This document and the information disclosed herein are proprietary data of WALTER MEIER LTD.
Neither this document nor the information contained herein shall be reproduced used, or disclosed to
others without the written authorization of WALTER MEIER LTD., except to the extent required for
installation or maintenance of recipient’s equipment. All re ferences to the NORTEC name should be
taken as referring to WALTER MEIER LT D.
LIABILITY NOTICE
NORTEC does not accept any liability for installations of humidity equipment installed by unqualified
personnel or the use of parts/components/equipment that are not authorized or approved by
NORTEC.
COPYRIGHT NOTICE
Copyright 2008, WALTER MEIER LTD. All rights reserved.
SPECIFICATION LABEL LOCATION
The Specification Label for your NH Series humidifier is located on the bottom of the unit. You will
find it attached to the skirt that separates the electrical and plumbing comp ar tments on the electrical
compartment side.
RECORD OF REVISIONS
For each revision, put the revised pages in your manual and disca rd the superseded pages. W rite the
revision number and revision date, date put in manual, and the incorporator’s initials in the applicable
columns on the Record of Revisions.
The NHTC humidifier is controlled by Nortec’s Patented Auto adaptive Water Management
Control System. This system allows the humidifiers to adapt to basically any potable
incoming water and changes that occur to the water supply. This eliminates the need to
readjust drain timers, changes complete cylinders or time consuming adjustment of
electrode spacing’s. The system also adjusts the drain rate of the humidifier to reduce the
amount of drain water exiting the humidifier as water conditions change. This reduces
energy loss due to excessive draining of hot water and extends cylinder life since less water
and minerals enter the humidifier.
The following is a brief description of how the Auto-Adaptive water Management System
works.
The electrode steam system produces pure uncontaminated steam with variable output
through electronic power control of the electrodes. Water borne minerals remain in the
cylinder and are periodically flushed out through the automatic cylinder drain. On NHTC and
NHPC models the drain automatically empties the steam cylinder if it is not operated for
three days. Solid mineral scale sinks to the bottom of the cylinder which, when filled with
residue, is easily removed and replaced.
A. PROPORTIONAL + INTEGRAL AUTO-ADAPTIVE CONTROL SYSTEM FOR THE
NHTC/ NHPC
(1) NORTEC’s patented P+I Auto-Adaptive control system allows the unit to operate at
an optimal low water level using the same fixed electrode spacing regardless of the
incoming water conditions. Boiling of the water allows the minerals in the water to
remain behind in the cylinder. This raises the contained water conductivity to a
value higher than the incoming water. The P+I Auto-Adaptive control system
monitors and adjusts the contained water conductivity as these changes occur.
(2) The humidifiers are designed to produce full steam output at the lowest possible
electrode coverage to obtain maximum cylinder life.
(3) The units operate between A and D of the main steam output demand.
Accordingly, the current flow between the electrodes in the cylinder is maintained
between these pre-established limits programmed into the P+I Auto-Adaptive
control system.
(4) As the water boils away and the electrode coverage is reduced, the steam output is
also reduced slightly. A pre-determined design parameter of every NORTEC
cylinder is the known time (To) (time optimum) that it takes to boil down from A to
D of output (also referenced to as amp trigger points) at a pre-designed contained
water conductivity. (See Figure 2.)
(5) Whenever the conductivity in the cylinder water is lower than the designed
conductivity, the (Ta) (time actual) to boil down from A to D will be longer than the
To. (See Figure 3.)
10-00
Page 3
2008-10-01
(6) As the water is boiled away, the minerals left behind increase the conductivity of
the water in the cylinder. As soon as the conductivity is greater than design, the Ta
to boil from A to D will be shorter than To and a drain cycle is initiated.
(7) The fill valve always opens during timer drains, adding cold water to mix with the
hot water from the cylinder during automatic drain cycles. This tempering process
is required to meet plumbing codes.
(8) As can be seen from a typical sequence depicted in Figure 4, the P+I Auto-
Adaptive system allows the unit to be self-regulating. It drains only when necessary
and only the amount of water to maintain optimum operating conditions.
(9) Relying on the proportional (P) feedback only to decide how much to drain is like
guessing what is happening based on a ‘snapshot’ only. By taking into
consideration a series of “snapshots”: (one from each of the past ten cycles for
example), the control system has more data on which to base its decision to drain.
The integral (I) part of the P+I Auto-Adaptive system provides this added feedback.
(10) The proportional (P) and integral (I) factors have been weighted as to the relative
influence each will have when the NHTC/NHPC calculates a drain. The
preprogrammed weighing was derived through extensive field and laboratory tests.
When supply water conductivity is extremely high (requiring substantially more
drains), the NHTC/NHPC will see the pattern developing in cycles stored in
memory. It will then initiate additional drains to adjust the contained water
conductivity.
(11) If low conductive water conditions occur, the P+I control will reduce the drains
necessary to maintain optimum operating conditions within the cylinder. If extreme
water conditions are encountered, the NHTC/NHPC can be reprogrammed with
factory instructions to compensate.
(12) NORTEC’s P+I Auto-Adaptive control system has been designed to benefit users
who demand very tight control of the relative humidity. It maintains steam output
above the B level, even during auto drains. (See Figure 4.)
(13) The P+I Auto-Adaptive control system allows the humidifier to maintain tighter
humidity control without the problem of rh depression during drain cycles that occur
with other humidifiers. This results in more consistent space rh levels, even with a
simple on/off control system.
10-00
Page 4
2008-10-01
Figure 2. Optimum Boiling Time
Figure 3. Conductivity
10-00
Page 5
2008-10-01
B. NH CAPACITY ADJUSTMENT
(1) Each NORTEC NH Series humidifier is rated at its maximum output capacity. By
means of the alphanumeric display and keypad on the NHTC/NHPC, the
humidifiers can be adjusted to obtain an output between 20% and 100% of its rated
capacity.
C. DRAIN CYCL E AND CYLINDER LIFE
(1) Water Type Used (Potable or Softened)
(a) The electrode steam product line is one of the most efficient humidifier
systems since it uses the minerals in the water to conduct electricity. If no
minerals are present no current can pass from one electrode to another, thus
no steam production can occur.
(b) Although the electrode steam humidifier is ideal for potable water, it should
not be used with pure reverse osmosis or deionized water since the
conductivity is too low.
(2) Water Conditions vs Cylinder Life
(a) The NH Series is designed to adapt to most potable or softened water
supplies. Since the output of all NH Series humidifiers is pure, clean steam,
minerals originally in the incoming water are left behind in the steam cylinder.
Many of these minerals will be removed during short flush cycles within the
cylinder. Therefore, the water chemistry, the unit running time, and output
capacity setting ultimately determines the cylinder life. (See Figure .)
(3) Output vs Cylinder Life
(a) As minerals build-up on the electrodes in the cylinder of the NORTEC NH
Series humidifier, the patented P+I Auto-Adaptive control system
automatically raises the water level slightly in the cylinder. This exposes fresh
electrode surface to the water and maintains peak output and efficiency from
the humidifier. Once the
(b) electrode surface is completely encrusted by the minerals, the user is alerted
to change the cylinder. Other humidifiers’ performance degrades gradually as
the minerals build-up. The NH Series maintains maximum efficiency then the
cylinder is replaced. (See Figure .)
(4) Water Conditions vs Drain Rate
(a) The P+I Auto-Adaptive control system automatically adjusts the drain rate to
maintain the design water conductivity required for proper operation. This
ensures regular flushing of minerals which become concentrated in the water,
and minimizing wastage of hot water. The humidifier automatically adjusts it’s
drain rate with changes in incoming water conductivity through the Autoadaptive water management system.
10-00
Page 6
2008-10-01
0. Store previous cycle’s drain decision in integral (l) memory.
1. Fill to A trigger (use all places below 1-10).
2. Boil to C trigger without timing to allow previous fill water to mix thoroughly during boiling.
3. Boil from C to D while monitoring time (T actual).
4. Decide how long (how much) to drain, then fill to B.
5. Drain according to the P+I calculated drain time, fill on to control outlet temperature.
6. At D, stop draining and postpone remaining drain, fill to B.
7. Continue remaining drain.
8. With drain finished, fill to A.
9. Boil to D, timing from C to D.
10. Decide how long to drain (in this case zero) based on present and past cycles.
Figure 4. Typical Auto-Adaptive Operation
10-00
Page 7
2008-10-01
It is important to note that the drain rate shown includes the make-up water,
mixed with the drain water, which tempers the drain water to 140°F (60°C) or
less.
NOTE
The electrode steam process provides optimum efficiency because all resistance to
current passage is converted to usable energy. Unlike cal-rod or infrared humidifiers
which convert some of their capacities into unusable heat.
Figure 5. Capacity Setting & Cylinder Life
Figure 6. Output vs Service Life
10-00
Page 8
2008-10-01
3. PRE-INSTALLATION EQUIPMENT VERIFICATION
A. GENERAL
(1) Ensure the available voltage and phase correspond with humidifier voltage and
phase as indicated on the humidifier’s specification label.
(2) Ensure that the external fuse disconnect is sufficient size to handle the rated
amperage as indicated on the humidifier’s specifications label. Refer to local building
codes.
(3) Report any discrepancy immediately to the site engineer.
(4) Location and mounting is described in Chapter 10-10.
(5) For typical installation see Figures 6 & 7.
10-00
Page 9
2008-10-01
Figure 6. Typical NHRS Installation (Sheet 1 of 2)
10-00
Page 10
2008-10-01
10-00
Page 11
2008-10-01
Figure 7. Typical NHRS Installation (Sheet 2 of 2)
10-10
HUMIDITY,
STEAM ABSORPTION
AND
DISTRIBUTION
10-10
Page 12
2008-10-01
HUMIDITY, STEAM ABSORPTION AND DISTRIBUTION
1.HUMIDITY
A.ESTIMATING THE HUMIDIFICATION LOAD
Note: The humidification load can easily be calculated by using Nortec’s Humidification Engineering
and Load-sizing Program (HELP). The softward can be downloaded at www.humidity.com
(1) Relative humidity is the percentage of moisture in the volume of air at a given
temperature, compared to the maximum amount of moisture that the volume of air can
hold at the same temperature and atmospheric pressure. As air becomes warmer, it
can absorb more moisture per unit volume. Therefore a quantity of air containing a
specific amount of moisture will have different values of relative humidity as the
temperature changes.
(2) It is this process that causes dry air in building. As cold incoming air is heated, its
relative humidity value drops. Therefore moisture must be added to attain an
acceptable level of humidity within the building. Determining how much moisture must
be added is the object of this brochure. Table 2 simplifies the calculations which are
described here in detail.
B.LOAD CALCULATION SUMMARY
(1) In order to determine the humidification load three basic values need to be known:
(a) The design conditions of the humidified space, i.e., the temperature and humidity
required.
(b) The conditions of the incoming air, i.e., the temperature and humidity available.
(c) Incoming air volume and secondary conditions that can affect the humidification
load.
(2) Data and calculations required to estimate humidification load are described in
Tables 1, 2 and 3.
C.TEMPERATURE AND HUMIDITY REQUIRED
(1) The design temperature and humidity of a space depends mostly upon the job being
performed. Once the design temperature and humidity have been established, the
required moisture can be found in gr/ft
worst case (highest temperature, highest humidity).
(2) Formula 1
For example:
The press room of a printing plant should be kept at 76 - 80
Therefore, the worst case is 80
From Table 3 the required moisture is 11.04 gr/ft
D.TEMPERATURE AND HUMIDITY AVAILABLE
(1) The outdoor conditions tell us the moisture available in the incoming air. Approximate
values can be obtained from Table 4 and combined with Table 3 to find moisture
available. Once again we must take the worst case (here, it is lowest temperature,
lowest humidity). As can be seen, the contribution of moisture from the outside air is
almost zero.
Chart shows what the residual indoor RH would be at 70°F under varying outdoor conditions if a proper humidification
system were not installed in the building. Studies indicate that the recommended RH should be between 40% and 60%
for optimum benefits to the occupants.
Outdoor temperature
Table 2. Load Calculation Summary Sheet
Determine the moisture required in the space (Table 3)
Grains from Table 3 at space temp. ______ x Indoor RH
Determine the moisture level of incoming air (Table 4)
Grains from Table 4 at space temp. ______ x Outdoor RH
Therefore: moisture to be added: (moisture) M - A - B ______ gr/ft3 →M ______ gr/ft
Determine the volume of air to be humidified. Choose the largest
value.
1. Natural ventilation: Volume x number of air changes.
Assume our printing plant is located in Denver, Colorado. From Table 4, the worst
case is -10
From Table 3:
0.29 gr/ft
°F with 37% rh
3
x 37% rh - 0.11 gr/ft
3
Combining this result with that of Moisture Required (A) we see that we will need
5.19 - 0.11 = 5.08 grains of moisture for every cubic foot of outside air brought in.
E.INCOMING AIR VOLUME
(1) The following outlines the steps necessary to determine the amount of outside air being
brought into the humidified space and the corresponding amount of moisture required.
There are three basic means by which outside air is introduced into the humidified
space. These are:
(a) Through natural ventilation, for example, opening and closing doors and windows,
and by infiltration through cracks and openings in the building construction.
(b) Through mechanical ventilation, for example, the introduction of make-up air, or
the exhausting of stale air by the building HVAC system.
(c) Through the economizer section of the HVAC system - if this feature is included in
the system.
(2) For maximum accuracy, all three should be estimated and the largest chosen.
10-10
Page 15
2008-10-01
Table 4. Design Outdoor Conditions
JANUARY
Relative Humidity
(% RH)
State City °C
AlabamaBirmingham
ArizonaFlagstaff
ArkansasLittle R o ck-1558067689585555935
CaliforniaEureka
ColoradoDenver
ConnecticutNew Haven-1807565699577647435
DelawareWilmington-1807762709580526935
District of
Scranton
Rhode IslandProvidence-1807360679379577334
South CarolinaCharleston
Columbia
South DakotaHuron
Rapid City
TennesseeKnoxville
Memphis
TexasAmarillo
Corpus Christi
Dallas
El Paso
Houston
San Antonio
UtahSalt Lake City-23-108071729556272335
VermontBurlington-23-108169789076546732
VirginiaRichmond-9158460689581577235
WashingtonSeattle
Walla Walla
West VirginiaCharleston
Parkersburg
WisconsinGreen Bay
Milwaukee
WyomingCheyenne-26-155948559573364035
Province City
AlbertaCalgary
Edmonton
Grande Prairie
Lethbridge
Medicine Hat
British ColumbiaEstevan Point
Fort Nelson
Penticton
Prince George
Prince Rupert
Vancouver
Dry
Bulb
-15
-18
-18
-23
-21
-18
-21
-18
-12
-18
-18
-23
-23
-21
12
-18
-18
-18
-21
-9
-12
-29
-29
-18
-18
-23
-7
-12
-12
-7
-7
-9
-21
-18
-23
-26
-26
-34
-34
-42
-36
-34
-8
-40
-18
-38
-12
-9
°F
-10
10
-10
-10
10
15
10
-20
-20
-10
20
10
10
20
20
15
-10
-15
-15
-29
-29
-43
-32
-30
17
-40
-37
11
15
7:30
A.M.
5
0
0
-5
0
-5
0
0
0
-5
0
0
0
-5
0
0
-5
0
0
79
72
73
75
79
72
81
82
82
82
81
83
79
83
87
72
74
77
80
87
81
79
71
83
82
71
88
81
63
85
82
86
80
79
82
75
76
1:30
P.M.
71
75
80
66
73
84
79
81
82
87
87
68
79
62
63
72
61
73
59
57
70
72
71
72
81
82
49
65
67
67
55
57
72
69
65
67
51
66
62
45
66
60
80
74
64
66
68
70
7:30
P.M.
JULY
Relative Humidity
(% RH)
81
75
77
79
78
75
80
88
86
84
79
78
76
69
86
78
78
80
77
88
83
86
71
83
85
77
93
79
60
90
88
86
50
88
80
85
81
1:30
P.M.
34
42
38
30
31
32
32
44
53
54
41
72
51
55
52
53
58
50
56
55
52
52
52
52
68
63
51
52
52
50
64
56
52
42
55
55
43
58
50
37
58
49
63
33
53
52
58
58
7:30
P.M.
82
65
68
64
63
68
60
73
72
60
58
60
59
36
48
62
64
63
82
68
49
40
66
59
42
68
47
30
66
45
47
22
67
65
64
64
°C
35
35
35
34
34
35
35
34
35
35
35
35
35
32
32
35
35
35
35
--
35
35
35
35
35
35
38
35
38
38
35
38
29
35
35
35
35
35
31
30
29
33
36
31
34
29
23
27
27
10-10
Page 17
2008-10-01
Table 4. Design Outdoor Conditions (cont)
JANUARY
Relative Humidity
(% RH)
ProvinceCity °C
ManitobaBrandon
Churchill
The Pas
Winnipeg
New BrunswickCampbellton
Fredericton
Moncton
Saint John
NewfoundlandCorner Brook
Gander
Goose Bay
St. John’s
N.W.T.Frobisher
Resolute
Yellowknife
Nova ScotiaHalifax
Sydney
Yarmouth
OntarioThunder Bay
Hamilton
Kaspuskasing
Kingston
Kitchener
London
North Bay
Ottawa
Peterborough
Sioux Lookout
Sudbury
Timmins
Toronto
Windsor
Sault St. Marie
P.E.I.Charlottetown-21-686845729
QuebecKnob Lake
Mont Joli
Montreal
Port Harrison
Quebec City
Sept-Iles
Sherbrooke
Trois Rivieres
SaskatchewanPrince Albert
Regina
Saskatoon
Swift Current
Yukon TerritoryDawson
Whitehorse
Dry
Bulb
-34
-40
-37
-34
-28
-27
-24
-24
-23
-21
-32
-17
-43
-45
-45
-18
-17
-15
-33
-18
-34
-24
-19
-18
-29
-27
-25
-36
-29
-36
-19
-16
-29
-40
-24
-27
-39
-28
-33
-28
-28
-41
-37
-37
-34
-49
-43
°F
-29
-40
-35
-29
-18
-16
-12
-12
-10
-26
-45
-49
-49
-27
-30
-11
-20
-17
-13
-33
-20
-33
-20
-40
-11
-16
-39
-19
-27
-18
-18
-41
-34
-34
-29
-56
-45
7:30
A.M.
-5
1
0
1
5
0
-3
0
-3
-3
1:30
P.M.
73
76
77
78
77
72
82
82
84
76
85
77
71
82
83
84
83
80
75
79
84
80
77
77
78
81
79
82
79
75
76
81
77
81
76
79
76
80
7:30
P.M.
Dry
Bulb
°F
90
79
85
90
87
89
88
81
84
85
86
79
63
54
78
83
84
76
86
91
87
85
88
90
87
90
90
65
89
90
90
92
88
55
62
88
86
80
87
88
88
92
90
93
57
78
7:30
A.M.
JULY
Relative Humidity
(% RH)
1:30
P.M.
50
57
54
50
54
47
52
62
47
45
42
60
67
81
50
50
56
70
52
52
52
69
58
53
46
50
53
69
44
45
56
51
48
70
71
58
60
47
58
58
60
40
7:30
P.M.
°C
32
26
29
32
31
32
31
27
29
29
30
26
17
12
26
28
29
24
30
33
31
29
31
32
31
32
32
18
32
32
32
31
29
13
17
31
30
27
31
31
31
33
32
34
14
26
10-10
Page 18
2008-10-01
(3) Using the natural ventilation method requires knowing the volume of the humidified
space and the type of construction. A tightly constructed building will have a least one
air change per hour. A loosely constructed building will have at least one and one half
changes per hour, and this same building with a large a amount of incoming or exiting
traffic will have at least two air changes per hour.
(a) Formula 3
Assume our print shop has a floor area of 100'
large amount of traffic. This requires
100' x 100' x 20' x 2 = 400,000 ft
Using our example, the moisture required is
400,000 x 5.08
_______________
7000 grains/lb
(4) Using make-up air:
(a) Formula 4
Assume our print shop has a 15,000 CFM HVAC system and uses 10%
make-up air during winter. The amount of outside make-up air entering the
HVAC system will, therefore, be 10% of 15,000 CFM = 1,500 CFM. The
moisture required will be
1,500 x 5.08 x 60 min/hr
_________________________
7,000 grains/lb
(Refer to Figure 1.)
= 290 lbs/hr
= 65 lbs/hr
3
x 100' with a 20' ceiling with a
/hr.
Figure 1. Schematic of a Typical Print Shop HVAC System
10-10
Page 19
2008-10-01
(5) Using an exhaust air fan:
(a) Formula 5
Assume the print shop has a 1,000 CFM fan to exhaust a drying room. The
moisture required to humidify the drying room only is
1,000 x 5.08 x 60 min/hr
_________________________
7,000 grains/lb
= 44 lbs/hr
(Refer to Figure 1.)
(6) Using an economizer cycle:
(a) Care should be taken in sizing humidification load when an economizer cycle is
incorporated into a building HVAC system. The purpose of an economizer cycle is
to provide building cooling using outside air, rather then the building refrigeration
system when outside air conditions permit.
(b) The economizer cycle senses and compares outdoor air temperature and return
air temperature during the cooling season.
(c) W hen the HVAC system calls for cooling and the outdoor air temperature is low
enough – typically 55°F or lower – the outside air and exhaust air dampers are
positioned to provide the required supply air temperature to maintain cooling, and
the recirculated air damper is positioned to maintain the required supply air
volume. When the outdoor air temperature is higher than the supply air
temperature required to maintain cooling but is lower than the return air
temperature, the make-up air and exhaust air dampers are 100% open. The
recirculation air damper closes, and the building refrigeration system provides the
portion of cooling load that cannot be provided by outside air intake.
(d) From this it can be seen that it is possible to introduce 100% outside air into a
building during the cooling season.
(e) Formula 6
For example, if out print shop were using 100% outdoor air at 55°F and
40% rh, then the moisture required is
5.19 - (4.89 x 40% rh) = 3.23 gr/ft
3
Therefore, on a 15,000 CFM system, the humidification load will be
15,000 x 3.23 x 60 min/hr
__________________________
7,000 grains/lb
= 415 lbs/hr
(f)In the above examples, the largest humidification load was due to the economizer
cycle at 415 lbs/hr.
(7) Using cooling or refrigeration loads:
(a) As air is cooled, it loses it’s ability to hold moisture. If it is cooled enough, some of
the moisture will condense out. This is known as cooling load. Cooling load
calculations can be important for process applications or refrigeration applications
to product dehydration.
10-10
Page 20
2008-10-01
(b) Formula 7
Assume that during the summer the HVAC system is in the cooling mode. The
air leaving the cooling coil is at 55°F and 90% rh. In order to maintain the
desired 47% rh in the space, moisture must be added using the following
formula:
Desired space 80°F 47% rh= 5.19 gr/ft
3
(Formula 1)
55°F 90% = 4.89 x 0.90= 4.40 gr/ft
__________________________________
3
Grains to add= 0.79 gr/ft3
15,000 x 0.79 x 60 min/hr
_________________________
7,000 grains/lb
= 101.57 lbs/hr
(8) In considering Process and Environment, in Tables 5 through 7 you will find conditions
and processes that may affect your calculation and should be addressed.
(a) Table 5 shows the outdoor temperature at which the rh would cause condensation
on the windows to the outside. Should your outdoor conditions make this a
possibility, an outdoor setback sensor may be a solution.
(b) Table 6 describes the moisture gain of various material and if your process or
environment includes a great amount of these materials that are constantly
introduced to the area, its affects must be considered.
(c) Table 7 identifies many recommended indoor conditions for various locations and
processes, these can be of use when deciding what conditions would be most
beneficial in your application.
(d) In Figure 2, you will find the ASHRAE physchrometric chart describing the
enthalpy of dry air and the effects to and from rh in the air.
Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windows
Flour and Powdered Product Storage
Fermentation (Bread Dough)
Retarding of Doughs
Final Proof
Counterflow Cooling
Brewing
Hop Storage
Yeast Culture Room
Candy
Chocolate Pan Supply Air
Enrober Room
Chocolate Cooling Tunnel Supply Air
Hand Dippers
Moulded Goods Cooling
Chocolate Packing Room and Finished Stock Storage
Centers Tempering Room
Marshmallow Setting Room
Grained Marshmallow (deposited in starch) Drying
Gum (deposited in starch) Drying
Sanded Gum Drying
Gum Finished Stock Storage
Sugar Pan Supply Air (engrossing)
Polishing Pan Supply Air
Pan Rooms
Nonpareil Pan Supply Air
Hard Candy Cooling Tunnel Supply Air
Hard Candy Packing
Hand Candy Storage
Caramel Rooms
Raw Material Storage
Nuts (insect)
Nuts (rancidity)
Eggs
Chocolate (flats)
Butter
Dates, Figs, etc.
Corn Syrup
Liquid Sugar
Comfort Air Conditioners
Ceramics
Refractory
Molding Room
Clay Storage
Decalcomania Production and Decorating room
Cereal Packaging
Cheese Curing
Cheddar
Swiss
Blue
Brick
Limburger
Camembert
Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Product and/or Process
Clean Rooms – Computer Rooms
Computer Room
Clean Room – General
Clean Room – Critical
Distilling
Grain Storage
General Manufacturing
Aging
Electrical Products
Coil and Transformer Winding
X-ray Tube Assembly
Instruments Manufacture and Laboratory
Thermostat and Humidistat Assembly and Calibration
Close Tolerance Assembly
Meter Assembly and Test
Fuse and Cutout Assembly, Capacitor Winding and Paper Storage
Conductor Wrapping with Yarn
Lightning Arrestor Assembly
Thermal Circuit Breaker Assembly and T est Water Wheel Generators
Thrust
Runner Hopping
Processing Selenium and Copper Oxide Plates
Fruit Storage
Apples
Apricots
Grapefruits (California)
Grapefruits (Florida)
Grapes (Eastern)
Grapes (Western)
Lemons
Oranges (California)
Oranges (Florida)
Peaches and Nectarines
Plums
Specialty Citrus Fruit
Fur Storage 40 – 50 4 – 10 55 – 65
Gum
Manufacture
Rolling
Stripping
Breaking
Wrapping
Hospitals
Operating, Cystoscopic and Fracture Rooms
Patient Rooms
Intensive Care Unit
Administrative and Service Areas
Leather
Drying
Storage, Winter Room Temperature
Lenses (Optical)
Fusing
Grinding
Temperature
°F°C
70 – 80
70 – 74
71.5 – 72.5
60
0 – 75
65 – 72
72
68
70
76
72
76
73
75
68
76
70
74
30 – 40
31 – 32
58 – 60
50
31 – 32
30 – 31
58 – 60
40 – 44
32 – 34
31
30 – 32
38 – 40
77
68
72
74
74
68 – 76
75
75
70 – 80
70 – 120
50 – 60
75
80
21 – 27
21 – 23
22 – 22.5
16
16 – 24
18 – 22
22
20
21
24
22
24
23
24
20
24
21
23
-1– 4
-1 – 0
14 – 16
10
-1 – 0
-1
14 – 16
4 – 7
0 – 1
-1
-1 – 0
3 – 4
25
20
22
23
23
20 – 24
24
24
21 – 27
21 – 49
10 – 16
27
27
Relative
Humidity
%RH
40 – 60
40 – 60
43 – 47
35 – 40
45 – 60
50 – 60
15
40
50 – 55
50 – 55
40 – 45
60 – 63
50
65 – 70
20 – 40
30 – 60
30 – 50
30 – 40
90
90 – 95
85 – 90
85 – 90
85
90 – 95
86 – 88
85 – 90
85 – 90
90
90 – 95
90 – 95
33
63
53
47
58
50
40 – 50
40
30 – 50
75
40 – 60
45
80
10-10
Page 24
2008-10-01
Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Product and/or Process
Libraries and Museums
Normal Reading and Viewing Rooms
Rare Manuscript Storage Vaults
Art Storage Areas
Matches
Manufacture
Drying
Storage
Meat and Fish
Beef (Fresh)
Beef, Fish, Lamb and Pork (Frozen)
Fish (Fresh)
Lamb and Pork (Fresh)
Mushrooms
Sweating-out Period
Spawn Added
Growing Period
Storage
Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Product and/or Process
Textiles
Opening and Picking
Cotton
Man-Made
Carding
Cotton
Wool
Man-Made
Silver and Ribbon Lapping
Cotton
Man-Made
Combing
Cotton
Wool
Man-Made
Drawing
Cotton and Wool
Man-Made
Roving
Cotton
Man-Made
Spinning
Cotton
Wool
Man-Made
Winding and Spooling
Cotton
Wool
Man-Made
Twisting
Cotton
Man-Made
Warping
Cotton
Wool
Man-Made
Knitting
Cotton
Man-Made
Weaving
Cotton
Wool
Man-Made
Tobacco
Cigar and Cigarette Making
Softening
Stemming and Stripping
Filler Tobacco Casing and Conditioning
Filler Tobacco Storage and Preparation
Wrapper Tobacco Storage and Conditioning
Temperature
°F°C
75 – 80
70 – 75
75 – 80
75 – 80
70 – 75
75 – 80
70 – 75
75 – 80
75 – 80
70 – 75
75 – 80
70 – 75
75 – 80
70 – 75
75 – 80
75 – 80
70 – 75
75 – 80
75 – 80
70 – 75
75 – 80
70 – 75
75 – 80
75 – 80
70 – 75
76
76
75 – 80
75 – 80
70 – 75
70 – 75
90
75 – 85
75
78
75
24 – 27
21 – 24
24 – 27
24 – 27
21 – 24
24 – 27
21 – 24
24 – 27
24 – 27
21 – 24
24 – 27
21 – 24
24 – 27
21 – 24
24 – 27
24 – 27
21 – 24
24 – 27
24 – 27
21 – 24
24 – 27
21 – 24
24 – 27
24 – 27
21 – 24
24
24
24 – 27
24 – 27
21 – 24
21 – 24
32
24 – 29
24
26
24
Relative
Humidity
%RH
55 – 70
50 – 55
50 – 55
60 – 70
50 – 60
55 – 60
55 – 65
55 – 65
65 – 75
55 – 65
50 – 60
50 – 60
50 – 60
50 – 60
35 – 60
50 – 55
50 – 65
55 – 65
55 – 60
60 – 65
50 – 65
50 – 65
55 – 70
50 – 65
50 – 65
60 – 65
50 – 60
70 – 85
50 – 60
60 – 70
55 – 65
85 – 88
70 – 75
75
70
75
10-10
Page 26
2008-10-01
Figure 2. Psychrometric Chart
10-10
Page 27
2008-10-01
2.STEAM ABSORPTION AND DISTRIBUTION
A.VARIABLES THAT AFFECT ABSORPTION DISTANCES
(1) This manual will help in the design of a steam distribution system to provide the
optimum performance from the humidifier and absorption of steam within the duct
system.
(2) Experience has shown that absorption of steam is affected primarily by the
psychrometric conditions of the air based on how much residual capacity at a given air
volume and temperature exist to hold the moisture being introduced.
(3) To properly introduce steam into an air stream, five variables must be known:
(a) Temperature (°F or °C). If the air temperature varies, pick the lowest temperature.
(b) Highest humidity level before the distributor (%rh).
(c) The amount of moisture being added resulting in a change of rh in the duct or
plenum (
(d) Minimum velocity of the air (FPM).
(e) The size of the duct or plenum (cross section area).
(4) As a guide, Table 8 shows how each variable affects the absorption distance.
(5) Table 9 shows examples of typical absorption distances in air handling systems.
(6) Referring to Figure 3, ‘D’ can vary between 1 to 20 feet depending on the airflow’s:
Δ %rh).
(a) Velocity (V)
(b) Temperature (T)
(c) Humidity (H)
(7) When (V) is 500 fpm, (T) is high (90 to 130°F) and (H) is low (10% to 30% rh) the ‘D’ will
be 1 to 2 feet. As the (H) goes up ‘D’ becomes longer. Similarly, as (T) goes down, ‘D’
goes up. High velocity also increases ‘D’ by moving the steam further down stream
before it can mix. Multiple distributors will shorten the steam absorption distance.
Table 8. Variables That Affect Absorption Distances
Variables
Air Temperature ↑
Air Temperature ↓
Air Humidity ↑
Air Humidity ↓
Large Increase of RH
Small Increase of RH
High Air Velocity (1000 fpm or above)
Low air Velocity (between 100 and 500 fpm)
Small Duct or Plenum (short distributor)
Large Duct or Plenum (long distributor)
Effect On Absorption Distance
(NOTE: ↑ Increase ↓ Decrease
↓
↑
↑
↓
↑
↓
↑
↓
↑
↓
10-10
Page 28
2008-10-01
Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier
FPM°F°C% RHFTCM
(V)(T)(H)(D)
5007021303.091Air handler before coils
5005 513804.5137Air handler after cooling
9007 021303.5107Supply air duct, on cool, no heat
9005513706.0183Supply air duct, on cool
10005513908.0244Supply air duct, on cool with high humidity
100011043102.576Supply air duct, on heating with low humidity
10007021454.0123Return air duct conditions
200055134510.0305Supply air duct higher pressure system
500014060102.061After operating heating coil
(V) = Velocity at distributor location (T) = Temperature at distributor location
(D) = Absorption distance (visible steam) (H) = Humidity level after steam is absorbed
NOTE: This chart is for reference only; multiple distributors can reduce absorption distances.
T ypical System
Figure 3. Steam Distributor Location
10-10
Page 29
2008-10-01
B.CALCULATING THE DOWN STREAM HUMIDITY LEVEL
(1) Table 10 indicates the amount of water that each 1000 CFM of duct air holds in pounds
of water per hour at various combinations or air temperature and relative humidity.
Subtract the water vapour in the duct air before the steam distributor from the
maximum allowed after the distributor. The chart indicates how many lbs/hr of water
can be added to 1000 CFM of airflow.
Table 10. Water (lbs/hr) Contained in 1000 CFM of Air
3000 CFM air handler with 60°F and 30% rh air before the steam distributor.
Calculate the maximum rate of steam addition without exceeding 80% rh in the duct.
60° & 80% = 39.76 lbs/hr
60° & 30% = 14.91 lbs/hr
____________________
24.85 lbs/hr can be added to 1000 CFM
x 3 (3000CFM)
____________
74.55 lbs/hr can be added to 3000 CFM
If the load calculation of this system requires a 100 lbs/hr unit, then due to the above
possible conditions, the project requires a modulating high limit humidistat to limit the
humidifier output to a maximum of 74 lbs/hr and maintain 80% rh.
Example 2:
Humidification load is 30 lbs/hr. To avoid exceeding 80% rh in the duct, calculate the
minimum allowable CFM at 55°F. Duct conditions are 55°F and 50% rh.
55° & 80% = 33.53 lbs/hr
55° & 50% = 20.95 lbs/hr
____________________
10-10
Page 30
2008-10-01
12.57 lbs/hr can be added to 1000 CFM
(30 lbs/hr ÷ 12.57) x 1000 = 2386 CFM minimum
NOTE
Maximum capacity of the NHTC/NHPC humidifier can be limited through the keypad.
C.CONTROL OF DUCT OR PLENUM SATURATION
(1) NORTEC always recommends the use of a high limit humidistat set at 85% relative
humidity in combination with an air-proving switch to assure air movement. Both of
these controls are wired in series across the primary control terminals of the humidifiers
so that should either of these conditions not be satisfied the hu midifiers cannot operat e.
(2) Low temperature, shallow ducts or branch ducts might require a field supplied
condensate drain pan and should be accessible to service and inspection (See
Figure 4.).
(3) The most effective method of ensuring controlled absorption distances is to install a
modulating high limit humidistat. By controlling the down stream [after distributor(s)]
humidity levels and modulating the humidifier’s output, one of the variables affecting
absorption distance is now a constant. NORTEC recommends modulating high limit
humidistats on all economizer systems, VAV, VVT, and systems, which are primarily
cooling.
Figure 4. Condensate Drain Pan
10-10
Page 31
2008-10-01
3.STEAM RUNS AND CONDENSATE RETURNS
A.STEAM RUNS
(1) Steam runs between the humidifier and the distributors can be accomplished by using
flexible NORTEC steam hose or insulated copper pipe. The longer the steam run,
including elbows, the lower the efficiency of the system. The more elbows and turns,
the higher the losses become. The humidifier should be as close as possible to the
distributor and the steam run should be as direct as possible.
(2) Guidelines for installation are:
(a) Locate humidifier as close as possible to the duct system.
(b) NORTEC steam hose should only be used on short steam runs below 10 feet.
(c) Minimize elbows and turns.
(d) Ensure that no condensate produced in the steam line will remain trapped. Steam
naturally flows upward and condensate naturally flows downward. Always slope
the steam run towards the steam source at a 15°
(e) Oversize condensate line and steam line of long runs (consult your
representative).
(f)See material recommended for use in Table 11. To eliminate corrosion, NORTEC
does not recommend the use of steel piping.
(g) Consult Table 12 and Table 13 for steam and condensate sizing guidelines when
using steam distributors.
pitch no more (See Figure 5.).
Figure 5. Proper Slope
see Fig 9 for proper P Trap design and installation
10-10
Page 32
2008-10-01
Figure 6. Drain Tee
Table 11. Steam Line Material
Steam HoseCopper TubeStainless Steel Tube
Short run < 10 feet (3 m)yesyesyes
Long run > 10 feet (3 m)yesyes
NOTE: Steel, Iron and aluminum tubing or pipe must not be used for the steam distribution lines with these humidifiers.
Plastic tubing and pipe also must not be used for steam distribution lines.
Table 12. Recommended Material and Size for Steam Run
LoadSteam Run
lb/hrkg/hrftm
0-300-130-100-3Copper Tube¾" MED-L
0-300-1310 +3 +Copper Tube1"MED-L Tubing
0-300-130-100-3Stainless Steel
0-300-1310 +3 +Stainless Steel
30-10013-450-200-6Copper Tube1½" MED-L
30-10013-4520 +6 +Copper Tube2"MED-L Tubing
30-10013-450-200-6Stainless Steel
30-10013-4520 +6 +Stainless Steel
NOTE: Options shown in a bold-italic font require that reducers be used at both ends. These extra large sizes are to
allow for better condensation removal in long steam runs. These sizes do not permit the use of hose couplings
to connect either humidifier or distributors.
NOTE: Insulate all copper or stainless steel steam lines with minimum one inch high temperature insulation.
Steam Line
Material
Tube
Tube
Tube
Tube
Steam Line
Description
Tubing
(f" OD)
(1c" OD)
f" Tube x
0.049" thick.
1c"Tube x
0.049” thick.
Tubing (1e"
OD)
(2c"OD)
1¾" Tube x
0.065" thick.
2" Tube x
0.065" thick.
Table 13. Recommended Condensate Line at Distributor(s)
* Use one inch copper steam supply for longer runs.
** Use two inch copper steam supply for longer runs.
NOTES: 1. This table gives the maximum recommended length of steam run by unit size.
2. The use of any steam line other than copper or NORTEC supplied steam hose will void the warranty and
may adversely effect the operation of the humidifier.
(4) Steam lines should slope upwards from the humidifier to the steam distributor. (See
Figure 7.)
(5) Flexible steam hose, if used, must be supported to avoid crimps, bends, and sags.
(Please consult local agent if proper slopes are not available.)
(6) If the steam supply line must be routed below the humidifier location, a condensate trap
‘tee’ will be required to prevent blockage at the low point in the steam line. Run the
condensate hose to the nearest floor drain after trapping. (See Figure 8.)
(7) Long steam runs with improper slopes can produce spitting at the distributor because
the steam is travelling at a high velocity and will push condensate out the distributor. If
a slope of 2" for every 12" of steam run cannot be achieved, then condensate must be
removed before the distributor. (See Figure 4.)
B.CONDENSATE RETURN
(1) Each steam distributor has a built-in condensate return. (See Figure 9.) Flexible
condensate return hose (available from NORTEC) is recommended for routing
condensate back into the humidifier’s fill cup, or to a drain. A short length of d" OD
copper tubing is supplied by NORTEC when routing condensate hose back to the fill
cup. Similarly, a short length of d" condensate hose is supplied to serve as a flexible
coupling with field-supplied copper condensate line. Long condensate runs should be
drained to a floor drain to prevent excessive condensate water from entering the
cylinder.
NOTE
Excessively long steam runs (over 20 feet) may require the use of ½" OD condensate
return lines – supplied by others.
10-10
Page 34
2008-10-01
(2) Use vertical condensate leg of
distributor only. Do not
over-tighten clamp.
(3) Drip stations on steam mains must
be located at all low points in the
system, at each elevation change
and or directional change.
(4) Horizontal runs of steam must
have a 2" rise per foot (10°) when
flow is going away from drip station
and the steam run is to fall ½" per
foot (2°) when flow is going
towards drip station.
(5) In a horizontal run of the steam
main, drip stations must be located
at regular intervals of 20 feet.
(6) The drip station itself is a section
of piping connected to the bottom
of the main. A full size tee must be
used to create a drip station to
allow the condensate to fall in the
drip station.
Figure 7. Steam Line Connection
Figure 8. Condensate Tee At Any Low Point
In Steam Line
Figure 9. Trap To Prevent Steam In
Condensate Line
10-10
Page 35
2008-10-01
(7) Vertical drop of the drip station should be 1.5 times the diameter of the steam main but
no less then 12".
(8) Install the P trap at the botom of the drip station. The P trap height is to be a minimum
of 6 inches or 2 “ greater than the static pressure in the duct.
(9) All distributors must be individually trapped.
10-10
Page 36
2008-10-01
4.STEAM DISTRIBUTORS (ASD, BSD, CSD)
A.STEAM DISTRIBUTORS
(1) NORTEC’s steam distributors, in use for over twenty years, are a proven design to suit
applications for the introduction of atmospheric steam.
(2) Features and benefits of steam distributors are:
(a) Expanded diameter of tube to reduce steam velocity and the potential for
condensate carryover into the duct.
(b) Positive removal of condensate.
(c) Lower mass of metal (stainless steel), which reduces ‘radiator effect and
condensate’ and results in higher efficiency of humidifier output while reducing
condensate formation.
(d) Designed specifically for atmospheric steam generation.
(e) Modular so that the exact quantity of distributors can be configured to meet
specific application requirements. This reduces system complexity and installation
costs.
B.DISTRIBUTOR CHARACTERISTICS
(1) NORTEC steam distributors are constructed of stainless steel and include in low point
condensate return to prevent the condensate from collecting in the steam distributor.
This enables entrained condensate to settle to the bottom of the steam distributor
where it is removed by the condensate return. These features allow the NORTEC
steam distributors to be installed level in the duct, thereby utilizing the full available
width of the duct. (See Figure 10.)
Figure 10. Levelling the Distributor
10-10
Page 37
2008-10-01
(2) Ensure the total capacity of the humidifier is not higher than the allowable maximum
steam capacity of the following distributors:
(a) ASD: 25 lbs/hr (9 kg/hr)
(b) BSD: 35 lbs/hr (13 kg/hr)
(c) CSD: 115 lbs/hr (45 kg/hr)
C.DISTRIBUTOR LOCATIONS AND MOUNTING
(1) NORTEC distributors can be mounted in air handlers, supply air ducts or return air
ducts. Return air ducts should only be considered if all of the return air enters the
building again and is not exhausted by the air handling device. Distributors should be
mounted center or low within the duct or plenum. (See Figure 11.) Laminar airflow is
best. Down stream obstruction must be considered. The non-absorbed steam may
affect devices like smoke detectors down stream. Total steam absorption must be
accomplished before filters and silencers.
(2) Distributors come complete with a mounting plate. (See Figure 12.) Most ducts and
plenums are rigid enough to support the distributor.
(3) Longer distributors (more than 36") and distributors mounted on lighter gage sheet
metal which cannot support the distributor level in the duct will need to b e supported on
the end. (See Figure 10.)
D.MULTIPLE DISTRIBUTOR APPLICATIONS
(1) The use of multiple steam distributors can reduce the absorption distance in most
situations. Distributors can be manifolded together to create a grid to achieve shorter
absorption distances. (Consult agent and/or see Nomogram Figure 13.
CAUTION
THESE INSTALLATION
GUIDELINES APPLY FOR DUCT
VELOCITIES UNDER 2000 FT/
MIN (610 M/MIN), PLEASE
CONSULT FACTORY FOR
HIGHER VELOCITIES
CAUTION
PLEASE MAKE SURE NO
OBSTACLES (ELBOW, FILTER,
OR DIFFUSER) ARE LOCATED
AFTER THE DISTRIBUTOR IN
THE DIRECTION OF THE
AIRFLOW CLOSER THAN THE
ABORPTION DISTANCE
CALCULATED FOR YOUR
APPLICATION.
CAUTION
FOR APPLICATIONS WITH
HIGH STATIC PRESSURES
PLEASE CONSULT FACTORY
Figure 11. Single Steam Distributor
Installation – Minimum Clearance
10-10
Page 38
2008-10-01
Figure 12. Cutting Duct For Mounting
Figure 13. Humidification Distance Nomogram
10-10
Page 39
2008-10-01
CAUTION
UNLESS YOU KNOW THE EXACT ABORPTION DISTANCE
REQUIRED FOR THE STEAM ABSORPTION INTO THE AIR STREAM,
THE DISTRIBUTOR SHOULD BE LOCATED AT LEAST 8-10 FT (2-3 M)
AWAY FROM ANY OBSTACLE IT MAY CONDENSE ON (ELBOW,
DIFFUSER, FILTER, ETC.)
(2) Duct vertical clearance requirements for standard steam distributors are as follows:
(a) ASD - 8 in. vertical duct height for 1st ASD
- 5.5 in. additional duct height for each additional ASD
= ROUNDDOWN (‘DuctHeight’ - 8")/5.5) + 1
(b) BSD - 10 in. vertical duct height for 1st BSD
- 6.375 in. additional duct height for each additional BSD
= ROUNDDOWN (‘DuctHeight’ - 10")/6.375) + 1
(c) CDS - 14 in. vertical duct height for 1st CSD
- 9 in. additional duct height for each additional CSD
= ROUNDDOWN (‘DuctHeight’ - 14")/9) + 1
NOTE
These requirements apply to vertical arrangements of multiple distributors ONLY.
Diagonal arrangements utilize an alternative method.
E.LOCATION OF STEAM DISTRIBUTORS WITHIN AN AIR HANDLER
(1) Humidify after the heating
coil (H/C) so that absorption will
occur in the 3 to 4 feet before the
cooling coil (C/C). If steam carries
over and condenses on the coil,
any excess water will be drained
away. There is little chance of
condensation on the blower,
blower motor, or fan isolation
components, especially if you use
a modulating high limit humidistat.
All steam distributors should be 8"
from the H/C and evenly spaced. If
wetting is a problem, add more
steam distributors. (See
Nomogram Figure 13 and
Figure 14).
F.DISTRIBUTOR ABSORPTION
DISTANCE
(1) The water vapor discharged from
the steam distributor must be
adequately mixed with air to
prevent condensation on
downstream components. The
nomogram in figure 13 will
Figure 14. Best Location for Multiple Steam
Distributors in AHU
10-10
Page 40
2008-10-01
determine the number of steam distributors that must be use for short saturation
distances.
(2) If the ‘Saturation Distance’ for one steam distributor is not sufficient, add more steam
distributors until the minimum saturation distance is attained. (See Figure 13.)
(3) To determine the number of distributors required, complete the following list:
(a) Air humidity after humidification _____ %rh. (A high limit humidistat should be set
at 80 – 85% to prevent wetting of ducts.)
(b) Air temperature before humidification _____.
(c) Air velocity in duct _____ ft/min.
(d) Maximum steam mass flow _____ lbs/hr.
(e) Active zone H of steam distributor _____ in. (See Figure 13.)
NOTE
The manufacturer recommends the appropriate distance modification factors when
filters or humidification sensors are installed downstream. For applications that are
outside of the Nomogram’s range, please consult a NORTEC representative.
G. TYPICAL APPLICATIONS
(1) Representations of typical applications are found in Figure 15 and Figure 16.
H.DISTRIBUTOR DIMENSIONS
(1) Distributor dimensions for the various distributor models can be found in
Chapter 10-30.
Figure 15. Roof Top Units 2-20 Tons –
Typical Location
Figure 16. Small Units On Residential
Furnaces
10-10
Page 41
2008-10-01
5.SHORT ABSORPTION MANIFOLD (SAM-e)
A.GENERAL
(1) NORTEC’s best performing steam absorption system for use in Air Handling Units and
duct systems where short steam absorption distance is critical.
(2) The SAM-e, Figure 17, distributes clean steam, precisely controlled, uniformly into the
entire air stream, void of any condensate spray. Steam distribution takes place via
distributor tubes with integrated nozzles. The steam is kept dry as condensate is
drained through the main header.
(3) The stainless steel distribution tubes are typically mounted vertically but can also be
mounted horizontally (10° slope) for vertical airflow applications. The distribution tubes
come equipped with evenly spaced stainless steel nozzles providing optimum steam
distribution, over the entire length of the tube.
(4) The nozzles extend into the center of the distribution tube ensuring only condensate
free steam is released. (See Figure 18.) Condensate drains out of the distribution
tubes, through the header, eliminating the need for jacketed tubes. A permanent bond
between the nozzle and distribution tube is made when the nozzle is pressed into the
tube. The nozzles and tubes have the same thermal expansion characteristics
guaranteeing a permanent union. The specifically sized orifices ensure consistent
output from each nozzle.
10-10
Page 42
2008-10-01
Figure 17. SAM-e Tubes
Figure 18. Cross-Section of Distributor Pipe
(5) The features of the short absorption manifold are:
(a) Inlets/Outlets located on same side, one access point required.
(b) All stainless steel distributors and nozzles ensure permanent bond.
(c) Stainless steel header with rubber grommet seals for easy installation of
distribution tubes.
(d) Adjustable mounting frame available for quick and easy installation.
(e) Available with 3", 6", 9", or 12" center-to-center distributor spacing.
(f)Atmospheric steam source.
(g) Two year limited warranty.
B.DETERMINING THE STEAM ABSORPTION DISTANCE
NOTE
Visit www.humidity.com to download our Humidification Engineering & Loadsizing
Program (H.E.L.P.) to help you calculate the absorption distance.
(1) Injecting steam into the air requires a certain amount of time before the steam is
absorbed completely.
(2) In a moving air stream, this time results in the steam moving a fixed distance from the
manifold before it is fully absorbed.
(3) Knowing the absorption distance will ensure that steam will not condense on any
critical components following the steam distribution area.
(4) The system should be designed to eliminate the possibility of wetting internal
components by positioning the manifold in the optimum location and by keeping the
absorption distance to a minimum.
(5) The absorption distance can be calculated using the Z ratio. The Z ratio and the
following method may be used as a guide to calculate the absorption in various air
handlers, and ducts with different conditions. It can be calculated as follows:
- RH
(RH
Z =––––––––––
RH
RH
ah
(100 - RH
= Percentage of relative humidity after humidification.
ah
= Percentage of relative humidity before humidification.
bh
bh
bh
)
)
Example 1:
• 55°F (12.8°C)/ 12% RH - Conditions before humidification.
3
• 20 000 CFM (33 980 m
/h)
• 400 lbs/hr (181 kg/hr) load
Using the H.E.L.P. Software or a psychrometric chart you can find that the
humidity conditions after adding 400 lbs/hr (181 kg/h) of steam, are 55°F (12.8°C)
(7) Reference Figures 19, 20, 21 and 22 to determine the center-to-center spacing
required.
NOTES
1. The absorption distance data is based on 55°F (13°C) minimum temperature
before humidification.
2. Data is based on velocities between 200 fpm (101 cm/s) and
2500 fpm (1270 cm/s).
3. Absorption distance: This is the distance between the SAM-e and the first
obstruction (coil, elbow, damper, etc.) and the first obstruction steam may hit.
Traces of steam may pass this obstruction, but will not condense, leaving
obstructions dry.
4. If any of the duct AHU conditions are changed, the absorption distance may
change due to increase or decrease in duct temperatures, amount of fresh air,
various outside conditions, set point requirements, etc. If this occurs, re-calculate
the absorption distance, and determine if the SAM-e needs to be modified or
relocated.
C.STATIC AIR PRESSURE
(1) Table 15 shows the static pressure loss created by a SAM-e in various velocities.
(2) NORTEC recommends the installation of a condensate drain on the steam inlet run
prior to entering the SAM-e.
Table 16. Condensate Loss
Air Velocity fpm (cm/s)
500 (255) 15% 12%
1000 (510) 20% 15%
NOTE: These values may increase or decrease due to many unknown conditions or variables. This is only a guideline.
Condensate Losses (% of Maximum Capacity)
55°F 70°F
E.CORRECT CHOICE OF PRODUCT APPLICATIONS (WITHIN SAM-e)
(1) The SAM-e has been designed exclusively for use in building ventilation duct systems,
where manufacturing, processing and hi-tech activities are conducted. Applications that
do not conform to the design parameters are not recommended and will be at the
user’s own risk. NORTEC produces a wide range of different humidification systems to
suit virtually all normal applications, and will be happy to recommend the most
appropriate system to suit each particular requirements.
F.SAM-e DIMENSIONS
(1) Dimensions for the SAM-e and mini SAM-e can be found in Figure 6 and Figure 7 in
Chapter 10-30.
G. SAM-e HEADER SELECTION
(1) NORTEC offers different ranges of manifolds to cover capacities and duct sizes. The
absorption distance and capacity required will determine the center to center spacing
between each steam tube on the header. There are four options: 3" (7.6 cm),
6" (15.2 cm), 9" (22.9 cm) or 12" (30.5 cm). The smaller the spacing, the more tubes
the header can accommodate, thus giving a better absorption distance and greater
capacity. (See Tables 17 to 20.)
(2) The header remains the same for in-duct or outside duct mounting, for atmospheric
steam, and for vertical or horizontal flow applications. (See Figure 23.)
(3) Atmospheric manifolds with a capacity over 801 lbs/hr (362 kg/hr) will include a second
steam inlet on the header. Consult factory submittal drawings for specific details.
(4) Select the header part number associated with your duct or air handling unit’s width.
For example, if the duct width is 80" (198.11 cm), select part number 150-3279 for
3" (7.6 cm) center-to-center spacing.
H.SAM-e STEAM TUBE SELECTION
(1) Constructed of 1.5" (3.81 cm) OD 304 stainless steel tubing, the steam tubes can
accommodate duct heights between 18" (45.72 cm) - 144" (365.76 cm) for in-duct
header mounting. For smaller duct applications, a mini SAM-e can accommodate sizes
starting at 12" (30.5 cm) wide x 8" (20.3 cm) high. (See Figure 20.) Each steam tube
has a different amount of stainless steel nozzles to evenly disperse steam into the duct
or air handling unit. The nozzles take the steam from the center of the tube, elimina ting
any need for jacket heating, and a temperature switch. All the accumulating
condensate is drained vertically down to the main header, and then out the condensate
drain. NORTEC’s unique ‘slip in’ installation method makes for a very quick and
effortless assembly. (See Figure 24.)
10-10
Page 46
2008-10-01
(2) There is a selection of four types of
steam tubes. Each are capable of
distributing different capacities. To
select the steam tube for your
application refer to Table 17.
Type A 15 lbs/hr (7 kg/hr)
Type B 35 lbs/hr(16 kg/hr)
Type B+ 55 lbs/hr (25 kg/hr)
Type C 75 lbs/hr (34 kg/hr)
(3) The humidifiers maximum capacity
and SAM-e header will determine
the steam tube type required. The
selected header will determine
how many steam tubes are
required, refer to Tables 18, 19, 20
and 21. Remember to calculate
your condensate losses.
Figure 23. SAM-e Header
Figure 24. SAM-e Tubes
Figure 25. Steam Inlet
10-10
Page 47
2008-10-01
I.SAM-e STEAM INLET CONFIGURATION SELECTION
(1) Atmospheric Steam (NH, GS, SE)
(a) The steam inlet, Figure 25, is determined by the selected humidifier. Refer to
submittals, Chapter 10-30 to determine the size of steam outlet required.
(b) For a typical SAM-e installation, see Figure 26.
J.MINI SAM-e
(1) For the mini SAM-e installation, refer to Tables 18, 19, 20 and 21 for headers, tubes
Table 21. Mini Inlet Configurations – For Atmospheric Steam Unit
SAM-e Steam InletPart Number
f" OD1509839
1¾" OD1509837
2 X 1¾" OD1509838
10-10
Page 49
2008-10-01
Figure 26. Typical SAM-e Installation for Atmospheric Steam Applications
10-10
Page 50
2008-10-01
6.BLOWER PACKS (BOBP, RMBP)
STEAM DISTRIBUTOR ON THE BUILT-ON AND REMOTE BLOWER
PACKS HAVE A HOT SURFACE THAT COULD RESULT IN BURNS IF
TOUCHED. NORTEC RECOMMENDS MOUNTING AT LEAST 8 FEET
ABOVE THE FLOOR.
A.BLOWER PACKS
(1) Optional blower packs are used to distribute steam to localized areas such as computer
rooms or in areas that do not have a built-in air distribution system.
(2) Blower packs are available integrally mounted on humidifier BOBP, (See Figure 27.) or
detached and field-piped and wired to humidifier RMBP. (See Figure 28.)
(3) Blower packs consist of a matching powder coated steel cabinet containing: three axial
blowers with finger guards powered by 120 VAC or line voltage humidifiers, with built-in
multi-tap transformer (when necessary), fuse, high temperature plastic distributor with
stainless steel lid, horizontal and vertical adjustment knobs for directional control, builtin thermostat to activate blowers, speed control rocker switch and safety loop relay.
(4) Refer to Table 22 for ceiling and frontal clearances required for blower packs.
Dimensions apply to both built-on and remote-mounted versions of blower packs.
(5) Mount remote blower pack(s) using factory supplied wall mounting bracket with
clearances as recommended in Table 22.
WARNING
Figure 27. NH Series Humidifier With
Built-On Blower Pack
Figure 28. NH Series Remote Mounted
Blower Pack
10-10
Page 51
2008-10-01
Table 22. Ceiling and Frontal Clearances for Blower Packs
NOTES: 1. Remote mounted only. Four remote mounted blower packs are recommended on the 200 model.
2. Clearances based on 72°F at 35% RH.
Minimum Number Of
Blower Packs
Minimum Ceiling Clearance
in. (cm)
Minimum Front Clearance
in. (cm)
10-10
Page 52
2008-10-01
7.CONTROLS
A.GENERAL
(1) NORTEC humidifiers all accept on/off controls for their security loop. Many NORTEC
humidifiers can also accept modulating or transducer signals for control (See the
features section for each specific model).
REGARDLESS OF SELECTING ON/OFF OR MODULATING CONTROL
METHOD, NORTEC HUMIDIFIERS MUST HAVE CLOSED CIRCUIT
ACROSS ITS ON/OFF SECURITY LOOP CONTROL TERMINAL TO
OPERATE. NORTEC HIGHLY RECOMMENDS THE USE OF A HIGH
LIMIT HUMIDISTAT AND AN AIR PROVING SWITCH IN SERIES FOR
THIS FUNCTION.
B.ON/OFF CONTROLS
(1) On/Off controls are used in all NORTEC humidifier security loops. The digital
humidistat can also be used as a space humidity controller. These controls include:
CAUTION
(a) Air Proving Switch
point from 0.07 IWC to 12.0 IWC, good for positive, negative or differential
pressure applications, stops humidifier if duct air pressure is not sensed. Turns
humidifier off if air handler fails.
(b) Duct Mounted Digital Humidistat
15-90% rh with accuracy fixed at ±3% at 25°C
on humidity drop for control and opens on rise for high limit duct application.
(c) Wall Mounted Digital Humidistat
15-90% rh with accuracy fixed at ±3% at 25°C
on humidity drop for control and opens on rise for high limit application.
(d) On/Off Controls Supplied by Others
of contacts capable of passing a 24-VAC, 2-A maximum signal.
C.MODULATING CONTROLS
(1) Modulating Controls are used to send a modulating demand signal to the NORTEC
humidifier. Different models can accept different signals (see features section for each
specific model) NORTEC supplied controllers send a 0-10 VDC demand signal. This
signal can be used as a control and in some models can also be used as a modula ting
high limit. These controls include:
(a) Wall Mounted Digital Humidistat with Integrated Sensor
adjustable set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outpu ts a
0-10 VDC signal.
– duct mounted, pressure differential switch, adjustable set
– control or high limit, adjustable set point from
, operating range of 0-95% rh, closes
– control or high limit, adjustable set point from
, operating range of 0-95% rh, closes
– Can be used as long as they have a dry set
– control or high limit,
(b) Wall Mounted Digital Humidistat Without Sensor
set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outputs a 0-10 VDC
signal. Requires a remote transducer sensor supplying a 2-10 VDC signal.
(c) Duct Mounted Digital Humidistat With Sensor
remote sensor and a wall mounted controller without sensor. Control or high limit,
adjustable set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outpu ts a
0-10 VDC signal.
– control or high limit, adjustable
– This package comes with both a
2008-10-01
10-10
Page 53
(d) Modulating Demand Signal Supplied by Others – A signal that is a linear demand
signal that rises on need for humidity can be used in conjunction with NORTEC
humidifiers. See features section for a list of which models can accept which
signal)
D.OUTDOOR TEMPERATURE SETBACK
(1) The outdoor temperature setback sensor is used to prevent condensation on windows
or other surfaces that are adjacent to outdoor air. This sensor can be used in
conjunction with the NORTEC controls mentioned above (both the on/off and
modulating demand signal controllers) The sensor allows the controller to override the
set point to prevent the humidifier from humidifying when condensation could be
possible. (See Figure 29.) Locate the temperature sensor near the fresh air intake. This
will ensure accurate representation of the outdoor air temperature.
E.TRANSDUCER SENSORS
(1) Transducer Sensors are signals sent back to either a controller or back to the
humidifier. Limited models can accept a direct transducer signal. (See features section
for each specific model) The sensors include:
(a) Wall Mounted Humidity Transducer
95% rh.
(b) Duct Mounted Humidity Transducer
95% rh.
(c) Transducer Sensor By Others
rh in the room.
– Humidity sensors that rise linearly with the sensed
– Sensor, output of 2-10 VDC, range of 0 to
– Sensor, output of 2-10 VDC, range of 0 to
10-10
Page 54
2008-10-01
Figure 29. Set Point Versus Outdoor Temperature
F.POSITIONING CONTROLS AND SENSORS
(1) When positioning controls and sensors, ensure other factors do not influence these
devices and give incorrect inputs to the unit. Some of these influences are:
(a) The wall humidistat should not be installed on an outside wall or hot or cold
surface.
(b) The sensor should be installed away from any heat source and away from direct
sunlight and away from any water vapor producing source.
(c) The wall surface should be flat and clean.
(d) Any draft originating from the wall interior should be prevented from interacting
with the humidity sensor. A vapor barrier should be installed.
(e) Location of sensor must be representative of space humidity therefore avoid
drafts, temperature variation or overhangs that may prevent the sensor from
sensing an accurate representation of the space humidity.
(f)Duct sensors should be placed in a location that assures any and all absorption
has been accomplished.
G. NORTEC ONLINE
(1) NORTEC OnLine enables secure, internet based monitoring, simplifies interoperability
and automated email service notification. Using standard Internet Explorer, version 6.0
or newer, NORTEC OnLine provides both monitoring and control, from any location
with Internet access, for a period of one year. (See Figure 30.) During the service
period, NORTEC OnLine will also generate automatic e-mails when scheduled service
is required and/or abnormal operation occurs. Up to three customer(s) e-mail
addresses may be added to the automatic notification feature, to provide instant
notification.
(2) NORTEC OnLine factory technicians will remotely view each humidifier weekly and
record key status information, which will be used for an annual report to the key
customer contact. This contact will also receive notification of corrections, or service
recommendations from the NORTEC OnLine technician responding to automated
e-mail notifications.
(3) The factory-installed NORTEC OnLine controller is located internally to the humidifier.
(4) Key features of NORTEC Online include:
(a) Graphical representation of humidifier performance
(b) Enable/disable humidifier
(c) Adjust %rh set point(s), if equipped
(d) Adjust manual Limited Capacity
(e) Automated e-mail advisories for scheduled service or abnormal conditions
(f)Up to fifty incidents, of factory direct support and follow-up
(g) First year of remote access includes factory direct monitoring
(h) Weekly checks by NORTEC OnLine factory technicians
(i)Remote factory diagnostics and programming capability
(j)Individual account access to www.norteconline.com
(k) Monitor up to seventy parameters from each humidifier
.
10-10
Page 55
2008-10-01
10-10
Page 56
2008-10-01
Figure 30. NORTEC OnLine Monitoring
(l)Access to service history
(m) Option to add up to seven slave humidifiers to each NORTEC OnLine module
(n) Monitor up to eight humidifiers (one master, seven slaves) with one Internet
connection
(o) Up to three years of coverage can be purchased at time of order
(p) Secure 128-bit Internet connectivity (SSL)
(5) Different networking configurations may be achieved and are mostly dependant on the
type of network present at the site. Specify at the time of order using the form in
Figure 31. Connection options include:
(1) Provides a network connection to a BMS system using one of the following protocols:
(a) BACnet IP
(b) BACnet MSTP
(c) LonWorks
(d) Modbus (Standard on the NHTC and NHTC Outdoor)
(e) Johnson N2.
(2) NORTEC Links provides monitoring and control allowing humidifier(s) to communicate
to your Building Management System (BMS). The controller is factory installed and is
located internally to the humidifier. NORTEC Links can be integrated with NHTC,
NHSC/DI, GSTC/SETC technologies. Simply specify at time of order, using the form in
Figure 32, what operating protocol you are using BACnet IP, BACnet MSTP,
LonWorks, Modbus or Johnson N2.
(3) Some features of NORTEC links are:
(a) Digital feedback for unit standby/humidifying mode.
(b) Digital feedback for service required.
(c) Digital feedback for fault indication.
(d) System demand display.
(e) Control enable/disable.
(4) Combined with direct sensor connection to either the humidifiers or BMS it is also
capable of:
(a) Control room set point
(b) Control high limit set point
(c) Control room %rh
(d) Control high limit %rh.
10-10
Page 57
2008-10-01
I.TYPICAL INSTALLATION LAYOUT FOR NHTC/NHPC
(1) The following are examples of typical control installation possibilities. There are many
more configurations possible, be sure to consider the application and positioning as a
priority. Figures 33, 34, 35, and 36 show typical control installation.
J.NORTEC CONTROLLER DIMENSIONS
(1) See dimensions in Chapter 10-30.
10-10
Page 58
2008-10-01
NORTEC ONLINE CONFIGURATION FORM
Please complete the information below.
Attention:Date:
Company:Fax #:
From:Page:of
Subject:NORTEC Online Information
G FOR YOUR INFORMATIONG RESPONSE REQUESTED
Agent P.O. Number: ____________________Sales Order Number: ____________________
Time Zone:____________________
Company Name:____________________
Address:____________________
____________________
____________________
Phone Number:____________________
Main Contact Person: ____________________
Unit 8
Figure 31. NORTEC Online Configuration Form
10-10
Page 59
2008-10-01
NORTEC LINKS FORM
Please complete the information below.
Attention:Date:
Company:Fax #:
From:Page:of
Subject:NORTEC Links Information
G FOR YOUR INFORMATIONG RESPONSE REQUESTED
MESSAGE
Agent P.O. Number: ____________________Sales Order Number: ____________________
Desired NORTEC Links Option:
BACnet/IP
BACnet/MSTP
Johnson N2
LonWorks
Humidifier Ordering:
Humidifier
Model/Size
Settings for BACnet/IP only:
Default Gateway Address:____________________
Network Number:____________________
Subnet Mask:____________________
Module IP Address:____________________
Desired Unit Order
Lead Humidifier
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
Unit 9
Unit 10
Unit 11
Unit 12
Unit 13
For all GS/SE humidifiers equipped with
NORTEC Links and NH units with BACNET/IP.
Figure 32. NORTEC Links Form
10-10
Page 60
2008-10-01
Figure 33. Humidifier Controlled by Air Proving, On/Off Duct Mounted High Limit and
Modulating Wall Mounted Space Controller
Figure 34. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and
Modulating Wall Mounted Space Controller
10-10
Page 61
2008-10-01
Figure 35. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and
Modulating Wall Mounted Return Air Sensor with Wall Mounted Controller
Figure 36. Humidifier Controlled by Air Proving, Duct Mounted High Limit Sensor and
Modulating Duct Mounted Return Air Sensor with Networking Option
10-10
Page 62
2008-10-01
10-20
SPECIFICATIONS
10-20
Page 63
2008-10-01
1.HUMIDIFIERS
A.GENERAL
(1) Work Included
(a) NORTEC NH Series electrode steam humidifier(s) as indicated on drawing(s) and
as indicated on schedule(s).
(b) Complete and operable humidification system (which meets applicable building
codes).
(c) Equipment start-up and project inspection by qualified factory trained
representative.
(2) Submittals
(a) Submit product data under provisions of Section 15010. Include product
description, model, dimensions, component sizes, rough-in requirements, service
sizes, and finishes. Include rated capacities, operating weights, furnished
specialties, and accessories.
(b) Include piping details, plans, elevations, sections, details of components, and
dispersion tubes. Submit wiring diagrams including power, signal, and control
wiring.
(3) References
SPECIFICATIONS
(a) Certifications, C-UL_US Listed.
(b) ISO 9001-2000.
(c) ANSI/NFPA 70 – National Electrical Code.
(d) ARI 640, ‘Standard for Commercial and Industrial Humidifiers’.
(e) ASHRAE SSPC 135 BACnet, ANSI/EIA 709.1 LonTalk.
(4) Warranty
(a) Product shall be warranted to be free from defects in material and workmanship for
a period of two years after installation or 30 months from manufacturers ship date,
whichever date is earlier. If operating with NORTEC web-based service program
warranty is extended to 42 months from ship date.
B.PRODUCTS
(1) Electrode Steam Humidification System – NORTEC Model NHTC
(a) NORTEC NHTC electrode steam generating system using regular type potable
water supply.
(b) Packaged unit, wall mounted, requiring steam distributor(s) or Short Absorption
Manifold(s) for mounting into AHU/duct(s) or Remote/Built-On Mounted Blower
Pack(s) for direct space applications. Refer to Humidifier Dispersion Options in
paragraph B.(4).
(c) Atmospheric pressure steam generation and mineral separation contained within
an electrode steam cylinder(s). Resistive element technology and boiler steam
(pressure steam) technology not acceptable. The disposable electrode steam
cylinder shall have:
1
Published life expectancy.
10-20
Page 64
2008-10-01
2Published replacement pricing.
3
Cylinder seams must be spin welded to ensure long-term water tightness and
leak resistance.
4
Integral electronics to ensure safe operation.
5
High water sensor circuitry to prevent over filling.
6
Efficient operation over a wide range of water conditions.
7
Simple maintenance without disassembly or removal of humidifier. No
specialized tools required.
8
Full output and maximum energy efficiency through entire cylinder life.
9
‘Drain through bottom’ to ensure highest mineral concentration is effectively
removed. Simple skimmers are not acceptable.
10
Large perforated strainer at drain outlet to prevent blockage of drain valve or
drain lines.
11
Tool-less primary electrical connection for use with factory installed, spring
loaded, gold plated connectors.
12
Safety characteristics ensuring no current flow with absence of water,
independent of safety controls. Resistive element not acceptable.
(d) Unit(s) to be complete with:
1
‘Total Controller’ microprocessor to control all humidifier functions with
interface capabilities for remote communication technologies, including
Internet or BMS requirements.
2
Advanced water management utilizing the patented Proportional plus Integral
Autoadaptive control system for optimal energy efficiency, water usage and
cylinder life.
3
Microprocessor controlled fill valve and drain valve allowing automatic water
management.
4
Internal drain water tempering to ensure maximum 140°F (60°C) drain water.
5
Integral fill cup with minimum 1-inch (25-mm) air gap to prevent back
siphoning.
6
Smart cylinder EPROM for improved operation providing:
a
Cylinder identification with model, data, and capacity.
Full cylinder indication and pre-notification of automatic shutdown at end of
cylinder life.
8
Automatic pulse feature to clean any obstruction from the drain solenoid valve
when needed.
9
Automatic off-season shut-down (after 3 days of ‘no call’) will completely drain
the cylinder(s) and automatically restart on call for humidity. Adjustable on/off
and time sequence. Provides extended cylinder life, while ensuring stagnant
water does not remain in the system.
10-20
Page 65
2008-10-01
10 Accepts a signal from BMS/BAS system or modulating humidistat.
11
Single or dual channel signal acceptance.
12
Isolated plumbing and electrical compartment with cabinet made of 18-gauge
powder coat paint finish and 20 gauge plumbing electrical door. Modular
plumbing and electrical fully assembled and pre-wired (no field assembly
required).
13
Removable door (no special tools required) to allow user full front access of
plumbing and electrical sections.
14
Plumbing door interlock safety switch to allow power interruption when
installing or servicing the humidifier.
15
Standard of acceptance NORTEC NHTC Series.
16
C-UL_US listed.
17
Spec
(2) Humidifier Controls (NHTC and NHTC Outdoor)
(a) Total Controller microprocessor with the following features or functions:
1
Full function user interface with touch type keypad and backlit alphanumeric
graphic display with trend log.
2
Real time clock indicating date and time with battery back up.
3
Built-in controller with adjustable set point, proportional range, and integral for
use with humidity transducers.
4
Acceptance of industry standard (analogue continuous control demand
signal [0-5 VDC] [1-5] [0-10 VDC] [0-20 mA] [4-20 mA]) relative humidity
transducers.
5
Keypad programming to configure, monitor and control humidifier parameters
on graphic backlit display
a
Relative humidity set point and actual conditions in space from humidity
transducer.
b
Relative humidity set point and actual conditions in duct for variable air
volume (VAV) applications from humidity transducer.
c
Relative humidity high limit set point and actual from humidity transducer.
d
System demand in lbs/hr (kg/hr).
e
On screen service history with date stamp.
f
On screen fault history with troubleshooting list and date stamped.
g
On screen attention indication.
h
Security loop status open/close.
i
Control Channel 1 demand %.
j
Control Channel 2 demand %.
k
Control mode (single or dual modulation).
l
Control type (demand or rh proportional, rh proportional + integral).
10-20
Page 66
2008-10-01
mManual capacity output adjustment range of 20-100%.
n
Humidifier model, capacity, software version.
o
Cylinder model # and capacity rating.
p
Humidifier run time weighted hours.
q
Date and time (year, month, day, hour and minute).
r
Stand by heating to increase steam production response time.
s
Rapid modulation capability reduces response time upon start-up.
t
Short cycling detection and correction diagnostics.
u
Foam detection and correction capability.
v
Scroll through start-up and troubleshooting checklist on graphical display.
w
Self-diagnostics during start-up to system test to prevent unsafe operation
of the unit(s).
x
User adjustable drain/flush frequency.
HUMIDIFIER CONTROLS NHPC
(b) Proportional Controller microprocessor with following features or functions:
1
Graphic function display with user interface with touch type key pad.
2
Acceptance of industry standard [analogue continuous control demand signal
[0-1Vdc] [1-5Vdc] [0-10 Vdc] [2-10 Vdc] [0-16 Vdc] [0-20 mA]
(c)
3
Keypad/Display to monitor and control humidifier parameters.
a
System demand in lbs/hr (kg/hr).
b
Security loop status open/close.
c
Control Channel 1 demand %.
d
Manual capacity output adjustment range of 20-100%.
e
Self-diagnostics during start-up to system test to prevent undase
operation of the Unit[s].
f
Control signal type.
g
Software version.
1
Internal communications via Modbus RTU protocol provides monitoring and
control allowing humidifier(s) to communicate to Building Management
System (BMS). Supporting a RS485 port with a configuration of 9600bps,
8-bits, no parity, one stop bit shall support the following variables:
a
Change Cylinder – Indicates cylinder needs to be replaced (read).
b
Channel 1 Input – Humidifier input value being supplied to channel 0100% (read/write).
c
Channel 1 Set point – Control channel 1 setpoint for relative humidity in
space 0-100% (read/write).
10-20
Page 67
2008-10-01
d
Channel 2 Input – Humidifier input value being supplied to channel 0100% (read/write).
eChannel 2 Set point – Control channel 2 setpoint for relative humidity in
space 0-100% (read/write).
f
System Demand – Indicates humidifier system demand based on input
signal calculations 0-100% (read).
g
Demand/rh_Configuration Parameter – Configures humidifier to accept
demand or %rh signal(s) (read/write).
h
Remote fault Indication – System fault indication and alarm status (read).
i
Network Sensors – Allows network-enabled sensing or control (read/write).
j
Remote Disable – Provides remote humidifier enable/disable system
control. (read/write).
k
Remote Service Indication – Provides remote humidifier service
indication (read).
l
Remote Status Indication – Provides remote humidifier on/standby
system status indication (read).
(3) Remote Monitoring And Control Options (NHTC and NHTC OUTDOOR only)
Reference: Section 15900 - Building Controls and Automation
(a) NORTEC OnLine web based monitoring and control from any location with Internet
access, using standard Internet Explorer, version 6.0 or newer.
(b) NORTEC OnLine remote monitoring hardware using secure <DHCP Ethernet
Connection> or <Static IP Ethernet Connection> or <Dial-up Internet Connection>
or <GPRS wireless Internet Connection> Internet communication protocols.
(c) NORTEC OnLine Monitoring Service (NOMeS) with weekly humidifier examination
by factory direct technicians for first year, renewable/extendable up three
consecutive years.
(d) One additional year (third year), extended humidifier warranty when renewed/
extended for third year of NORTEC OnLine Monitoring Service (NOMeS).
(e) Packaged accessory, factory installed and ready for customer supplied <Ethernet>
or <Modem> communication connection.
(f)Package will include the listed items in either paragraph (f) 1
paragraph (g) 1
1
Internet accessible graphical representation of humidifier performance.
2
Remotely enable/disable humidifier.
3
Remotely adjust rh% set point(s), if equipped.
4
Remotely adjust ‘limited capacity’.
5
Automated e-mail advisories for scheduled service or abnormal conditions.
6
Up to three customer e-mail addresses available for automated e-mail
advisories.
7
Up to 50 incidents, of factory direct support and follow-up per humidifier.
8
First year of remote access includes factory direct monitoring.
9
Weekly checks by NORTEC OnLine factory technicians.
through 7:
through 17 or
10
Remote factory diagnostics and programming capability.
10-20
Page 68
2008-10-01
11 Individual account access to www.norteconline.com.
12
Monitor up to seventy parameters from each humidifier.
13
Access to service history.
14
Option to add up to <seven> or <six NMTC> ‘slave’ humidifiers to each
NORTEC OnLine module.
15
Monitor up to <eight humidifiers (one master, seven slaves)> or <seven
humidifiers (one master, six slaves)> with one <Ethernet> or <Modem>
connection.
16
Up to three years of coverage can be purchased at time of order, extending
humidifier limited warranty to three years.
17
Communication using secure 256-bit Internet connectivity (SSL) and Jabber
protocol.
(g) NORTEC Links remote building management system capability using BACnet
MSTP, BACnet /IP LonTalk, or Johnson N2 networks for monitoring and
controlling. The package will include:
1
Variable definitions, addresses, and values.
2
For complete function capabilities refer to 1.B.(2)(a)6.
3
Monitor up to 13 humidifiers (one master, 12 slaves) using a single interface.
4
External Interface File (XIF) for LonWorks integration.
5
Protocol Implementation Conformance Statement (PICS) for BACnet
integration.
6
BACnet Interoperability Building Blocks (BIBBS) for BACnet Services.
7
User graphic with trending charts, complete with all humidifier details. Refer to
1.B.(2)(a)6
(4) Humidifier Dispersion Options
(a) Single Tube(s) Steam Dispersion with condensate drain – NORTEC Model(s)
ASD, BSD,
1Allows for direct introduction of steam into a duct system or air handling unit.
Distributor tube is made of stainless steel and can be installed in a horizontal,
upflow, or downflow duct applications.
2
Steam inlet connection size is f" (22.2 mm) O.D for ASD, BSD models and
1¾" (44.5 mm) for CSD model.
3
Rated capacities per single dispersion tube(s) model - ASD up to 25 lbs/hr,
BSD up to 35 lbs/hr and CSD up to 115 lbs/hr.
4
All single tube(s) distributors have an integral condensate return, allows for
condensate produced at the distributor to be drained through a d" (9.5 mm)
drain leg either back to the humidifier or to a convenient floor drain.
(b) Wall Mounted Direct Steam Dispersion System – NORTEC Model(s) RMBP or
BOBP (for NHTC and NHPC only)
.
CSD
10-20
Page 69
2008-10-01
1
Packaged unit, wall mounted allows for direct space/room humidification when
steam introduction into a ducted system is not feasible.
2The factory assembled blower pack includes an integral steam distributor,
three tubeaxial (box) fans, fusing, wall mounting bracket, and air proving
safety circuitry.
3
Primary and control voltage terminal blocks facilitate field connections
between the humidifier.
4
Blower pack may be remote mount or built-on the humidifier.
(c) Short Absorption Manifold – NORTEC Model SAM-e
1
Short Absorption Manifold designed for atmospheric steam humidifiers or
pressurized steam from a boiler, to directly inject the steam into ducted air for
humidification.
a
Absorption distance characteristic shall prevent water accumulation on
any induct surfaces beyond ___in. (___mm) downstream of the steam
dispersion panel.
b
Steam dispersion panel consisting of a (one) horizontal stainless steel
header supplying steam to a bank of closely spaced 3" (7.6 cm) or
6" (15.2 cm) or 9" (22.9 cm) or 12" (30.5 cm) vertical tubes, as necessary
to meet absorption distance requirements, and to reduce condensation
losses.
c
Single horizontal stainless steel header to provide steam to vertical
distributor tubes and to reduce condensation losses. Dual header
systems creating unnecessary condensation, or systems needing to be
installed on a partition or requiring blank off plates are not acceptable.
C.EXECUTION
(1) Examination
d
Header design is primarily round tube to minimize pressure drop. Square
headers are not acceptable.
e
Steam inlet and condensate return located on the same side and at the
bottom of the header to allow single point entry and floor mounting.
f
Headers and tubes are 304 stainless steel construction.
g
Vertical stainless steel distribution tubes to promote condensate
evacuation. Horizontal distributor tubes are not accepted.
h
Distribution tubes shall include threaded standoffs for trouble free
attachment to factory supplied support bracket.
i
Stainless steel nozzle inserts ensure condensate free steam is
discharged from the center of the distribution tubes. Systems without
nozzle inserts, or other than stainless steel, are not acceptable.
j
Stainless steel nozzle inserts shall have metered orifices, sized to provide
even distribution of the discharged steam, spaced for optimum steam
absorption.
k
Nozzles of dissimilar metals are likely to dislodge due to inconsistent
rates of expansion and therefore not accepted.
l
Adjustable mounting frame available for quick and easy installation.
(a) Examine ducts, air handling units, and conditions for compliance with requirements
for installation tolerances and other conditions affecting performance.
10-20
Page 70
2008-10-01
(b) Examine roughing-in for piping systems to verify actual locations of piping
connections before humidifier installation.
(c) Proceed with installation only after unsatisfactory conditions have been corrected.
(2) Installation
(a) Install humidifiers and steam dispersion panels per manufacturers’ instructions.
(b) Seal humidifier dispersion-tube duct penetrations with flange.
(c) I nstall with required clearance for service and maintenance.
(3) Commissioning
(a) System verification testing is part of the commissioning process. Verification
testing shall be performed by the contractor and witnessed and documented by the
commissioning authority. Refer to section 01810, Commissioning, for system
verification tests and commissioning requirements; or
(b) Manufacturer's Field Service: Engage a factory-authorized service representative
to inspect field-assembled components and equipment installation, including
piping and electrical connections. Report results in writing. Responsibilities
include:
1
Leak Test: After installation, charge system and test for leaks. Repair leaks
and retest until no leaks exist.
2
Operational Test: After electrical circuitry has been energized, start units to
confirm proper unit operation. Remove malfunctioning units, replace with new
units, and retest.
3
Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
(4) Testing
(a) System testing is accomplished through either of the following methods:
1
System verification testing is part of the commissioning process. Verification
testing shall be performed by the contractor and witnessed and documented
by the commissioning authority. Refer to section 01810, Commissioning, for
system verification tests and commissioning requirements; or
2
Manufacturer’s Field Service: Engage a factory-authorized service
representative to inspect field-assembled components and equipment
installation, including piping and electrical connections. Report results in
writing. Responsibilities include:
a
Leak Test: After installation, charge system and test for leaks. Repair
leaks and retest until no leaks exist.
b
Operational Test: After electrical circuitry has been energized, start units
to confirm proper unit operation. Remove malfunctioning units, replace
with new units, and retest.
c
Test and adjust controls and safeties. Replace damaged and
malfunctioning controls and equipment.
(5) Training
10-20
Page 71
2008-10-01
(a) Equipment training can be accomplished in one of the following two ways:
1Training of the owner’s operation and maintenance personnel is required in
co-operation with the commissioning authority. Provide competent, factory
authorized personnel to provide instruction to operation and maintenance
personnel concerning the location, operation, and troubleshooting of the
installed systems. The instruction shall be scheduled in coordination with the
commissioning authority after submission and approval of formal training
plans. Refer to System Demonstrations, section 01670, for contractor training
requirements. Refer to section 01810, Commissioning, for further contractor
training requirements; or
2
Engage a factory-authorized service representative to train owner’s
maintenance personnel to adjust, operate, and maintain humidifiers.
a
Train owner’s maintenance personnel on procedures and schedules for
starting and stopping, troubleshooting, servicing, and maintaining
equipment and schedules.
b
Review data in maintenance manuals. Refer to Division 1 Section
Contract Closeout.
c
Review data in maintenance manuals. Refer to Division 1 Section
Operation and Maintenance Data.
d
Schedule training with owner, through architect, with at least seven days
advance notice.
10-20
Page 72
2008-10-01
10-30
SUBMITTALS
10-30
Page 73
2008-10-01
1. SUBMITTAL DESCRIPTIONS
A. INTRODUCTION
(1) The information found in this section is general in nature and consists of part
numbers, product descriptions and options, dimensions, specifications and
equipment features.
B. NH UNIT
(1) The different wiring connections to the humidifier unit can be found in Figure 2. All
wiring is to be in accordance with existing national and local electrical codes.
(2) Performance data for single and double units can be found in Figure 3, Figure 4,
and Figure 5.
(3) NH Series unit options and common accessories universal are found in Tables 1
and 2.
C. DISTRIBUTORS
(1) A description of the accessories for the steam distributor can be found in Table 3.
(2) Dimensions for the steam distributor are found in Figure 6, Figure 7, Figure 8.
D. SAM-e
(1) This section identifies the dimensions for the various configurations and
components that make up a SAM-e installation.
(2) General dimensions for the SAM-e and Mini SAM-e are found in Figures 9 and 10.
(3) For an in-duct/AHU installation without mounting frame refer to Figure 11.
(4) For an in-duct/AHU installation with mounting frame refer to Figure 12.
(5) For an outside duct installation without mounting frame refer to Figure 13.
(6) For an outside duct installation with mounting frame refer to Figure 14.
(7) For a vertical duct installation refer to Figure 15.
(8) For outside duct mounting cover plates refer to Figure 16.
(9) For atmospheric SAM-e adapter dimensions refer to Figure 17.
(10) For atmospheric steam header and adapter configuration refer to Figure 18.
E. BLOWER PACK
(1) Remote Blower Packs
(a) Remote blower packs are powered from the NH humidifier from a primary
voltage terminal block provided and fed from the leaving side of the unit
contactor to operate blower pack in conjunction with unit operation. A matching
terminal block is incorporated in the blower pack. Field wiring is required
10-30
Page 74
2008-10-01
between the NH unit and remote blower pack terminal blocks or can be
powered by a seperate 12 ov supply.
(b) Disk thermostat mounted on the top of steam distributor will start the fan when
steam is generated and will allow to cool down the blower pack when there is
no call for humidity.
(c) A minimum of two (2) 050-100 RMBP’s are required with the NH-150 or NH-
200 units. It is recommended that four (4) RMBP’s be used to reduce the steam
absorption distances.
(d) It is recommended that a minimum of two (2) remote blower packs be used on
NH 075-100 units to reduce the steam absorption distances.
(e) For recommended ceiling and frontal clearances, see Chapter 10-10.
(f) For blower pack dimensions refer to Figure 19, Figure 20, Figure 21.
(2) Built-On Blower Pack (NHTC and NHPC only)
(a) Built-on blower packs are factory mounted and wired to operate in conjunction
with the humidifier. Factory installed and wired manual reset thermostat will not
allow humidifier operation if blower pack becomes overheated.
(b) Built-on blower packs are not available on NH 150-200. Remote blower packs
can be used with these units, multiple blower packs are required on NH 150-
200.
(c) Built-ON Blower Pack, Wall Mounted Direct Steam Distribution System. Allows
for direct space/room humidification when steam introduction into a ducted
system is not feasible. The factory assembled Built-On Blower Pack includes
an integral steam distributor, three direct drive fans for quiet operation, fan
adjustable louvers for installation flexibility, fusing and safety circuitry with fan
airflow rate at a total of 330 cfm.
(d) It is recommended that a minimum of two (2) remote blower packs be used on
NH 075-100 units to reduce the steam absorption distances.
(e) For recommended ceiling and frontal clearances, see Chapter 10-10. Note
minimum frontal clearance is 36" (91 cm).
(f) For blower pack dimensions refer to Figure 19, Figure 20, and Figure 21.
F. CONTROLS
(1) NHTC/NHPC humidifiers can be easily modified to accept a control signal from a
modulating humidity controller as supplied by others. Controller must have a builtin adjustable %rh set point. Signal from controller must increase with a drop in
sensed %rh below set point. Humidifier will respond by controlling unit output
between 0% and 100% of rated capacity to match changes in load requirements.
(2) Double circuit humidifiers (NH 150-200) will require two external controllers by
10-30
Page 75
2008-10-01
others to enable each circuit to operate independently of the other. Alternatively,
coupled circuits can be specified. Coupled circuits will enable the two circuits to be
operated from one controller without compromising the safety features of the
humidifier (order Part No.146-9000).
(3) The humidifier shall be controlled directly using a humidity sensor (transducer)
supplied by others. The sensor will be field wired to the humidifier for a direct
control at the humidifier. The same sensor(s) can be shared in parallel to a Building
Automation System for monitoring purposes. Allows keypad setpoint of rh and
display of actual sensed rh on the NHTC’s graphical display.
(4) Double circuit humidifiers (NHTC 150-200) will require two external sensors by
others to enable each circuit to operate independently of the other. Alternatively,
coupled circuits can be specified. Coupled circuits will enable the two circuits to be
operated from one sensor without compromising the safety features of the NHTC
humidifier (order Part No.146-9000).
(5) All controls are available from the factory as options. If controls were not ordered
with the humidifier, they may be purchased/supplied by others. The following
information is relevant to all controls, factory supplied or otherwise.
(6) A, B and C are to be wired in series (only one path for current) across terminals 1
and 2 on the low voltage control terminal strip, or replaced with a jumper wire for
constant operation.
(a) The Control On/Off Humidistat is wired to make on drop in humidity, break on
rise. Set to desired %rh.
(b) The High Limit On/Off Humidistat is wired to make on drop in humidity, break
on rise. Set to a higher set point (max. 85%rh) as a safety to prevent
saturation.
(c) The Air Proving On/Off Switch is wired to make when sensing air flow, break
when no air flow. As a safety to prevent saturation when no air flow.
(7) The factory offers various versions of A, B and C to suit each application. In
general, A is essential, whereas B and C are highly recommended.
(8) Field wiring from humidistat to humidifier and between devices should be 18 AWG
or heavier.
(9) The low voltage control terminal strip is provided in the electrical compartment. The
internal side is factory wired. The external side is to be field wired, unless the
external controls have been cabinet mounted at the factory.
(10) Each unit is supplied with a wiring diagram adhered to the inside face of the
cabinet door.
10-30
Page 76
2008-10-01
Figure 1. Low Voltage Control Terminal Strip
(11) A and B: Mount any wall humidistat (control or high limit) over a standard electrical box
at a height similar to a typical thermostat. Any wall humidistat should be in a location
representative of the overall space being humidified and not in the path of a blower pack
or an air supply grille.
(12) A: Mount any duct control humidistat in a location representative of the overall air
humidity, usually the return duct. Do not mount it directly in front of the steam distributor
or in a turbulent or mixing zone. Mount it where the air’s humidity and temperature are
uniform and representative air is over-humidified or approaching saturation.
10-30
Page 77
2008-10-01
Figure 2. Primary (Line) Voltage Wiring to Unit
10-30
Page 78
2008-10-01
10-30
Page 79
2008-10-01
Figure 3. Physical Data – NHTC/NHPC 005-030
Figure 4. Physical Data – NHTC/NHPC 050-100
10-30
Page 80
2008-10-01
10-30
Page 81
2008-10-01
Figure 5. Physical Data – NHTC/NHPC 150-200
Unit Model NH 005-020 NH 030 NH 045-100 NH 135-200
Distributor Model
No. of Cylinders
No. of Outlets/Cylinder
OD of Cylinder Outlet (NHTC,P,B)
OD of Cylinder Outlet (NHSC/DI)