Nortec NH-EL User Manual

Important: Read and save these instructions. This guide to be left with equipment.
2570435 D | 25 JUN 2014
NH-EL
Series
Installation and Operation Manual
Includes installation, operation maintenance and troubleshooting information for your NH-EL Electric Steam humidifier
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
Thank you for choosing Nortec.
Proprietary Notice
This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Nortec Humidity Ltd., except to the extent required for installation or maintenance of recipient’s equipment.
Liability Notice
Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec.
Copyright Notice
Copyright 2014, Nortec Humidity Ltd. All rights reserved.
Contents
1 Introduction
2 Receiving and Unpacking
3 Humidifier Components
5 NH-EL Models
6 Options and Accessories
9 Installation
10 Typical Humidifier Installation
11 Location
13 Mounting with Keyholes
14 Plumbing
15 Steam Distributor
16 Steam Lines and Condensate
Returns
21 Electrical
48 Operation
49 LED Status Lights
51 How the Humidifier Works
54 NH-EL Humidifier Configuration
62 Maintenance and
Servicing
63 Required Maintenance
68 Extended Shutdown
69 NH-EL Maintenance Checklist
70 Troubleshooting
72 General Troubleshooting
75 NH-EL Warnings and Faults
81 NH-EL Wiring Diagram (Cylinder A)
82 NH-EL Wiring Diagram (Cylinder B)
22 External Controls
36 Options and Accessories
38 Start Up
39 Installation Check
40 NH-EL User Interface
41 Start Up Procedure
42 Information Screens
43 Nortec Digital Controls
46 NH-EL Pre-Start Up Checklist
47 NH-EL Start Up Checklist
83 Spare Parts 95 Warranty
CAUTION: Servicing
Humidity Ltd.
CAUTION: Electrical
CAUTION: Plumbing
All plumbing work should be done according to local plumbing code.
CAUTION: Installation
proving switch in series for this function.
Introduction
Disconnect main power before any servicing.
The plumbing and electrical compartments contain high voltage components and
wiring. Access should be limited to authorized personnel only.
During and following operation of the humidifier, the steam and components in
contact with the steam such as the cylinder, blower pack, steam lines, steam distributors, and condensate lines can become hot and can burn if touched.
Nortec Humidity Ltd. does not accept any liability for installations of humidity
equipment installed by unqualified personnel or the use of
parts/components/equipment that are not authorized or approved by Nortec
All electrical work should be done according to local electrical code.
Electrical connection to be performed by a licensed electrician.
Plumbing to be performed by a licensed plumber.
Drain water from humidifier can be very hot. Do not drain to public sink.
Do not mount on hot surfaces.
Do not mount in area where freezing can occur.
Do not mount on vibrating surface.
Do not mount on floor.
The NH-EL produces steam at atmospheric pressure; no devices which could block
steam output should be connected to the steam outlet.
Steam lines must be installed so that no restriction can produce back pressure in
the humidifier. Failure to follow installation instructions will result in improper operation and could void warranty.
Regardless of selecting On/Off or modulating control method, NORTEC humidifiers
must have a closed circuit across its On/Off security loop control terminal to operate. NORTEC highly recommends the use of a high limit humidistat and an air
1 | Introduction
Receiving and Unpacking
1 Check packing slip to ensure ALL material has been delivered. 2 All material shortages are to be reported to NORTEC within 48 hours from receipt of goods.
NORTEC assumes no responsibility for any material shortages beyond this period.
3 Inspect shipping boxes for damage and note damages on shipping waybill accordingly. 4 After unpacking, inspect equipment for damage and if damage is found, notify the shipper
promptly.
5 All NORTEC products are shipped on a Free-On-Board (FOB) factory basis. Any and all
damage, breakage or loss claims are to be made directly to the shipping company.
Before Installation
1 Ensure that available voltage and phase corresponds with humidifier voltage and phase as
indicated on humidifier’s specification label.
2 Ensure that the dedicated external fuse disconnect is of sufficient size to handle the rated
amps as indicated on the specification label. Refer to local codes.
3 Report any discrepancy immediately to the site engineer. 4 Ensure sufficient clearances will be available as described in Location on page 11. 5 Ensure steam lines can be routed to distributor or blower pack as described in Steam Lines
and Condensate Return on page 16.
Figure 1: Specification Label Location
Introduction | 2
Steam Outlet
Condensate Return
Fill Cup
Drain Valve
Drain Canal
Fill Valve
Cylinder
Cylinder Strap
Cylinder Plug
High Water Sensor Plug
Touch Screen Display
On/Off Switch
Auxiliary Drain Switch
Door Interlock Switch
Driver Board
Remote Relay Board
Contactor
High Voltage Terminal Block
Transformer
Integrated Controller
Control Terminal Strip
NOTE:
NH-EL 005-030 shown, component location may vary slightly for other models.
TEST
Humidifier Components
3 | Introduction
Figure 2: NH-EL Humidifier Components
Component
Function of Component
Auxiliary Drain
Drains water from cylinder by activating drain valve. Note that initiating a drain in this manner will not induce Drain Water Cooling.
Condensate Return
Provides a connection to return condensate to humidifier.
Contactor
Turns On/Off power to cylinder electrodes.
Control Terminal Strip
Terminal strip for connecting external controls and blower pack to humidifier.
Cylinder Plug
Power connectors to electrodes in cylinder.
Cylinder strap
Securely holds cylinder in place.
Cylinder
Holds electrodes in water. Current between electrodes generates heat used to generate steam.
Touch Screen Display
User interface for configuring the humidifier.
Door Interlock Switch
Prevents contactor from engaging when door is removed (pull out to override this safety feature while troubleshooting).
Drain Canal
Combines cylinder drain water and fill cup overflow into a single drain outlet.
Drain Valve
Drains water from cylinder.
Driver Board
Provides input and output connections to humidifier components.
Fill Cup
Provides an air gap for backflow prevention.
Fill Valve
Controls flow of water into humidifier.
High Voltage Terminal Block
Primary power connection from remote disconnect to humidifier.
High Water sensor Plug
Used to detect max water level in cylinder.
On/Off Switch
Turns power On/Off to humidifier controller. Note: Turn off humidifier disconnect to shut off primary power to the humidifier.
Remote Relay Board (option)
Provides a terminal strip to dry contacts which open/close to indicate the humidifier is on, humidifying, needs service, or is in a fault condition.
Steam Outlet
Connect to steam line with steam hose.
Integrated Controller
Controls all functions of the humidifier’s operation and provides user
interface for configuration of the humidifier.
Transformer
Steps primary voltage down to 24 VAC for the controller and internal components such as the fill valve and drain valve.
Description of Components
Table 1: Humidifier Components
Introduction | 4
NH-EL 005-030 NH-EL 050-100 NH-EL 150-200
Fill Connections Drain Connections
NH-EL Models
The NH-EL with its Integrated Controller and state-of-the-art features and options is the most advanced electrode steam humidifier available. As well as controlling the operation of the humidifier, the Integrated Controller can be connected directly to BACnet and to the Internet. The NH-EL is available in capacities ranging from 5 lb/hr (2 kg/hr) to 200 lb/hr (90 kg/hr). NH­EL humidifiers are packaged in three different cabinets depending on capacity. Figure 3: NH-EL Sizes shows the configuration and relative size of the three different cabinets. NH-EL models up to 100 lb/hr (45 kg/hr) are also available with a built on blower pack. Table 3 provides specifications for the NH-EL product line.
Figure 3: NH-EL Sizes
Double Unit (NH-EL 150-200)
NH-EL double units have two cylinders to provide increased capacity. The construction and installation of double units is identical to units with a single cylinder with the following exceptions:
Double units have two driver boards (designated A and B). One driver board controls each
cylinder. (See Figure 3: NH-EL Sizes).
Double units can operate both cylinders in series or parallel from a single set of control
signals or independently based on two sets of control signals (see Double Mode (NH-EL 150- 200 only) on page 56 for configuration instructions).
Independent Operation - If configured for independent operation then 2 sets of control
wiring must be provided. Control wiring for each cylinder must be connected to the
cylinder’s corresponding driver board/terminal strip and each cylinder performs
independent of the other.
Parallel Operation - If configured for parallel operation then only one set of control wiring is
required and the cylinders operate in parallel. The advantage is even wear on both cylinders.
Series Operation If configured for series operation, then only one set of control wiring is
required and the cylinders operate in series. Cylinder A’s output range is 0-50% and Cylinder B’s output range is 50-100%. The advantage is the lower turndown ratio of one cylinder.
Double units have one primary power connection but have individual fill, drain, and steam
outlet connections for each cylinder.
5 | Introduction
Option / Accessory
Application
Steam Distributors
Adding steam into air ducts.
Remote Blower Pack
Adding steam into a space remote from the humidifier.
SAMe Steam Distribution Manifold
Adding steam into air ducts where short absorption is required.
Digital or Analog Control Humidistats
Controlling the output of the humidifier based on sensed RH (can be mounted in the space being humidified or in the duct).
Digital RH Transducers
Communicating RH in a space or duct to the humidifier.
Digital or Analog High Limit Humidistats
Preventing over humidification in a duct by shutting down or throttling down the humidifier when duct RH gets high.
Air Proving Switches
Ensuring humidification only occurs when air is moving in a duct.
Fill Cup Extension
Increasing the steam back pressure capability of an NH-EL.
Drain Water Cooling (Extreme)
Cooling drain water to less than 120 °F (49°C).
Foam Detection Kits
Increasing the range of water quality in which an NH-EL can operate.
Options and Accessories
NORTEC provides a complete line of options and accessories for every humidification application. The following options and accessories are available and may have been delivered with your NH-EL humidifier. Refer to the installation instructions that came with the accessories for the proper installation and operation.
Table 2: Options and Accessories
Introduction | 6
Phase
Capacity
lb (kg)
Volts
NH-EL
Part No.
Amps
Max
Ext
Fuse
KW
Stand-
ard
Cylinder
Fill
gal (l)
per min
Net/Full
Weight
lb (kg)
1
5 (2.3)
110-120
2573379
15.6
20
1.9
202
0.13 (0.5)
45/55
(21/25)
10 (4.5)
208
2573380
18.3
25
3.8
202
0.13 (0.5)
220-240
2573382
15.9
20
3.8
202
277
2573383
13.7
20
3.8
202
440-480
2573385
7.9
15
3.8
204
550-600
2573386
6.3
15
3.8
204
20 (9)
208
2573388
36.6
45
7.6
321
0.13 (0.5)
45/65
(21/30)
220-240
2573389
31.7
40
7.6
321
277
2573390
27.5
35
7.6
321
440-480
2573392
15.9
20
7.6
309
550-600
2573393
12.7
20
7.6
309
3
20 (9)
208
2573394
21.1
30
7.6
303
0.13 (0.5)
220-240
2573395
18.3
25
7.6
303
440-480
2573397
9.2
15
7.6
311
550-600
2573398
7.3
15
7.6
311
30
(13.5)
208
2573399
31.7
40
11.4
421
0.3
(1.2)
45/80
(21/37)
220-240
2573400
27.5
35
11. 4
421
440-480
2573402
13.7
20
11.4
411
550-600
2573403
11.0
15
11.4
411
50
(22.5)
208
2573404
51.9
70
18.7
621
0.5
(2.0)
85/150
(39/68)
220-240
2573405
45.0
60
18.7
621
440-480
2573407
22.4
30
18.7
605
550-600
2573408
18.0
25
18.7
605
75 (34)
208
2573409
77.9
100
28.1
621
0.5
(2.0)
220-240
2573410
67.4
90
28.1
621
440-480
2573412
33.8
45
28.1
605
550-600
2573413
27.0
35
28.1
605
100 (45)
208
2573414
94.4
125
34.0
621
0.9
(3.3)
220-240
2573415
90.0
125
37.4
621
440-480
2573417
45.0
60
37.4
605
550-600
2573418
36.0
45
37.4
605
150 (68)
208
2573419
155.8
200
56.1
621
0.5**
(2.0**)
120/245
(55/112)
220-240
2573420
135.0
175
56.1
621
440-480
2573422
67.4
90
56.1
605
550-600
2573423
54.0
70
56.1
605
200 (90)
208
2573424
188.7
250
68.0
621
0.9**
(3.3**)
220-240
2573425
180.0
225
74.8
621
440-480
2573427
90.0
125
74.8
605
550-600
2573428
72.0
90
74.8
605
Table 3: NH-EL Specifications
** Note: Per cylinder basis.
7 | Introduction
Phase
Capacity
lb (kg)
Volts
NH-EL Space
Part No.
Amps
Max
Ext
Fuse
KW
Stand-
ard
Cylinder
Fill
gal (l)
per min
Net/Full
Weight
lb (kg)
1
5 (2.3)
110-120
2573429
17.2
25
2.0
202
0.13 (0.5)
83/93
(38/42)
10 (4.5)
208
2573430
19
25
4.0
202
0.13 (0.5)
220-240
2573431
16.5
25
4.0
202
277
2573432
14.2
20
4.0
202
440-480
2573434
8.2
15
4.0
204
550-600
2573435
6.6
15
4.0
204
20 (9)
208
2573436
37.3
45
7.8
321
0.13 (0.5)
83/103
(38/47)
220-240
2573437
32.3
40
7.8
321
277
2573438
28
35
7.8
321
440-480
2573440
16.2
20
7.8
309
550-600
2573441
13
20
7.8
309
3
20 (9)
208
2573442
21.8
30
7.8
303
0.13 (0.5)
220-240
2573443
18.9
25
7.8
303
440-480
2573445
9.5
15
7.8
311
550-600
2573446
7.6
15
7.8
311
30
(13.5)
208
2573447
32.4
40
11.7
421
0.3
(1.2)
83/118
(38/54)
220-240
2573448
28.1
35
11.7
421
440-480
2573450
14
20
11.7
411
550-600
2573451
11.3
15
11.7
411
50
(22.5)
208
2573452
52.6
70
18.9
621
0.5
(2.0)
123/188
(56/85)
220-240
2573453
45.6
60
18.9
621
440-480
2573455
22.7
30
18.9
605
550-600
2573456
18.3
25
18.9
605
75 (34)
208
2573457
78.6
100
28.3
621
0.5
(2.0)
220-240
2573458
68
90
28.3
621
440-480
2573460
34.1
45
28.3
605
550-600
2573461
27.3
35
28.3
605
100 (45)
208
2573462
95.1
125
34.5
621
0.9
(3.3)
220-240
2573463
90.6
125
37.7
621
440-480
2573465
45.3
60
37.7
605
550-600
2573466
36.3
45
37.7
605
Table 4: NH-EL Space Specifications
Introduction | 8
Installation
10 Typical Humidifier Installation 11 Location 13 Mounting with Keyholes 14 Plumbing 15 Steam Distributor 16 Steam Lines and Condensate Return Instructions 21 Electrical 22 External Controls
22 Control Wiring
22 Control Location
24 On/Off Control Wiring
25 Keep Warm Wiring
26 Modulating Control Wiring
28 Transducer Control Wiring
29 Double Unit Control Wiring
33 Remote Fault Option Wiring 34 Multi Mode Wiring 35 Modbus Digital Control 36 Options and Accessories
37 Fill Cup Extension
37 Extreme Drain Water Cooling
37 Condensate Cooling (External)
37 Foam Protection
37 Internal Fusing
37 Remote Fault Indication
9 | Installation
Typical Humidifier Installation
6 in.
(15 cm)
min.
right
clearance
36 in. (90 cm)
min. front clearance
24 in.
(60 cm)
min.
3 in. (7.5 cm) Screws
1- 24 VAC 2- Security Loop 3- Common 4- Channel 1 5- Channel 2 6- 5 VDC 7- Ground 8- Blower Pack 9- Blower Pack
On/Off
Controls
Modulation
Controls
E X
T E R
N A L
N H
­E L
L1L2L3
Ground
Dedicated
Circuit
Breaker or
Disconnect
NH-EL
EXTERNAL
Cold potable water 150-1200 microsiemens 30-80 psig
Air Gap
½ in NPT
2 in.
(5 cm)
min.
1ft (30 cm)
1 ft (30 cm)
min.
1 – 24 VAC 2 – Security Loop 3 – Common 4 – Channel 1 5 – Channel 2 6 – 10 VDC 7 – Ground 8 – Blower Pack 9 – Blower Pack
0” (0 cm)
right
clearance
6” (15 cm)
recommended
Mounting Pg 13
Steam
Distribution
Pg 15
Controls Pg 22
Plumbing Pg 14
Electrical Pg 21
Figure 4: Typical Humidifier Installation
Installation | 10
6 in.
(15 cm)
Recommended
Side
Clearance
36 in. (91.5 cm)
Min. Front Clearance
24 in.(61 cm)
Min Height
Mount Humidifier
Level
5-95%
(See Table for
Blowerpack
clearances)
(See Table for
Blowerpack
clearances)
(See Table for
Blowerpack clearances)
If Blowerpack is used,
mount so that the steam
outlet is at least
96 in. (244 cm)
above ground level.
Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or floor.
Location
Mount on a suitable wall or vertical surface. Do not sit the unit on the floor to allow
clearances required for plumbing and electrical connections.
Clearance dimensions shown are for reference only and are the minimum required for
maintenance of the humidifier. Consult local and national codes before final location and installation. NORTEC does not accept responsibility for installation code violations.
Install only in areas with ambient temperature 41-104 °F (5 – 40 °C) relative humidity 5 -
95% (non condensing).
When possible install the humidifier below the steam distributor. Take care to provide proper
steam line routing and proper condensate traps.
DO NOT locate the humidifier any further than absolutely necessary from the steam
distributor location. Net output will be reduced as a result of heat loss through the steam line.
When possible, mount the NH-EL humidifier at a height convenient for servicing.
11 | Installation
Figure 5: Mounting Location / Clearance
Humidifier
Capacity
lbs/hr (kg/hr)
Minimum
No. of
Blower
Packs
Min. Frontal
Clearance
Inches (cm)
Min. Overhead
Clearance
Inches (cm)
Min. Left side
Clearance
Inches (cm)
Min. Right side
Clearance
Inches (cm)
30 (13.6)
1
132 (336)
12(31)
12 (31)
12 (31)
100 (45.4)
1
Not
recommended
Not
recommended
Not
recommended
Not
recommended
Humidifier
Capacity
lbs/hr (kg/hr)
Minimum
No. of
Blower
Packs
Min. Frontal
Clearance
Inches (cm)
Min. Overhead
Clearance
Inches (cm)
Min. Left side
Clearance
Inches (cm)
Min. Right side
Clearance
Inches (cm)
30 (13.6)
1
120 (305)
12(31)
12 (31)
12 (31)
100 (45.4)
1
248 (630)
36 (91)
30 (76)
30 (76)
Table 5: Clearances for Blower Packs on Low Speed*
Table 6: Clearances for Blower Packs on High Speed*
*NOTES: Nominal Conditions 72˚F (22.2˚C), 43% RH. Low speed not recommended for 100 lbs/hr humidifier. Consult factory for recommendations. Blower Pack should not be installed near cold surfaces or where dew point may be reached. Higher humidity or lower room temperature may result in longer absorption distances.
Installation | 12
B
A
Install “L” brac ket
after hanging humidifier
#12 x 3 in. (7.5 cm) Wood Screws
Insert screws so that
1/4 in. (6 mm) exposed,
hang unit, tighten
screws.
Unit Size Screws Dim A in (cm). Dim B in. (Cm)
5-30 2 11.9 (30.2) -
50-100 2 16 (40.6) -
150-200 3 16 (40.6) 16 (40.6)
SPACESPACE
SPACESPACE
Mounting with Keyholes
1 The NH-EL Series humidifier is wall mounted using keyholes located on the back of the unit
cabinetry.
2 Use #12 x 3 in. (7.5 cm) screws mounted into 2x4 studs or better. Two screws are needed
for a single unit (NH-EL 010 to 100). Three screws are needed for a double unit (NH-EL 150 to 200).
3 Keyholes are spaced 16 in. (40.6 cm) apart center to center for large units and 11.9 in.
(27.2 cm) apart for small units. Insert screws into the studs until there is 1/4 in. of screw exposed. Be sure the screws are level to each other.
4 Raise the unit and place the screws through the keyholes. Make sure the unit is level, then
tighten the screws to secure the unit in place.
5 Place L Shaped brackets on top of the unit, with holes inline with the studs. Using the
appropriate sized wood screw, fasten the “L” brackets to the studs, securing the unit from any upward motion. See Figure 6: Mounting with Keyholes.
Note: Use screws longer than 3” (7.5 cm) if drywall or other spacer is present.
13 | Installation
Figure 6: Mounting with Keyholes
Min. 7/8 in. OD drain line. Keep as short as possible. Slope down to floor drain or main drain. Increase size if combining multiple drains as in double unit.
1.2 in. (30 mm). OD un-threaded outlet with factory supplied bent hose and clamp.
Air gap required. 2 1/2 in. to 7/8 in. copper reducer is ideal. (NORTEC option P/N 2522172) Hose must not touch the bottom of the funnel.
Always install a water shut-off valve.
1/2 in. NPT
Use union to connect
supply pipe to unit.
*Pipe and water shut-off valve not supplied by NORTEC.
Note:
Use material suitable for 212°F (100°C) for drain and condensate lines.
Plumbing
Drain Water is very hot, do not drain to public sink
Supply cold potable water (not Reverse Osmosis or Demineralized). Conductivity:
150–750 microsiemens and pressure: 30-80 PSIG.
All water supply and drain line connections should be installed in accordance with local
plumbing codes.
Supply water should at 30 to 80 PSIG and be between 150-750 microsiemens (Hardness
0-12 GPG). For 750-1200 microsiemens, please consult factory.
Install water shut off valve and union before humidifier to facilitate servicing. The drain line should not end in a sink used frequently by personnel, or where plumbing
codes prohibit. Route to a floor drain or equivalent for safety reasons.
Ensure drain line is adequately sized to provide free and easy draining and that an air gap is
installed as shown. A restricted drain can cause cylinder water to over concentrate, resulting in poor operation or result in water backing up at the air gap.
Figure 7: Water Supply and Drain Connection
Installation | 14
12 in.
(30 cm)
min.
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
Mount distributor
to side of duct
2 x duct
height min.
2/3 Duct height
Note:
Steam Distributor
Steam generated by the NH-EL may be distributed directly into a space with a built on or
remote blower pack, or into an air handling system using either Nortec steam distributors or Nortec’s SAMe steam distribution manifold.
Whichever method is used, the steam distributor should be installed as close as possible to
the humidifier. Short steam distribution lines minimize condensate losses and the possibility of generating back pressure in the steam distribution line.
Figure 8: Distributor Location in Duct provides common guidelines for locating a steam
distributor in a duct.
Figure 8: Distributor Location in Duct
Install the NH-EL as close as possible to whatever steam distributor is used.
Refer to distributor, SAMe, or remote blower pack installation manuals for detailed installation instructions.
15 | Installation
NH-EL
Maximum Steam
MED-L
Stainless
Possible Steam Losses
Model
Line Length
Copper
Steel
(based on 1” insulated copper pipe)
ft
(m)
Tube
Tube
lb/hr/ft
(kg/hr/m)
5
7
(2)
3/4
0.875 X 0.049W
0.06
(0.09)
10
12
(3.5)
20
17
(5)
30
22
(6.5)
50
43
(13)
1 1/2
1.75 X 0.065W
0.11
(0.16)
75/150**
47
(14)
100/200**
50
(15)
Oversized Steam Line (Use for longer steam runs)***
5
14
(4)
1
1.125 X 0.049W
0.06
(0.09)
10
24
(7)
20
34
(10)
30
44
(13)
50
86
(26)
2
2.0 X 0.065W
0.11
(0.16)
75/150**
94
(28)
100/200**
100
(30)
Nortec Steam Hose
5-30
10
(3)
Pt No 1328810 (7/8”)
0.1
(0.15)
50-200**
10
(3)
Pt No. 1328820 (1 3/4”)
0.15
(0.22)
Danger:
Steam Lines and Condensate Return Instructions
The following instructions must be followed for installation of steam lines for ASD, BSD, CSD, SAM-e, and remote blower packs. Failure to use material recommended in
Table 7, exceeding maximum recommended length in Table 7, or failure to follow any other steam line installation instructions will result in improper operation and could void the warranty.
The NH-EL is an atmospheric humidifier that will only operate properly when its steam distribution system is installed so that it provides no significant backpressure.
Installing the NH-EL in such a way that backpressure can develop during operation could result in serious injury or damage to property.
Table 7: Recommended Steam Line Material*, Maximum Length, Losses
Note: * The use of steam line other than copper, stainless steel tube or Nortec supplied steam line will void the warranty and may
adversely affect the operation of the humidifier.
** Use one steam line per cylinder for NH-EL 150-200 humidifiers. Do not combine lines except at distributor using a Nortec adapter
designed for that purpose and only if humidifiers operate in parallel.
*** These diameters require a reducer at humidifier and steam distributor connection.
Installation | 16
Ste
am
D
irectio
n
Ste
a
m Dir
ectio
n
S
t
e
a
m
D
i
r
e
c
t
i
o
n
2 in. (5 cm)
1 ft (30 cm)
1ft (30 cm)
0.5 in. (12 mm)
10 Degrees
2 Degrees
Use Appropriate Slope Insulate Pipe
1 in. (2.5 cm) pipe
insulation
Minimal Slope (up)
Minimal Slope (down)
Figure 9: Steam Line Slope and Insulation
Trap condensate
12 in. (30 cm)
min drop to
top of ‘P’ Trap
P Trap min
6 in. (15 cm)
or
duct static
pressure + 2 in
whichever is
greater
Tee is same size
as steam line
Use a full size tee, not a 90 degree elbow for vertical to horizontal transitions.
‘P’ Traps Use:
- NORTEC 0.375 in condensate hose
- 1/4 in Med-L copper tubing, or
- 0.375 in stainless steel tubing
Condensate drains must be sloped down.
1 ft (30 cm)
0.25 in (0.6 cm)
Trap at all low points and recommended intervals using full size ‘T’ for traps.
Condensate should not be routed to a sink used frequently by personnel. Route to a floor
Route condensate to floor drain or equivalent in multi-unit to single SAM-e installation.
17 | Installation
drain or equivalent. Condensate normally cools in traps but is still hot. A SAMe or larger steam line generates more condensate and water may not cool in the trap. A drain water cooler option may be installed if required by code.
Figure 10: Condensate Traps
Hose cuff with clamps
2 in. (5 cm)
min.
1 ft (30 cm)
‘P’ Trap
1 ft (30 cm) min. before
any bend
Condensate line Route to fill cup or drain .
Use steam hose and clamps between cylinder and steam line.
Insulated copper steam line. Support so weight is not on cylinder.
Never
1 ft (30 cm)
min.
< 1 ft (30 cm)
Best
Never
< 1 ft (30 cm)
Best
Good
Never
Never
1 ft (30 cm)
min 0.5 in. (12 mm)
1 ft (30 cm)
min 2 in.
(5 cm)
Steam Line Rules
Figure 11: Typical Steam Line Installation
The following 10 points provide rules for installing steam lines connecting the NH-EL humidifier to ASD, BSD, CSD, SAMe and remote blower packs. In addition to these rules never use unapproved material for steam lines.
1. Allow minimum of 12 in. (30 cm) before first bend in steam line.
2. Slope the steam lines.
Installation | 18
> 10 ft (1.5 m)
Never
< 5 ft (1.5 m)
Note: 1) Always support hose. 2) Do not exceed 10 ft (3 m) hose length
Best
Best
Never
12 in. (30 cm) min. Radius
< 12 in. (30 cm) Radius
Never
< 12 in. (30 cm) Radius
Good
min. 12 in.
(30 cm)
Never
< 12 in. (30 cm)
< 12 in. (30 cm)
Good Never
Notes: 1. Units must operate in parallel.
2. Also for double units (cylinders must operate in parallel).
Condensate Traps
Good
Never
3. Use steam hose only for short distances.
4. For steam hose maintain minimum 12 in. (30 cm) bend radius.
5. Install traps on condensate lines at least 12 in. (30 cm) below
connection.
6. Only combine steam lines at steam distributor with Nortec adapter.
7. Install condensate traps at low points and horizontal to vertical
transitions.
19 | Installation
Best
Good Never
Nortec Condensate Trap
Sloping Down
Increase =
Condensate
Blockage
max. 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
Never
> 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
Good
Never
> 15 ft
(4.5 m)
Never
Install a valve or other obstruction
Never Never
Reduce Steam Line Size Install Copper or SST without Insulation
Never Never
Never
Never Never
Never
Never
After Installation Always:
Ensure all condensate lines / traps flow.
8. Increase diameter either on down slope or install condensate trap.
9. Install condensate traps if steam line > 15 ft (4.5 m).
10. In addition never:
Purge steam lines to remove any contaminants and installation materials
Installation | 20
L1 L2
Ground
L1 L2
Ground .
L1 L2 L3
Neutral
Ground
L1 L2 L3
Neutral
Ground
L1 L2
Ground
L1 Neutral
Ground
L1 L2 L3
Neutral
Ground
L1 L2
L3
Ground
Three Phase NH-EL
Single Phase NH-EL
Single Phase Supply
Three Phase Supply
(Note: Load will be unbalanced)
Three Phase Supply
Dedicated
Circuit Breaker
or
Fused Disconect
Note: 1
2
3
4
Optional internal fuses are not
a substitute for external fuses.
Dedicated external fused disconnect must be installed. Fusing must not exceed max circuit protection as indicated on the specification label.
Ensure that adequate power is available to carry full humidifier amp draw as indicated on the specification label.
All wiring to be in accordance with national and local electrical codes.
E X T
I
N
T
E X T
I N T
E X T
I N T
E X T
I N T
Three Phase Supply
(Note: Load will be unbalanced)
Electrical
Caution: Wiring to be performed by a licensed electrician.
21 | Installation
Figure 12: Primary Power Connection
1
2 3
10 ft min.
Humidity Control
(return air duct or location representative of the room)
Duct High
Limit
4
Out
door
temp.
sensor.
Air
Proving
Switch
Humidity Control
(return air duct or location representative of the room)
Caution: Failure to wire the humidifier in accordance with the wiring instructions could cause permanent damage. Such errors will void the warranty.
External Controls
Control Wiring
The following information is relevant to all controls, factory supplied or otherwise. For wiring use a minimum of 18 AWG and keep as short as possible. The NH-EL humidifier can be operated with two modulating inputs. Signal types must be the same (both demand or both transducer). The NH-EL can also be operated as On/Off. See NH-EL Humidifier Configuration on page 54 for configuration.
Control Location
Figure 13: Control Location (Duct Humidification)
Duct Humidification
1 Air Proving Switch
Locate so that it can sense air flow or lack of it.
2 Duct High Limit
NH-EL can be modulating, On/Off, or a humidity sensor. Locate at least 10 feet from steam distributor or far enough that under normal conditions
steam is fully absorbed.
3 Humidity Control
NH-EL can be Modulating, On/Off, or a Humidity Sensor. Can be located either in return air duct (preferred) or in room being humidified. Mount in area representative of room humidity (draft, doorways, sunlight, or overhang such
as a shelf can affect reading). Avoid placing near discharge diffuser of humidified air.
4 Outdoor Temperature Sensor Mount in area representing outdoor air temperature (makeup air duct, outside).
Installation | 22
1
Humidity Control
(in location representative of the space)
1
Humidity Control
(in location representative of the space)
1
Humidity Control
(in location representative of the space)
Note: Regardless of selecting on/off or modulating control method, Nortec humidifiers must have a
closed circuit across its security loop control terminal to operate. Nortec highly recommends the use
of a high limit humidistat and an air proving switch in series for this function.
Space Humidification
Figure 14: Control Location (Space Humidification)
1 Humidity Control
NH-EL can be modulating, On/Off, or a humidity transducer. Locate in room being humidified but not in discharge zone of blower pack(s). Mount on indoor wall in area representative of room humidity (draft, doorways, sunlight, or
overhang such as a shelf can affect reading).
2 High Limit Humidistat (not shown) Install a high limit On/Off humidistat in area representative of room humidity.
3 Outdoor Temperature Sensor (not shown) Mount outside in area representing air temperature.
23 | Installation
Figure 16: Digital On/Off Humidistat
Note: 1
2 3
4
Humidifier will run when circuit between terminal 1 a n d 2 on h u midifier is closed. T e rminal 1 is 24 VAC Hot, turn uni t o ff to avoid shorting while wiring. Digital Humidi stat requires 24 VAC power from terminals 1 and 3 of humidifier.
2520273 - Digital On/Off Duct Humidistat can also be used for duct high li mit. W ire in series to 3 - Common and 4 - Digital Out of the humidistat.
Humidifier Terminal Strip
Air Proving
Switch
Duct High
Limit
2548731 - Digital
On/Off Humidistat
1 – Common
8 – Temperature
On/Off Control Wiring
Figure 15: On/Off Controls
2 – 24 VAC
3 – Digital In
4 – Digital Out
5 – Fan Activation
6 – Fan Activation
7 – Temperature
Installation | 24
Air Proving
Switch
Duct High
Limit
Digital On/Off
Humidistat
Duct Sensor
1 - Common
2 - 24 VAC
3 - Analog Out
Wire remote sensor to digital display as shown below,
wire digital display to humidifier as shown above.
2520273 - Digital On/Off Duct Humidistat Package
1 - Ground
2 - 24 VAC
7 - Analog In
The security loop must be closed for keep warm to operate when the humidifier is in standby.
Install an On/Off high limit humidistat between terminal 1 and 2.
Optional Modulating
Humidity Controller
Channel 2
Humidity Controller
Channel 1
Other On/Off Controls
Figure 18: Keep Warm Wiring
1 – Common
7 – Analog In
Keep Warm Wiring
For the keep warm feature to work the security loop between terminal 1 and 2 on the low voltage terminal strip must be closed. To accomplish this:
1 Install an On/Off high limit humidistat between terminal 1 and 2. 2 Install any other On/Off controls in series with the control signal connected to terminal 4
(Channel 1 control signal).
3 If desired a modulating high limit humidistat can also be installed and connected to terminal
5 (Channel 2 control signal).
2 – 24 VAC
Figure 17: Duct Sensor Wiring
25 | Installation
Note: 1
2
3
4
Install On/Off controls or jumper between terminal 1 a n d 2 o f h u midifier in order to run. Terminal 1 is 24 VAC Hot, turn unit off to avoid shorting while wiring.
High Limit Humidistat must be duct mounted. It can be On/Off or modulating. Control Humidistat can be mounted in space or in return air duct and can be On/Off or modula ting.
Air Proving
Switch
High Limit Humidistat
Control Humidistat
Humidifier Terminal Strip
SPACE
SPACE
Figure 20: Digital Modulating Humidistats
1 – Common
2 – 24 VAC
1 – Common
2 – 24 VAC
Analog Out -3
24 VAC – 2
Common – 1
Modulating Control Wiring
Figure 19: Modulating Controls
Installation | 26
Air Proving
Switch
Duct High
Limit
2520261 - Digital Wall W/O Sensor
1509858 - Wall
Sensor
1 - Common
2 - 24 VAC
7 - Analog In
1 - Common
2 - 24 VAC
6 - Analog Out
Wire wall sensor to digital display as shown
below, wire digital display to humidifier as shown
for 1510142 - Digital Wall Humidistat.
+
1509858 - Wall Sen so r
2520261 - Dig ital Wall W/O Sensor
2520261 - Digital Wall W/O Sensor
1509858 - Wall
Sensor
Figure 22: Digital Wall Humidistat - On/Off High Limit Duct Humidistat
1 – Common
2 – 24 VAC
1 – Common
8 – Temperature
Figure 21: Digital Wall Humidistat – Remote Wall Sensor
2 – 24 VAC
3 – Common
4 – Digital Out
7 – Temperature
27 | Installation
Loading...
+ 69 hidden pages