Nortec NHDI, NHSC User Manual

NHSC / NHDI Resistive Element Steam Humidifiers
Installation, Operation,
Maintenance, and
Troubleshooting Guide
NHSC
NHDI
IMPORTANT: Read and save these instructions. This guide to be left with equipment owner.
Table Of Contents
INSTALLATION 1
RECEIVING & UNPACKING EQUIPMENT ................................1
PRE-INSTALLATION CHECKPOINT ...................................1
BASIC HUMIDIFIER CONFIGURATION..................................1
LOCATION & MOUNTING .........................................2
HUMIDIFIERS ·············································2
BLOWER PACKS ···········································3
STEAM DISTRIBUTORS AND SHORT ABSORPTION MANIFOLD ·················3
PLUMBING .................................................6
WATER SUPPLY LINE ········································6
DRAIN LINE ··············································6
STEAM LINE AND CONDENSATE RETURN LINE ··························7
ELECTRICAL................................................7
PRIMARY VOLTAGE SUPPLY WIRING TO HUMIDIFIER ······················7
PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER(S) TO BLOWER PACKS ·······7
LOW VOLTAGE CONTROL WIRING ·································9
CONTROL INSTALLATION ······································9
OPTIONAL MODULATION (CONTINUOUS CONTROLS)······················10
OPTIONAL MODULATION (CONTINUOUS CONTROL) PACKAGES BY NORTEC ········11
OPERATION 11
INTRODUCTION .............................................11
LAYOUT AND FUNCTION ........................................11
LEVEL REGULATION ········································11
STEAM GENERATION REGULATION································12
FLUSHING ··············································12
SCALE COLLECTOR TANK ·····································12
NHSC/ NHDI OPERATION ........................................12
STARTING OPERATION ·······································12
INTERROGATION OF THE OPERATING STATUS ···························14
MAINTENANCE..............................................17
NOTES ON MAINTENANCE .....................................17
DISMANTLING AND REASSEMBLYWORK .............................18
NOTES ON CLEANING........................................18
FAULT ELIMINATION ........................................19
SCALE TANK SERVICING ......................................20
REPLACING UNIT FUSES ......................................21
RESETTING FAULT INDICATION“ERROR” .............................21
HEATING ELEMENT REPLACEMENTINSTALLATION INSTRUCTIONS ................21
TROUBLESHOOTING ··········································23
CONTROL CIRCUIT TERMINALBLOCK .................................25
PRE-START-UP CHECKLIST ......................................26
START-UP CHECKLIST .........................................27
MAINTENANCE CHECKLIST .......................................28
EXPLODED VIEWS ............................................30
WIRING DIAGRAMS ...........................................34
INSTALLATION
.
as indicated on the spec label. Refer to local codes.
RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has been delivered.
2. All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
3. Inspect shipping boxes for damage and note on shipping waybill accordingly.
4. After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
5. All NORTEC products are shipped on an F.O.B. factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
PRE-INSTALLATION CHECKPOINT
1. Ensure that available voltage and phase corresponds with humidifier voltage and phase as indicated on humidifier’s spec label (see Figure #1).
3. Report any discrepancy immediately.
BASIC HUMIDIFIER CONFIGURATION
NORTEC NHSC / NHDI humidifiers share a modular sheet metal cabinet. Each unit has a right side electrical compartment. Each electrical compartment has a hinge-down front door which is removable from any partially or fully opened position. Each electrical compartment has a screw-mounted right side cover which can open for ease of electrical connection. For safety, the door when closed keeps the side cover from being opened.
Single units have a plumbing compartment attached to the left side of the electrical. Double units have a second plumbing compartment. Each plumbing compartment has a hinge-down front door. For safety, the door must be closed in order to engage the safety interlock. To avoid any danger, never operate the humidifier with a door off.
To open the doors, unlock, lift door up slightly and pull top of door forward. Door will hinge 180 degrees and hang straight down. To remove door, swing door parallel to floor. Then lift up slightly and out. To reinstall door, hold parallel to floor and insert hinge pins at bottom.
2. Ensure that the dedicated external disconnect is of sufficient size to handle the rated amps
Figure #1
NHSC / NHDI Series Humidifier
SteamOutlet
1.75" O.D.
Water
Supply
NOTE: NHDI does not have the scale collector tank.
Scale Collector Tank
Spec Label
Drain Valve
Optional SSR Cooling Fans
Keypad Display
Power and Control Wiring
Figure #2
Minimum Steam Line Clearance
Min. 10 Degree Slope
Min. 12"
Trap
* See Section On
Condensate
Return Line
NOTE: Trap must be 3' minimum down from steam distributor If not, condensate must be routed to drain.
-1-
Figure #3
Clearance Required (Top View)
Condensate Return
Steam Outlet
NOTE: Local and national codes may deviate, please consult applicable codes for clearance requirements. Right side min. 36" side clearance. Min. 36" frontal clearance recommended see note. Top 12” Min, Bottom 12” Min, and Left Side 2” Min.
LOCATION & MOUNTING
HUMIDIFIERS
Right Side
Front
1. Location of the humidifier should be below and as close as possible to the steam distributor location. If possible, DO NOT locate humidifier any further than absolutely necessary from steam distributor location, as controllability and net output will be reduced as a result of heat loss through the steam hose (see Steam Distribution Engineering Manual).
2. Where possible, mount humidifier at a height convenient for servicing.
3. Wall mounting bracket provided should be securely attached horizontally and open edge facing upwards, using field-supplied fasteners. For a single unit, use a minimum of 4 - #12 x 3” long wood screws. For a double unit, use a minimum of 6 - #12 x 3” long wood screws. These screws must be fastened securely on a 2 x 4 wood stud or equivalent support. If any spacer material is used between the bracket and the structural material such as drywall, increase fastener length accordingly. In addition, install a minimum of 2 field supplied fasteners in the holes provided in the back of the unit to prevent the unit from being bumped off the wall bracket. See Figure #4.
NHSC / NHDI Series humidifiers are designed to mount on a suitable wall or vertical surface. Do not sit the unit on floor due to clearances required for plumbing, electrical, and control entrances. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. NORTEC will not accept responsibility for installation code violations.
Figure #4
Wall Bracket Mounting
Frontal clearance min. 36" (91 cm) Right side clearance min. 36" (91 cm) Left side clearance min. 2" (5 cm)
Wall
7.7"
(19.6 cm)
4. Mount unit on hanging bracket after ensuring the bracket is properly anchored to the wall. Raise the unit and place it on the hanging bracket ensuring that the flanges in the mounting bracket are properly aligned and centered with the flanges of the unit. Push the unit in towards the wall to properly interlock the two flanges. Note: This will result in the unit shifting slightly down. Ensure that the hanging bracket’s flanges are fully engaged
Figure #5
Installation of the Scale Tank Bracket (NHSC only)
1.
2.
1) Line up holes in bracket with
3.
1.
holes in drain pan. Fasten the bracket to the drain pan using the four Nylon lock nuts provided.
2) Fasten the front of bracket with the two #10-24 self tapping screws provided.
3) The two locking screws for the bracket should already be installed.
-2-
and visible from within the plumbing section of the unit, and that the unit’s flanges are properly contained within the wall bracket.
5. Install tank bracket. See Figure #5. (NHSC Version only). Mounting the scale tank. (NHSC Version only).
Figure #6
Remote Mounted Blower Pack
Figure #7
Remote Mounted Blower Packs (RMBP)
23.0"
(58.4 cm)
11.0"
(28.0 cm)
Condensate
Steam
Power
14.2"
(36.2 cm)
2.9"
(7.3 cm)
Wall
Mounting
Bracket
Remote
Mounted
Blower Pack
Scale Collector Tank
6. Make sure humidifier is level.
7. DO NOT mount humidifier on hot surfaces.
8. If humidifiers are mounted on roof, a thermostatically ventilated weatherproof
Typical Remote Mounted Blower Pack Installation
Figure #8
Dimensions Shown Are Steam Line Connections Allow Minimum 12" (31 cm)
7.7"
(19.5 cm)
7.2"
(18.2 cm)
Clearance On Each Side
cabinet provided by others should be used. Consult factory.
9. DO NOT mount humidifiers on vibrating surfaces or duct work.
BLOWER PACKS
1. Blower packs are an optional accessory used to directly distribute steam to localized areas (such as computer rooms) or in structures that do not have a built-in air distribution system.
Remote Mounted Blower Packs (RMBP) Only
NHSC
uses Nortec steam hose 1.75" O.D.or stainless steel pipe.
uses Nortec steam
3"
Min. Trap Height 3" Required
Humidistat
Scale
Collector
Tank - NHSC
Water
Supply 3/8”
Drain Line
1.75” O.D.
Air
Gap
NHSC / NHDI using a Remote Mounted Blower Pack (RMBP)
NHDI
hose 1.75” O.D. or stainless steel pipe.
Do not exceed 10 ft when using steam hose.
Steam Line Connection
LCD Keypad Display with LED Status
Low Voltage Controls Wiring 24 Vac
Primary Wiring Copper Funnel
Drain (by others)
-3-
2. All NHSC / NHDI Series blower packs consist of a steel cabinet containing: blower/motor powered by voltage directly from the humidifier, fuse, relay, speed select switch, stainless steel steam distributor, supply air grille with adjustable louvers, and a built-in manual reset safety thermostat to turn off the humidifier if the blower pack gets overheated. Control thermostat, mounted on the steam distributor, starts the fan when steam is generated. When supply voltage differs from voltage required to run blower motor, the blower pack will contain the proper transformer. All blower packs provide intake air filters, if required.
3. For installation details about the blower pack, please refer to the blower pack installation manual located in the blower pack box, Form #XX-277.
STEAM DISTRIBUTORS AND SHORT ABSORPTION MANIFOLD
1.1. Steam distributors are an optional accessory used to directly distribute steam to localized areas (such as computer rooms) which are served by ducted air. These distributors are made of stainless steel and are mounted level to the duct.
6. For installation details, please refer to the installation manual located in the Steam Distributor box, Form #XX-231.
7. For calculating absorption distances, refer to H.E.L.P. Software or the Steam Distribution Engineering Manual, Form #XX-232.
2. The SAM-e optional accessory has the same function, to distribute steam inside a duct. The only difference is that this system is designed to reduce the absorption distance of the steam in the duct by optimizing the steam distributors.
3. Each cylinder requires its own steam line
and at least one distributor (do not join two or more cylinders to one larger steam line).
Any cylinder’s steam line may be divided into multiple branches to feed more than one distributor. Steam supply line “tees” are common stainless fittings that are available for this purpose.
4. Steam distributor locations are typically as follows: supply air duct, return air duct, air handling unit. Proper location should consider: air temperature, relative humidity before the distributor, air velocity, dimensions of the location, amount of steam being introduced into the duct, downstream obstructions, and surfaces vulnerable to wetting.
5. The NHSC / NHDI can overcome 6” of W.C. duct static pressure max. Consult the factory if you exceed 6” of W.C.
-4-
SAM-e
static pressure
Trap depth
2” greater
than duct
Min 24”
Condensate return
to floor drain, sump
pump or back to the
humidifier
Supply 3/8”
Steam Inlet
Collector
Drain Line
1.75" O.D.
Water
Figure #9
Typical AHU / Duct Application using a SAM-e
NHSC
uses Nortec steam hose 1.75” O.D. Or Med. L Copper Insulated
NHDI
uses Nortec steam hose 1.75” O.D. or stainles steel pipe.
Do not exceed 10 ft
Gap
Air
when using steam hose.
Steam Line Connection
LCD Keypad Display with LED Status
Low Voltage Controls Wiring 24 Vac
Primary Wiring Copper Funnel
Drain (by others)
Scale
Tank
NHSC
Humidistat
NHSC using a Short Absorption Manifold(SAM-e)in Duct/AHU
Figure #10
Typical Duct Application using Standard Distributor
NHSC
uses Nortec steam hose 1.75” O.D. Or Med. L Copper Insulated
NHDI
uses Nortec steam hose 1.75” O.D. or stainles steel pipe.
Do not exceed 10 ft when using steam hose.
Steam Line Connection
LCD Keypad Display with LED Status
Low Voltage Controls Wiring 24 Vac
Primary Wiring Copper Funnel
Drain (by others)
Condensate trap
must be 2” greater
than duct static
pressure.
Steam Inlet
Min 24”
Scale
Collector
Tank
NHSC
Drain Line
1.75" O.D.
Water
Supply 3/8”
Humidistat
Air
Gap
NOTE: NHDI does not have the scale management system.
-5-
PLUMBING
All water supply and drain line connections should be installed in accordance with local plumbing codes and should be copper or other material suitable for potable water at 140ºF (60ºC).
WATER SUPPLY LINE - NHSC
1. The humidifier is intended to operate on potable water.
2. Standard fill valves are sized for water pressure ranging from 30 to 80 psig. For other pressures, consult factory. This pressure should be measured at the humidifier if the water pressure is suspect.
3. ALWAYS supply and install a shut off valve in the fill water supply line dedicated to the humidifier to facilitate servicing. Use ½" OD copper to within 4 feet of the humidifier. Reduce to 3/8" OD and connect to the factory-supplied 3/8" olive compression fitting under the humidifier.
4. Same installation as #3, but add Drain Water Cooler instead of fill.
#11). A field-supplied funnel (see Figure #12) is recommended. It will prevent backup in the drain pan and in the cylinder due to partially blocked or badly installed drain lines. This prevents rusting of the drain pan.
2. The NHSC scale collector tank is also equipped with its own drain. It is recommended to pipe, with a flex hose, the scale collector tank to allow drainage, if required while maintaining ease of servicing (DO NOT HARDPIPE).
3. The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons, since drain water from humidifier can be very hot.
4. Keep drain lines as short as possible. Keep
drain lines sloped down, not level and not up since low spots in drain lines will accumulate sediment and cause backup.
The drain line should be 2.0” O.D. copper pipe or larger. Do not use plastic pipe for drain lines. Consult factory.
DRAIN LINE - NHDI
WATER SUPPLY LINE - NHDI
1. Humidifier is intended to operate on Reverse Osmosis (RO) water or De-ionized (DI) water with a water conductivity of less than 20 Microsiemens.
2. Standard fill valves are sized for water pressure ranging from 30 to 80 psig. For other pressures, consult factory. This pressure should be measured at the humidifier if the water pressure is suspect.
3. ALWAYS supply and install a shut-off valve in the fill water supply line dedicated to the humidifier to facilitate servicing. Use ½" OD plastic or stainless steel to within 4 feet of the humidifier. Reduce plastic or stainless steel to 3/8" OD and connect to the factory-supplied 3/8" olive compression fitting under the humidifier.
4. Same installation as #3, but add Drain Water Cooler instead of fill.
DRAIN LINE - NHSC
1. Humidifier is equipped with a 1.5”" O.D. unthreaded drain outlet on underside of drain canal on bottom of the humidifier (see Figure
1. Humidifier is equipped with a 1.5” O.D. un-threaded drain outlet on underside of drain canal on bottom of the humidifier (see Figure #6). A field-supplied funnel (see Figure #8) is recommended. It will prevent backup in the drain pan and in the cylinder due to partially blocked or badly installed drain lines. This prevents rusting of the drain pan.
2. The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. If the Drain Water Cooler is used with potable water then copper may be used. Route to a floor drain or equivalent for safety reasons, since drain water from humidifier can be very hot. Verify with local codes on DI and RO water. Drains should be verified for their suitability for RO or DI water and local codes should be checked.
3. Keep drain lines as short as possible. Keep
drain lines sloped down, not level and not up since low spots in drain lines will accumulate sediment and cause backup.
The drain line should be 2.0” O.D. S.S. pipe or larger. Do not use plastic pipe for drain lines. Consult factory.
-6-
l
A
Supply Water
t
Connection
3/8“
Drain
Water Cooler
Connection 3/8”
Drain
Connection
1.5" O.D.
Figure #11
Drain Line Connection
NHSC Scale
Collector
Tank
A
7.95
B
(58.4)
Model 010-090 135-180 Left 135-180 Right
23.0
(20.2)
A (in.)
1.7”
1.7”
1.7”
Figure #12
Drain Connection
B (in.)
5.4”
5.4”
20.3”
Power Inlet
Controls Inlet
Optional Cooling Ki for SSR (consult factory)
STEAM LINE AND CONDENSATE RETURN LINE
1. Refer to the installation manual of the steam
distribution system used in your application. Steam Distributor Form #XX-231, SAM-e Form #XX-249, and Blower Pack Form #XX-277.
ELECTRICAL
PRIMARY VOLTAGE SUPPLY WIRING TO HUMIDIFIER
1. Check and ensure that available voltage and
phase corresponds with operating voltage and phase of humidifier as indicated on the humidifier spec label, see Figure #1.
2. Ensure that an adequate power supply is
available to carry full humidifier amperage drawn as specified by rated amps on the humidifier spec label, reference to local codes.
3. A dedicated external disconnect must be
installed. Do not exceed the maximum circuit protection amps as indicated on the nameplate label.
ir
Gap
Clamp and1.5”ID Hose Factory Supplied
Install aCopper Funnelfor theNHSC mode and aStainless SteelFunnel forthe NHDI model (byothers).
4. Connect ground wire to cabinet ground clamp.
Do not use neutral wire of four wire supply as ground.
5. Single phase humidifiers may be run on three
phase power, but load may unbalance power
NOTE: Steam hose should not reach bottom of the funnel.
Install a2” O.DCopper Pipefor theNHSC model and2”O.D. Stainless SteelPipe for the NHDImodel(by others).
grid.
6. External wiring sizes must be in accordance
with NEC and/or CEC and existing local electrical codes and by-laws.
Figure #13
Drain Pump by others (if necessary)
PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER(S) TO BLOWER PACKS
1. All blower packs are wired (by others) to be
powered from the humidifier.
Humidifier
2. As a safety feature, blower packs come
equipped with a manual reset safety thermostat and relay built into the blower pack cabinet. The manual reset thermostat turns
Recommended Model Gould - Model SSH Consult Factory
Floor
Surface
Line
Drain Line
off the humidifier if the blower pack gets overheated. The control thermostat, mounted on the steam distributor, starts the fan when steam is generated.
3. All blower packs have high efficiency blowers
to minimize the frontal and overhead clearance required to absorb the steam.
-7-
(ACTUAL)
Figure #14
Primary Voltage Supply Wiring
PRIMARY (LINE) VOLTAGE WIRING TO UNITVOLTAGE
(BY OTHERS)
L1
L2
- Single Phase Unit.
- Single Phase Supply.
- Required Voltage Between L1 And L2.
- Load Balanced.
L1
L2
L3
Neutral
Ground
Ground
- Single Phase Unit.
- 3 Phase Supply.
- Required Voltage Between L1 And L2.
- Load Will Be Unbalanced.
Ground Wire
Dedicated
Disconnect
Ground Wire
Dedicated
Disconnect
Circuit
Breaker
Or
Circuit
Breaker
Or
Ground Leg
2Pole Te rm i na l Block
E
I
X
N
T
T
Ground Leg
2Pole Te rm i na l Block
E
I
X
N
T
T
Ground Wire
L1
L2
L3
Neutral
Ground
Dedicated
Circuit
Breaker
Or
Disconnect
- 3 Phase Unit.
- 3 Phase Supply.
- Required Voltage Between Any Two Legs.
- Load Will Be Balanced.
NOTE: VoltageAt TerminalBlock Must Be InAccordance With Spec. Label. All Wiring ToBe InAccordance With Existing NationalAnd Local Electrical Codes.
-8-
Ground Leg
3Pole Te rm i na l
Block
E
I
X
N
T
T
4, All blower packs require field wiring between
two pole primary voltage terminal blocks and two low voltage control (class 1 circuit wiring required) terminal strips; one of each located in the humidifier and the remote blower pack cabinet. To properly access the primary block on the humidifier, it is necessary to open the side pan. To connect the primary and control (class 1 circuit wiring required) wiring, the wiring is fed through the grommet provided in the bottom of the blower pack. The terminal block and strip are accessed by removing the blower pack cover.
5. Field wiring of remote blower packs must conform to national and local electrical codes. Refer to wiring diagram supplied inside the humidifier.
6. Use approved wire for power connection from two pole terminal block of remote blower pack to additional two pole terminal block inside electrical section of humidifier.
7. Use approved wire to connect the ground clamp of remote mounted blower pack to ground clamp provided in the electrical section of humidifier.
LOW VOLTAGE CONTROL WIRING
A - Wall or Duct Mounted Control On/Off
Humidistat: Wired to make on drop in humidity, break
on rise to set-point. Set to desired % RH. Can be a make/break set of contacts from a Building Automation System.
B - Duct Mounted Safety High Limit On/Off
Humidistat (if used): Wired to make on drop in
humidity, break on rise to safety set-point. Set to approximately 85% RH as a safety to help prevent saturation and wetting in the duct.
C - Duct Mounted Safety Air-Proving On/Off
Switch (if used): Wired to make with sensed air flow,
break when no air flow. Used as a safety to prevent saturation when there is no airflow.
1. NORTEC offers various versions of A, B and C to suit each application. In general, A is essential, whereas B and C are highly recommended in ducted applications.
2. Field wiring from humidistat to humidifier and between devices should be 18 AWG or heavier and kept as short as possible.
3. Low voltage control terminal strips are provided in the electrical compartment. Internal sides are factory wired. External sides are to be field wired.
On-Off Controls
Figure #15
External Wiring of On/Off Controls
A
B
C
D
External
Internal
10
8
Controls are available from NORTEC as accessories. If controls were not ordered with humidifier, they must be supplied by others. The following information is relevant to all controls, factory supplied or otherwise.
A, B, C and D (described below) are to be wired in series (only one path for current) across terminals 8 and 10 on the low voltage control terminal strip or replaced with a jumper wire for constant operation. Caution: this is the “hot” wire from the 24V control transformer; it will blow the 3A fuse if any control field wiring touches ground.
4. Each humidifier is supplied with a wiring diagram inside.
D - Blower pack safeties
CONTROL INSTALLATION
1. Mount any wall humidistat (control or high limit) over standard electrical box at height similar to typical thermostat. Any wall humidistat should be in location representative of overall space being humidified and not in path of blower pack or air supply grille. Do not mount on a outside wall where temperature fluctuation can affect control response.
2. Mount duct humidistat in location representative of overall air humidity, usually in the return duct. Do not mount it directly in front of steam distributor or in turbulent or mixing zone. Mount it where humidity and temperature are uniform and representative of spaces being humidified.
3. Mount duct high limit humidistat downstream of steam distributors far enough that, under normal humidity and air flow
-9-
Loading...
+ 28 hidden pages