Nor-Lake NOVA Refrigerators and Freezers User Manual

REFRIGERATORS AND FREEZERS
Installation, Operation and
Maintenance Instructions
INSPECTION
INSTALLATION
GENERAL
For shipping purposes, the condensing unit compressor is secured on the extra low
temperature models. Remove the spring clips and loosen the mounting bolts prior to operation. See the label attached to the condensing unit.
If the doors are out of alignment on the cabinet, the doors can be adjusted. This can be accomplished by opening the door(s) and loosening the screws that hold both the top and bottom hinges to the cabinet. After adjusting the door so that it is aligned correctly, tighten the screws to securely hold the hinges in place.
VAPORIZER INSTALLATION
1 06/11 Rev. B 127717
Note: Disconnect power prior to installation.
1. Connect the power cord to the vaporizer and place it in the vaporizer bracket.
2. Attach the vaporizer bracket to the back of the unit using the four screws as shown, making sure the plastic drain tube is in the vaporizer pan.
LOCATION
The refrigeration system located at the top of the cabinet requires free air access for proper operation. Allow a minimum four (4) inch clearance on the top, rear, and sides of the cabinet. The cabinet should also be levelled when it is placed in its permanent location. There are no provisions for easily levelling the Roll-In models except by the use of shims. Only minimal shimming is allowable. A cabinet that will sit directly on the
floor without casters should be levelled when placed in its permanent location. If casters are not used, it is required by NSF that the cabinet be sealed to the floor with an approved sealant
such as Dow Corning #732 silicone.
ELECTRICAL
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.
GENERAL OPERATION
These refrigerators and freezers utilize a programmable controller to control the temperature and defrost settings. The controller, which is located on the facade of the unit, is factory set. Please see the default settings sheet and separate instructions that are included on the operation of this controller.
2 06/11 Rev. B 127717
REFRIGERATORS
FREEZERS
surface. The programmable controller is factory set to allow four defrosts per day.
and all heat generated by the defrost is removed, the unit cooler fans will not operate until
the coil temperature reaches approximately 25°F [-4ºC]. Note: Running a cold wall model freezer in an unconditioned environment may result in frost
build-up inside the cabinet.
GENERAL MAINTENANCE
PERIODIC CLEANING
vacuum cleaner to remove the loosened particles. Failure to keep the condenser coil clean
and clear of obstructions could result in temperature loss and damage to the compressor.
3 06/11 Rev. B 127717