Nortec MES-U User Manual

MES-U Electrode Steam Humidifiers
Installation, Operation,
Maintenance, Spare Parts, and
Exploded Views Guide
IMPORTANT: Read and save this guide for future
reference. This guide to be left with equipment owner.
Form 03-111 Rev. 1
INSTALLATION 1
RECEIVING EQUIPMENT..............................1
PRINCIPAL OF OPERATION ............................1
WATER SUPPLY AND PLUMBING ..........................2
WATER CONNECTION .............................2
START-UP AND OPERATION ............................2
CAPACITY ADJUSTMENT ............................3
CYLINDER REPLACEMENT.............................3
WHEN TO REPLACE THE STEAM CYLINDER ...................3
REMOVING THE OLD CYLINDER .........................3
INSTALLING THE NEW CYLINDER ........................4
MAINTENANCE 4
EXTENDED SHUTDOWN..............................4
TROUBLESHOOTING 4
– TERMS USED ..................................4
– STARTING POINT.................................5
– PHYSICAL DIMENSIONS DIAGRAM .........................7
– WIRING DIAGRAM ................................8
– SPARE PARTS LIST................................9
– EXPLODED VIEWS DIAGRAM ...........................10
INSTALLATION
2
S
RECEIVING EQUIPMENT
Figure #1
Operation Schematic
1. Check packing slip to ensure ALL material has been received.
2. Inspect box for damage and note on shipping waybill accordingly.
3. After unpacking, inspect unit for damage and if damage is found, advise shipper as soon as possible.
4. Inspect unit (humidifier) to ensure it is the correct model, phase, and voltage. If any are incorrect, advise the factory or your local representative immediately.
NOTE: All products are shipped on an F.O.B.
factory basis. Any and all damage, loss, or breakage claims are to be made directly to the shipping company.
The NORTEC MES-U electrode humidifier is the
culmination of many years of research and development in the electrode humidifier industry. This unit has been built by skilled craftspeople and thoroughly tested before shipment and should, if the following instructions are observed, provide many years of trouble-free operation.
FOR HUMIDIFIERS INSTALLED IN THE CITY
OF LOS ANGELES: A city of Los Angeles approved
spring-loaded double ball CHECK VALVE should be supplied and installed by the contractor on each of the potable water inlets to each humidifier.
Recommended valve manufacturer: Watts
Regulator (phone 508-688-1811), model #7, size 3/8” NPT inlet and outlet.
CONDENSATE RETURN
(OPTIONAL)
FILL CUP
1. INLET CHAMBER
. FILL CHAMBER
3. WATER OVERFLOW CHAMBER (SAFETY DRAIN IN CASE OF FILL VALVE/ CONTROL BOARD FAILURE)
STRAINER
TAP
WATER
SUPPLY
FILL
VALV E
CONNECTION
1
DRAIN
1” AIR GAP
3
2
DRAIN VALV E
DRAIN CANAL
(OPEN TO ATMOSPHERE)
STEAM HOSE
ELECTRODE
CYLINDER
DRAIN PAN
An electronic timer uses the rate of amp fall to determine the water level. The objective is to concentrate current-carrying minerals in the cylinder so that a smaller volume of water is required to produce the rated steam output.
This achieves the longest life for the disposable cylinder because of minimal electrode coverage and use of less energy because the high concentration allows a minimal drain rate.
Each drain line from these humidifiers shall be routed, without dips or sags, to terminate above the flood level rim of a City of Los Angeles approved indirect waste receptor.
No combustible materials shall be placed in the duct and/or the air plenum.
When 90% F.L.A. is reached, the fill valve will open refilling cylinder to 110% F.L.A. On occasion, the drain valve will also come on if water level is too low, indicating too high a concentration and the requirement for a dilution of the water in the cylinder.
If the water reaches top of cylinder before 110% F.L.A., the fill valve shuts off via the sensor and fill-boil-fill-boil cycle continues, cycling off the red high
PRINCIPAL OF OPERATION
water sensor light until the concentration becomes high enough to reach 110% F.L.A. The above
When the humidistat calls, the cylinder fills to
described control process will then take over.
110% of the Full Load Amperage (F.L.A.) or to the top of the cylinder, whichever comes first. See Figure #1.
If it reaches 110% F.L.A. the water heats and boils
away to a level giving 90% F.L.A.
-1-
WATER SUPPLY AND PLUMBING
n
1. The orifice in the fill valve is sized for an extended water pressure range of 30 to 85 psi.
2. For water pressure between 15 and 30 psi, notify the factory and the next larger size fill valve will be supplied.
for water pressure from 30 to 85 psi and are protected by the built-in strainer.
4. For inlet water pressure outside this range, the factory should be contacted. (See Water Supply and Plumbing section of this manual.)
START-UP AND OPERATION
3. For cases below 15 psi, notify the factory and a fill valve with an oversized orifice will be supplied.
4. For cases above 85 psi, install a pressure reducing valve in the water feed line to the unit.
5. With extremely dirty or muddy water sources, e.g., some well sources, ensure proper filtration by adding an external filter to the water line entering the unit. (Consult factory for accessories such as filters.)
6. DO NOT use completely demineralized water with this unit as it is the minerals that allow the electrode principle to work.
7. DO NOT use a hot water source as it will cause deposits that will eventually block the fill valve orifice.
WATER CONNECTION
Figure #2
Bottom View of MES-U Unit
3/8" Cold Water
Olive Connection
Check to see that the unit is securely mounted on a level surface with the proper drain and water supply. Check for correct voltage with appropriately sized service. Check that the steam distributor, steam supply hose, and condensate line are correctly installed and routed back to the unit. Ensure that the external control humidistat is located in an area to properly sense the relative humidity to be maintained by the humidifier, and that the interconnecting low voltage wires between the humidistat and the unit’s control terminal strip are in accordance with the wiring diagram.
Check all electrical connections for wires which may have become loose in shipping. Components damaged due to loose connections are NOT under warranty.
Check electrode plugs to ensure they are pressed firmly onto the electrode pins. Important: Loose connections will cause overheating of the cylinder plugs, possibly melting the plugs and/or cylinder.
Open the isolating valve in the feed water line to the unit.
Make sure the humidistat is set high enough to call for humidification.
7/8" Drain Connectio
Use 7/8" I.D. Hose From Factory
A copper compression olive type coupling for 1/4"
1. O.D. soft copper tubing is provided with unit and requires no soldering for the water connection to the unit. See Figure #2.
2. An isolating valve should ALWAYS be placed in the feed water line allowing service of the fill valve.
3. Each unit is fitted with a fill solenoid valve located on the base drain pan. Flow orifices are designed
Turn on the main disconnect in the primary service feeding the unit and check that unit has power at the primary terminal block.
PUSH THE AUTO ON/OFF/DRAIN SWITCH TO “ON”.
Water will start to enter the cylinder through its bottom port and rise in the cylinder to a point determined by the solid-state control circuitry.
It is not unusual upon initial start-up for the water to fill the cylinder and cycle on the red high water sensor light.
The red light simply acts as a safety to shut off the fill valve and prevent over-filling. With the red light on, the water in the cylinder will continue to heat and, after a few minutes, start to boil. After the boiling action of the water has lowered the water level below the sensor at the top of the cylinder, the red light will go
-2-
out and the fill solenoid will again open until the cylinder is again full.
This cycling of the red light and fill valve will continue until the unit’s full output capacity is reached after which the water level will automatically lower itself in the cylinder. (The increased concentration allows for lower electrode coverage while maintaining the same output.) When a stabilized condition is reached the water will be boiling close to the cylinder seam level. The solid state circuitry will maintain the proper concentration in the cylinder by introducing short drains only when necessary.
cylinder is completely used as indicated by the red high water sensor light illuminated on the cabinet. When this condition is reached, a new replacement cylinder is to be installed.
NOTE: Red light may come on during initial start-up but does not mean cylinder replacement. See Start Up and Operation section of this manual.
Consult factory or agent for replacement. Quote the cylinder model from the white 3-digit label on the cylinder or quote model, voltage, and serial number from unit specification label.
If the cylinder is manually drained the above
process will repeat itself.
Low Water Conductivity
Should normalization of the unit be required immediately after start-up, the installer may speed up the process by artificially increasing water conductivity. During a fillcycle, the installer should dissolve half a teaspoon of table salt (no more) in a cup of water and add it to the cylinder by means of the fill cup attached to the plumbing section.
Open the plumbing compartment and add salt solution through cylinder outlet. Excessive amounts of salt will result in erratic operation of the unit; however, normalization of the unit will occur automatically through the solid-state control sequence.
CAPACITY ADJUSTMENT
Figure #3
Adjustable Pot
WHEN TO REPLACE THE STEAM CYLINDER
The steam cylinder is disposable and must be replaced at the end of cylinder life. Cylinder life is dependent on water supply conditions and humidifier usage. Failure to replace the cylinder at the end of cylinder life may result in unit damage. NORTEC is not responsible for any damages resulting from, or attributable to, the failure to replace a used cylinder (see Manufacturer’s Warranty).
Figure #4
Cylinder Removal
Adjustable Capacity Pot
The MES-U series of humidifiers come with adjustable capacity (AC) PC boards. These boards have a pot labeled 20 to 100%. See Figure # 3.
CYLINDER REPLACEMENT
After an extended period of operation, in accordance with life expectancy information, the
REMOVING THE OLD CYLINDER
n
See Figure # 4.
1. Turn off the water supply to unit.
-3-
Loading...
+ 9 hidden pages