NEFF D 26 Installation Instructions Manual

Installation instructions for the
built-in cooker hood
D 26...
NEFF (GB) Ltd
Before reading this manual, please unfold the illustrations at the back.
Important
Old appliances still have some resi­dual value. An environment-friendly method of disposal will ensure that valuable raw materials can be recovered and used again.
Before you dispose of your old applian­ce, make sure that it has been rendered inoperable.
Your new appliance was protected by suitable packaging while it was on its way to you. All materials used for this purpose are environment-friendly and suitable for recycling. Please make a contribution to protecting the environ­ment by disposing of the packaging appropriately.
Up-to-date information concerning opti­ons for disposing of your old appliance and the packaging from the new one can be obtained from your retailer or local government office.
a minimum distance of 650 mm (Fig. 1) is only permissible above a gas hob if the following rated heat loads (Hs) are not exceeded:
Gas cookers
load on one burner max. 03.0 kW load on all burners max. 08.3 kW load on oven max. 03.9 kW
Gas hobs
load on one burner max. 03.9 kW load on all burners max. 11.3 kW
Gas glass-ceramic hotplate
The data on nominal heat loads do not apply to gas glass-ceramic hot­plates. Be sure to observe the instructions provided by the manu­facturer of the hotplate.
Solid-fuel cookers
The maximum nominal heat loads and the minimum distance are the same as for gas cookers.
The extractor hood can be used for both exhaust (vented) and recirculation (ventless) operation.
Always position the extractor hood over the middle of the hob.
The minimum distance between the hob and the lower edge of the extractor hood is 650 mm, Fig. 1.
Additional directions concerning gas cookers:
Current installation specifications and directives of the gas appliance manufac­turers must be complied with.
Only one side of the extractor hood should be next to a full-height cabinet or a wall. Minimum distance: 50 mm.
nstallation of the extractor hood is
I
only permissible over a solid fuel stove (which may constitute a fire hazard, e.g. from sparks), provided the solid-fuel stove has an enclosed, non-removable cover and national regulations are com­plied with. This restriction does not apply to gas cookers and gas hobs.
The closer the extractor hood is to the hob, the greater the possibility that rising steam will condense into drops below the extractor hood.
2
Before installation
Exhaust air operation, Fig. 2
Exhaust air is discharged upwards through a ventilation shaft or directly through the outside wall into the open.
The exhaust air must not be dischar-
D
ged into a functioning smoke or exhaust flue or into a shaft used for ventilating rooms in which stoves are located.
When discharging air into smoke or exhaust flues which are not in use, local authority approval is required.
When the extractor hood is operated
D
with exhaust air at the same time as fire installations that require a chimney (such as gas, oil or coal-fired central heating systems, instant water heaters or hot-water boilers), provision must be made for an adequate supply of air for stove combustion.
Safe operation is possible if the under­pressure in the room where the stove is installed does not exceed 4 Pa (0.04 mbar).
This can be achieved if the combustion air can flow through non-closable ope­nings such as in doors, windows, wall vent-boxes or other technical features or arrangements whereby combustion air can be replenished.
Note: In assessing this possibility, the entire combined ventilation of the home must be taken into consideration. This rule does not apply to operation of coo­king appliances such as hobs and gas cookers.
Exhaust air routing must always comply with local authority regulations.
If the extraction hood is used in recircu­lating operation - with activated carbon filter - unrestricted operation is possible.
With exhaust mode, a backwash valve should be installed unless it is already incorporated in the exhaust pipe or wall box. (Fig. 3). If a backwash valve is not included with your appliance, your dealer can supply you with one (see the section on acces­sories in the operating instructions).
Installation backwash valve:
1. Cut out the protective grid in the air
connector, Fig. 5.
2. Insert the backwash valve in the
mounting openings on the air connector, Fig. 3.
If the exhaust air is being routed through the outside wall, a telescopic
wall box should be used, Fig. 4.
Connection between extractor hood and telescopic wall box:
With an exhaust hose or an exhaust pipe.
Optimal efficiency of the extractor hood:
Short, smooth exhaust pipe.
As few bends as possible.
Pipe diameter as large as possible and wide pipe bends.
Round pipes
we recommend a min. inside diame­ter of 120 mm.
Flat ducts must have an inside cross­section equivalent to that of the round
pipes.
l 120 mm dia. approx. 113 cm l 150 mm dia. approx. 177 cm
In the case of different pipe diame-
2
2
ters, insert sealing strip.
For exhaust air operation, ensure that there is an adequate supply of air.
3
Preperation for Installation Electrical connection
Connecting to Ø 100 mm exhaust­air duct:
Cut out the protective grid in the air outlet. Fig. 5.
Attach the reducing adapter (enclosed or available from specialist dealer) to the air outlet. Fig. 6. Attach the exhaust-air duct to the adapter.
Connecting to Ø 120 mm exhaust­air duct:
Cut out the protective grid in the air outlet. Fig. 5.
Attach the exhaust-air duct directly to the air outlet.
Connecting to Ø 150 mm exhaust­air duct:
Cut out the protective grid in the air outlet. Fig. 5.
Attach the enlarging adapter (enclosed or available from specialist dealer) to the air outlet. Fig. 6. Attach the exhaust-air duct to the adapter.
If a backflow flap has been installed,
check that it functions properly.
Recirculating air operation, Fig. 7
(if there is no possibility of exhaust air operation).
The air purified by an additional activa­ted carbon filter is returned to the room.
Preparation
Push the filter screen up slightly, lift it towards you over the brackets and take it out downwards.
Insert the screw through the wing nut and bushing and screw into the housing (only necessary upon initial fitting, Fig. 19). The screw and wing nut are included with activated carbon filter.
Using a screwdriver or similar, press the two lugs in the housing through to the back (only necessary upon initial fitting), Fig. 20.
After installing the extractor hood, insert the activated carbon filter. See operating manual for item no. and description.
If the extractor hood is installed beneath a cabinet, ensure that there is an adequate air outlet (min. 177 cm
4
2
).
The extractor comes as standard equip­ped with a protective grid in the air connec­tor. If this is has been removed (in the case of exhaust air operation), the air connector must be supplemented by a reducer piece with protective grid (see section on special accessories in the instruction manual).
Electrical connection
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: Fitting a Different Plug:
The wires in the mains lead are coloured in accordance with the following code:
Green and Yellow – Earth Blue – Neutral
Brown – Live If you fit your own plug, the colours of these wires may not correspond with the identify­ing marks on the plug terminals. This is what you have to do:
1. Connect the green and yellow (Earth)
wire to the terminal in the plug marked ‘E’ or with the symbol ( ), or colou­red green or green and yellow.
2. Connect the blue (Neutral) wire to the
terminal in the plug marked ‘N’ or colou­red black.
3. Connect the brown (Live) wire to the ter-
minal marked ‘L’, or coloured red.
The extractor hood should only be connec­ted to a safety socket installed in accordan­ce with specifications. The safety socket should be located as accessibly as possible in the area of the extractor hood.
For repairs, always disconnect the
appliance.
Length of the connection cable: 1.30 m. If permanent connection is necessary:
The extractor hood should only by connec­ted by an electrician registered with the local electricity board.
A disconnecting device must be supplied locally. Disconnecting devices shall be swit­ches with a contact opening of more than 3 mm and all-pole disconnection. They inclu­de on-load switches and contactors.
This appliance complies with EU regulations on interference suppression requirements.
Installation
Please note: A wall hanging set can be
obtained from your dealer (see section on special accessories in the instruction manual) for fastening the hood (e.g. at the end of the row of kitchen units).
The extractor hood is designed for
installation between two wall cabinets.
1. Remove grease filter (see instruction
manual).
2. Using the enclosed template mark
the positions of the screws on the side panels of the neighbouring cabinets, Fig. 8.
The extractor hood can also be installed slightly lower, depending on the height of the wall cupboards. Position the template correspondingly lower.
Observe the minimum distance
from hob to extractor hood of 650 mm (the fixing screws must be fitted at least 1040 mm above the hob).
3. Predrill (with bradawl or 2 mm bit)
and screw in the screws to 5 mm, Fig. 9.
4. Suspend the extractor hood on the
two screws between the wall cabinets, Fig. 10.
5. The two door carriers of the extractor
flap must be pushed into the appliance to the stops, Fig. 11.
6. Align the extractor hood with the
leading edge of the side cabinets. Important: If the door of the unit is at
a distance from the body of the unit (e.g. due to rubber stops), the extractor hood must be drawn forward by the same distance.
Mark the position of the lower fixing screws, predrill and fasten the screws.
All four fixing screws must be firmly tightened. Fig. 12.
7. Connect pipes.
8. Connect electricity.
Mounting the door:
Door thickness: min. 16 mm Door height: 380 to 700 mm Door weight: max. 7 kg.
In order to match the wall cabinets on either side, the door can project at the top and bottom. Fig. 13.
1. Remove the two door carriers to the
right and left, by pulling both the red plastic catches inwards and removing the door carrier out towards you. Fig. 14.
2. Mark the fixing points on the door.
For dimensions of vertical screw fixings, see Fig. 15.
If the top edge of the door is not
flush with the top edge of the cabinet, amend the dimensions accordingly.
If the tops of the cabinets are
not installed flush with each other, the door must be mounted corre­spondingly higher.
The screw locations on the door can be marked directly on the door in situ. If you are doing this, leave the door carriers in the appliance. Position the door, align it and mark the back.
Keep precisely to the dimension
570 ± 2.
3. Screw the door carriers to the door,
making sure your left-right orientation is correct. Fig. 16.
4. Insert the complete door into the
extractor hood. Fig. 11.
Check that the door meets the stops on both sides when pulled out. This means that it is safely locked in place.
The red plastic catches can only be released if the door is not swung out to the stop.
5. The two screws to the right and left
inside the housing can be used to adjust door gliding according to the weight of the door. Fig. 17.
Turning the screws clockwise will make the door more difficult to move..
5
Installation
Mounting wall covering rail:
The gap between the hood and the rear wall can be dressed with the enclosed covering rail. Fig. 18.
Screw-fasten the covering rail to the underside of the extractor hood. Fig. 18.
Refit the grease filter (see instruction manual).
If the unit door has to be removed:
Pull the red plastic catches in the housing on both sides inwards to release the door, which can then be pulled out towards you. Fig. 14.
Technical data
Ventilation capacity in m3/h according to DIN 44971 and freeblowing
Exhaust air operation
Appliance version
2 fan speeds single motor
Speed
min. max.
120 mm dia.
DIN
160 250
blowing
free-
170 265
150 mm dia.
DIN
120
170
blowing
free-
130
200
Recirculating air
operation with
activated carbon
filter
140 210
3 fan speeds single motor
3 fan speeds dual motor
slide control single motor
slide control dual motor
Weight in kg
Appliance version
single motor
dual motor
min. max.
min. max.
min. max.
Normal speed min. max.
full speed
Exhaust air
6,5
8,0
140 280
170 360
170 300
200
380
500
Recirculating
air
7,8
9,3
160 290
180 380
180 320
220
400
540
130
230
120
280
180 320
230
410
540
We reserve the right to construction changes within the context of technical development.
140
260
140
330
185 330
230
420
560
120 230
140 300
140 260
140
290
360
6
NEFF (UK) Ltd Grand Union House, Old Wolverton Road, Old Wolverton Milton Keynes, MK12 5PT Tel: 01908/328300 Fax: 01908/328399
5750 175652
Printed in Germany 1106 Hi.
Loading...