NEFF D 26 Installation Instructions Manual

Installation instructions for the
built-in cooker hood
D 26...
NEFF (GB) Ltd
Before reading this manual, please unfold the illustrations at the back.
Important
Old appliances still have some resi­dual value. An environment-friendly method of disposal will ensure that valuable raw materials can be recovered and used again.
Before you dispose of your old applian­ce, make sure that it has been rendered inoperable.
Your new appliance was protected by suitable packaging while it was on its way to you. All materials used for this purpose are environment-friendly and suitable for recycling. Please make a contribution to protecting the environ­ment by disposing of the packaging appropriately.
Up-to-date information concerning opti­ons for disposing of your old appliance and the packaging from the new one can be obtained from your retailer or local government office.
a minimum distance of 650 mm (Fig. 1) is only permissible above a gas hob if the following rated heat loads (Hs) are not exceeded:
Gas cookers
load on one burner max. 03.0 kW load on all burners max. 08.3 kW load on oven max. 03.9 kW
Gas hobs
load on one burner max. 03.9 kW load on all burners max. 11.3 kW
Gas glass-ceramic hotplate
The data on nominal heat loads do not apply to gas glass-ceramic hot­plates. Be sure to observe the instructions provided by the manu­facturer of the hotplate.
Solid-fuel cookers
The maximum nominal heat loads and the minimum distance are the same as for gas cookers.
The extractor hood can be used for both exhaust (vented) and recirculation (ventless) operation.
Always position the extractor hood over the middle of the hob.
The minimum distance between the hob and the lower edge of the extractor hood is 650 mm, Fig. 1.
Additional directions concerning gas cookers:
Current installation specifications and directives of the gas appliance manufac­turers must be complied with.
Only one side of the extractor hood should be next to a full-height cabinet or a wall. Minimum distance: 50 mm.
nstallation of the extractor hood is
I
only permissible over a solid fuel stove (which may constitute a fire hazard, e.g. from sparks), provided the solid-fuel stove has an enclosed, non-removable cover and national regulations are com­plied with. This restriction does not apply to gas cookers and gas hobs.
The closer the extractor hood is to the hob, the greater the possibility that rising steam will condense into drops below the extractor hood.
2
Before installation
Exhaust air operation, Fig. 2
Exhaust air is discharged upwards through a ventilation shaft or directly through the outside wall into the open.
The exhaust air must not be dischar-
D
ged into a functioning smoke or exhaust flue or into a shaft used for ventilating rooms in which stoves are located.
When discharging air into smoke or exhaust flues which are not in use, local authority approval is required.
When the extractor hood is operated
D
with exhaust air at the same time as fire installations that require a chimney (such as gas, oil or coal-fired central heating systems, instant water heaters or hot-water boilers), provision must be made for an adequate supply of air for stove combustion.
Safe operation is possible if the under­pressure in the room where the stove is installed does not exceed 4 Pa (0.04 mbar).
This can be achieved if the combustion air can flow through non-closable ope­nings such as in doors, windows, wall vent-boxes or other technical features or arrangements whereby combustion air can be replenished.
Note: In assessing this possibility, the entire combined ventilation of the home must be taken into consideration. This rule does not apply to operation of coo­king appliances such as hobs and gas cookers.
Exhaust air routing must always comply with local authority regulations.
If the extraction hood is used in recircu­lating operation - with activated carbon filter - unrestricted operation is possible.
With exhaust mode, a backwash valve should be installed unless it is already incorporated in the exhaust pipe or wall box. (Fig. 3). If a backwash valve is not included with your appliance, your dealer can supply you with one (see the section on acces­sories in the operating instructions).
Installation backwash valve:
1. Cut out the protective grid in the air
connector, Fig. 5.
2. Insert the backwash valve in the
mounting openings on the air connector, Fig. 3.
If the exhaust air is being routed through the outside wall, a telescopic
wall box should be used, Fig. 4.
Connection between extractor hood and telescopic wall box:
With an exhaust hose or an exhaust pipe.
Optimal efficiency of the extractor hood:
Short, smooth exhaust pipe.
As few bends as possible.
Pipe diameter as large as possible and wide pipe bends.
Round pipes
we recommend a min. inside diame­ter of 120 mm.
Flat ducts must have an inside cross­section equivalent to that of the round
pipes.
l 120 mm dia. approx. 113 cm l 150 mm dia. approx. 177 cm
In the case of different pipe diame-
2
2
ters, insert sealing strip.
For exhaust air operation, ensure that there is an adequate supply of air.
3
Loading...
+ 4 hidden pages