenance Checklist
71
Troubleshooting
73 General Troubleshooting
23 External Controls
32 Options and Accessories
33
Start Up
34 Installation Check 35 Nortec SETC User Interface 36 Start Up Procedure 37 Status Screens
39 Digital Controls
41 Start Up Checklists
76 Nortec SETC Warnings and Faults
82 SEP Faults 83 Wiring Diagrams
85 96
Spare Parts Warranty
1 | Introduction
Introduction
CAUTION: Servicing
Disconnect main power before any servicing. Shut off pressurized steam supply and ensure steam pressure is safely relieved
before any servicing of pressurized steam components.
The electrical compartment contains high voltage components and wiring. Access
should be limited to authorized personnel only.
During and following operation of the humidifier, the steam and components in
contact with the steam such as the tank, blower pack, steam lines, steam distributors, and condensate lines can become hot and can burn if touched.
Condair does not accept any liability for installations of humidity equipment
installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Condair.
CAUTION: Electrical
All electrical work should be done according to local electrical code. Electrical connection to be performed by a licensed electrician.
CAUTION: Plumbing / Steam Lines
Plumbing to be performed by a licensed plumber. Pressurized steam line installation to be performed by a qualified installer. Drain water from humidifier can be very hot. Do not drain to public sink. All plumbing and pressurized steam supply line work should be done according to
local plumbing code.
CAUTION: Installation
Do not mount on hot surfaces Do not mount in area where freezing can occur Do not mount on vibrating surface The Nortec SETC/P produces steam at atmospheric pressure no devices which
could block steam output should be connected to the steam outlet.
Steam output lines must be installed so that no restriction can produce
backpressure in the humidifier.
Regardless of selecting On/Off or modulating control method, Condair humidifiers
must have a closed circuit across its On/Off security loop control terminal to operate. Condair highly recommends the use of a high limit humidistat and an air proving switch in series for this function.
Unit damage caused by water quality outside of the specified ranges is not
covered under warranty.
Introduction | 2
Receiving and Unpacking
Note: A steam valve, actuator, and wye strainer are shipped along with the SETC/P humidifier but in separate small boxes.
1 Check packing slip to ensure ALL material has been delivered. 2 All material shortages are to be reported to Condair within 48 hours from receipt of goods.
Condair assumes no responsibility for any material shortages beyond this period.
3 Inspect shipment for damage and note damages on shipping waybill accordingly. 4 After unpacking, inspect equipment for damage and if damage is found, notify the shipper
promptly.
5 All Condair products are shipped on an FOB factory basis. Any and all damage, breakage
or loss claims are to be made directly to the shipping company.
Before Installation
1 Ensure that available voltage and phase corresponds with humidifier voltage and phase as
indicated on humidifier’s specification label.
2 If steam supply is from a Medium or High Pressure boiler ensure supply steam line includes
a relief valve to prevent supply pressure from exceeding 15 psig.
3 Ensure means for returning boiler steam condensate to boiler at atmospheric pressure are
available.
4 Ensure sufficient clearances will be available as described in Location on page 11. 5 Ensure steam lines can be routed to distributor SAM-e manifold or blower pack as described
in Steam Lines and Condensate Returns on page 17.
6 Report any discrepancy immediately to the site engineer.
Figure 1: Specification Label Location
3 | Introduction
Humidifier Components
Tank
Clean Out
Port
Heat
Exchanger
Gasket
Base
Total Controller
Manual Drain Switch
Float Chamber
Heat Exchangers (Faceplate)
Display and Keypad
Steam Outlet
Transformer
Fill Box
Vacuum Break
Steam Inlet (Boiler Steam)
Control Terminal Strip
On/Off Switch
Remote Relay Board
Driver Board
High Voltage Terminal Block
Actuator
Wye Strainer
Steam Trap
Drain Pump
Mixing Box
Figure 2: Nortec SETC Humidifier Components
CV Valve
Fill Valve
Drain Outlet P Trap
Condensate Drain (Boiler Steam)
Auxiliary Drain Outlet
Introduction | 4
Description of Components
Component
Function of Component
Actuator
Opens and closes the CV valve in proportion to demand for steam.
Auxiliary Drain Outlet
Drains water from tank in case of pump failure. Base
Provides an integrated floor support for the humidifier.
Clean Out Port
Provides access to clean scale from the tank and heat exchanger.
Condensate Drain
Drains condensate formed from boiler steam in the heat exchanger(s)
Control Terminal Strip
Terminal strip for connecting external controls and blower pack to humidifier.
CV Valve
Controls the amount of steam allowed into the heat exchanger which in turn controls the output of the humidifier.
Display and Keypad
User interface for configuring the humidifier.
Drain Outlet
Drain port used for draining water from the humidifier tank.
Drain Pump
Drains water from humidifier.
Driver Board
Provides input and output connections to humidifier components.
Fill Box
Provides an air gap for backflow prevention.
Fill Valve
Controls flow of water into humidifier.
Float Chamber
Measures water level in the humidifier tank.
Gasket
Seals heat exchanger face plate and clean out port cover to tank.
Heat Exchanger(s)
Exchanges energy from boiler steam to the tank water to produce steam for humidification. The faceplate mounts the heat exchanger to the tank.
High Voltage Terminal Block
Primary power connection from remote disconnect to humidifier. Manual Drain Switch
Manually activates pump to drain water from the tank.
Mixing Box
Blends hot tank water with cool fill water to provide drain water cooling.
On/Off Switch
Turns power On/Off to humidifier controller. Note: Turn off humidifier disconnect to shut off primary power to the humidifier.
P Trap
Prevents steam from flowing out the drain outlet.
Remote Relay Board
Provides a terminal strip to dry contacts which open/close to indicate the humidifier is on, humidifying, needs service, or is in a fault condition.
Steam Inlet
Connection for boiler steam, it is connected to the heat exchangers.
Steam Outlet
Connect to steam line with steam hose.
Steam Trap
Drains condensate from the heat exchanger without letting boiler steam escape to drain.
Tank
Holds the water used to generate clean steam for humidification.
Total Controller
Controls all functions of the humidifier’s operation and provides user interface for configuration of the humidifier.
Transformer
Steps primary voltage down to 24 VAC for the controller and internal components such as the fill valve and drain valve.
Vacuum Break
Prevents a siphon from occurring when the drain pump is stopped.
Wye Strainer
Protects CV valve and other system components from dirt and rust in the piping system.
Table 1: Humidifier Components
5 | Introduction
Nortec SETC/P Models
SETC5 0
Note:
SE 750 has
2 steam outlets
SE 525-750
SE 100-175
SE 1050
SE 250-375
The Nortec SETC with its Total Controller and state-of-the-art features and options is the most advanced steam exchange humidifier available. The base model Nortec SEP provides steady and reliable humidification using the same proven heat exchanger technology as the Nortec SETC. The Nortec SETC/P is available in capacities ranging from 50 lb/hr (23 kg/hr) to 1050 lb/hr (475 kg/hr). Nortec SETC/P humidifiers are packaged in five different cabinets depending on their capacity. Figure 3: Nortec SETC/P Models shows the configuration and relative size of the five different cabinets. Table 3 provides specifications for the Nortec SETC/P product line.
The Nortec SE 50, 100, 175, 250, and 375 all have a single heat exchanger. The Nortec SE 525 and 750 have two heat exchangers. The Nortec SE 1050 has three heat exchangers. All models have a single pressurized steam inlet and condensate drain with internal manifold connecting separate heat exchangers if they are present.
Figure 3: Nortec SETC/P Models
Introduction | 6
Outdoor Model (Nortec SETC Only)
Option / Accessory
Used For
Freeze Protection Package (Nortec SETC Only)
Emptying the tank in case of fault or power failure to prevent freezing. (Factory installed)
Floor Stand
Supporting the humidifier 27 inches above the floor (height can be reduced by cutting legs of floor stand). (field assembled)
Ceiling Mounting Kit (Nortec SE50 Only)
Providing a drain pan and support brackets for mounting an Nortec SE50 unit from the ceiling.
Steam Distributors
Adding steam into air ducts
Remote Blower Pack
Adding steam into a space remote from the humidifier.
SAM-e Steam Distribution Manifold
Adding steam into air ducts where short absorption is required.
Digital or Analog Control Humidistats
Controlling the output of the humidifier based on sensed RH (can be mounted in the space being humidified or in the duct).
Digital RH Transducers
Communicating RH in a space or duct to the humidifier
Digital or Analog High Limit Humidistats
Preventing over humidification in a duct by shutting down or throttling down the humidifier when duct RH gets high.
Air Proving Switches
Insuring humidification only occurs when air is moving in a duct.
Condair LINKS 2 (Nortec SETC Only)
Connecting the humidifier to a building management interface. hardware allows control of the humidifier via BACnet, Lonworks, Johnson N2, or Modbus.
Condair OnLine (Nortec SETC Only)
User and factory monitoring and configuration of the humidifier via the internet.
The outdoor model of the Nortec SETC provides a weatherproof enclosure that allows the Nortec SETC to be installed on rooftops in moderately cool climates. Refer to the Nortec SETC installation manual that is provided with the outdoor model to insure proper installation.
Options and Accessories
Condair provides a complete line of options and accessories for every humidification application. The following options and accessories are available and may have been delivered with your Nortec SETC/P humidifier. Refer to the installation instructions that came with the accessories for their proper installation and operation.
Table 2: Options and Accessories
9 | Installation
Nortec Model
SETC
Part No
SEP
Part No.
CV
Valve
CV Valve,
Steam
Inlet, Wye Port (NPT)
Cond­ensate Port
(NPT)
Net/Full
Weight
lb (kg)
Required
fill line
flow
gal (l)
/min
Required
Drain
capacity
gal (l)
/min
Electrical
50
2552765
2520383
2.8
1/2
3/4
125/180
(57/82)
2.6 (10)
5.2 (20)
Voltage
110-120
100
2550073
2525132
5.5
3/4
3/4
267/423
Phase
1
175
2550074
2525133
10 1 3/4
(121/192)
250
2550075
2525134
12 1 3/4
355/599
Amps
(161/272)
1.25 A
375
2550076
2525135
20
1 1/4
3/4
Power
525
2550077
2553312
28
1 1/2
1
529/992
0.15 KW
750
2550078
2553313
40 2 1
(240/450)
4.5 (17)
8 (29)
Max
1050
2550080
2525139
77 2, 2 1/2,
2 1/2
1 1/4
703/1384 (318/628)
Disconnect
15 A
Nortec Model
*Supply
Steam
Pressure
(psig)
*Max Output lb/hr (kg/hr)
Approximate Boiler Steam Consumption
lb/hr (kg/hr)
**Water
Consumption
gal (l) /hr
**Drain Volume
gal (l) /hr
50
5
13 (6)
15 (7)
2.3 (9)
0.8 (3)
10
32 (14)
36 (16)
5.7 (21)
1.9 (7)
15
50 (23)
58 (26)
9.0 (34)
3.0 (11)
100
5
26 (12)
30 (14)
4.7 (18)
1.6 (6)
10
63 (29)
72 (33)
11.3 (43)
3.8 (14)
15
100 (45)
115 (52)
18.0 (68)
6.0 (23)
175
5
46 (21)
52 (24)
8.2 (31)
2.7 (10)
10
110 (50)
127 (58)
19.8 (75)
6.6 (25)
15
175 (80)
201 (91)
31.5 (119)
10.5 (40)
250
5
65 (30)
75 (34)
11.7 (44)
3.9 (15)
10
158 (72)
181 (82)
28.3 (107)
9.4 (36)
15
250 (114)
288 (131)
44.9 (170)
15.0 (57)
375
5
98 (44)
112 (51)
17.5 (66)
5.8 (22)
10
236 (107)
272 (123)
42.5 (161)
14.2 (54)
15
375 (170)
431 (196)
67.4 (255)
22.5 (85)
525
5
137 (62)
157 (71)
24.5 (93)
8.2 (31)
10
331 (150)
380 (173)
59.5 (225)
19.8 (75)
15
525 (239)
604 (274)
94.4 (357)
31.5 (119)
750
5
195 (89)
224 (102)
35.1 (133)
11.7 (44)
10
473 (215)
543 (247)
84.9 (321)
28.3 (107)
15
750 (341)
863 (392)
134.8 (510)
44.9 (170)
1050
5
273 (124)
314 (143)
49.1 (186)
16.4 (62)
10
662 (301)
761 (346)
118.9 (450)
39.6 (150)
15
1050 (477)
1208 (549)
188.7 (714)
62.9 (238)
Table 4: Nortec SETC/P Capacities and Water Consumption
Table 3: Nortec SETC/P Specifications
* Supply steam pressure must be present at the CV valve to achieve rated output
** At maximum output , 25% blow down, and with drain water cooling activated
Installation | 8
Nortec
Nortec
Nortec
9 | Installation
Installation
10 Typical Humidifier Installation 11 Location 12 Mounting on Optional Stand 13 Ceiling Mounting (Nortec SE50 Only) 14 Plumbing
15 Boiler Steam and Boiler Condensate
Return
17
Steam Lines and Condensate Returns 22 Electrical 23 External Controls
23 Control Wiring
23 Control Location 24 On/Off Control Wiring 25 Modulating Control Wiring
27 Transducer Control Wiring
28 Optional Outdoor Temperature Reset 29 CV Valve Actuator Wiring 30 Remote Relay Board Wiring 31 Staged Modulation Wiring (Nortec SETC Only) 32 Options and Accessories
32 Remote Blower Pack
Installation | 10
E
L1
N
Ground
Typical Humidifier Installation
Location
Mounting
Pg 11
Steam
Distribution
Pg 17
1 ft (30 cm)
Plumbing
Pg 14
Boiler Steam Pg 15
Controls
Pg 23
Electrical
Pg 22
Modulation
Controls
2 in.
(5 cm)
min.
min.
1ft (30 cm)
On/Off
Controls
30 in.
(76 cm)
Min.
SE 1050
Figure 5: Typical Humidifier Installation
SAM-e Distribution Manifold
36 in. (91 cm)
Min. Top Clearance
(0 in SE 50)
30 in.
(76 cm)
Min.
1­2­3- Ctrl Ground 4­5-
7­8-
9- Ground 10­11-
12-
S
E X T T
C
/
P
24 VAC On/Off Loop
Control Signal Limit Signal
6-
5 VDC
Ground Tank Blow Down
Actuator Actuator
0-10 VDC Out
Side
Clearance
Condensate return to boiler
Dedicated
Circuit Breaker
or Disconnect
30 in.
(76 cm)
Min.
Front
Clearance
Pressurized steam supply
Water supply 30-80 psig
Air gap
Tank drain
SETC/P
EXT
11 | Installation
Location
As Close as
Possible to Steam
Distributor
30 in.
(76 cm)
Min.
SE 1050
only
Mount
Humidifier
5-95%
30 in.
(76 cm)
Min. Side
Clearance
Condensate drain
line must be
sloped down, do
not use to lift
condensate
30 in.
(76 cm)
Min. Front Clearance
36 in. (91 cm) Min.
Top Clearance
(0 in. for SE50 only)
Note:. Condensate drain line must be sloped downward to boiler condensate return. Use pump (by others) or stand (optional) if necessary.
The Nortec SE series humidifiers are designed to be either floor mounted or stand mounted (stand optional). Nortec SE 50 models can also be ceiling mounted with the optional ceiling installation kit, part number 2520345.
Install only in areas with ambient temperature 41-104 °F (5 – 40 °C) relative humidity 5 -
95% (non condensing).
Ensure mounting surface is strong enough to support the full weight of the humidifier and
accessories (see Table 3: Nortec SETC/P Specifications).
Install in location where electrical power, boiler steam, and drain can be connected to the
humidifier.
When possible install below the steam distributor. If mounted above the steam distributor
take care to provide proper steam line routing and proper condensate traps.
DO NOT locate the humidifier any further then absolutely necessary from the steam
distributor location as net output will be reduced as a result of heat loss through the steam line.
Condensate drain is located close to the bottom of the humidifier. Locate the unit so that
condensate line slopes down to boiler or use pump (by others) to lift to boiler. Use stand if necessary.
Avoid mounting humidifier on combustible surfaces including (but not limited to) carpet, tile,
or certain insulating materials.
Clearance dimensions shown are for reference only and are the minimum required for
maintenance of the humidifier. Consult local and national codes before final location and installation. Condair does not accept responsibility for installation code violations.
Figure 6: Installation Location / Clearance
Installation | 12
Mounting on Optional Stand
Fasten Nortec SE humidifier
to stand with bolts, lock
washers, and nuts provided.
Tighten
to 200 in-lb (22.6 Nm).
Note: Center support only
present on Nortec SE 525 and larger.
Secure stand to floor four places. (hardware by others)
Note: The humidifier must be secured to the stand (hardware provided) and the stand must be secured to the floor (hardware by others).
The optional Nortec SE floor stand positions the Nortec SE humidifier at a convenient working height and provides additional clearances for sloping drains. The stand must be assembled at site.
Assemble the stand according to the instructions that are provided with it. Ensure the stand and humidifier are installed on a level surface Permanently secure the stand to the floor via the holes in the leg support plates following
any local codes or regulations.
Mount stand on level surface
Ensure humidifier is Level
Figure 7: Mounting on Optional Stand
13 | Installation
Note:. The Nortec SE50 requires regular maintenance including removal of scale from the heat exchanger and tank. Make sure it is installed in a location where
the maintenance can be performed.
Ceiling Mounting (Nortec SE50 Only)
12.8 in.
Anchor 3/8 in (M10)
support rods to ceiling
(by others)
Support rods and hardware
(by others) must not extend
below support bracket flange.
Figure 8: Ceiling Mounting the Nortec SE50
(32.6 cm)
Sloped drain 1/2 in. pipe (by others)
Condair offers an optional ceiling mounting kit (part number 2520345) which allows the Nortec SE50 to be ceiling mounted with zero clearance to the ceiling. Follow the following guidelines for installation.
Follow the instructions provided with the ceiling mounting kit. Install in a location where regular maintenance can be performed. Provide clearance as
The Nortec SE50 weighs 180 lb (82 kg) when filled with water and without any
The humidifier cannot be used as a structural member. All piping connected to the unit
A drain line emptying into an open drain must be connected to the ceiling kit drain pan.
shown in Figure 6: Installation Location / Clearance.
accessories or piping. It is the installer’s responsibility to calculate the total weight which must be supported, to ensure the ceiling structure is adequate, and to install support rods and to connect drain pan per local codes and regulations.
must be supported independently.
Condair recommends a 1/2 in. pipe with sufficient slope to ensure any water collected in the pan will drain from it.
Installation | 14
Plumbing
Note:
Drain Water is very hot, do not use plastic pipe for drain or condensate lines, do not
drain to public sink. Route to floor drain or equivalent.
Supply cold potable water, deionized water or reverse osmosis water at 30 - 80 PSIG.
Hardness 5-7 grain or 90 – 120 mg/l (as Ca
+2
as CaCO3) Total Dissolved Solvents (TDS) 0.5-3 mg/l or Conductivity 1 to 70 mho/cm Chlorides 0-25 ppm PH 7.2-8.5 Alkalinity 30-130 mg/l (as CaCO3)
0.75 in. (19 mm). OD
un-threaded drain outlet
Connect with hose cuff
and hose clamps.
*Pipe, unions, and water shut-off valve not supplied by Condair.
All water supply and drain line connections must be installed in accordance with local
plumbing codes.
1/2 in. NPT Use union to connect supply pipe to unit.
Always install a water shut-off valve.
Air gap required. 2 1/2 in. to 1 1/4 in. copper reducer is ideal. Hose/line must not touch the bottom of the funnel.
Min. 1 1/4 in. OD drain line. Slope down. Increase size if combining multiple drains.
Axillary drain, 1/2 in. female NPT For draining tank without pump. Leave
valve closed except if freeze protection is installed.
Figure 9: Water Supply and Drain Connection
See Table 3 and Table 4 on page 7 for supply water flow requirements. Install water shut off valve and union before humidifier to facilitate servicing. Insure drain line is adequately sized to provide free and easy draining and that an air gap is
installed as shown. See Table 3 and Table 4 on page 7 for flow requirements.
Auxiliary drain connection with manual shut off valve is recommended for all units. Valve to
be left closed on units without freeze protection option installed. Valve to be left open on units with freeze protection option installed except during servicing.
High hardness or silica content supply water may require increased maintenance. Unit damage caused by water quality outside of the specified ranges is not covered under
warranty.
15 | Installation
6 in.
(15 cm)
Max
Boiler steam supply
line. Max 15 psi, Min 5 psi
measured at CV Valve
Boiler steam
Actuator
inlet port location on Nortec SE 1050
CV Valve (see table 3)
Pressure
gauge (optional)
F&T Trap
Wye Strainer
Isolation Valve
Boiler steam inlet port
(see table 3)
Condensate Drain Port (see table 3)
Condensate drain line.
Gravity feed to boiler.
Use pump if condensate
must be lifted.
Boiler Steam and Boiler Condensate Return
Note:.
Pressurized steam line installation to be performed by a qualified installer. Damage to Nortec SE heat exchanger will occur if it is exposed to pressure above
20 psi.. A safety relief valve must be installed to prevent the Nortec SE from being exposed to pressure in excess of 15 psi when the Nortec SE is connected to a medium or high pressure boiler via a pressure reducing valve.
The steam supply line must be designed to provide design pressure at the CV valve
when there is 100 % demand (CV valve completely open). Pressure losses in the steam supply line will reduce Nortec SE output.
Condensate must be drained to a non-pressurized boiler condensate return line.
Note: Condair supplies CV valve,
actuator and wye strainer. All other components and fittings by others.
Not pressurized
condensate header
(slope down)
Pressurized condensate header
Figure 10: Nortec SE Boiler Steam and Condensate Connection
Installation | 16
Condair supplies a CV valve, actuator and wye strainer with each Nortec SE humidifier. The port
Caution: Condensate leaves the steam traps inside the Nortec SE under slight pressure. Steam flash could occur in the condensate drain line.
sizes of the CV valve, boiler steam inlet port, and condensate drain port are given in Table 3: Nortec SETC/P Specifications on page 7. Follow the following guidelines for installation.
All steam line connections must be installed in accordance with local codes. Install the CV valve actuator following the procedure in Figure 11: CV Valve Actuator
Installation after the CV valve is installed on the steam line. Wire the actuator as described in CV Valve Actuator Wiring on page 29.
Boiler steam supply line design is the responsibility of the installer. The boiler steam supply
line must be designed so that that design pressure is present at the CV valve when the CV valve is completely open (100% demand). The diameter of the supply line up to the wye strainer may have to be oversized to insure proper steam pressure.
The Nortec SE will operate on supply steam pressures between 5 and 15 psi measured at
the CV valve. Lower steam supply pressures will result in lower output. See Table 4: Nortec SETC/P Capacities and Water Consumption on page 7 for capacities at different supply pressures.
If condensate cannot be gravity fed to the boiler then a pump must be used to lift the
condensate. See Spirax Sarco (www.spiraxsarco.com) and others for pumps and additional information on condensate management.
The boiler steam and condensate connections are independent. Boiler steam condensate
should be returned to the boiler and should not be mixed with water from the tank drain.
The steam supply pressure can be entered into the Nortec SETC control software to provide
display of unit output. See Pressure Based on page 56.
Install jam nut
and lock washer
Turn stem extension until holes
line up
1/2 in. (1.2 cm)
CV Valve
Install stem
extension
min.
Figure 11: CV Valve Actuator Installation
Insert connecting pin
Actuator
Raise valve stem to full up
2 turns then push in and 1/8 turn to lock
Tighten jam nut against stem extension
Install and tighten mounting nut
17 | Installation
St
eam
Dire
ction
Steam Line
Material
Lb/hr (kg/hr)
Steam Line Length
ft
m
Steam Line Description
Copper Tube
0-100 (0-45)
0-90
0-27
1 1/2 in. MED-L Tubing (1.625 in. OD)
101-250 (46-113)
0-180
0-54
3 in. MED-L Tubing (3.125 in. OD)
251-650 (114-295)
0-260
0-79
**4 in. MED-L Tubing (4.125 in. OD)
*Stainless Steel
Tube
0-100 (0-45)
0-90
0-27
1.75 inch Tube x 0.065 inch thick wall
101-250 (46-113)
0-180
0-54
3 inch Tube x 0.065 inch thick wall
251-650 (114-295)
0-260
0-79
**4 inch Tube x 0.065 inch thick wall
Condair Hose
31-100 (14-45)**
<15
<4.5
***Part Number 1328820 (1 3/4”)
10 Degrees
2 in. (5 cm)
1 ft (30 cm)
MAIN RULES FOR ATMOSPHERIC STEAM LINES
Slope the steam lines. Trap condensate (Use full size ‘T’ for Traps). Steam lines must not have any restrictions which could cause back pressure. Insulate with 1.0 in. (2.5 cm) pipe insulation. Follow recommended materials, size and length see tables.
Steam Hose Odour: Condair hose may generate a slight odour during initial use. This odour is temporary and will disappear after a short period of time.
Steam Lines and Condensate Returns
Use Appropriate Slope Insulate Pipe
2 Degrees
0.5 in. (12 mm)
1ft (30 cm)
Figure 12: Main Steam Line Requirements
1 in. (2.5 cm) pipe
insulation
Note: * Use only stainless steel tube for reverse osmosis and deionized water applications.
** Use 2 x 4 in. steam lines for steam capacities higher than 750 lb/hr (307 kg/hr)
*** Use one steam hose per 100 lb/hr (45 kg/hr) of output.
Table 5: Recommended Steam Line Material
Installation | 18
4 8 (2.4) 4 (
Figure
1.2) 15 (4.5)
1.6
13: Condensate Traps
Table 6: Maximum Recommended Length of Steam Line
Note: Condensate should not be routed to a sink used frequently by personnel. Route to a floor drain or equivalent. Condensate normally cools in traps but is still hot. A SAM-e or larger steam line generates more condensate and water may not cool in the trap. A drain
water cooler option may be installed if required by code.
as steam line
Unit Size
Steam Output
lb/hr (kg/hr)
Steam Outlet and Line Size
copper (SST)
Maximum
Length
ft (m)
Possible Loss
lb/hr/ft (kg/hr/m)
Possible Loss at
Max. Length
lb/hr (kg/hr)
50
50
(23)
1 1/2 (1 3/4)
37 (11)
0.11 (0.16)
4 (2)
100
100
(45)
1 1/2 (1 3/4)
90 (27)
0.11 (0.16)
10 (4.5)
175
175
(80)
3 (3)
90 (27)
0.16 (0.24)
14 (6.5)
250
250
(114)
3 (3)
180 (55)
0.16 (0.24)
28 (13)
375
375
(170)
4 (4)
180 (55)
0.22 (0.33)
39 (18)
525
525
(239)
4 (4)
220 (67)
0.22 (0.33)
48 (22)
750
750
(341)
2X 4 (4)
260 (79)
0.44 (0.66)
114 (52)
1050
1050
(477)
2X 4 (4)
260 (79)
0.44 (0.66)
114 (52)
Tube Diameter
in.
90 Degree
Elbow ft (m)
45 Degree Elbow
ft (m)
Side Outlet Tee
ft (m)
Gate Valve
ft (m)
Control Valve
ft (m)
1 1/2 or 1 3/4
3.5 (1)
1.75 (0.5)
7 (2.1)
0.8 (2.4)
34 (10)
3
5 (1.5)
2.5 (0.75)
11 (3.3)
1.1 (3.1)
54 (16)
4
8 (2.4)
4 (1.2)
15 (4.5)
1.6 (0.5)
80 (24)
NOTE:
12 in. (30 cm)
min drop to
top of ‘P’ Trap
plus duct
static pressure
See Table 7 for equivalent length of common fittings.
Table 7: Equivalent Length of Some Common Fittings
Tee is same size
P Trap
min 8 in.
(20 cm)
Use a full size tee, not a 90 degree elbow for vertical to horizontal transitions.
‘P’ Traps Use:
-
Condair 0.375 in condensate hose .
-
1/4 in Med-L copper tubing, or
-
0.375 in stainless steel tubing
Condensate drains must be sloped down. Route to humidifier fill cup if possible.
Possible Loss at
Max. length
lb/hr
(kg/hr)
Globe Valve
ft (m)
19 | Installation
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
2 x duct
height min.
2/3 Duct height
12 in.
(30 cm)
min.
Mount distributor
to side of duct
Figure 14: Distributor Location in Duct
Note:
Refer to distributor or SAM-e installation manuals for detailed installation instructions.
Insulated copper
steam line. Support
so weight is not on
steam outlet.
1 ft (30 cm) min. before
Figure 15: SAM-e/Steam Distributor Above Humidifier (Copper Steam Line Shown)
anybend
with clamps
2 in. (5 cm)
min.
Hose cuff
1 ft (30 cm)
Condensate line
‘P’ Trap
To drain
Use steam hose between steam outlet and steam line.
Installation | 20
1 ft (30 cm)
0.5 in. (1.2 cm) min.
1ft (30 cm)
min. before
any bend
Obstruction
1 ft (30 cm) min.
Use full size condensate tee
at low point. Slope lines up
to “T” and immediately after it.
‘P’ Trap
To drain
‘P’ Trap
To drain
Hose will soften over time proper support Is necessary
Min 12 in.
(30 cm)
radius
1 ft (30 cm) min. Before any bend
Support Brackets
‘P’ Trap
To drain
Figure 16: Steam Distributor/SAM-e Below Humidifier (Hose Shown)
Install Condensate Tee Before Distributor
To drain
1 ft (30 cm) min.
‘P’ Trap
Figure 17: Steam Under Obstruction (Copper Steam Line Shown)
21 | Installation
Method for Longer Runs With Limited Vertical Space
1 ft (30 cm) min before turn
Condensate
tee every
15-20 ft
(4.5 - 6 m)
Install condensate tee
before distributor
Condensate
tee at low
points
Individually trap multiple condensate
returns before joining on common line.
1 ft (30 cm)
min.
To Drain
Figure 18: Long Steam Run
Installation | 22
Caution:
Wiring to be performed by a licensed Electrician. All SE humidifiers operate on 120 VAC, single phase, 60 HZ power. Refer to
specification label for power requirements.
Electrical
Knockouts provided in top and bottom panels. Install strain relief (by others)
High voltage
terminal block
Note:
1 Dedicated external fused
disconnect must be installed. Fusing must not exceed max circuit protection as indicated
on the specification label.
2 Ensure that adequate power is
available to carry full humidifier amp draw as indicated on the specification label.
3 All wiring to be in accordance
with national and local electrical codes.
Figure 19: Primary Power Connection
Single Phase Supply Ground
L1
Neutral
Nortec SETC / P Primary Power
Dedicated circuit
breaker or fused
disconect.
Ground
L1 Neutral
E I X N
T T
23 | Installation
Figure 20: Control Location
External Controls
Note: Regardless of selecting on/off or modulating control method, Condair humidifiers must have a closed circuit across their on/off security loop control terminal to operate. Condair highly recommends the use of a high limit humidistat and an air proving switch in series for this function.
Caution: Failure to wire the humidifier in accordance with the wiring instructions could cause permanent damage. Such errors will void the warranty.
Control Wiring
Controls are available from Condair as accessories. If controls were not ordered with humidifier they must be supplied by others. The following information is relevant to all controls, factory supplied or otherwise. For wiring use minimum of 18 AWG and keep as short as possible.
The Nortec SETC humidifier can be operated with two modulating inputs. The Nortec SEP has one modulating input which can be used for a duct high limit or humidity control. Both the Nortec SETC and Nortec SEP can be operated as On/Off. See Control Setting on page 53 for Nortec SETC configuration and On/Off or Modulating Control (J10) on page 61 for Nortec SEP configuration.
Control Location
10 ft min.
1
Air Proving Switch
1 Air Proving Switch
2
Duct High
Limit
3
Humidity Control
(return air duct or in room)
Locate so that it can sense air flow or lack of it. 2 Duct High Limit
Nortec SETC can be modulating, On/Off, or a humidity sensor. Nortec SEP can be modulating or On/Off. Locate at least 10 feet from steam distributor or far enough that under normal conditions
3 Humidity Control
Nortec SETC can be Modulating, On/Off, or a Humidity Sensor. Nortec SEP can be modulating or On/Off. Can be located either in return air duct (preferred) or in room being humidified. Mount in area representative of room humidity (draft, doorways, sunlight, or overhang such
steam is fully absorbed.
as a shelf can affect reading). Avoid placing near discharge diffuser of humidified air.
Installation | 24
On/Off Control Wiring
Connect 24 VAC ,
term inal 1 of hum id ifie r to
term inal 2 of controllers.
Com N/O
1 -
Groun
d
2 -
24
VAC
3 -
Common
4
-
Digital
Out
5
-
Fan
Relay
6
-
Fan
Relay
7
-
NTC
Sensor
8
-
NTC
Sensor
1 -
Groun
d
2 -
24
VAC
3 -
Common
4
-
Digital
Out
5
-
Fan
Relay
6
-
Fan
Relay
7
-
NTC
Sensor
8
-
NTC
Sensor
Humidifier Terminal Strip
Air Proving Switch
Wire to make when
sensing air flow
Air Proving
Switch
Duct High Limit
2548732 - On/Off
Duct Humidistat
Knockouts provided in top and bottom panels. Install strain relief (by others)
Figure 21: On/Off Controls
Duct High Limit
2548732 - On/Off Duct Humidistat
Wire to make on drop in humidity
Humidity Control
2548731 - On/Off
Wall Humidistat
Note: 1 Humidifier will run when circuit between
terminal 1 and 2 on humidifier is closed.
2
Terminal 1 is 24VAC Hot, turn unit off to avoid shorting while wiring.
3
Digital Humidistats require 24 VAC power from terminals 1 and 3 of humidifier.
4
Humidity Control can be wall mounted as shown or return air duct mounted.
Humidity Control
2548731 - On/Off Wall Humidistat or,
2548732 - On/Off Duct Humidistat
OR
E S
X E
T
1- 24 VAC 2 - On/Off Loop 3 - Ground 4 - Control Signal
5 - Limit Signal (SETC only) 6 - 5 VDC 7 - Ground 8 - Full Tank Blow Down 9 - Ground 10 - Actuator power 11 - Actuator power 12 - 0-10 VDC Out
Figure 22: Digital On/Off
25 | Installation
Modulating Control Wiring
1 - Ground 2 - 24 VAC
6 - Analog
Out
7 - Analog
In
8 - Temperature
1 - Ground
2 - 24 VAC
6 - Analog
Out
8 - Temperature
Air Proving
Switch
Humidifier Terminal Strip
2520266 - Digital Duct Humidistat
Package
High Limit Humidistat
Note: 1
Install On/Off controls or jumper between
terminal 1 and 2 of humidifier in order to run.
2
Terminal 1 is 24 VAC Hot, turn unit off to avoid shorting while wiring.
3
High Limit Humidistat must be duct mounted. It can be On/Off or modulating.
4
Control Humidistat can be mounted in space or in return air duct and can be On/Off or modulating.
5
The Nortec SEP can only accept one modulating signal.
Knockouts provided in top and bottom panels. Install strain relief (by others)
Figure 23: Modulating Controls
1510142 - Digital Wall Humidistat
Control Humidistat
Analog Out - 3
24 VAC - 2 Ground - 1
Connect 24 VAC, terminal 1 of
Nortec SETC/P to terminal
2 of controllers.
Figure 24: Digital Modulating Humidistats
Insert On/Off
controls or jumper
between 1 and 2
E
S
X T E
1- 24 VAC 2 - On/Off Loop
3 - Ground 4 - Control Signal
5 - Limit Signal (SETC only) 6 - 5 VDC
7 - Ground 8 - Full Tank Blow Down 9 - Ground 10 - Actuator power 11 - Actuator power 12 - 0-10 VDC Out
Installation | 26
1 - Ground 2 - 24 VAC
6 - Analog
Out
7 - Analog
In
8 - Temperature
1 - Ground 2 - 24 VAC
6 - Analog
Out
Connect 24 VAC, terminal
1 of SETC/P to terminal
2 of controllers.
1- 24 VAC 2 - On/Off Loop 3 - Ground
4
- Control Signal
5
- Limit Signal (SETC only)
6
- 5 VDC
7
- Ground
8
- Full Tank Blow Down 9 - Ground 10 - Actuator power 11 - Actuator power 12 - 0-10 VDC Out
Air Proving
Switch
Duct High
Limit
2520261 - Digital Wall W/O Sensor
1509858 - Wall
Sensor
Humidifier Terminal Strip
2520261 - Digital Wall W/O Sensor
+
1509858 - Wall Sensor
Wire wall sensor to digital display as shown
below, wire digital display to humidifier as shown
for 1510142 - Digital Wall Humidistat.
Knockouts provided in top and bottom panels.
Install strain relief (by others)
Figure 25: Digital Wall Humidistat – Remote Wall Sensor
2520261 - Digital Wall W/O Sensor
1509858 - Wall
Sensor
Figure 26: Remote Wall Sensor Wiring
27 | Installation
1 - Ground 2 - 24 VAC 3 - Analog
Out
Transducer Control Wiring (Nortec SETC Only)
Connect 24 VAC ,
terminal 1 of SETC to
terminal 2 of controllers
1 - Ground 2 - 24 VAC
6 - Analog
Out
E
Figure 27: Transducers
1509857 - 2-10V Duct Humidity
Humidifier Terminal Strip
Transducer
Air Proving Switch
1509858 - 2-10V Wall Humidity
Figure 28: Digital
Duct High Limit 1509857 - 2-10V Duct Humidity Transducer
Note: 1
Knockouts provided in top and bottom panels. Install strain relief (by others)
Install On/Off controls or jumper between terminal 1 and 2 of humidifier .
2
Terminal 1 is 24 VAC Hot, turn unit off to avoid shorting while wiring.
3
Duct High limit can be duct humidity transducer as shown or duct On/Off
humidistat.
4
Humidity Control can be wall humidity transducer as shown, duct humidity transducer, or On/Off humidistat.
Transducer
E X T
Humidity Control 1509858 - 2-10V Wall
Humidity Transducer
Insert On/Off
controls or jumper
between 1 and 2
S
1- 24 VAC 2 - On/Off Loop 3 - Ground 4
- Control Signal
5
- Limit Signal (SETC only) 6 - 5 VDC 7
- Ground 8
- Full Tank Blow Down 9 - Ground
10 - Actuator power 11 - Actuator power 12 - 0-10 VDC Out
Installation | 28
Optional Outdoor Temperature Reset
Connect 24 VAC, terminal
1 of humidifier to terminal
2 of controllers.
1 - Ground 2 - 24 VAC 3 - Common 4 - Digital
Out
5 - Fan
Relay
6 - Fan
Relay
7 - NTC
Sensor
8 - NTC
Sensor
1 - 24 VAC 2 - Temperature
Figure 29: Outdoor Temperature Reset
Each digital controller is equipped with an integrated reset function that can reduce the
setpoint during cold weather operation. This will prevent condensation on windows and building structures. The above graph illustrates how the setpoint reset feature operates.
On modulating humidistats this feature is enabled by removing the jumper from terminals 8
and 1 on the humidistat and wiring the outdoor temperature sensor to these terminals. On On/Off humidistats this feature must be activated with the humidistat’s keypad.
When the outdoor temperature setback feature is in effect, the humidistat will normally
display the calculated setpoint limit based on the outdoor air temperature. A snowflake will also be displayed to indicate cold weather operation. When any key on the controller is pressed, the LCD screen will display the customer specified setpoint for a short duration.
2548731 - On/Off Wall Humidistat or,
2548732 - On/Off Duct Humidistat
2520263 - Outdoor Temperature
Sensor
OR
E S X
E
Note: 1 The Temperature sensor is
intended for duct mounting.
2 Locate the temperature sensor
near the fresh air intake. This will ensure accurate representation of the outdoor air temperature.
Figure 30: Outdoor Temperature Sensor (Modulating Control)
Insert Other
On/Off
controls
in series
T
1- 24 VAC 2 - On/Off Loop
3 - Ground 4 - Control Signal 5 - Limit Signal (SETC only)
6 - 5 VDC 7 - Ground 8 - Full Tank Blow Down 9 - Ground 10 - Actuator power 11 - Actuator power
12 - 0-10 VDC Out
29 | Installation
2520263 - Outdoor Temperature
Connect 24 VAC, terminal
1 of SE to terminal
2 of controllers.
1 - 24 VAC 2 - Temperature
1 - Ground 2 - 24 VAC 6 - Analog
Out
8 - Temperature
Sensor
1510142 - Digital Wall Humidistat or,
2520266 - Digital Duct Humidistat Package
Note: 1
The Temperature sensor is
intended for duct mounting.
2
Locate the temperature sensor
near the fresh air intake. This will ensure accurate representation of the outdoor air temperature.
Insert On/Off
controls or jumper
between 1 and 2
E S X E
T
1- 24 VAC 2 - On/Off Loop 3 - Ground 4 5 6 - 5 VDC 7 8 9 - Ground 10 - Actuator power 11 - Actuator power 12 - 0-10 VDC Out
- Control Signal
- Limit Signal (SETC only)
- Ground
- Full Tank Blow Down
Figure 31: Outdoor Temperature Setback (On/Off Control)
CV Valve Actuator Wiring
Nortec
SE 50 - 750
Actuator
Note: 1 Wire the CV valve actuator
to the humidifier’s low voltage terminal strip.
2 Use minimum of 18 AWG wire
and keep as short as possible.
3 After installation and powering
humidifier verify that travel of actuator at full demand is to the fully open position.
Figure 32: CV Valve Actuator Wiring
Nortec SE 1050 Actuator
Nortec SE 1050 low
voltage terminal strip
Bk
R
Gr
Y/Bk
SE 50 - 750 Terminal Strip
9 - Ground
R
Bk
Y/Bk
10 - Actuator 24 VAC 11 - Actuator Ground 12 - 0-10 VDC Out
9 - Ground 10 - Actuator 24 VAC 11 - Actuator Ground 12 - 0-10 VDC Out
Installation | 30
Unit
ON
Steam Service
Remote Relay Board Wiring
NO
COM
NO
COM
NC
NO
COM
NC
NO
COM
Error
The Nortec SETC (not SEP) remote relay board provides the output signal for the CV Valve Actuator and includes 4 relays that can provide remote status indication. The remote relay board is located as shown in Figure 33: Remote Relay Board Wiring. The PCB with the relays includes markings which indicate the function of each terminal on the board. The relays indicate the following status;
1 Unit On – The normally open relay is closed when the humidifier has power and the On/Off
switch is set to on.
2 Steam – The normally open relay is closed when the control board sends a signal to the CV
valve actuator to open the CV valve and steam is being produced.
3 Service – The relay can be wired to open (NC) or close (NO) when a warning is displayed on
the humidifier display and the yellow service LED is illuminated.
4 Error – The relay can be wired to open (NC) or close (NO) when a fault is detected by the
humidifier controls.
Figure 33: Remote Relay Board Wiring
31 | Installation
Staged Modulation Wiring (Nortec SETC Only)
Daisy Chain up to 16
Humidifiers
Slave 1
Slave X
Master
Daisy chain pole 2 and 3 of terminal
J2a-RS485
of the
driver board.
Connect up to 10 units (equivalent of 10,500 lb/hr (4,770 kg/hr)) using 18-24 AWG multi-
strand, twisted pair, shielded cable.
Connect humidistats/transducers and On/Off safety loop to master unit only. See Multi Mode on page 54 and Multi Unit Op. Range on page 56 for software configuration.
Note:
Do not reverse polarity. Do not connect to pole 1 or 4.
Figure 34: Staged Modulation Wiring
Installation | 32
Options and Accessories
Note: For installation of options and accessories follow the instructions that are provided with
them.
Remote Blower Pack
Remote blower packs are available for the Nortec SETC/P for applications where steam for humidification must be introduced directly into the space being humidified. For instructions on installing the remote blower pack refer to the installation instructions supplied with it. The steam line and condensate return instructions provided in this manual are also applicable to remote mounted blower packs.
The blower packs include a safety relay which should be used to prevent the humidifier from operating if the blower packs do not have power. Wire humidifier security loop in series through all blower packs and other On/Off controls.
Drain Water Cooling (External)
Pneumatic and electric drain water coolers are available from Condair for installation outside the humidifier or on condensate drains from steam traps, distributors, and SAM-e headers. If condensate cannot be routed back to the humidifier tank via the humidifier’s fill cup then an external drain water cooler may be required to meet regulations restricting the temperature of hot water that can be fed to drain. The external drain water cooler is only available for field installation.
33 | Start Up
Start Up
34 Installation Check 35 Nortec SETC User Interface
35 Manual Drain Switch
36 Start Up Procedure 37 Status Screens 39 Condair Digital Controls 40 Staged Modulation (Nortec SETC Only) 40
LINKS 2 40 Condair ONLINE 41 Nortec SETC/P Pre-Start Up Checklist 42 Nortec SETC/P Start Up Checklist
Start Up | 34
Installation Check
Before turning on power to the Nortec SE, inspect the installation to insure that it was carried out correctly. Refer to Figure 35: Installation Check, to the Nortec SETC/P Pre-Start Up Checklist on page 41, and to the chapter on Installation that starts on page 9.
2 x duct height
from fan or
On/Off Controls
(Air Proving)
in series between
terminal 1 and 2
Steam Line
- Adequate slope
- No restrictions
- No kinks (hose)
- Condensate traps on long runs
Mounting
- Unit level
- Service clearance
- Properly anchored if on stand
transition
Disconnect
Correct voltage,
amps, phase
Calculated absorption distance
to any obstruction or 8 - 10 ft
P Trap(s) with 12 in . (30 cm) min. drop(s) .
Actuator,
- Opens CV Valve fully at 100% demand
- Closes fully at 0%.
Boiler Condensate
- Gravity fed to boiler
Figure 35: Installation Check
Min 10 ft (3 m)
(2.4 - 3 m) if unknown.
Boiler Steam
- Max 15 psi
- Safety valve if from med. or high press. boiler.
- Design pressure at 100% demand.
Air gap
Spec label
or lift pump
1/2 in line min 30-80 PSI
Not plastic drain, Not to sink.
High Limit
- Wired to terminal 5
- On/Off in series
between terminal
1 and 2
Control
- Wired to terminal 4.
- On/Off in series between terminal 1 and 2.
- In return duct or location which represents humidified space (no drafts, not by door, not
by diffuser).
35 | Start Up
SETC User Interface
Manual drain switch
Figure 37: Manual Drain Switch
Manual Drain Switch
LCD Display and Input Buttons
(Buttons used to navigate . status screens and configure the humidifier, correspond to icons on the display)
Status LEDs
Software Drain Button
(Initiates a software controlled drain)
On/Off Switch
(Turns humidifier On/Off)
Figure 36: Nortec SETC User Interface
The Nortec SETC/P has a manual drain switch that can drain the tank even if software is not functioning. To drain the tank put the switch into the drain position. For normal operation the switch should be in the off position.
Start Up Procedure
Warning: Damaged units or improperly installed units must not be operated. Damaged or improperly installed units may present a danger to persons and property.
Menu
Request – xx%
Idle
0 lb/hr
04/30/09 14:25:22
Security loop: Closed
Note: on initial startup with cold water in the Nortec SE’s tank it may take 5 to 15 minutes (depending on unit size) for the Nortec SE to reach a full boil and produce its rated steam.
Start Up | 36
Note:
Pressing the ESC key on the keypad will interrupt the float and drain test and the
humidifier will go straight to normal operating mode.
If an error is detected during the self-diagnostic sequence a Fault will be displayed.
See troubleshooting section for information on diagnosing and correcting faults.
Nortec SEP does not have an LCD display. The information on the Nortec SETC’s
LCD depends on the Nortec SETC’s configuration and actual operating conditions. It may vary from display shown.
1 Examine the humidifier and installation for damage and or improper installation.
2 Open the supply water shut off valve. If the auxiliary drain valve is installed ensure it is
closed.
3 Slowly open boiler steam isolation valve to allow boiler steam into the steam supply line up
to the CV valve.
4 Turn on the main power using the installed disconnect then turn the On/Off switch on the
front of the humidifier to On.
The LCD display will illuminate and the humidifier will perform a self-diagnostic sequence during which the LED’s and internal components will be momentarily activated. The Nortec SE will then begin filling with water. The fill time is between 10 and 30 minutes depending on the size of the unit.
5 Once the water level is close to the top of the tank the LED
lights on the SE’s float chamber will light up and indicate the water level. On start up the Nortec SE will perform a float and drain pump test by first filling until just the green LED is lit and then draining until just the red LED is lit. After the float and drain test the humidifier is in normal operation mode.
6 If On/Off or a control humidistats have been installed check and adjust the control setpoint
on the control and high limit humidistat (see Nortec Digital Controls on page 39). If transducer controls have been installed then adjust the humidity setpoint using the keypad and display (see Transducer Control on page 39)
7 When either the external humidistat or internal controller generate a demand for humidity
higher than 15%, the security loop is closed, and the float chamber indicates the tank is full the SE will transmit a signal to the CV valve to open. Steam will flow into the SE’s heat exchanger(s) and the SE will heat the water in its tank.
37 | Start Up
8 The green humidifying LED on the front of the humidifier will light up and the display will
Menu
Request – 100%
Idle 04/30/09 Security loop:
750 lb/hr 14:25:22 Closed
Menu
Request – xx%
Idle 04/30/09 Security loop:
0 lb/hr 14:25:22 Closed
Menu
CONTROL Man Cap. Demand Limit Output
: 100% : 55% : 80% : 0 lb/hr
CONTROL Man Cap. RH CNT CNT Set-Pt RH Limit LIM Set-Pt Output
Menu
: 100% : 55% : 50% : 100% : 70% : 0 lb/hr
Menu
HUMIDIFIER
Model Capacity Multimode REG Mode Software Press. In
: SETC 750 : 750 lb/hr : StandAlone : Demand : XVXX : 15 psi
Caution:
Improper control configuration can result in over humidifying which can result in
damage to property.
See Advanced Control Configuration if the controls displayed in the control
information screen do not match those connected to the humidifier.
indicated “Humidifying” and the amount of steam being produced (Nortec SETC only).
Status Screens
In addition to the main status screen the Nortec SETC includes several status screens which provide additional information about the humidifier. The additional screens can be reached by pressing the buttons corresponding to the left and right arrow key on the LCD display.
Main Status Screen
This screen reports the current request for humidity, status, output, date and time, and security loop status. If status is not idle or humidifying the left arrow key becomes a “?”. If the button corresponding to the arrow key is pressed the display will give additional information on the status of the humidifier.
Control Information Screen
Output is the lb/hr steam output of the unit. Man Cap is the user configured capacity limitation. Depending on the control configuration the screen also reports the current inputs of channel 1 and 2. If the unit is configured for internal control it also provides the current humidity and setpoints.
Humidifier Information Screen
Model is the humidifier model type. Capacity is maximum output if the unit is supplied 15 psi steam. Multimode indicates if the humidifier is operating as part of a group controlled by a single control signal
REG Mode is the configured control method. Software is the installed software version. Press. In is the boiler steam supply pressure.
Start Up | 38
Menu
Analog Output
Output Signal Capacity Total O/P Tank Monitor Quick Warm Press. Base
: X.X VDC : xxx lb/hr : xxx lb/hr : On/Off : On/Off : On/Off
Menu
100%
0%
-4 hrs
0 hrs Demand: 45%
Menu
TANK STATUS
Fill Valve : ON/OFF Drain Pump : ON/OFF Float Level 5 Run Time : xxx hr Serv. Time : xxx hr Serv Due : xxx hr
Menu
SENSOR INPUTS
Sec. Loop : Closed Tank Temp. : Closed
Menu
FEATURES LIST
Idle Mode : Idle Drain FTBD : On/Off Time Prop. : On/Off BD Rate : 25% Drain Cool :On/Off/Smart Float Check : On/Off
Menu
FEATURES LIST
Idle Mode : Idle Drain FTBD : On/Off Time Prop. : On/Off BD Rate : 25% Drain Cool :On/Off/Smart Float Check : On/Off
Analog Output Information
Output Signal is the signal currently being output to the actuator. Capacity is maximum output based on actual boiler steam press. Total O/P is the current output of the humidifier. Tank Monitor indicates if tank monitoring is On/Off. Quick Warm indicates if Quick Warm is On/Off. Press Base indicates if output is based on actual steam pressure.
Tank Status
Fill Valve indicates if the fill valve is open or closed. Drain pump indicates if the drain is on or off. Float level indicates the current float level. Run Time is total weighted operating hours since last service. Serv Time is the service interval set for the humidifier Serv Due is the time remaining before service is required.
Sensor Inputs
Sec. Loop indicates if the security loop is open or closed. Tank Temp indicates if the tank is cold (open) or hot (closed)..
Features List
Idle Mode indicates what the humidifier is configured to do when there is no demand.
FTBD indicates if full tank blow down is enabled. BD Rate indicates water drained for scale control as % of output
Drain Cool indicates configuration of drain water cooling feature Float Check indicates if the humidifier will perform float checks.
Operational Hours
Total indicates the number of hours the humidifier has been producing steam.
Weighted indicates the total amount of steam the humidifier has produced expressed as number of hours running at 100% output.
Trend Graph
This graph provides a history of the humidifiers output for the past 4 hours. It displays a percentage of full output which corresponds to the demand signal. The current demand signal is displayed at the bottom of the screen.
39 | Start Up
Digital Controls
Condair provides optional On/Off, Modulating Control, or Transducer digital controls. Figure 38 and Figure 39 show the function and meaning of the Digital Control’s display and buttons. All controls are available either wall mounted or with a remote sensor for duct mounting.
Humidity (RH %)
Indicates the
humidistat is on.
A half moon
indicates it is off.
Snowflake indicates the
setpoint is being
overridden by outdoor
temperature.
Power button turns off the humidiistat if
pressed for 2 seconds
Figure 38: Modulating and On/Off Digital Control Operation
Output signal is shown on modulating controller proportional to the demand.
State of On/Off humidistat
Setpoint (RH%)
Option button accesses sensor calibration.
See troubleshooting
Increase / Decrease Setpoint
Modulating Control
The modulating controls use a PI control algorithm to transmit a 0-10V control signal to the humidifier. Adjust the setpoint to the desired setting by using the up/down arrow buttons on the controller.
On/Off Control
The On/Off controls use a PI control algorithm to open and close a relay that opens and closes the humidifier’s On/Off loop. Adjust the setpoint to the desired setting by using the up/down arrow buttons on the controller.
Transducer Control
The transducer controls transmit a 2-10V control signal proportional to the sensed relative humidity to the humidifier. Humidity setpoint is not set at the transducer. The setpoint is set on the Nortec SETC’s display and keypad.
Note: It is possible to field calibrate Condair Digital controls if the displayed humidity is found to
be different than a known trusted source. See Digital Humidistat on page 75 of chapter on Troubleshooting.
Start Up | 40
Humidity (RH %)
Option button accesses
sensor calibration.
See troubleshooting
Adjust calibration
while in calibration
mode
Power button will
display “NO” if an
attempt is made to
turn off the transducer.
Figure 39: Transducer Control Operation
Staged Modulation (Nortec SETC Only)
Start up of each humidifier configured and installed for Staged Modulation is the same as starting up standalone humidifiers with the exception that for the humidifier to fill and produce steam the demand to the master unit must be greater than the Multi Unit Op. Range setting of the unit being started. (Example for a slave unit configured to operate between 20 and 30% the demand to the master must be greater than 22%)
Each unit connected in a staged modulation system will display its demand as a percentage of the range for which it is configured. Example, a slave unit configured to operate between 20 and 30% demand will display a demand of 50% when demand to the master is 25%.
Note: See Multi Mode on page 54 and Multi Unit Op. Range on page 56for software
configuration. See Staged Modulation Wiring on page 31 for control wiring of humidifiers in a Staged Modulation system.
LINKS 2 (Nortec SETC Only)
LINKS 2 is an option that can be integrated with the Nortec SETC. It allows a Building Management System to monitor and / or control the humidifier. For complete information about LINKS 2 and its operation and configuration, go to www.condair.com and look up the LINKS 2 manual.
Condair ONLINE (Nortec SETC Only)
Condair ONLINE is an option that can be integrated with the Nortec SETC. It allows a user to monitor their unit from any computer with an internet connection by logging in to
www.condaironline.com.
It can also be configured to send service reminders and fault warnings when they occur.
41 | Start Up
Nortec SETC/P Pre-Start Up Checklist
Unit Serial #:
Unit
type:
Tag:
Voltage:
V/
ph Steam output: lb/hr
Customer/Job:
Water Quality:
Potable (0-12 grains/gal, 0-14 ppm Silica, 0-25 ppm Chlorides)  RO  DI 
Address:
Humidifier Mounting: (Clearances around the unit Acceptable Obstruction)
Level  Front/Side Clearance  Anchored (if on stand) 
Steam Line(s):
Slope up (min 2 in/ft). Slope down (min 0.500 in/ft) Diameter / Size Material Low point condensate traps No Hose Kinks / Restrictions Insulated Type of Insulation
Condensate Line(s):
P Trap min 8 in. (20 cm) plus duct static pressure P Trap min 12 in drop 
Water Line:
Can provide required flow  Water pressure: 30-80 psig 
Drain Line:
Air gap within 3 ft of the unit Diameter / Size Auxiliary drain connected with shut off valve 
Boiler Steam
Boiler Pressure psi Pressure to humidifier psi 15 psi relief valve if med/high press boiler Actuator closes and opens CV valve fully Design pressure at CV valve Condensate return Gravity feed or pump 
Wiring:
Wiring connections and connectors secured yes no 
Controls:
Control Location Control to Terminal 4 High Limit Location High Limit to terminal 5 
Power:
Voltage, amp, fuse per Spec Label: yes no Disconnect switch located close to humidifier yes no 
Inspected by: Date of inspection: / /
Company:
Start Up | 42
Nortec SETC/P Start Up Checklist
Water supply valve opened
yes 
no 
Boiler steam isolation valve open
yes 
no 
Mains disconnect switched on
yes 
no 
Turn On/Off switch on
yes 
no 
On/Off Security loop (Terminal 1 and 2) closed.
yes 
no 
Demand greater than 15%
yes 
no 
Note: 1) It can take 10 to 30 minutes for the tank to fill depending on humidifier size.
2) Once filled it can take 5 to 15 minutes (depending on humidifier size) for a cold tank to come to a full boil.
Unit Serial #:
Unit
type:
Tag:
Voltage:
V/
ph Steam output: lb/hr
Customer/Job:
Address:
Preliminary:
Pre-start-up checklist completed? yes no 
If no, perform Pre-Start-up Checklist before starting humidifier.
Start-Up Procedure:
The prerequisites for the humidifier activating the CV valve actuator to make steam are as follows:
Controls:
Installed Controls Match Configuration yes no 
Control Setpoint: High Limit Setpoint:
Demand (Modulating Humidistat) yes no 
or
Sensed RH < Setpoint (Transducer) yes no 
The Humidifier will undergo a self-test when the power is turned on activating the LED’s and other internal components followed by a float test.
If the above listed prerequisites are fulfilled the humidifier will fill the tank, open the CV valve and begin normal operation.
Remarks:
Started by: Date of Start Up: / /
Company:
43 | Operation
Operation
44 Nortec
SETC LED Status Lights 44 Nortec SEP LED Status Lights 45 How the Humidifier Works
45 Steam Generation 46 Drains
46 Steam Distribution
47 49
Selecting an RH Setpoint Nortec SETC Humidifier Configuration
49 Navigating the Nortec SETC Software
49 Main Menu (Nortec SETC Password) 50 Service Level 51 User Defined Settings
53 Control Setting
56 Multi Unit Op. Range 57 RH Settings
59 Diagnostic Menu
60
Nortec SEP Humidifier Configuration
Operation | 44
Nortec SETC LED Status Lights
The keypad and display panel includes 3 LED’s which provide information about the humidifier’s current status.
Fault LED On
Indicates the controller has detected a
fault condition and stopped humidifier.
Check display for fault information
Service LED On
Indicates that service may be required
or that a warning condition exists.
Check display for warning information
Service LED Blinking
Indicates drain button has been pushed
and unit is draining.
ON LED On
Indicates steam is being produced.
ON LED Blinking
Indicates demand with safety loop open.
Figure 40: Nortec SETC LED Status Lights
Nortec SEP LED Status Lights
DEMAND LED On
Indicates steam is being produced.
DEMAND LED Blinking
Indicates humidifier is in standby waiting
for a demand.
SERVICE LED Flashing
Indicates the controller has detected a
fault. The flash sequence of the LED
indicates which fault has been detected.
FAULT LED On
Indicates the controller has detected a fault condition and stopped humidifier. Read Service LED’s flash sequence to
determine fault detected.
Figure 41: SEP LED Status Lights
DEMAND
SERVICE
FAULT
ON
OFF
DRAIN
45 | Operation
Humidifier Schematic
Heat Exchanger
Steam Line
Steam Distributor
CV Valve Actuator
‘P’ Trap
Tank
Float Chamber
Fill Box
Cooling to Float Chamber
Dual Fill Valve
Boiler Steam
CV Valve
Vacuum Break
Drain Outlet
Steam Trap
‘P’ Trap / Overflow
Condensate Return to
Boiler
Auxiliary Drain
Lower Mixing Box
Drain Pump
How the Humidifier Works
The Nortec SETC/P is an atmospheric steam generator that uses energy from pressurized steam flowing through a heat exchanger submerged in water to generate steam. The Nortec SETC/P is designed for air humidification via steam distributor, blower pack, or steam manifold (Nortec SAM-e).
Steam Generation
After initial start-up and tank filling the humidifier will sit in standby mode, awaiting a call for
When a call is received, the humidifier will send a signal to the electric actuator. The
Energy from the boiler steam is transferred to the fresh water tank through a heat exchanger
Figure 42: Humidifier Schematic
humidity.
actuator will open as required and the flow of boiler steam will begin.
inside of the unit. This causes the water to boil. Full boil from a cold tank can take up to 15 minutes. On Nortec SETC models, the Keepwarm feature can be activated to reduce boil time, see Idle Mode on page 52.
Operation | 46
Once the humidifier has reached full boil, the humidifier will modulate the actuator,
controlling the flow of steam into the unit. This will allow the unit to reduce its output level as the humidity levels in the space being humidifier are reached.
During the boiling process minerals are left behind from the water. The unit will occasionally
activate the drain pump to flush out some of the minerals in the water and reduce the concentration in the tank. The fill valve will also be activated periodically to replace water that is boiled off during normal operation.
When the demand to the unit ceases, the unit will close the steam valve and steam
production will stop. The unit will enter standby mode and await a call for humidity. If Keepwarm is activated (Nortec SETC only), the CV valve will be opened periodically to heat the tank.
Drains
As steam is produced minerals are left behind in the Nortec SE’s tank. The Nortec SE
performs periodic drains to reduce the amount of minerals that will precipitate as scale.
In general more frequent drains result in less maintenance. The amount of water drained to
control mineral concentration in the tank can be configured in the Nortec SETC’s software.
To cool drain water the Nortec SE activates the fill valve whenever the drain pump is activated.
Cool fill water flows down from the fill box and blends with hot tank water in the lower mixing box before being drawn into the drain pump. The drain cooling feature can be deactivated via software (see Drain Cool on page 51).
Steam Distribution
Steam generated by the humidifier may be introduced into the air in several different ways. The most common method for adding the steam into the air is to mount a steam distributor tube in a supply air duct as shown in Figure 42: Humidifier Schematic. For larger ducts or larger loads it is also common to use a steam manifold with a single steam line connection and multiple tubes for distributing the steam, see Figure 43: Nortec SAM-e Manifold. For introducing steam directly into a room, remote mounted blower packs are used see Figure 44: Remote Blower Pack.
Steam Line
The steam line between the tank steam outlet and the distributor may be Condair steam hose, copper pipe, or stainless steel pipe or tube. The Nortec SETC/P is an atmospheric steam generator so it is very important no restrictions are present in the steam line and that the steam line is sized properly to carry the full output capacity of the humidifier. It is also important to minimize the length of steam lines. See Steam Lines and Condensate Returns on page 17 for information on selecting steam lines and maximum recommended lengths.
Whenever steam is distributed condensate is formed in the distribution system and steam distributor, manifold, or blower pack. Insulating steam lines is one important way to reduce the amount of condensate formed. Steam lines must be sloped so that condensate does not collect in the lines and create a restriction to steam flow.
Condensate Return
The condensate must be collected and removed from the system so that it does not build up and leak into the duct (or room if blower pack is used). Condensate must be collected and fed to drain.
47 | Operation
Selecting an RH Setpoint
Note: The job site design may have specified a setpoint chosen specifically for the site. Refer to site documentation and where possible use setpoints specifically determined for the site.
The optimum humidity setpoint depends on the reasons that a space is being humidified. The “ASHRAE Handbook – HVAC Applications” recommends specific design relative humidities for specific applications. See also Condair publication “When You Need Humidity” (Form 124A) for more information on humidity settings.
Health and Comfort - The benefit of humidity is most pronounced for health and comfort in the 40-60% range. A humidity setting of 40-50 % is recommended for this purpose to prevent over humidifying.
Temperature Setback - In cold climates it is often necessary to reduce the humidity level in a space to prevent build up of condensation on the inside of exterior walls, windows, and trim. It is highly recommended that the temperature setback function of the Condair digital controls be used under these conditions to prevent damage from condensation. The digital control with an outdoor temperature sensor installed will automatically setback the humidity setpoint to correspond with outdoor temperature.
Duct High Limit – The duct high limit is intended to prevent saturation and wetting in duct work at high load conditions. Condair recommends a setting of 85% for the duct high limit. It may be necessary to reduce this setting If the duct work is very cold or in contact with exterior cold surfaces.
SAMe Manifold
Insulated copper
steam line. Support
so weight is not on
steam outlet.
Condensate line
‘P’ Trap
Figure 43: Nortec SAM-e Manifold
Operation | 48
Insulate steam lines
Blower Pack Blower Pack
Balance steam
line length to all
blower packs
Figure 44: Remote Blower Pack
Blower pack condensate drain and ‘P’ Trap
Provide 120 V disconnect for
blower packs
power.
Wire bl ower pack safety loop terminals in series with humidifier safety loop.
Condensate to drain
Oversize condensate line to combine multiple condensate returns
49 | Operation
5
Service Level
45 %
Nortec SETC Humidifier Configuration
Press to go
Press to
?=Press for
Press to go
Press to
Press to
down a
go left
information
up a menu
increase/
accept
menu level
/right one
about current
level
decrease
setting and
screen
warning or fault
message
value
go up a
level
Request – 100%
Idle 04/30/09 Security loop :
150 lb/hr 14:25:22 Closed
Menu
?
?
Menu
Menu
Set
Menu
Set
Main Menu
Service Level
User Defined Settings Control Settings Diagnostics
Request – 100%
Password
0335
Idle
30 lb/hr
04/30/09 14:25:22
Enter Code
Security loop:
Closed
Confirm with Set
Screen Displays
Set P
45%
45%
ESC
S et
Navigating the Nortec SETC Software
The four input buttons below the digital display are used to navigate in the Nortec SETC’s software and to enter values. The function of the four buttons changes depending on what is being displayed on the screen. In all cases 4 icons representing the functions of the buttons are shown at the bottom of the screen.
Screen Displays
Figure 45: Navigating the Nortec SETC Software
Main Menu (Nortec SETC Password)
The menu levels of the Nortec SETC are password protected to prevent configuration changes by unauthorized persons. In order to access the menu level press the button corresponding to the Menu icon and when prompted enter the password 0335.
Enter Password
Press the Menu button from any status screen. Enter the user level code 0335 using the up arrow to change the value of each digit and the right arrow to move to the next digit. Press the Set button.
Main Menu
From here you can access all user configurable settings. Select any sub-menu by using the up/down arrow buttons and pressing Set when the desired one is highlighted. Note: Do not make changes unless you are familiar with the software.
Operation | 50
500 hr
Service Reminder :500
Interrupt Operation
Tank Drain
Interrupt Operation?
(This Operation
Can Take >1 hr)
Tank PreClean
Reset Serv. Reminder
Reset Serv. Reminder
Service Level
Set No Yes Menu
Set
No
Yes
Menu
Set
No
Yes
Menu
Menu
Menu
Set
Service Level
Service Reminder : 500
Service Reminder
500 hr
500
Tank Drain Tank PreClean Reset Error History Reset Serv. Reminder
Set
Reset Error History
Reset Error History
Menu Yes No Set
The selections in the Service Level allow you to reset service reminders and the fault history. Press Set while highlighting Service Level in the Main Menu.
Service Reminder
Sets the maintenance time interval for the humidifier based on run time at 100% output. The controller will display a warning when the time expires. (Default = 500 hr)
Tank Drain
If the yes button is pressed the controller activates the drain pump and empties the tank.
Tank Pre Clean
Preparation for regular maintenance to remove loose scale that may be present in the tank.
Reset Error History
Deletes the list of errors stored in the error history. The Error History is located in the Diagnostics Menu. Resetting the error history is not normally required, but can be done after repairs to remove faults that are no longer needed.
Reset Service Reminder
Resets the service reminder after the humidifier has been serviced.
51 | Operation
Drain Cool : Off
On
Hour 23
100
On
User Defined Settings
Menu
Set
Menu
Drain Cool
On
Off
On
Smart
User Defined Settings
Drain Cool : On
BD Rate FTBD FTBD Time FTBD Hours Idle Mode Idle Time Fill Corr Drain Corr Float Ck Date Time Unit Language Contrast Leak Ck
: 25% : Off : Off : 100 : Idle Drain : 72 hr : 100% : 100% : 23:30 : 06/27/09 : 13:22 : lb/hr : English : 10 : Off
Set
Menu Set
Blowdown Rate
25%
BD Rate : 25%
Menu Set
FTBD Time
Hour 23
FTBD Time : Off
Menu Set
FTBD Hours
100
100
FTBD Hours : 100f
Menu Set
Full Tank Blowdown
Off
On
FTBD : Off
The selections in User Defined Settings allow you to configure most user configurable features available with the Nortec SETC. Press Set while highlighting User Defined Settings in the Main Menu.
Drain Cool
Selects whether drain water cooling will be performed by adding fill water to drain water. Off = fill valve not activated during drain. On = fill valve activated whenever drain pump is on, Smart = fill valve only activated with drain pump when tank is hot. (Default = Smart)
Blowdown Rate
Sets the amount of water as a
will be drained to control mineral concentration in the tank. (Default – 25%)
Full Tank Blowdown
Sets whether the tank will be periodically flushed to help flush minerals and scale. Blowdown frequency is controlled by the FTBD Hours parameter below. (Default = On)
FTBD Time
Sets the time of day when a full tank
interrupting humidifier operation during critical times. (Default = 23:30)
FTBD Hours
Sets the number of hours between full tank blow downs. Hours are accumulated on a weighted basis (1 hour at 50% demand = 0.5 hrs). (Default = 100 hr)
Operation | 52
Idle Drain
72 hr
100 %
100 %
Hour 23
Day 27
(User Defined Settings Continued)
Menu Set
Idle Mode
Idle Drain
Idle Drain
Keep Warm
Idle Mode : Idle Drain
Menu Set
Idle Time
72 hr
72 hr
Idle Time : 72 hr
Menu Set
Fill Correction
100 %
100 %
Fill Corr : 100%
Menu
Set
Drain Correction
100%
Drain Corr : 100%
Menu
Set
Float Ck
Hour 23
Minute 30
Float Ck : 23:30
Menu
Set
Date
Day 27
Month 06
Date : 27/06/09
Idle Mode
Sets what the humidifier will do
Only = Do nothing. Idle Drain = Drain the tank if there is no demand (wait time set with idle Time parameter). Keep Warm = periodically open CV valve to keep tank warm. for a demand and drain the tank if no demand (Default = Idle Drain)
Idle Time
Sets the time without demand before the Idle Drain function will drain the tank (if activated). (Default = 72 hr)
Fill Correction
Increases or decreases the length of fill valve pulses to compensate for abnormal site conditions. (Default = 100%)
Drain Correction
Increases or decreases the length of
site conditions. (Default = 100%)
Float Check
Sets the time of day when a float check to verify drains and float operation will take place. Can also disable the float check. (Default = 23:30 and On)
Date
Sets the date. Selecting Day, Month, or year takes the user to a submenu that allows the value to be increased or decreased by pressing up/down arrows. Set accepts the setting.
53 | Operation
Hour 13
lb/hr
English
10
Off
(User Defined Settings Continued)
Menu
Set
Time
Hour 13
Minute 22
Time : 13:22
Menu
Set
Unit Steam
lb/hr
lb/hr
kg/hr
Unit : lb/hr
Menu
Set
Language
English
English
French Dutch German
Language : English
Menu
Set
Contrast
10
10
Contrast 10
Menu
Set
Leak Check
Off
Off
On
Leak Ck : Off
CAUTION: Improper control configuration can result in over humidifying which can result in damage to property.
Time
Sets the time of day. Selecting Hour or Minute takes the user to a submenu that allows the value to be increased or decreased by pressing u/down arrows. Set accepts the setting.
Unit
Sets the units of measure to use for display of steam output to either lb/hr or kg/hr. (Default = lb/hr)
Language
Sets the language to use for the software menu. (Default = English)
Contrast
Adjusts the contrast of the LCD display to improve visibility under different lighting conditions. (Default = 10)
Leak check
Sets whether the controller should monitor tank level during periods of no demand. If on a fault will be generated if water level drops with no demand. (Default = Off)
Control Setting
Control Setting allow you to set the type of external controls the humidifier is connected to. In most cases the Nortec SETC humidifier is factory configured to operate with the external controls that were specified for the site. Press Set while highlighting Control Setting in the Main Menu.
Operation | 54
Source : Analog
Analog
Demand
Single CH
StandAlone
(Control Settings Continued)
Menu
Set
Control Setting
Source : Analog
REG Mode : Demand MOD Mode : Dual CH Multi Mode : Standalone CNT Type : 0-10
LIM Type : 0-10
Only present if Mod Mode set to Dual CH
Short CD : On
Short CD Tm : 30 s
Only present if Short CD set to On
Time Prop. : Off Manual Cap : 100%
Mulit Unit Op Range
Only present if Multimode set to Master or Slave
Modbus Settings Press Base : On
Supply Press. : 15 psi
Only present if Press Base set to On
RH Settings
Only present if REG Mode set to RH (P) or RH (PI)
Analog
Digital
Menu
Set
Source
Analog
Menu
Set
Regulation Mode
Demand
On/Off RH (P) RH (PI)
REG Mode : Demand
Menu
Set
MOD Mode
Single CH
Single CH
MOD Mode : Single CH
Menu
Set
Multi Mode
StandAlone
Standalone
Slave
Multi Mode : Standalone
Source
Configures the humidifier to either accept analog control signals from a humidistat or digital signals from a Building Management System
REG Mode
Configures the type of control used
proportional only internal control based on a transducer signal. RH (PI) is proportional control with an integral.
MOD Mode
Configures the humidifier to either
(control only) or dual channel (control and high limit). If an On/Off high limit humidistat is used set MOD Mode to Single CH
Multi Mode
Use Multi Mode to configure the
humidifier of a group controlled by a single control signal / transducer signal. See Multi Unit Op. Range later in this section. (Default = Standalone)
55 | Operation
0-10V
Off
0-10V
30 s
Off
100%
(Control Settings Continued)
Menu
Set
CNT Type
0-10 V 0-5 V 1-5 V
0-10 V
2-10 V 0-16 V 32-16 V 0-20 mA 4-20 mA
CNT Type : 0-10
Menu Set
Short Cycle Delay
Off
Off
Short CD : Off
Menu Set
LIM Type
0-10 V 0-5 V
0-10 V
2-10 V 0-16 V
3.2-16 V
LIM Type : 0-10V
Menu Set
Short Cycle Delay Time
30 s
Short CD Tm : 30 s
Menu Set
Time Proportioning
Off
Off
Time Prop. : Off
Menu
Set
Manual Capacity
100% 100% Manual Cap : 100%
CNT Type
Configures the Volt or amp range of the control signal connected to the humidifier
LIM Type
Configures the Volt or amp range of the high limit control signal connected to the humidifier. The type of control, VDC or mA, must be the same as that of CNT Type.
Short Cycle Delay
Sets whether the humidifier must
by the Short CD Tim parameter) whenever demand falls below the On threshold to prevent short cycling. (Defualt = Off).
Short CD Tim
Specifies the minimum time the
whenever demand drops to the off condition. It is only checked if Short CD is set to On. (Default = 30 s)
Time Prop
Sets whether the humidifier will run
demand is less than 15%. On results in the humidifier turning on and off for short periods of time to simulate low output. (Default = Off).
Manual Cap
Reduces the maximum capacity of the humidifier to a percentage of its full capacity. Use up/down buttons to increase/decrease and press Set to save the setting. (Default = 100%)
Operation | 56
Full Out : 20%
Parity : Even
On
(Control Settings Continued)
Menu
Set
Modbus Settings
Parity : Even
Timeout : 300 s Rem Disable : On
Modbus Settings
Menu Set
Pressure Based
On Off
Press. Based : On
NOTE: The Multi Unit Op. Range submenu is only displayed if the humidifier has been configured as either a Master or Slave. It is not displayed in Standalone mode.
Multi Unit Op. Range
Full Out : 20%
Zero Out
: 0%
Menu
Set
Multi Unit Op. Range
The Nortec SETC can be configured to network up to sixteen (10) humidifiers (or equivalent of 10,500 lb/hr) using a master slave configuration. To operate the Nortec SETC in a staged modulation system;
The humidifiers must be connected in parallel (daisy chained) using the linkup terminal (J2a)
on the Nortec SETC driver board (See Staged Modulation Wiring on page 31).
One humidifier must be designated the master and all others as slave units (see Multi Mode
on page 54 for software configuration). The master unit must be the unit to which external controls / transducers and safety loop are connected.
Each humidifier in the system including the master must have the range of demand signal in
which it will operate configured (see below). Example, for four humidifiers with equal capacity set the master to operate between 0% and 25%, set the fist slave for 26% to 50%, set the second slave for 51% to 75%, and set the third slave for 76% to 100%.
The Multi Unit Op. Range submenu is used to configure the humidifier’s operating range when Multi Mode in the User Defined Settings menu is set to either Master or Slave. The menu is not displayed if the humidifier is set to Standalone operation. Access the Multi Unit Op. Range submenu by pressing the menu button while Multi Unit Op. Range is highlighted in the Control Settings menu.
Multi Unit Op. Range
Multi Unit Op. Range
Full Out sets the system demand at
its full capacity. Zero Out sets the system demand at which the humidifier should shut off.
Modbus Settings
Allows configuration of
Selecting an item brings up a screen that allows the value to be changed by using the up/down arrow keys. Rem Disable allows the user to turn the humidifier on if it has been remotely disabled.
Pressure Based
Configures the humidifier to use steam supply pressure to calculate system output. If set to off the output displayed is based on a supply pressure of 15 psi.
57 | Operation
15 psi
40% RH
15% RH
CNT Set-P : 40% RH
5 min
(Control Settings Continued)
RH Settings
CNT Set-P : 40%
CNT Band : 15% RH CNT Itime : 5 min
LIM Set-P : 80% RH LIM Band : 15% RH LIM Damp : 5 s
Only present if MOD Mode is set to Dual CH
RH Alerts : On
RH High : 75% RH RH Low : 33% RH
Only present if RH Alerts is set to On
RH Settings
Menu Set
Menu Set
Supply Pressure
15 psi 15 psi
Supply Press. : 15 psi
Menu Set
Control Set Point
40% RH
40% RH
CNT Set-P : 40%
Menu Set
Control Band
15% RH
CNT Band : 15% RH
Note: The RH Settings menu selection will only be displayed in the Control Settings menu if REG Mode is set to RH (P) or RH (PI).
Menu Set
Control Integral Time
5 min
CNT Itime : 5 min
Supply Press
Sets the steam supply pressure for the humidifier to us in displaying its steam output. It is only displayed if Press Based is set to On. (Default = 15 psi)
RH Settings
The RH Settings submenu is used to adjust setpoint, the proportional band, and the integral time if REG Mode is set to RH (P) or RH (PI) and the humidifier is connected to humidity sensors. Access the RH Settings submenu by pressing the menu key while RH Settings is highlighted in the Control Settings menu.
CNT Set-P
Sets the humidity setpoint value. The humidifier will attempt to maintain this humidity level in the space where the control transducer is installed.
CNT Band should not normally be changed. The CNT Band setting
humidifier will modulate between 0 and 100% output. (Default = 15%)
Int Time should not normally be changed. Int Time adjusts the
corrects for proportional control error. It is only displayed if REG Mode is set to RH (PI) (Default = 5 min)
Operation | 58
80% RH
15% RH
5 s
On
75% RH
33% RH
(RH Settings Continued)
Menu Set
Limit Set Point
80% RH
LIM Set-P : 80%
Menu Set
Limit Band
15% RH
LIM Band : 15% RH
Menu Set
Limit Damping
5 s
LIM Damp : 15% RH
Menu Set
RH Alerts
On
On
RH Alerts : On
Menu Set
RH High
75% RH
RH High : 75%
Menu Set
RH Low
33% RH
RH Low : 33% RH
LIM Set-P
Sets the duct high limit setpoint
the high limit the output of the humidifier will be throttled back to prevent wetting the duct. (Default = 80%)
LIM Band
Should not normally be changed. The
within which the humidifier will throttle down the humidifier output from 100 to 0%. (Default = 15%)
Limit Damping
Sets the number of seconds the
band before output is throttled down. (Default = 5 s)
RH Alerts
Sets whether the humidifier will
above or falls below configured limits. (Default = Off)
RH High
Sets the RH level above which the
is generated. Warning is only generated if RH Alerts is set to on.
RH Low
Sets the RH level below which the
is generated . Warning is only generated if RH Alerts is set to on.
59 | Operation
Fault History
Diagnostic Menu
Menu
Menu
Set
Diagnostic Menu
Fault History
Service History Output Test Remote Test
Fault History
04.14.07 21:48 E19A
03.20.09 02:35 E19A
Set
Menu
Set
Service History
Service History
04.21.07 09:10
03.21.09 10:10
Menu
Set
Output Test
Output Test
Inlet Valve: Off
Menu Set
Remote Test
Remote Test
Steam Relay: Off
The Diagnostic Menu provides a historical list of errors and service recorded by the humidifier’s software as well as providing the ability to manually activate humidifier components for troubleshooting purposes. Press Set while highlighting Diagnostic Menu in the Main Menu.
Fault History
Displays a list of faults which the controller has recorded. It shows the date and time at which the faults occurred. Refer to Table 13: Troubleshooting Warnings and Faults for meaning of codes and suggested actions to correct faults.
Service History
Displays a list of service that has been performed on the humidifier. It displays the date and time of service.
Output Test
Provides a means for activating all humidifier components (inlet valve, drain pump, etc.) for diagnostic purposes. Components can be activated one at a time. Scroll to component to be tested using up/down buttons, press Set once to activate, press again to turn off.
Remote Test
Provides a means for testing of remote fault relays to confirm they are operating correctly. Relays can be activated one at a time. Scroll between relays with up/down arrow buttons and press Set once to turn on relay, press again to turn it off.
Operation | 60
SEP Humidifier Configuration
Caution: Never adjust jumpers other than those listed in this section. Other jumpers are factory set and must not be changed.
The Nortec SEP is factory configured to operate under most conditions without the need for any changes to its configuration. If required several settings can be made using jumpers on the Nortec SEP’s control board. The blowdown of the Nortec SEP can also be adjusted by using a potentiometer on the Nortec SEP’s control board. See Figure 46: Nortec SEP Control Board Jumpers for location of jumpers and the blowdown adjustment potentiometer.
Note: Condair recommends not making any configuration changes unless they are required
and that any changes to the Condair SEP’s settings be performed by a qualified technician.
Blowdown Adjustment Potentiometer
Jumpers
Blowdown Adjustment
Figure 46: Nortec SEP Control Board Jumpers
J11 to J18
Jumper J10
25%
Sets the amount of water as a percentage of steam produced that will be drained to control mineral concentration in the tank. The blowdown adjustment potentiometer is located on the side of the control board as shown in Figure 46. It can adjust the blowdown between 0% and 50% of steam produced. (Factory setting = 25% blowdown).
0% 50%
Note: 0% blowdown should never be used even with Deionized
water. Minimum recommended setting is 5%.
61 | Operation
On/Off or Modulating Control (J10)
Resulting Control
J11
J12
J13
SEP 50/100
0 0 0
SEP 175
1 0 0
SEP 250
0 1 0
SEP 375
1 1 0
SEP 525
0 0 1
SEP 750
1 0 1
SEP 1050
1 1 1
Resulting Control
J14
J15
No Full Tank Blowdown
1
1
96 hours between FTBD
0
0
48 hours between FTBD
1
0
24 hours between FTBD
0
1
The Nortec SEP’s output can be controlled by either an On/Off humidistat or a modulating humidistat. To set the Nortec SEP to operate with a modulating humidistat remove Jumper J10. (Factory setting = jumper removed, modulating operation)
J10 Removed– Modulating operation, the controller monitors the demand signal on terminal point 4 of the control terminal strip and adjusts humidifier output to match it.
J10 Installed - The Nortec SEP is configured for On/Off operation. The controller will ignore any modulating signals even if they are connected.
Nortec SEP Model (J11 to J13)
The Nortec SEP model is configured using Jumper 11 to 13. The jumper setting is configured at the factory and should not be adjusted in the field.
Table 8: SEP Model Configuration
Full Tank Blowdown (J14 and J15)
The Nortec SEP can be configured to periodically drain the tank to help flush minerals and scale. Jumpers 14 and 15 control blowdown frequency. Hours are accumulated on a weighted basis (1 hour at 50% demand = 0.5 hrs). (Default = J14 and J15 installed, no full tank blowdown)
Table 9: Full Tank Blowdown Jumper Configuration
Modulation Offset (J16)
The Nortec SEP controller can be configured to work with a modulating humidistat with 4-20 mA or 2- 10 VDC output. Modulation offset can be configured with jumper 16. (Factory setting = Jumper removed, 0-10 VDC or 0-20 mA control signal)
J16 Removed – Controller is configured for a 0-10 VDC or 0-20 mA control signal.
J16 Installed – Controller is configured for a 2-10 VDC or 4-20 mA control signal.
Note: For mA control a 500resister is required between terminals 3 and 4 on the low voltage
control terminal.
Operation | 62
Resulting Control
J10
J16
On/Off
1
No Affect
Modulating 0-10 VDC or 0-20 mA
0
0
Modulating 2-10 VDC or 4-20 mA
0
1
Table 10: Control Jumper Configuration
Drain Water Cooling (J17)
The Nortec SEP can be configured to cool drain water by activating the fill valve whenever the drain pump is activated. To disable drain water cooling remove jumper J17. (Factory setting = jumper installed, drain water cooling active)
J17 Removed – The fill valve is not activated together with the drain pump.
J17 Installed – The fill valve activated together with the drain pump to cool drain water.
Float Check (J18)
Whenever the Nortec SEP is first powered it performs a float check to ensure water level detection is working properly. The float check can be deactivated via jumper 18. (Factory setting = jumper removed, float check is performed)
J18 Removed – A float check is performed whenever the Nortec SEP is powered on.
J18 Installed – A float check is not performed whenever the Nortec SEP is powered on.
63 | Maintenance and Servicing
Maintenance and Servicing
64
69 Maintenance Shutdown and Extended
70 Nortec SETC/P Maintenance Checklist
Required Maintenance
64 Service Warning / Fault 65 Maintenance Schedule 66 Cleaning the Tank 67 Cleaning the Heat Exchanger 68 Cleaning the Float Chamber
68 Resetting Service Reminder
Shutdown
Maintenance and Servicing | 64
Required Maintenance
Caution: Power to the humidifier should always be turned off using the dedicated external disconnect before removing the door or side panel, or before doing any service work on
the humidifier.
Service Warning / Fault
The Nortec SETC controller includes a timer that monitors the humidifier’s operating hours and generates a warning when service is required. Optimal maintenance time is dependent on water supply conditions and humidifier usage. The default factory service reminder is equivalent to 500 hours of operation at 100% output. Failure to perform maintenance when the service warning is displayed will cause the unit to lock out. Condair is not responsible for any damages resulting from, or attributed to not performing required maintenance. (See Manufacturer’s Warranty).
Service LED On
+
HMW - Humidifier
Maintenance
=
Service timer has
expired and humidifier
needs maintenance
+ 200 Hours
Fault LED On
HMF - Humidifier
Service timer + 200 hours has passed. Maintenance
must be performed.
+
Maintenance
=
Humidifier has
shut down.
Request – 68%
Warning
HMW - Humidifier Maintenance
Humidifying 134 lb/hr 04/30/09 14:25:22 Security loop: Closed
Menu
Request – 68 %
Fault
HMF - Humidifier Maintenance
Fault 34 lb/hr 04/30/09 14:25:22 Security loop: Closed
Menu
Warning
When the software determines that the service timer has elapsed it first
displays a warning and turns on the
?
yellow service LED. The humidifier will continue to operate for another 200 hours after the warning is displayed.
Fault
After 200 hours the humidifier will display a fault and shut down.
?
If maintenance is not possible the humidifier can be temporarily put
back into service by turning the humidifier off and on. The humidifier will run for another 200 hours.
This reset can be repeated 4 times after which the humidifier will not run until the Reset Service Reminder function is entered in the software’s service level.
Figure 47: Service Warning / Fault
65 | Maintenance and Servicing
Maintenance Schedule
Item
30 Days
After
Start-up
When
Service
Light is
Lit
End of
Season
What to Do
Tank



1. Remove service door and inspect for scale.
2. Remove scale deposits from tank walls using plastic scraper.
3. Collect scale deposits from tank bottom using wet vac or scraper and bucket.
Heat Exchanger



1. Remove service door and inspect for scale.
2. Remove scale deposits from tank walls using plastic scraper.
3. Collect scale deposits from tank bottom using wet vac or scraper and bucket.
4. Once per season remove heat exchanger, clean, and inspect.
Gaskets
 

1. Inspect for cracking or damages.
2. Remove any scale deposits before re-installing.
Float Chamber



1. Remove float chamber, and float chamber lid.
2. Clean any scale deposits from walls and float magnets.
3. Re-install magnets.
Heater System

1. Inspect for dust and dirt build-up.
2. Blow clean with compressed air.
Fill System
 
1. Inspect for leaks at float chamber and fill valve.
Drain System
 
1. Inspect for leaks at drain pump, auxiliary drain, and
internal vacuum break.
Steam Trap

1. Inspect for deposits and float operation.
2. Replace thermal disk if necessary.
3. Clean all ports and inside of trap body.
Wye Strainer

1. Remove service plug and clean out collector screen.
Steam Valve

1. Inspect actuator operation.
2. Perform leakage test to ensure that valve is closing properly.
Boiler Pressure

1. Inspect Pressure Reducing Valve operation. Pressure must not exceed 15 psig
Note: After performing the first maintenance on the Nortec SETC it is possible to increase or decrease the service period to match water conditions. If the tank, heat exchanger, and float chamber are relatively clean and free of scale increase the service period. If there is a lot of scale and it is difficult to remove then reduce the service period and consider increasing the blow down setting. (See Nortec SETC Configuration)
Regular maintenance is required to keep the Nortec SE Series humidifier operating at its peak capacity and efficiency. Follow the maintenance schedule shown in Table 11: Nortec SE Humidifier Maintenance Schedule to ensure long humidifier life and peak performance.
Table 11: SE Humidifier Maintenance Schedule
Maintenance and Servicing | 66
procedure in the next section.
Cleaning the Tank
Warning
Disconnect main power at the external disconnect before any servicing. Tank and piping may be hot, take care when handling.
Avoid using de-scaler chemicals or caustic chemical which can damage the tank or
heat exchanger.
The tank, heat exchanger, and float chamber should be cleaned at least once per season to remove scale and mineral deposits which can reduce unit efficiency. In areas with high mineral content in the water, cleaning should be more frequent.
1 Follow Maintenance Shutdown and Extended Shutdown procedure on page 69. Give the
unit some time to cool down to avoid injury when servicing.
2 Remove the cabinetry covers on the front (all models) and top (Nortec SE 525 – 1050
models) by removing the Phillips type screws and lifting the covers.
3 Remove the tank maintenance doors on the front (all models) and top (Nortec SE 525 –
1050 models) by applying anti seize compound to nuts and using 1/2 in. socket. Remove excess anti seize compound.
4 Inspect the tank door gaskets. Remove any scale from the gaskets, the tank door gasket
surface, and tank gasket surface.
5 Using a plastic scraper, such as those used for car windshields, remove scale adhered to
tank walls and visible portions of the heat exchanger. Remove this scale from the unit. A wet vacuum can be used for this purpose.
6 Inspect the heat exchanger. If significant scale build-up has occurred, follow the cleaning
Top Cover
Front Cover
Gaskets
Tank Door Locknuts. Apply anti seize compound to remove. Do not crush gasket. Max 5 ft-lbs torque.
Top Maintenance Door (Nortec SE 525 - 1050 Only)
Front Maintenance Door
Figure 48: Tank Access For Cleaning
67 | Maintenance and Servicing
7 Reinstall the tank door gaskets and tank doors. When tightening the tank door nuts, take
care not to over tighten. The tank door nuts should only be torqued to 5 ft-lbs to prevent crushing the gasket underneath.
Cleaning the Heat Exchanger
1 Follow Maintenance Shutdown and Extended Shutdown procedure on page 69. Give the
unit some time to cool down to avoid injury when servicing.
2 Remove the cabinet cover on the right side by removing the Phillips type screws and lifting
the covers.
3 Disconnect the union that transports steam into the heat exchanger and remove the F&T
trap by disconnecting the two unions that hold it in place.
4 Apply anti seize compound to heat exchanger nuts and remove with 1/2 in. socket.
Remove excess anti seize compound.
5 Remove the heat exchanger(s) by pulling on the handle and sliding the heat exchanger out
of the unit.
6 Note: Heat exchangers are heavy, use proper lifting technique when removing them. It is
helpful to have an assistant help remove the heat exchanger.
7 Inspect the heat exchanger gaskets. Remove any scale from the gaskets, the heat
exchanger gasket surface, and tank gasket surface.
8 Using a plastic scraper, such as those used for car windshields, remove scale adhered to the
heat exchanger.
9 Reinstall heat exchanger gaskets and heat exchanger. When tightening nuts, take care not
to over tighten. Only torque nuts to 5 ft-lbs to prevent crushing the gasket underneath.
Steam Connection Union
Heat Exchanger Gasket
Cabinet Cover
F&T Trap
Union
F&T Trap
F&T Trap
Union
Heat Exchanger
Figure 49: Heat Exchanger Removal
Heat Exchanger Locknuts Apply anti seize compound to remove. Do not crush gasket. Max. 5 in-lb torque
Maintenance and Servicing | 68
Cleaning the Float Chamber
Caution: Do not reverse
float chamber hoses
To tank
To fill valve
Squeeze tabs
to remove assembly
from humidifier
NOTE: If the “Service Reminder” is not reset the humidifier may fault out on the Humidifier Maintenance Fault despite the fact that the maintenance has been performed.
1 Follow Maintenance Shutdown and Extended Shutdown procedure on page 69. Give the
unit some time to cool down to avoid injury when servicing.
2 Remove the cabinet covers on the front of the unit by removing the Phillips type screws and
lifting the covers.
3 Disconnect the electrical connection to the float board. 4 Remove the hose clamps and the hoses from the top and bottom of the float chamber. 5 Remove the reusable tie-wrap from the float chamber by inserting a small screw driver into
the top of the buckle.
6 Squeeze both sides of the mounting bracket to release the float chamber from the slots on
the support bracket.
7 Use a screw driver to remove the 3 screws from top of the float chamber and remove the lid.
Using a small brush or plastic scraper remove any scale from the inside of the chamber.
8 Re-installation is the reverse of removal.
Resetting Service Reminder
After completing maintenance of the Nortec SETC reset the service reminder by following the procedure outlined in Reset Service Reminder on page 50.
Figure 50: Float Chamber Cleaning
69 | Maintenance and Servicing
Maintenance Shutdown and Extended Shutdown
Note: As long as the Nortec SETC is powered, it will automatically drain the tank when there has not been a call for humidity for an extended period of time. This feature will reduce or prevent the possible accumulation of algae and bacteria growing in the tank. The tank will remain empty until there is a call for humidity at which time the fill valve will open and refill the humidifier tank. The unit will go through its normal
process for optimum operation.
The following procedure should be followed to shut down the humidifier for maintenance or should it be required to disconnect power to the humidifier for a period of extended shut-down.
When performing maintenance, the Nortec SETC models include a Tank Pre-Clean feature. Tank Pre- Clean will activate the drain pump to flush out some of minerals in the bottom of the tank, then refill partially with cold water to cool the tank, and finally drain the contents of the tank. This cycle will cool the tank, as well as flush out some deposits.
1 Nortec SETC - Activate Tank Pre-Clean as described in Tank Pre Clean on page 50 or
press and release the drain button to simply drain the tank. Nortec SEP - Turn the On/Off/Drain switch to Drain.
2 Nortec SETC - If preclean was activated wait until the LCD display indicates the preclean is
complete otherwise wait until no water is coming out from the drain. Nortec SEP wait until there is no water coming out from the drain.
3 When the tank has completed draining, turn the main power switch to “Off”. Also, shut off
the electrical power at the disconnect.
4 Close the manual shut-off valve on the steam supply. 5 Close the manual shut-off valve on the water supply line. 6 Briefly open the manual valve on the auxiliary drain line (if applicable) to drain any remaining
water.
7 The unit can now be serviced (if maintenance is being performed), or “stored” in this state
until the next humidification season. Alternatively, Nortec SETC models can be left in 3 day drain state during an “off-season”.
8 To restart the unit follow Start Up Procedure on page 36.
Maintenance and Servicing | 70
Nortec SETC/P Maintenance
Checklist
Model #:
Tag:
Serial
#:
System Check
HMW (Maintenance Warning ) HMF (Maintenance Fault) Other warnings or Faults shown in display / LED’s? No Yes
(See Troubleshooting Chapter for actions to address warnings and faults if present)
Clean Tank / Heat Exchanger / Float Chamber
Tank drained. Disconnect open, On/Off switch to Off 
Water shut off and manual steam valve closed, cabinet covers removed. Anti seize compound applied to tank maintenance door nuts. Maintenance doors removed (front and top of 525+). Tank maintenance door gaskets cleaned and in good condition. Scale removed from tank. Heat Exchanger has scale and needs cleaning No  Yes 
If Yes
Steam supply and condensate unions disconnected Anti seize compound applied and heat exchanger nuts removed Heat exchanger removed. Heat exchanger gaskets cleaned and in good condition. Heat exchanger cleaned with plastic scraper. Heat exchanger reinstalled. Nuts torque to 5 ft-lb 
Steam supply and condensate unions reconnected. Tank maintenance doors reinstalled Nuts torque to 5 ft-lb Float Chamber removed inspected and cleaned 
General Inspection
Electrical wiring not loose and in good condition, Steam hoses and steam lines in good condition / No kinks in hose, No Signs of water leaking around humidifier, steam line, condensate returns, Cabinet covers replaced, water shut off valve opened, manual steam valve opened, On/Off
switch to On, Disconnect Closed 
Nortec SETC only - “Reset Service Reminder” in Software, (Password 0335, Service Level) 
 
Inspected by: Date of inspection: / /
Company:
71 | Troubleshooting
Troubleshooting
72
73
76 Nortec
Organization of Troubleshooting Chapter
72 Troubleshooting Requirements
General Troubleshooting
73 Humidifier 74 Steam Distributors 74 Nortec SAM-e 75 Blower Pack
75 Digital Humidistat
SETC Warnings and Faults
76 Warnings
76 Faults
76 Clearing a Fault
82 Nortec SEP Faults
82 Faults
82 Clearing a Fault
83 Nortec SETC Wiring Diagram 84 Nortec SEP Wiring Diagram
Troubleshooting | 72
Organization of Troubleshooting Chapter
NOTE: Most humidifier faults are not caused by faulty equipment but rather by improper installation. A complete fault diagnosis always involves a thorough examination of the entire system. Often, the steam hose connection has not been properly executed, or the
fault lies with the humidity control system.
CAUTION: Be aware, when troubleshooting, that the humidifier is powered by high voltage and pressurized steam. Familiarity with both good practices and wiring of the humidifier is recommended. Any troubleshooting that requires opening the cabinet should be done
by qualified personnel.
The troubleshooting chapter is broken down into 2 sections.
General Troubleshooting Deals with troubleshooting incorrect humidifier operation,
steam line and plumbing issues without any control software warnings or faults.
Humidifier Warnings and Faults Deals with warning and error messages that are generated
by the humidifier’s control software.
Troubleshooting Requirements
Ensure the installation meets the installation requirements outlined in the Installation
Chapter of this manual.
Familiarize yourself with the operation of the humidifier by reading the Operation Chapter of
this manual.
Wiring diagram specific for your humidifier is installed on the inside of the humidifier door. A
generic copy of the Nortec SETC and Nortec SEP wiring diagram is also included at the end of this chapter for reference purposes.
When contacting your local representative or Condair for troubleshooting assistance,
please ensure the serial number has been obtained for reference purposes.
73 | Troubleshooting
General Troubleshooting
Symptom
Cause
Corrective Action(s)
Nothing happens when On/Off switch is turned on.
1 Fuse blown
1 Check inline fuse in yellow housing
between transformer and driver board. Check and replace fuse on driver board.
2 Incorrect or no Voltage
2a Check voltage against spec label and
correct.
2b Check disconnect and insure
humidifier is getting power.
3 Step Down Transformer not
outputting 24VAC
3 Replace the transformer
Humidifier will not humidify or not reaching RH setpoint
1 Safety loop open
1a Check if green led is flashing on the
humidifier’s display.
1b Check if there is 24 VAC at terminal
2.
1c Check wiring and operation of On/Off
devices connected to terminal 1 and
2. Ensure they are closing when they should be.
2 High limit limiting output
2 Check if the high limit is installed too
close to the humidifier and if it is operating correctly.
3 No signal on Channel 1
3 Check voltage between terminal 3
and 4. For demand configuration 15% of full scale signal must be present for humidifier to start. For transducer configuration the signal must be lower than setpoint for the humidifier to start.
4 No signal on Channel 2
(For units configured for dual channel operation).
4 Check voltage between terminal 5 and
3. For demand configuration 15% of full scale signal must be present for humidifier to operate. For transducer configuration the signal must be lower than setpoint for the humidifier to start..
5 Capacity has been manually
limited
5 Check Manual Capacity on status
screens. Adjust “Manual Cap” in the “Control Setting” menu if necessary.
Humidifier has faulted or has a warning
1 Software has detected an
abnormal condition
1 Refer to Table 13troubleshooting
warnings and faults.
The following section provides general guidelines for troubleshooting the Nortec SETC/P humidifier and auxiliary components. For detailed troubleshooting information refer to the manuals that were provided with the auxiliary equipment, to Table 13: Troubleshooting Warnings and Faults, and to Table 14: Troubleshooting Nortec SEP Faults later in this chapter.
Humidifier
Table 12: General Troubleshooting
Troubleshooting | 74
Steam Distributors
Symptom
Cause
Corrective Action(s)
Distributor spitting out water
1 Distributor not level
1 Use support at end o distributor to
ensure it is level.
2 “P” Trap too close to distributor
2 “P” Trap must be a minimum of 12 in
(30 cm) below the distributor to ensure flow. Relocate if required.
3 Condensate line not sloped
sufficiently
3 Sufficient slope to insure flow is
required. Reinstall if required.
4 Trap blocked
4 Check that water flows through trap.
Clear out if blocked.
5 Condensate line double trapped
5 Condensate lines must not have two
traps in sequence. This can cause an air lock and prevent water draining.
6 Steam line not insulated
6 If steam line is long condensate build
up could overload distributor condensate port. Insulate line to improve efficiency and install additional condensate traps as required.
Condensation in duct
1 Installation clearances not
observed
1 Refer to distributor installation
manual for required clearances. Relocate distributor if required.
2 Design conditions changed
2 Check supply air temperature and
humidity to determine if conditions have changed.
3 High limit not functioning
3 Check setting and operation of high
limit. Replace if defective.
4 Air proving not installed or not
working
4 Check that the humidifier will only
operate when there is air moving in the duct.
5 Improper location of high limit
5 Check that high limit is installed
where it can detect high duct humidity.
Symptom
Cause
Corrective Action(s)
Nortec SAM-e spitting out water
1 “P” Trap too close to SAM-e
1 “P” trap must be at least 12 in (30
cm) below header. Relocate if required.
2 Condensate line not sloped
sufficiently
2 Ensure line is sloped sufficiently to
carry condensate produced.
3 Steam line not insulated
3 If steam line is long condensate build
up could overload the Nortec SAM-e condensate port. Insulate the steam line to improve efficiency and install condensate traps as required.
SAM-e
75 | Troubleshooting
Symptom
Cause
Corrective Action(s)
Nortec SAM-e Grommet leaks
1 Distributor tubes not seated
properly
1 Push distributor tubes down until
support washer is resting on rubber grommet.
2 Grommet Damaged
2 Replace any damaged grommets
Symptom
Cause
Corrective Action(s)
Blower not operating
Note: Blower pack does not come on unless the humidifier is producing steam.
1 No power to blower pack
1a Check power connection.
1b Check blower pack fuses
2 On/Off Thermostat not closing
2 Check wiring to thermostat replace if
it does not close when it is exposed to steam.
Symptom
Cause
Corrective Action(s)
Humidistat Reading incorrectly
1 Sensor out of calibration
1 Check reading against known
reliable instrument. If out of calibration it can be field calibrated ±10%. Press buttons together until calH appears on the display. Press to display the current calibration trim. Adjust using  buttons. Press button when done.
2 Improper sensor location
2 Check that the humidistat is
positioned in a location representative of room humidity.
3 Exposed to draft or heat source
3 Check that heat/cold fluctuations,
drafts, sunlight, doors, or vents are affecting the reading.
4 No vapour barrier
4 Insure drafts cannot affect reading
by ensuing vapour barrier is in place and working.
Blower Pack
Digital Humidistat
Troubleshooting | 76
Nortec SETC Warnings and Faults
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
CLF
Clock Fault
Red
Controller system clock
failure.
1 Software has detected
a hardware problem with main control board
1 Restart humidifier, if
error occurs within 1 minute replace main control board. If error does not occur then primary power fluctuation may be the cause.
DCF
Drain Ck Fault
Red
The drain pump is activated but water level has not decreased
1 Drain blocked
1 Check water flow at air
gap when drain activated. Flow should be > 5 gal (20 l) / min.
2 Pump not working
2a Check wiring to pump.
2b Activate pump with
diagnostic output test and verify pump runs and drains water.
The self-diagnostic system built into the SETC is continually monitoring the operation of the humidifier.
Warnings
When problem symptoms are detected, the Nortec SETC will attempt to take self-corrective
actions to try to correct the problem. A warning is displayed on the screen for information purposes and the humidifier continues to operate.
If the condition which generated the warning is eliminated the warning is cleared from the
display.
Faults
If the humidifier is not able to self correct a problem symptom it will if necessary respond by
shutting itself down.
When this occurs the humidifier illuminates the red “Fault” LED, shuts off the signal to the
CV valve actuator, and activates the “Error” relay of the remote relay board.
Clearing a Fault
Check the fault message that the humidifier is displaying and take any necessary actions to
correct the cause(s) as outlined in Table 13, Troubleshooting Warnings and Faults.
Power cycle the humidifier with the On/Off switch waiting 3 seconds between turning it off
and on.
Table 13: Troubleshooting Warnings and Faults
77 | Troubleshooting
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
DCF
(Cont)
3 Floats stuck
3a Watch float board lights
while manual drain is activated. Verify lights activate in sequence
3b Remove float chamber
and check for scale
FCF
Fill Check Fault
Red
The fill valve has been active for an extended time without increasing a float level.
1 Water supply off or
inadequate
1a Ensure water line is
open and that adequate water supply and pressure is available.
2 Fill valve strainer
blocked
2a Disconnect water
supply line and remove strainer. Clear if obstructed.
3 Fill Valve not activating
3a Check wiring to fill
valve.
3b Activate fill valve with
diagnostic output test. Verify water is flowing when activated.
4 Float board not
detecting water
4a Check wiring to float
board.
5 Manual drain switch on
or auxiliary drain open.
5a Check that manual
drain switch is not on.
5b Check that auxiliary
drain valve is closed.
FIF
Float Inconsist.
Red
On startup, the unit registers that the float levels do not increase logically from 1 to 5
1 High water flow from
fill valve to float chamber cooling.
1 Check flow from fill
valve hose connected to float chamber. Is only a trickle. If not check hose is connected to correct side of fill valve or if orifice is missing in fill valve.
2. Float chamber or board not in place
2 Check that float board
is properly installed in plastic support , that tie wrap is in place, and that float reservoir is in place.
3 Float level sensor is
malfunctioning.
3 Squeeze bottom hose
from float chamber and activate fill valve using diagnostic output test. Watch for proper light sequence. Replace assembly if sequence is incorrect.
Troubleshooting | 78
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
FLF
Float Level
Red
More than one Float Level is registering at the same time
1. Float chamber or board not in place
1 Check that float board
is properly installed in plastic support , that tie wrap is in place, and that float reservoir is in place.
FLF
(Cont)
2 Float level sensor is
malfunctioning.
2 Squeeze bottom hose
from float chamber and activate fill valve using diagnostic output test. Watch for proper light sequence. Replace assembly if sequence is incorrect.
FTF
Fill Fault /
Warning
Red
The fill valve has been active for an extended time without reaching level 1.
1 Water supply off or
inadequate
1a Ensure water line is
open and that adequate water supply and pressure is available.
2 Fill valve strainer
blocked
2a Disconnect water
supply line and remove strainer. Clear if obstructed.
FTW
3 Fill Valve not activating
3a Check wiring to fill
valve.
3b Activate fill valve with
diagnostic output test. Verify water is flowing when activated.
4 Float board not
detecting water
4a Check wiring to float
board.
5 Manual drain switch on
or auxiliary drain open.
5a Check that manual
drain switch is not on.
5b Check that auxiliary
drain valve is closed.
HMF
Maint. Fault /
Warning
Red
The Humidifier Maintenance interval and 72 hour window for cleaning has expired
1 Humidifier requires
maintenance
1 Perform humidifier
maintenance as described Maintenance Schedule on page 65
HMW
Yel
The preset service interval time has expired.
2 Service reminder not
reset after maintenance
2 Reset service reminder
as described in Reset Service Reminder on page 50
KWF
Keep Warm
Fault
Red
Keep Warm activated but tank temperature has not increased within time allotted
1 Tank temperature
sensor not detecting warm tank.
1a Check tank to see if hot
(caution).
1b Check wiring to tank
temperature sensor.
1c Check if sensor closed
when tank is hot.
79 | Troubleshooting
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
KWF
(Cont)
2 No steam supply to
humidifier.
2a Check that isolation
valve is not closed.
2b Check if boiler steam is
available.
2c Check if CV valve opens
using diagnostic output test.
3 Condensate not
draining from heat exchanger.
3a Check that F&T trap is
allowing condensate to drain.
LKF
Leak Fault /
Warning
Red
Float level has dropped multiple times while no steam is being produced.
1 Steam leaking through
CV valve
1a CV valve actuator not
adjusted. Follow Figure 11: CV Valve Actuator Installation on page 16.
1a CV valve defective.
Replace CV valve.
LKW
2. Auxiliary drain is leaking.
2a Check that auxiliary
drain valve is closed and is not leaking.
3. Tank or fittings are leaking.
3a Check for leaks from
tank, tank covers, and fittings.
LMI
Limit Instable
Limit signal Is not stable.
1 High limit humidistat
too close to steam distributor
1 Locate the high limit
humidistat a minimum of 10 feet (3 m) from the distributor.
2 High limit humidistat
setpoint too low
2 Adjust the high limit
setpoint to 85% or more.
3 Improper Proportional
and Integral settings in control
3 Adjust proportional and
integral settings to reduce swings in demand signal.
4 Defective control
4 Replace defective
control
MEM
Flash R/W Fault
Red
Controller Memory failure
1 Software has detected
a hardware problem with main control board
1 Restart humidifier, if
error occurs within 1 minute replace main control board. If error does not occur then primary power fluctuation may be the cause.
MTW
ModBus
Timeout
No Modbus signal
1 Loose connection
1 Check connections and
polarity of wires.
2 Incorrect Modbus
address
2 Check that Modbus
address of humidifier matches that of master.
Troubleshooting | 80
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
MTW
(Cont)
3 Humidifier configured
for Modbus but not connected to network
3 Configure controls
correctly in “Control Setting” level of software (see Operation Chapter).
4 Improper wire used
4 Use 120 Ohm
impedance shielded twisted pair cable.
5 Noise preventing
humidifier from detecting signal.
5 Eliminate source of
noise causing interference.
NSW
No Signal
Warning
No communication is detected from Master unit. (This unit is set up as slave)
1 Improper wiring
1 Check wiring
connections, polarity, and type of wire used. (See Staged Modulation Wiring (SETC Only) on page 31)
RDW
Remote
Disabled
The unit has been remotely disabled through modbus communication or Nortec Online.
1 Network signal
received by humidifier to shut down.
1 Normal operation for
humidifier on network control Contact network administrator to enable humidifier.
RHW
Rh High
Warning
The measured RH is above the RH High alarm setting.
1 Setpoint higher than
RH alarm setting
1 If the humidifier is still
operating then check and adjust setpoints.
RLW
Rh Low
Warning
The measured RH is below the RH Low alarm setting.
1 Humidifier not running
1 Check why humidifier is
not running and put it into operation.
2 Setpoint lower than RH
low alarm setting
2 Check and adjust
setpoints.
RMW
Rh Limit Warning
Operation is interrupted until an input higher than 3% is received.
1 Sensor not powered
1 Use multimeter to
check that sensor is powered.
2 Sensor not wired
correctly
2 Check wiring is secure
and wired correctly per instructions in installation chapter.
3 Defective sensor
3 Check if sensor is
outputting corresponding to RH. If not replace the sensor.
4 RH less than 5%
4 RH less than 5% are
interpreted as a broken sensor. Contact Condair Representative for recommendation.
81 | Troubleshooting
Code
Display
Message
LED
System Detected
Cause
Corrective Action(s)
5 Humidifier control
configuration incorrect
5 Check that the
humidifier control configuration matches the installed sensor output.
TCF
Tank Cold Fault
Red
The tank has not become hot with the steam valve activated.
1 Tank temperature
sensor not detecting warm tank.
1b Check tank to see if hot
(caution).
1a Check wiring to tank
temperature sensor.
1c Check if sensor closed
when tank is hot.
TCW
2 No steam supply to
humidifier.
2a Check that isolation
valve is not closed.
2b Check if boiler steam is
available.
2c Check if CV valve opens
using diagnostic output test.
3 Condensate not
draining from heat exchanger.
3a Check that F&T trap is
allowing condensate to drain.
Troubleshooting | 82
Nortec SEP Faults
Number of
Flashes / Fault
System Detected
Cause
Corrective Action(s)
One Flash
Humidifier Drain Fault
Water level is not dropping when pump is activated.
1 Internal drain
blocked
Check if water drains from unit when drain manually activated. If not then;
1a Check restrictor in drain line immediately after
pump for blockage.
1b Check pump rotor to see if it is blocked.
1c Check if scale has built up in sump at bottom of
tank and caused a blockage.
2 External drain
blocked
2 Check that water can flow freely through drain
lines.
Two Flashes
Humidifier Fill Fault
Water level not rising or not detected.
1 Water shut off
valve closed
1 Open shut off valve
2 Auxiliary drain
leaking
2a Close auxiliary drain valve if unit does not have
freeze protection.
2b Check freeze protection valve is closed if freeze
protection installed.
3 Fill valve
strainer blocked
3 Clean out strainer on fill valve inlet.
Four Flashes
Inconsistent Float Level
Floats have indicated water level not changing in sequence.
1 High cooling
flow into float chamber
1a Check that orifice in fill valve is in place. Flow
should be very low.
1b Check if tank fill and float cooling lines are
reversed. Flow to float chamber should be very low. Tank hoses to centre of float chamber.
2 Defective float
board.
2 Observe LED’s on float chamber as tank fills. If
LED’s do not light in sequence replace float chamber and float board.
The self-diagnostic system built into the Nortec SEP can display some fault conditions by flashing the yellow “Service” LED in sequence. The Nortec SEP does not display any warnings.
Faults
If the humidifier is not able to self correct a problem symptom it will if necessary respond by
shutting itself down.
When this occurs the humidifier illuminates the red “Fault” LED, Flashes the yellow LED in a
numerical sequence, shuts off the signal to the CV valve actuator, and activates the “Error” relay of the remote relay board.
Clearing a Fault
Count the number of flashes of the yellow LED and take any necessary actions to correct the
cause(s) as outlined in Table 14: Troubleshooting Nortec SEP Faults.
Power cycle the humidifier with the On/Off switch waiting 3 seconds between turning it off
and on.
Table 14: Troubleshooting SEP Faults
83 | Troubleshooting
Nortec SETC Wiring Diagram
Figure 51: SETC Wiring Diagram
Troubleshooting | 84
Nortec SEP Wiring Diagram
Figure 52: SEP Wiring Diagram
85 | Spare Parts
Spare Parts
Spare Parts| 86
Distributor Spare Parts
Figure 53: Distributor Exploded View and Spare Parts
87 | Spare Parts
Nortec SETC/P 100 – 1050 Plumbing Parts
4 3 5 8 9
6
10
19
2
7
18
11
15 1 14
13
12
16
17
Figure 54: SETC 100-1050 Plumbing Parts
Spare Parts| 88
Table 9: Nortec SETC/P 100-1050 Plumbing Parts List
Item
Description
Part No.
100
175
250
375
525
750
1050
1
Cover Plate Assy.
2544439
1 1 1 1 1 1 1 2 O-ring, Clean Out Port
2524361
1 1 1 1 1 1 1 3 O-ring, Clean Out Port,
2524361
1 1 2
4
Cover Plate, Clean Out Port
2547539
1 1 2
5
Fill Box Assy.
2526152
1 1 1 1 1 1 1 6 Lower Mixing Box
1506749
1 1 1 1 1 1 1 7 Drain Pump 24v 60 Hz
1502644
1 1 1 1 1 1 1
8
Vacuum Break Valve 1/2" NPT
1505959
1 1 1 1 1 1 1 9
P-Trap
2526521
1 1 1 1 1 1 1
10
Dual Fill Valve 10.0 l/min &
0.35 l/min
1505759
1 1 1 1 1
Dual Fill Valve, 17.0L/Min & 0.35L/Min
1508581
1
1
11
Auxiliary Drain Termination
1506925
1 1 1 1 1 1 1
12
Steam Trap, 15psi
1508849
1 1 1 1 2 2 3
13
Float Board
2511137
1 1 1 1 1 1 1
14
Float Chamber Mounting Bracket
1113777
1 1 1 1 1 1 1
15
Float Chamber
1115933
1 1 1 1 1 1 1
16
O-ring, Heat Exchanger, Large
2524403
1 1 2 2 3
O-ring, Heat Exchanger, Mini
2524405
1
1
17
Heat Exchanger Kit, Single
2581131
1 1 2 2 3
Heat Exchanger Kit, Mini
2581132
1
1
18
Modulating Actuator 0-10 VDC
1507549
1 1 1 1 1
1
Modulating Actuator 0-10 VDC, 2.5 Val
1508472
1
19
Valve 3/4 in. CV 5.5
1594322
1
Valve 1 in. CV 10.0
1594324
1
Valve 1 in. CV 12.0
1594332
1
Valve 1.25 in. CV 20.0
1594341
1
Valve 1.5 in. CV 28.0
1594350
1
Valve 2.0 in. CV 40.0
1594360
1
Valve 2.5 in. CV 65.0
1508473
1
89 | Spare Parts
Nortec SETC/P 100 – 1050 Cabinet and Electrical Parts
15
14
16
13
12 3 4 5 5
11 6 10
2
1
9
7 8 17
Figure 55: Nortec SETC/P 100-1050 Cabinet and Electrical Parts
Spare Parts| 90
Table 10: Nortec SETC B+/P 100 – 1050 Cabinet and Electrical Parts List
Item
Description
Part No.
100
175
250
375
525
750
1050
1
Service Door, Mini
2523709
1
1
Service Door, Single
2524402
1
1
Service Door, Double
2524401
1
1 Service Door, Triple
2523704
1 2 Recessed Handle,
2523444
1 1 1 1 2 2 2 3 Kit Processor Board SE
2553861
1
Not
Shown
Cable , 40 Pin Ribbon
2537230
1
4
Panel Processor Display,
2544253
1
Not
Shown
Membrane, Nortec
1509735
1
5
Switch Rocker DPST 10A-250V
2522489
1
6
Remote Fault Indication Board SETC
2550184
1
Not
Shown
Cable, 10pin Ribbon
2522062
1
7
PCB Driver Board
2535504
1
8
Transformer,120/240V, 24V,150VA
2532672
1
9
Door, Front, GS-SE
2523597
1
10
Panel, Electrical Cabinet
Reference - Contact Factory
11
Panel, Elec. Bottom
Reference - Contact Factory
12
Panel, Rear Elec.
Reference - Contact Factory
13
Panel, Tank Rear
Reference - Contact Factory
14
Panel, Elec. Top
Reference - Contact Factory
15
Panel, Top Tank
Reference - Contact Factory
16
Panel, Left,
Reference - Contact Factory
17
Base Assembly
Reference - Contact Factory
91 | Spare Parts
Nortec SETC/P 50 Plumbing Parts
1
10
11
12
13 9 8
14
15
18
17
16
2
7
3
19 5 4
6
Figure 56: Nortec SETC/P 50 Plubming Parts
Spare Parts| 92
Table 11: SETC B+/P 50 Plumbing Parts
Item
Description
Part No.
Qty
1
Tank Replacement Kit, SE50
2520458
1
2
Heat Exchanger Replacement Kits, SE50
2520460
1
3
Gasket, Tank/H.E. Assembly, SE50
1510179
1
4
F&T Trap Assembly, with Plumbing, SE50
1500181
1
5
Float Chamber Assembly, with Board and Connections, SE50
2520239
1 6
Float Board
2511137
1
7
Bracket, Float Chamber Mount, SE50
2520240
1
8
5 Cover Plate Kit, Clean Out Port, SE50
2520461
1
9
Gasket, Clean Out Port, SE50
1510180
1
10
P Trap Mount Assembly, SE50
2520137
1
11
Dual Fill Valve, 5.5L -.35 L/Min
1704234
1
12
Fill Box Assembly with Connections, SE50
2520235
1
13
Vacuum Break Valve 1/2" NPT
1505959
1
14
Termination Assembly with Connections, SE50
2520236
1
15
P Trap Assembly, Complete, SE50
1510187
1
16
Pump Drain, 24VDC, 60HZ (DPS 25-119)
1502644
1
17
Auxiliary Drain Termination
1506925
1
18
Modulating Actuator 0-10 Vdc
1507549
1
19
Valve 1/2in CV 2.80 / VB7263
1594316
1
93 | Spare Parts
Nortec SETC/P 50 Electrical and Cabinet Parts
Nortec SETC Electrical
NortecSEP Electrical
7 1 1
2
12
7 3 6
9 9 13
5
6
14
4
10
11
15
10
11
8
18
17
16
Figure 57: Nortec SETC/P 50 Electrical and Cabinet Parts
Spare Parts| 94
Item
Description
Part No.
Qty
1
Panel Assembly, Electrical Front, Cabinet SE50
2520268
1
2
Kit Processor Board SE
2553861
1
Not
Shown
Cable, 40 Pin Ribbon
2537230
1
3
Panel Assm, Display, Cabinet, SE 50 B+
2552793
1
4
PCB Driver Board
2535504
1
5
Remote Fault Indication Board SETC
2550184
1
Not
Shown
Cable, 10 pin Ribbon
2522062
1
6
Switch Rocker DPST 10A-250V
2522489
2
7
Bracket Assm, Keypad Mnt, SE50
2520272
1
8
Enclosure, Transformer, Cabinet, SE50
2549857
1
9
Transformer,120/240Vpri,24Vsec,150VA
2532672
1
10
Terminal Block 2 Pole
1473002
1
11
Ground Clamp
1323020
1
12
Switch DPDT ON/OFF/DRAIN SETC/SEP
2538961
1
13
SEP Display / Keypad Assembly, SE50
2520279
1
14
SEP, Led Board Assembly
1508619
1
15
SEP Control Board
1508577
1
16
Panel Access, Elect Right, Cabinet, SE50
2520283
1
17
SETC
Panel,Access,Electrical Front SE 50 B+
2552792
1
17
SEP
Panel Access, Elect Front, Cabinet, SE50
2520270
1
18
Panel, Access, Tank Front, Cabinet, SE50
2520267
1
Table 12: Nortec SETC B+/P 50 Electrical and Cabinet Parts
95 | Warranty
Warranty | 96
Warranty
Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
THE COMPANY makes no warranty and assumes no liability whatsoever for equipment that has failed due to ambient conditions when installed in locations having climates below 14°F (­10°C) during January or above 104°F (40°C) during July.
THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.
Certificate No. 002419
U.S.A. Condair Inc.
826 Proctor Avenue Ogdensburg, NY 13669
CANADA Condair Ltd.
2740 Fenton Road Ottawa, Ontario K1T 3T7
TEL: 1.866.667.8321 FAX: 613.822.7964
EMAIL: na.info@condair.com WEBSITE: www.condair.com
Loading...