SLIDING GLASS DOOR
DISPLAY REFRIGERATOR
Installation, Operation and
Maintenance Instructions
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to
ensure all crates and cartons have been received. All units should be inspected for concealed
damage by uncrating the units immediately. If any damage is found, it should be reported to the
carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and
tested in the Nor-Lake Manufacturing Facility and has been crated in accordance with
transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
INSTALLATION
GENERAL
After the unit crate and base have been removed, locate the legs or casters found inside the
cabinet. Legs or casters are optional on these units. Attach the legs or casters to the unit base by
screwing them into the same threaded fittings that were used to secure the crate base to the
cabinet. Insure that the legs or casters are screwed all the way into the base.
LOCATION
The refrigeration system located at the bottom of the cabinet requires free air access for proper
operation. Allow a minimum four-inch (10.2 cm) clearance to the rear and sides of the cabinet. The
cabinet should also be level when it is placed in its final location. If legs or casters are not used with
this unit, it is required by NSF that the cabinet be sealed to the floor with an approved sealant such
as Dow Corning #732 silicone.
Physical Specifications
Unit Exterior Dimensions Refrigerant
MR562 55" x 32-3/4" x 79-3/4" See Serial Tag
(139.7 cm x 83.2 cm x 202.6 cm)
* Note: Add 6 inches (15.2 cm) to the height for legs or 4-3/4 inches (12.1 cm) for casters.
Model Width x Depth x Height* Type/Amount
© Nor-Lake, Inc. 2004 7/04 106404
CANTILEVER SHELVING
The cantilever shelves can be installed at two different angles as shown below.
90° Setting 80° Setting
90° Setting: Insert the shelf bracket into the holes of the shelf standard. Make sure that it is
securely locked in position as shown in Figure 1. It may be necessary to use a rubber mallet to get
the shelf bracket to engage fully into the shelf standard.
80° Setting: Insert the shelf bracket into the holes of the shelf standard allowing the top of the
bracket to engage in the shelf standard as shown in Figure 2. Slowly lower the shelf to its angled
position.
Figure 1 Figure 2
ELECTRICAL
Check the proposed outlet to be used to ensure that the voltage, phase, and current carrying
capacity of the circuit from the electrical panel correspond to the requirements of the cabinet.
NEVER use an extension cord to run power to the unit. All inter-wiring between the electrical panel
and the unit must be done in accordance with the National Electric Code and all state and local
codes. Refer to the Serial Tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate electrical shock and
injury from moving parts when servicing equipment.
Electrical Data
Unit Type of
Model Connection Volt/Hz/Ph
MR562 Cord 115/60/1
2