This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document, nor the information contained herein shall be reproduced, used, or disclosed to others without the written
authorization of Nortec Humidity Ltd., except to the extent required for installation, operation or maintenance of
the customer's equipment.
Liability Notice
Nortec Humidity Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the
equipment, or due to the use of parts/components/equipment that are not authorized by Nortec Humidity Ltd.
Copyright Notice
Copyright 2016, Nortec Humidity Ltd, All rights reserved.
Unistrut® is a trademark of Unistrut Corporation.
Technical modication rights reserved.
Contents
1 Introduction 1
1.1 Before You Start! 1
1.2 General 1
2 For Your Safety 3
3 Receiving and Storage 5
3.1 Inspection 5
3.2 Storage and Transportation 5
4 Product Overview 7
4.1 General Description 7
4.2 Model Designation 9
4.3 Models Overview 10
4.4 Options 11
4.5 Accessories 11
5 Installation 13
5.1 General 13
5.2 Installation Overview 14
5.2.1 Air Handling Unit 14
5.2.2 Rooftop Curb 16
5.2.3 Exterior Wall 18
5.3 Site Requirements 20
5.4 Mounting the Humidier 22
5.4.1 Location and Suggested Clearances 22
5.4.2 Pipe Chase Location 23
5.4.3 Air Handling Unit Mounting 24
5.4.4 Rooftop Curb Mounting 26
5.4.5 Exterior Wall Mounting 28
5.4.6 Mounting Checklist 30
5.5 Steam Line Connections 30
5.5.1 Steam Line 30
5.5.2 Steam Connections Checklist 31
5.6 Water Connections 32
5.6.1 Water and Drain Lines 32
5.6.2 External Freeze Protection System 35
5.6.2.1 Normally-Open and Normally-Closed Valves 35
5.6.2.2 3-Way Normally-Closed Valve 36
5.6.3 Water Connections Checklist 37
5.7 Electrical Connections 38
5.7.1 Outdoor Enclosure Wiring Diagram 40
5.7.2 Electrical Connections Checklist 40
6 Commissioning 41
6.1 General 41
6.2 Commissioning 41
Nortec EL/RS Outdoor
2584597_B_EN_1705
iiiContents
7 Operation and Maintenance 43
7.1 Operating the Unit 43
7.2 Inspections During Operation 43
7.3 Maintenance 44
7.3.1 General 44
7.3.2 Heater and Fan 44
7.3.3 Freeze Protection System 44
7.3.4 Steam Cylinder 45
7.3.5 Cleaning 45
7.3.6 Scale Management (RS-OC Units only) 45
7.3.7 Restarting After a Freeze-up 46
8 Spare Parts List 47
9 Decommissioning 55
9.1 General 55
9.2 Removal from Service for Disposal or Long-term Storage 55
9.3 Disposal/Recycling 56
10ProductSpecications57
10.1 Performance Data 57
10.2 Operating Data 57
10.3 Weights 57
10.4 Dimensions 58
A Appendix i
A.1 Weather Data i
B Appendix v
B.1 Installation Checklist v
ivContents
2584597_B_EN_1705Nortec EL/RS Outdoor
1 Introduction
1.1 Before You Start!
Thank you for purchasing the Nortec EL/RS Outdoor humidier.
The Nortec EL/RS Outdoor humidier incorporates the latest technical advances and meets recognized
safety standards. Never-the-less, improper use of the Nortec EL/RS Outdoor humidier may result in
danger to the user or third parties, and/or damage to property.
To ensure safe, proper and economical operation of the Nortec EL/RS Outdoor humidier, please observe
and comply with all information and safety instructions contained in this manual, as well as all relevant
documentation of components of the installed humidication system.
If you have additional questions, please contact your Nortec representative. They will be glad to assist you.
1.2 General
Limitations
The subject of this manual is the Nortec EL/RS Outdoor humidier. It is intended as a supplement to
the Nortec EL/Nortec RS installation, operation and maintenance manuals. The various options and
accessories for the Nortec EL/RS Outdoor humidier may only be described in-so-far as is necessary
for proper installation and operation of the equipment. Additional information on available options and
accessories can be obtained in the instructions that are supplied with them.
This manual is intended for well trained personnel who are suitably qualied for their respective tasks.
About this Manual
This manual contains supplementary information that applies specifically to the
Nortec EL/RS Outdoor humidifier. The Nortec EL/Nortec RS manuals included with the
Nortec EL/RS Outdoor humidier shipment contain information on installation, operation and maintenance which apply to both the indoor and outdoor models.
For information on the installation of controls, interior piping, interior wiring and steam lines refer to the
respective Nortec EL/Nortec RS installation manual.
The operation of the Nortec EL/RS Outdoor humidier is identical to the indoor units. Refer to the respective Nortec EL/Nortec RS operation and maintenance manual for details.
The maintenance items described in this manual are specic to the outdoor model. This is in addition to
the regular maintenance that is described in the Nortec EL/Nortec RS operation and maintenance manual.
All illustrations in this manual are for representation purposes only. Actual appearance may vary.
Safety Warnings Usage
CAUTION!
The word "CAUTION" in conjunction with the general caution symbol is used to provide safety
instructions that, if neglected, may cause damage and/or malfunction of the unit or damage to
property.
Nortec EL/RS Outdoor
2584597_B_EN_1705
1Introduction
WARNING!
The word "WARNING" in conjunction with the general warning symbol is used to provide safety
instructions that, if neglected, may cause injury to personnel. Other specic warning symbols may
also be used in place of the general symbol.
DANGER!
The word "DANGER" in conjunction with the general danger symbol is used to provide safety
instructions that, if neglected, may cause severe injury to personnel or even death. Other specic
danger symbols may also be used in place of the general symbol.
Other Related Publications
Refer to "About this Manual" on page 1.
Storage of Manual
Keep this manual in a place where it is safe and readily accessible. If the equipment is moved to another
location, please make sure that it remains with the equipment.
If the manual is lost or misplaced, please contact your Nortec representative for a replacement.
2Introduction
2584597_B_EN_1705Nortec EL/RS Outdoor
2 For Your Safety
General
Every person who is tasked with the installation, operation and maintenance of the
Nortec EL/RS Outdoor humidier must read and understand this manual, as well as the respective
Nortec EL/Nortec RS installation, operation and maintenance manuals before performing any work.
Knowing and understanding the contents of these manuals is a basic requirement for protecting personnel against any kind of danger, preventing faulty operation, and operating the unit safely and correctly.
All labels, signs and marking applied to the Nortec EL/RS Outdoor humidier must be observed and
kept in a readable state.
PersonnelQualications
All procedures described in this manual must only be performed by personnel who are adequately qualied, well trained and are authorized by the customer.
For safety and warranty reasons, any activity beyond the scope of this manual must only be performed
by qualied personnel authorized by Nortec.
All personnel working with the Nortec EL/RS Outdoor humidier must be familiar with, and comply with
the appropriate regulations on workplace safety and prevention of accidents.
Intended Use
The Nortec EL/RS Outdoor humidier is intended exclusively for air humidication using a Nortec-approved steam distributor within specied operating conditions (refer to "Operating Data" on page 57 and "Site
Requirements" on page 20 for details). Any other type of application, without the express written consent
of Nortec, is considered to be NOT conforming to its intended purpose, and may lead to dangerous
operation and will void the warranty.
In order to operate the equipment in the intended manner all information contained in this manual, in
particular the safety instructions, must be observed closely.
Safety Precautions that Must be Observed
DANGER!
Risk of electric shock!
The NortecEL/RSOutdoorhumidierismainspowered.Livepartsmaybeexposedwhen
the door panels are opened. Touching live parts may cause severe injury or even death.
Prevention:
The Nortec EL/RS Outdoor humidier must be connected to the mains only after all installation work
has been completed, checked for correct workmanship, and the door panels are closed and fastened securely.
Only qualied personnel should perform maintenance or repairs on the unit.
DO NOT service the unit while standing on wet or icy surfaces, or in wet weather.
Follow lockout procedures whenever servicing the unit.
Nortec EL/RS Outdoor
2584597_B_EN_1705
3For Your Safety
WARNING!
Risk of severe burns from contact with hot steam vapors!
The Nortec EL/RS Outdoor humidier produces hot steam vapors for humidication. Bare skin in
contact with hot steam vapors can result in severe burns.
Prevention: Never perform any work on the steam system (including the steam lines, steam distributors, etc.) while the humidier is operating. Shut down the humidier and wait for the components
to cool down before working on the steam system.
WARNING!
Risk of severe burns from contact with hot surfaces!
The components in the humidier plumbing cabinet get very hot during operation. Bare skin in contact with hot surfaces can result in severe burns.
Prevention: Avoid contact with hot surfaces. Shut down the humidier and wait for the components
to cool down before working on the unit.
CAUTION!
Electrostatic discharge (ESD)!
The components in the control cabinet are sensitive to electrostatic discharge (ESD).
Prevention: Take appropriate measures to protect the electronic components inside the unit against
damage caused by electrostatic discharge (ESD). Refer to ANSI/ESD-S20.20.
Preventing Unsafe Operation
All personnel working with the Nortec EL/RS Outdoor humidier must immediately report to the customer
any alterations to the unit that may affect safety, and securethehumidieragainstaccidentalpower-up.
ModicationstotheUnitProhibited
ModicationsareNOTpermitted on the Nortec EL/RS Outdoor humidier without the express written
consent of Nortec.
4For Your Safety
2584597_B_EN_1705Nortec EL/RS Outdoor
3 Receiving and Storage
3.1 Inspection
After receiving the shipment, inspect the goods as follows:
–Inspect the shipping boxes for damage.
Report any shipping box damages to the shipping company without delay.
–Check the goods against the packing slip to ensure that all items have been delivered.
–Report any shortages to your Nortec representative within 48 hours of receipt of the goods. Nortec
does not assume responsibilities for any shortages beyond this period.
–Unpack the parts/components and check for any damage.
If parts/components are damaged, notify the shipping company immediately.
–Verify the model type, capacity and voltage on the specication label to ensure that it is suitable for
your installation site. Refer to Figure 3 on page 9.
3.2 Storage and Transportation
Moving and Handling the Unit
The Nortec EL/RS Outdoor humidier is bolted to a shipping skid and enclosed in a packaging crate
before it is shipped from the factory. While still attached to the skid, the humidier can be lifted onto a
rooftop or other mounting location using a forklift or crane. Refer to Table 9 on page 57 for weights.
CAUTION!
Risk of damage to equipment.
Prevention: DO NOT drop the humidier when handling the unit. Protect the unit from damage by
tethers and other lifting equipment.
Storage
Store the Nortec EL/RS Outdoor humidier in its original packaging inside a protected area that meets
the following requirements until it is installed, or if it needs to be stored for an extended period of time:
–Room temperature: 41 to 104°F (5 to 40°C)
–Room humidity: 10 to 75% RH
Transportation
For optimum protection always transport the unit and components in their original packaging, and use
appropriate lifting/transporting devices.
Packaging
Keep the original packaging of the unit/components for later use.
If the packaging needs to be disposed off, observe local regulations on waste disposal. Recycle packaging where possible.
Nortec EL/RS Outdoor
2584597_B_EN_1705
5Receiving and Storage
This page intentionally left blank
6Receiving and Storage
2584597_B_EN_1705Nortec EL/RS Outdoor
4 Product Overview
4.1 General Description
The Nortec EL/RS Outdoor humidier is UL-approved for installation outdoors. It is housed in an enclosure
that has an IP54 rating, and comes with built-in heating, ventilation and freeze protection for the plumbing components. The unit is intended to operate in -40 °F to 104 °F (-40 °C to +40 °C) temperatures.
The Nortec EL/RS Outdoor humidier comes in three different housing sizes depending on the steam
capacity. Refer to Figure 1. These units can range from 5 lb/h (2.2 kg/h) to 200 lb/h (91 kg/h) – refer to
"Models Overview" on page 10.
1
Figure 1:
1 Small housing, Nortec EL-OC
2 Medium housing, Nortec EL/RS-OC
3 Large housing, Nortec EL/RS-OC
Figure 2 on page 8 shows the major components of the Nortec EL/RS Outdoor humidier. The built-in
heating system consists of a heater that is activated during the winter months, and controlled by an
internal thermostat to maintain an appropriate operating temperature inside the enclosure. The heat
control is automatic, and cannot be activated manually.
In addition, a mechanical freeze protection valve drains all the water from the steam cylinder(s), ll cup,
valves and hoses to prevent freeze up when the temperature inside the enclosure drops down to 43 °F
(6 °C).
During warm weather, a weather-shielded exhaust fan moves air through the enclosure to maintain an
appropriate operating temperature. The exhaust fan is automatically controlled by a thermostat, and
cannot be activated manually.
The Nortec EL/RS Outdoor humidier is also equipped with a remote fault indication board (standard,
not shown) that can be used to remotely monitor the unit.
All other features of the Nortec EL/RS Outdoor humidier are similar to the Nortec EL/RS humidier.
Refer to the respective Nortec EL/RS humidier manuals for details.
Nortec EL/RS Outdoor Steam Humidier Model Sizes
2
3
Nortec EL/RS Outdoor
2584597_B_EN_1705
7Product Overview
A
16
13
14
15
11
10
12
-A-
9
8
7
1
2
3
4
Figure 2:
1 Side door
2 Controls cabinet
3 Touchscreen display
4 Intake shroud (and lter)
5 Mechanical freeze protection valve (RS-OC with scale
The specication label on the side of the Nortec EL/RS Outdoor humidier shows its model number,
serial number and ratings – refer to Figure 3. The breakdown of the model number is shown in Figure 4.
Table 2 shows the list of options for the Nortec EL/RS Outdoor humidier. Contact your local Nortec rep-
resentative for details.
Table 2: Nortec EL/RS Outdoor Humidier Options
OptionApplication
Mounting bracketProvides a means to attach the unit to an air handling unit or an exterior wall.
Scale tank (RS-OC only)Provides a separate reservoir underneath the steam cylinder for scale collection. The addi-
Accessory relay PCB
(printed circuit board)
Internal primary fusing (ELOC only)
BACnet MSTP BTLPCB to provide BTL-certied BACnet MS/TP. This option also enables full Master functional-
BACnet IP BTLPCB to provide BTL-certied BACnet IP.
LonWorks boardSupplementary board to connect the humidier to a building management system using
tion of this option reduces maintenance time signicantly. Minerals removed from the water
during steam production will collect in the scale reservoir rather than in the tank. For the unit
with two steam cylinders (RS-OC 90, 130 and 180), order two for each humidier.
Printed circuit board with relay contacts for connecting other accessories such as fans and
supply water ushing valves.
Optional internal fuse for heating voltage power supply in the EL-OC models (only). Only
available as a factory-installed option. Note: This is not a substitute for a dedicated external
disconnect switch.
ity when using BACnet MS/TP.
LonWorks.
4.5 Accessories
Table 3 shows the list of accessories for the Nortec EL/RS Outdoor humidier. Contact your local Nortec
representative for details. To install and operate the accessories, please refer to the instructions supplied with the accessories.
Steam distributorSteam distribution system for use in an air duct.
SAMe steam distribution
manifold
Digital or analog control
humidistat with either On/Off
or modulating operation
Digital RH transducerInput device used to communicate the relative humidity in a conditioned space or a duct to
Digital or analog high limit
humidistat with either On/Off
or modulating operation
Air proving switchInput device to ensure that humidication only occurs when air is moving through the duct.
Outdoor temperature sensorInput device used to communicate the outdoor temperature to the humidistat so that it can
Steam distribution system for use in an air duct where reduced absorption distance is required.
Input device used to meter the output of the humidier based on the sensed relative humidity.
The humidistat can be installed in the conditioned space that is being humidied, or within
the duct.
the humidier.
Input device used to limit the output of the humidier by either shutting it down or throttling it
down when the humidity in the duct approaches the high limit.
lower the setpoint value during cold weather to prevent condensation on exterior windows/
surfaces.
Nortec EL/RS Outdoor
2584597_B_EN_1705
11Product Overview
This page intentionally left blank
12Product Overview
2584597_B_EN_1705Nortec EL/RS Outdoor
5 Installation
5.1 General
Strictly observe and perform all installation tasks including the mounting of the unit and connection of
the water, steam and power supplies as described in this manual.
Comply with all local and national codes dealing with water, steam and electrical installations.
Nortec does not accept any liability for installation of humidication equipment by unqualied personnel,
or the use of equipment/parts that are not authorized by Nortec.
PersonnelQualications
All installation work must be performed only by licensed personnel authorized by the customer. It is the
customer’s responsibility to verify qualications of the personnel.
Safety
Observe all safety precautions noted in "For Your Safety" on page 3.
Nortec EL/RS Outdoor
2584597_B_EN_1705
13Installation
5.2 Installation Overview
The Nortec EL/RS Outdoor humidier can be installed in three different ways – mounted directly on a
suitably reinforced vertical surface on the air handling unit (AHU), rooftop on a curb, or a suitable vertical
surface on an exterior wall. Figure 5, Figure 6 on page 16 and Figure 7 on page 18 show overviews of the
different mounting arrangements.
5.2.1 Air Handling Unit
15
14
1
13
2
3
ON
OFF
15 in (380 mm)
min. clearance
4
14Installation
Figure 5:
5
12
11
10
9
8
6
7
Typical Installation on Air Handling Unit (medium size unit shown)
2584597_B_EN_1705Nortec EL/RS Outdoor
Legend:
1 Air handling unit
2 Steam outlet, connection into air handling unit
3 External fused disconnect switch (supplied by others)
4 Pipe chase (drain lines). See Note 1 below.
5 Drain line (freeze protection valve), 3/8 in (9.5 mm) I.D. See Note 2 below.
6 Drain line (main) – 1-3/16 in (30 mm) I.D. See Note 2 below.
7 Air gap funnel. See Note 3 below.
8 Filter, 5 μm (optional, but recommended)
9 Shutoff valve (supplied by others)
10 Union tting (supplied by others)
11 3-way normally-closed valve, or normally-open and normally-closed valves (supplied by others). See Note 4 below.
12 Pipe chase (water supply line)
13 Water supply line, minimum 1/2 in (13 mm). See Note 5 below.
14 Mounting bar (supplied – ×2 for small unit, ×3 for medium/large unit) secured to air handling unit. See Note 6 below.
15 Mounting bracket (×2 for small unit, ×3 for medium/large unit) secured to back of humidier
Note 1: Route all drain lines through a pipe chase. Seal the pipe chase to prevent rising steam from entering the bottom of the humidier enclosure, and to isolate the unit from the pressure inside the building.
Note 2: In cold climates all drain lines must be properly trace heated and insulated to prevent freezing.
Note 3: The air gap funnel should be located inside the building, as shown, and connected to a dedicated
building drain (recommended) with a drainage capacity of at least 2.3 gpm (8.7 L/min) for an EL-OC unit
and 6.7 gpm (30 L/min) for a RS-OC unit – per steam cylinder. The drain line exiting the funnel should be
minimum 7/8 in (22 mm) in diameter for an EL-OC unit, and minimum 1-3/4 in (45 mm) for a RS-OC unit.
The drain lines into the funnel must not touch the sides or bottom of the funnel. In large units, separate
air gap funnels must be used for drain lines from each cylinder.
Note 4: In cold climates the water supply line should be protected with a freeze protection system utilizing
either a normally-open and a normally-closed valve, or a 3-way normally-closed valve. Refer to "External
Freeze Protection System" on page 35 for details.
Note 5: The water supply line should have a 1/2 in NPT female end for connection to the unit. It must be
routed through a pipe chase. In cold climates it must be properly trace heated and insulated to prevent
freezing.
Note 6: The supplied mounting bars must be installed on a reasonably at vertical mounting surface on
the air handling unit, that is stable and suitably reinforced (strength equivalent to 2×4 stud or 1-5/8 in ×
1-5/8 in ×12 gauge Unistrut® channel). Make sure that the mounting surface is capable of supporting
the entire weight of the unit when it is in operation. Refer to Table 9 on page 57 for weight of the unit.
This mounting arrangement is advantageous because the steam piping is shorter, thus minimizing
condensate losses and backpressure in the line. Do not install the Nortec EL/RS Outdoor humidier in
an outdoor environment where the unit is exposed to severe weather or where the temperature drops
below -40 °F (-40 °C).
IMPORTANT! In units operating in cold climates, the area around the unit must kept clear of snow
and ice accumulation to permit opening and closing of the front and side doors.
Refer to "Site Requirements" on page 20, and "Air Handling Unit Mounting" on page 24 for mounting details. Make
sure the required clearance is maintained – refer to Figure 8 on page 22. Observe all local and national
installation codes. Nortec is not responsible for any installation code violations.
The water supply and all drain lines must be properly trace heated and insulated to prevent freezing.
IMPORTANT! The warranty does not cover damage to the humidier resulting from freezing.
Nortec EL/RS Outdoor
2584597_B_EN_1705
15Installation
5.2.2 Rooftop Curb
1
13
14
12
2
ON
OFF
3
4
5
11
10
9
8
6
7
Figure 6:
Typical Installation on Rooftop Curb (medium size unit shown)
1 Steam line, must maintain a constant minimum upslope of 10° or downslope of 2°, and must be insulated
2 External fused disconnect switch (supplied by others)
3 Curb. See Note 1 below.
4 Pipe chase (drain lines). See Note 2 below.
5 Drain line (freeze protection valve), 3/8 in (9.5 mm) I.D. See Note 3 below.
6 Drain line (main) – 1-3/16 in (30 mm) I.D. See Note 3 below.
7 Air gap funnel. See Note 4 below.
8 Filter, 5 μm (optional, but recommended)
9 Shutoff valve (supplied by others)
10 Union tting (supplied by others)
11 3-way normally-closed valve, or normally-open and normally-closed valves (supplied by others). See Note 5 below.
12 Pipe chase (water supply line)
13 Water supply line, minimum 1/2 in (13 mm). See Note 6 below.
14 Pipe chase (steam line)
Note 1: The curb must be capable of supporting the entire weight of the unit when it is in operation –
refer to Table 9 on page 57. The curb must be properly anchored to the rooftop.
Note 2: Route all drain lines through a pipe chase. Seal the pipe chase to prevent rising steam from
entering the bottom of the unit, and to isolate the unit from the pressure inside the building.
Note 3: In cold climates all drain lines must be properly trace heated and insulated to prevent freezing.
16Installation
2584597_B_EN_1705Nortec EL/RS Outdoor
Note 4: The air gap funnel should be located inside the building, as shown, and connected to a dedicated
building drain (recommended) with a drainage capacity of at least 2.3 gpm (8.7 L/min) for an EL-OC unit
and 6.7 gpm (30 L/min) for a RS-OC unit – per steam cylinder. The drain line exiting the funnel should be
minimum 7/8 in (22 mm) in diameter for an EL-OC unit, and minimum 1-3/4 in (45 mm) for a RS-OC unit.
The drain lines into the funnel must not touch the sides or bottom of the funnel. In large units, separate
air gap funnels must be used for drain lines from each cylinder.
Note 5: In cold climates the water supply line should be protected with a freeze protection system utilizing
either a normally-open and a normally-closed valve, or a 3-way valve. Refer to "External Freeze Protection
System" on page 35 for details.
Note 6: The water supply line should have a 1/2 in NPT female end for connection to the unit. It must be
routed through a pipe chase. In cold climates it must be properly trace heated and insulated to prevent
freezing.
The Nortec EL/RS Outdoor humidier is designed to be mounted on a curb. When choosing this mounting
arrangement, locate the humidier as close as possible to the steam distributor to minimize condensate
losses and backpressure in the line. Do not install the Nortec EL/RS Outdoor humidier in an outdoor
environment where the unit is exposed to severe weather or where the temperature drops below -40 °F
(-40 °C).
IMPORTANT! In units operating in cold climates, the area around the curb must kept clear of snow
and ice accumulation to permit opening and closing of the front and side doors in the unit.
Refer to "Site Requirements" on page 20, and "Rooftop Curb Mounting" on page 26 for mounting details. Make
sure the required clearance is maintained – refer to Figure 8 on page 22. Observe all local and national
installation codes. Nortec is not responsible for any installation code violations.
The water supply and all drain lines must be properly trace heated and insulated to prevent freezing.
IMPORTANT! The warranty does not cover damage to the humidier resulting from freezing.
Nortec EL/RS Outdoor
2584597_B_EN_1705
17Installation
5.2.3 Exterior Wall
14
1
13
2
ON
OFF
8
9
11
10
12
7
6
15 in (380 mm) min.
ground clearance
3
4
Figure 7:
5
Typical Installation on an Exterior Wall (medium size unit shown)
1 Pipe chase (steam line)
2 External fused disconnect switch (supplied by others)
3 Pipe chase (drain lines). See Note 1 below.
4 Pipe chase (water supply line)
5 Drain line (freeze protection valve), 3/8 in (9.5 mm) I.D. See Note 2 below.
6 Air gap funnel. See Note 3 below.
7 Drain line (main) – 1-3/16 in (30 mm) I.D. See Note 2 below.
8 Shutoff valve (supplied by others)
9 Filter, 5 μm (optional, but recommended)
10 Union tting (supplied by others)
11 3-way normally-closed valve, or normally-open and normally-closed valves (supplied by others). See Note 4 below.
12 Water supply line, minimum 1/2 in (13 mm). See Note 5 below.
13 Mounting bar (supplied – ×2 for small unit, ×3 for medium/large unit) secured to an exterior wall. See Note 6 below.
14 Mounting bracket (×2 for small, ×3 for medium/large unit) secured to back of humidier
18Installation
2584597_B_EN_1705Nortec EL/RS Outdoor
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.