Nelson Heat Trace TF4X40 Application Information

NELSON™ HEAT TRACING SYSTEMS

TF4X40 THERMOSTAT

SPECIFICATION / APPLICATION
DESCRIPTION
OUTLINE
ENCLOSURE
Molded Fiberglass Polyester
CLASSIFICATIONS
NEMA Type 4X IP66
TEMPERATURE RANGE
Fixed Range
4.4°C (40°F)
CAPILLARY
Length Material Max. Bulb Temp.
0.9m (3ft.) Copper 71°C (160°F)
ELECTRICAL DATA
CSA Rating UL Rating
22 amp Resistance 480VAC 22 amp Resistance 480VAC
CALIBRATION ACCURACY
2.2°C (4°F)
SWITCH TYPE
Single Pole Single Throw
38mm (1.5")
ø 1 1/8 Hole for .75" NPT Conduit Hub
25mm (1.0")
5mm (1/5") 2 pls
ø 10mm (3/8")
80mm (3 1/8")
4
ø 2mm (1/16")
83mm (3.25")
ø 6mm (.25") Mounting Hole, 2 pls
14mm (4.5")
133mm (5.25")
Two awg #14 Stranded 12" long
common - purple / NC - blue
Annual Maintenance:
1. Remove cover.
2. Spray a coat of lubricant and rust preventative such as CRC Stor & Lube, electrical grade, on the thermostat body.
3. Replace
cover.
Approvals:
General Locations
UL - E50023 CSA - LR52088-4 CE
64mm (2.5")
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336  www.nels
onheaters.com
GA-2240 Rev. 6
November 2007