Nec 60004574 User Manual

External Control NEC LCD Monitor
Rev.1.3 (G4)
INDEX
I. Application ............................................................................................................................................. 4
II. Preparation ........................................................................................................................................... 4
2. Connectors and wiring ......................................................................................................................... 4
2.1 RS-232C Remote control .................................................................................................................... 4
2.2 LAN control ......................................................................................................................................... 5
III. Communication specification ............................................................................................................ 6
3. Communication Parameter .................................................................................................................. 6
3.1 RS-232C Remote control .................................................................................................................... 6
3.2 LAN control ......................................................................................................................................... 6
3.3 Communication timing ....................................................................................................................... 6
4. Communication Format ........................................................................................................................ 7
4.1 Header block format (fixed length) ................................................................................................... 8
4.2 Message block format ...................................................................................................................... 10
4.3 Check code ....................................................................................................................................... 12
4.4 Delimiter ........................................................................................................................................... 13
5. Message type ...................................................................................................................................... 14
5.1 Get current Parameter from a monitor. .......................................................................................... 14
5.2 "Get parameter" reply ...................................................................................................................... 15
5.3 Set parameter ................................................................................................................................... 17
5.4 "Set parameter" reply ...................................................................................................................... 18
5.5 Commands ........................................................................................................................................ 19
IV. Control Commands ........................................................................................................................... 22
6. Typical procedure example ............................................................................................................... 22
6.1. How to change the “Backlight” setting. ........................................................................................ 22
6.2. How to read the measurement value of the built-in temperature sensors. ................................. 25
6.3. Operation Code (OP code) Table .................................................................................................... 28
7. Power control procedure ................................................................................................................... 46
7.1 Power status read ............................................................................................................................ 46
7.2 Power control ................................................................................................................................... 48
8. Asset Data read and write ................................................................................................................. 50
8.1 Asset Data Read Request and reply................................................................................................ 50
8.2 Asset Data write ............................................................................................................................... 51
9. Date & Time read and write............................................................................................................... 53
9.1 Date & Time Read ............................................................................................................................ 53
(1/139)
9.2 Date & Time Write ............................................................................................................................ 55
10. Schedule read and write .................................................................................................................. 58
10.1 Schedule Read ................................................................................................................................ 58
10.2 Schedule Write ............................................................................................................................... 62
11. Holiday read and write ..................................................................................................................... 70
11.1 Holiday Read ................................................................................................................................... 70
11.2 Holiday Write .................................................................................................................................. 72
12. Weekend read and write .................................................................................................................. 75
12.1 Weekend Read ................................................................................................................................ 75
12.2 Weekend Write ................................................................................................................................ 77
13. Self diagnosis ................................................................................................................................... 79
13.1 Self-diagnosis status read ............................................................................................................. 79
14. Serial No. & Model Name Read ....................................................................................................... 81
14.1 Serial No. Read ............................................................................................................................... 81
14.2 Model Name Read .......................................................................................................................... 83
15. Security Lock .................................................................................................................................... 85
15.1 Security Lock Control .................................................................................................................... 85
16. Direct TV Chanel Read & Write ....................................................................................................... 87
16.1 Direct TV Chanel Read & Reply ..................................................................................................... 87
16.2 Direct TV Chanel Write & Reply .................................................................................................... 88
17. Daylight Saving read & write ........................................................................................................... 89
17.1 Daylight Saving Read ..................................................................................................................... 89
17.2 Daylight Saving Write ..................................................................................................................... 91
18. Firmware Version ............................................................................................................................. 93
18.1 Firmware Version Read .................................................................................................................. 93
19. Auto ID .............................................................................................................................................. 95
19.1 Auto ID Execute.............................................................................................................................. 95
19.2 Auto ID Complete ........................................................................................................................... 96
19.3 Auto ID Reset .................................................................................................................................. 97
20. Input Name ....................................................................................................................................... 98
20.1 Input Name Read ............................................................................................................................ 98
(2/139)
(3/139)
I. Application
This document defines the communications method for control of the NEC LCD monitor, MultiSync P404 /P484 /P554 /V404 /V484 /V554/ V404-T/ V484-T/ V554-T/ P754Q/ V754Q/ V864Q/ V984Q/ C751Q/ C861Q/ C981Q when using an external controller.
II. Preparation
2. Connectors and wiring
2.1 RS-232C Remote control
Connector: 9-pin D-Sub
Cable: Cross (reversed) cable or null modem cable
(Please refer “Controlling the LCD monitor via RS-232C Remote control” on User’s manual.)
(4/139)
2.2 LAN control
Connector: RJ-45 10/100 BASE-T
Cable: Category 5 or higher LAN cable
(Please refer “Controlling the LCD monitor via LAN control” on User’s manual.)
(5/139)
III. Communication specification
3. Communication Parameter
3.1 RS-232C Remote control
(1) Communication system Asynchronous (2) Interface RS-232C (3) Baud rate 9600bps (4) Data length 8bits (5) Parity None (6) Stop bit 1 bit (7) Communication code ASCII
3.2 LAN control
(1) Communication system TCP/IP (Internet protocol suite) (2) Interface Ethernet (CSMA/CD) (3) Communication layer Transport layer (TCP) * Using the payload of TCP segment. (4) IP address (Default) Automatic setup * If you need to change, Please refer “Network settings” on User’s manual. (5) Port No. 7142 (Fixed)
(Note) The monitor will disconnect the connection if no packet data is received for 15 minutes. And the controller (PC) has to re-connect to control the monitor again, after 15 minutes or
more.
3.3 Communication timing
The controller should wait for a reply packet before the next command is sent. (Note) When the following commands are sent, a controller should wait for specified period after receiving the reply command before sending the next command.
Power On, Power Off: 15 seconds
Input, PIP Input, Auto Setup, Factory Reset: 10 seconds
(6/139)
Set Parameter
Set Parameter
Get Parameter
4. Communication Format
Header Message Check Code Delimiter
The command packet consists of four parts, Header, Message, Check code and Delimiter.
Note: Don't add extra data (Example: padding data) after Delimiter.
Recommended sequence of a typical procedure to control a monitor is as follows,
[A controller and a monitor, two-way communication composition figure]
■ For the general command (see the part "6.3. Operation Code (OP code) Table”)
Monitor Controller
Get Parameter
Get Parameter Reply
Get Parameter Reply
Save Current Setting Command
Save Current Setting Command Reply
The controller sends command to get a value from the monitor that you want to change.
The monitor replies a current value of the requested item.
The controller sends commands to set an adjusted value.
The monitor replies to the controller for confirmation.
The controller sends command to get a value for confirmation.
The monitor replies an adjusted value.
The controller requests to store the adjusted value to the monitor.
The monitor replies to the controller for confirmation.
■ For the special command (see the part 7 to 24. and 5.5.2)
Command
Command Reply
Monitor Controller
The control does not suitable for above fixed protocol; use the proper command for each control. Please refer section
5.5 and section 7 to 26.
The monitor replies a proper message defined for each
(7/139)
Destination
Destination
4.1 Header block format (fixed length)
Header Message Check code Delimiter
SOH Reserved
'0'
1st 2nd 3rd 4th 5th 6th -7th
st
1
byte) SOH: Start of Header
Destination Source Message
Type
Message Length
ASCII SOH (01h)
nd
2
byte) Reserved: Reserved for future extensions.
On this monitor, it must be ASCII '0'(30h).
rd
3
byte) Destination: Destination equipment ID. (Receiver)
Specify a commands receiver’s address.
The controller sets the “MONITOR ID” or “GROUP ID” of the monitor controlled in here.
On the reply, the monitor sets ‘0’ (30h), always.
“MONITOR ID”, “GROUP ID” to “Destination Address” conversion table is as follows,
Monito r ID
Destinatio n Address
Monito r ID
Destinatio n Address
Monito r ID
Destinatio n Address
Monito r ID
Destinatio n Address
1 41h(‘A’) 26 5Ah(‘Z’) 51 73h 76 8Ch 2 42h(‘B’) 27 5Bh 52 74h 77 8Dh 3 43h(‘C’) 28 5Ch 53 75h 78 8Eh 4 44h(‘D’) 29 5Dh 54 76h 79 8Fh 5 45h(‘E’) 30 5Eh 55 77h 80 90h 6 46h(‘F’) 31 5Fh 56 78h 81 91h 7 47h(‘G’) 32 60h 57 79h 82 92h 8 48h(‘H’) 33 61h 58 7Ah 83 93h 9 49h(‘I’) 34 62h 59 7Bh 84 94h 10 4Ah(‘J’) 35 63h 60 7Ch 85 95h 11 4Bh(‘K’) 36 64h 61 7Dh 86 96h 12 4Ch(‘L’) 37 65h 62 7Eh 87 97h 13 4Dh(‘M’) 38 66h 63 7Fh 88 98h 14 4Eh(‘N’) 39 67h 64 80h 89 99h 15 4Fh(‘O’) 40 68h 65 81h 90 9Ah 16 50h(‘P’) 41 69h 66 82h 91 9Bh 17 51h(‘Q’) 42 6Ah 67 83h 92 9Ch 18 52h(‘R’) 43 6Bh 68 84h 93 9Dh 19 53h(‘S’) 44 6Ch 69 85h 94 9Eh 20 54h(‘T’) 45 6Dh 70 86h 95 9Fh 21 55h(‘U’) 46 6Eh 71 87h 96 A0h 22 56h(‘V’) 47 6Fh 72 88h 97 A1h 23 57h(‘W’) 48 70h 73 89h 98 A2h 24 58h(‘X’) 49 71h 74 8Ah 99 A3h 25 59h(‘Y’) 50 72h 75 8Bh 100 A4h ALL 2Ah(‘*’)
Group ID
Destination Address
Group ID
Address
Group ID
Destination Address
Group ID
Address A 31h(‘1’) D 34h(‘4’) G 37h(‘7’) J 3Ah(‘:’) B 32h(‘2’) E 35h(‘5’) H 38h(‘8’) C 33h(‘3’) F 36h(‘6’) I 39h(‘9’)
(8/139)
Ex.) If you want to control a monitor that has the "ID No." as '1', specify a destination
address 'A'(41h). If you want to control all of the monitors which are connected by a daisy
chain, specify a destination address ‘*’(2Ah).
th
4
byte) Source: Source equipment ID. (Sender)
Specify a sender address.
The controller must be ‘0’ (30h).
On the reply, the monitor sets the own MONITOR ID in here.
th
5
byte) Message Type: (Case sensitive.)
Refer to section 4.2 “Message block format” for more details.
ASCII 'A' (41h): Command.
ASCII 'B' (42h): Command reply.
ASCII 'C' (43h): Get current parameter from a monitor.
ASCII 'D' (44h): "Get parameter" reply.
ASCII 'E' (45h): Set parameter.
ASCII 'F' (46h): "Set parameter" reply.
th
6
-7th bytes) Message Length:
Specify the length of the message (that follows the header) from STX to ETX.
This length includes STX and ETX.
The byte data must be encoded to ASCII characters.
Ex.) The byte data 3Ah must be encoded to ASCII characters '3' and 'A' (33h and 41h).
The byte data 0Bh must be encoded to ASCII characters '0' and 'B' (30h and 42h).
(9/139)
Message
Hi Lo Hi Lo
Hi Lo Hi Lo Hi Lo Hi Lo
Hi Lo Hi Lo Hi Lo Hi Lo
4.2 Message block format
“Message block format” is allied to the “Message Type” in the “Header”.
Refer to the section 4.1 “Header block format” for more detail.
1)Get current parameter
The controller sends this message when you want to get the status of the monitor.
For the status that you want to get, specify the “OP code page” and “OP code”,
refer to “Appendix A. Operation code table”.
“Message format” of the “Get current parameter” is as follows,
Refer to section 5.1 “Get current parameter from a monitor.” for more details.
2)Get Parameter reply
The monitor will reply with the status of the requested item specified by the controller
STX OP code
page
Header
OP code
Check code Delimiter
ETX
in the “Get parameter message”.
“Message format” of the “Get parameter reply” is as follows,
STX Result OP code
page
Refer to section 5.2 “Get parameter reply” for more details.
3)Set parameter
The controller sends this message to change a setting of the monitor.
Message format of the “Set parameter” is as follows,
STX
Refer to section 5.3 “Set parameter” for more details.
4)Set Parameter reply
The monitor replies with this message for a confirmation of the “Set parameter message”.
STX Result OP code
Refer to section 5.4 “Set parameter reply” for more details.
OP code
page
Hi Lo Hi Lo MSB
Message format of the “Set parameter reply” is as follows,
page
OP code
OP code
OP code
Type Max value Current Value ETX
MSB
Set Value ETX
LSB
Type Max value Requested setting
MSB
LSB MSB
Value
LSB MSB
LSB
ETX
LSB
5)Command
“Command message” format depends on each command.
Usually, this “command message” is used for some non-slider controls and some special operations,
such as “Save current settings”, “Get timing report”, “power control”, “Schedule”, etc. Refer
(10/139)
to section 5.5 “Commands message” for more details.
6)Command reply
The monitor replies to a query from the controller.
“Command reply message” format depends on each command.
Refer to section 5.5 “Commands message” for more details.
(11/139)
Chec k c o d e
Header
Message
Check
Delimiter
SOH Reserved
Destination
Source
Message
Message length
STX OP code
OP code
Set Value
ETX
4.3 Check code
Head e r Mess a g e
Deli m i t e r
Check code is the Block Check Code (BCC) between the Header and the End of Message except SOH.
27 26 25 24 23 22 21 20 SOH D0 Rese r v e d D1 Dest i n a t i o n D2 Sour c e D3 Type D4 Leng t h ( H ) D5 Leng t h ( L ) D6 STX D7 Data D8 | | | | ETX Dn Chec k c o d e D
P P P P P P P P
n+1
D
= D1 XOR D2 XOR D3 XOR ,,, D
n+1
n
XOR: Exclusive OR
Following is an example of a Check code (BCC) calculation.
code
Address
Address
type
page
(BCC)
01 30 41 30 45 30 41 02 30 30 31 30 30 30 36 34 03 77
D
D1 D2 D3 D4 D5 D6 D7 D
0
D
D
D
D
D
D
D
D
8
9
10
11
12
13
14
15
D
16
Check code (BCC) D
= D1 xor D2 xor D3 xor … xor D14 xor D15 xor D16
17
= 3 0 h x o r 41h x o r 3 0h x o r 4 5 h xor 3 0 h xor 41h
xor 02h xor 30h xor 30h xor 31h xor 30h xor 30h
xor 30h xor 36h xor 34h xor 03h
= 7 7 h
0D
D18
17
(12/139)
Delimiter
4.4 Delimiter
Packet delimiter code; ASCII CR(0Dh).
Header Message Check code
(13/139)
Hi Lo Hi
5. Message type
5.1 Get current Parameter from a monitor.
STX OP code
page
1st 2nd-3rd 4th–5th 6th
OP code ETX
Lo
Send this message when you want to get the status of a monitor.
For the status that you want to get, specify the “OP code page” the “OP code”, refer to
“Appendix A. Operation code table”.
st
1
byte) STX: Start of Message
ASCII STX (02h)
nd-3rd
2
bytes) OP code page: Operation code page.
Specify the “OP code page” for the control which you want to get the status.
Refer to “Appendix A Operation code table” for each item.
OP code page data must be encoded to ASCII characters.
Ex.) The byte data 02h must be encoded to ASCII characters '0' and '2' (30h and 32h).
OP code page 02h -> OP code page (Hi) = ASCII '0' (30h)
OP code page (Lo) = ASCII '2' (32h)
Refer to Operation code table. (Appendix A)
th–5th
4
bytes) OP code: Operation code
Refer to “Appendix A Operation code table” for each item.
OP code data must be encoded to ASCII characters.
Ex.) The byte data 3Ah must be encoded to ASCII characters '3' and 'A' (33h and 41h).
OP code 3Ah -> OP code (Hi) = ASCII '3' (33h)
OP code (Lo) = ASCII 'A' (41h)
Refer to Operation code table.
th
6
byte) ETX: End of Message
ASCII ETX (03h)
(14/139)
Hi Lo Hi Lo Hi Lo Hi Lo
5.2 "Get parameter" reply
STX
Result OP code
OP code
Type Max value Current Value ETX
page
st
MSB
1
2nd-3rd 4th–5th 6th –7th 8th -9th 10th -13th 14th -17th 18
LSB
MSB
LSB
The monitor replies with a current value and the status of the requested item (operation code).
st
1
byte) STX: Start of Message
ASCII STX (02h)
nd-3rd
2
bytes) Result code.
These bytes indicate a result of the requested commands as follows,
00h: No Error.
01h: Unsupported operation with this monitor or unsupported operation under current
condition.
This result code from the monitor is encoded to ASCII characters.
Ex.) The byte data 01h is encoded to ASCII character '0' and '1' (30h and 31h).
th–5th
4
bytes) OP code page: Operation code page.
These bytes indicate a replying item's OP code page.
This returned value from the monitor is encoded to ASCII characters.
th
Ex.) The byte data 02h is encoded to ASCII character '0' and '2' (30h and 32h).
Refer to the operation code table.
th
6
–7thbytes) OP code: Operation code
These bytes indicate a replying item's OP code.
This returned value from the monitor is encoded to ASCII characters.
Refer to the operation code table.
Ex.) The byte data 1Ah is encoded to ASCII character '1' and 'A' (31h and 41h).
th
8
-9thbytes) Type: Operation type code
00h: Set parameter
01h: Momentary
Like the Auto Setup function which automatically changes the parameter.
This returned value from the monitor is encoded to ASCII characters.
Ex.) The byte data 01h is encoded to ASCII character '0' and '1' (30h and 31h).
th
10
-13thbytes) Max. value: Maximum value which monitor can accept. (16bits)
This returned value from the monitor is encoded to ASCII characters.
Ex.) '0','1','2' and '3' means 0123h (291)
th
14
-17thbytes) Current Value: (16bits)
This returned value from the monitor is encoded to ASCII characters.
Ex.) '0','1','2' and '3' means 0123h (291)
(15/139)
18thbyte) ETX: End of Message
ASCII ETX (03h)
(16/139)
Hi Lo Hi Lo
5.3 Set parameter
STX
OP code
OP code
Set Value ETX
page
st
MSB
1
2nd-3rd 4th-5th 6th-9th 10
LSB
Send this message to change monitor’s adjustment and so on.
The controller requests a monitor to change value.
st
1
byte) STX: Start of Message
ASCII STX (02h)
nd-3rd
2
bytes) OP code page: Operation code page
This OP code page data must be encoded to ASCII characters.
Ex.) The byte data 02h must be encoded to ASCII '0' and '2' (30h and 32h).
Refer to the Operation code table.
th-5th
4
bytes) OP code: Operation code
This OP code data must be encoded to ASCII characters.
th
Ex.) OP code 1Ah -> OP code (Hi) = ASCII '1' (31h)
OP code (Lo) = ASCII 'A' (41h)
Refer to the Operation code table.
th-9th
6
bytes) Set value: (16bit)
This data must be encoded to ASCII characters.
Ex.) 0123h -> 1
th
10
byte) ETX: End of Message
st
(MSB) = ASCII '0' (30h)
nd
2
= ASCII '1' (31h)
rd
3
= ASCII '2' (32h)
th
4
(LSB) = ASCII '3' (33h)
ASCII ETX (03h)
(17/139)
5.4 "Set parameter" reply
STX Result OP code
page
Hi Lo Hi Lo Hi Lo Hi Lo MSB
OP code Type Max value Requested setting
Value
LSB MSB
LSB
1st 2nd-3rd 4th-5th 6th-7th 8th-9th 10th-13th 14th -17th 18th
The Monitor echoes back the parameter and status of the requested operation code.
st
1
byte) STX: Start of Message
ASCII STX (02h)
nd-3rd
2
bytes) Result code
ASCII '0''0' (30h, 30h): No Error.
ASCII '0''1' (30h, 31h): Unsupported operation with this monitor or unsupported operation
under current condition.
th-5th
4
bytes) OP code page: Echoes back the Operation code page for confirmation.
Reply data from the monitor is encoded to ASCII characters.
Ex.) OP code page 02h -> OP code page = ASCII '0' and '2' (30h and 32h)
Refer to Operation code table.
th-7th
6
bytes) OP code: Echoes back the Operation code for confirmation.
Reply data from the monitor is encoded to ASCII characters.
ETX
Ex.) OP code 1Ah -> OP code (Hi) = ASCII '1' (31h)
OP code (Lo) = ASCII 'A' (41h)
Refer to Operation code table
th-9th
8
bytes) Type: Operation type code
ASCII '0''0' (30h, 30h): Set parameter
ASCII '0''1' (30h, 31h): Momentary
Like Auto Setup function, that automatically changes the parameter.
th
10
-13thbytes) Max. value: Maximum value that monitor can accept. (16bits)
Reply data from the monitor is encoded to ASCII characters.
Ex.) '0''1''2''3' means 0123h (291)
th
14
-17thbytes) Requested setting Value: Echoes back the parameter for confirmation. (16bits)
Reply data from the monitor is encoded to ASCII characters.
Ex.) '0''1''2''3' means 0123h (291)
th
18
byte) ETX: End of Message
ASCII ETX (03h)
(18/139)
5.5 Commands
"Command message format" depends on each command. Some commands are shown with usage. Refer to
section 7 to 25.
5.5.1 Save Current Settings.
The controller requests for the monitor to store the adjusted value.
ASCII: 01h-30h-41h-30h-41h-30h-34h-02h-30h-43h-03h-CHK-0Dh
The monitor replies the packet for confirmation as follows;
SOH-'0'-'0'-'A'-'B'-'0'-'6'-STX-'0'-'0'-'0'-'C'-ETX-CHK- CR
STX
Send "OC"(30h, 43h) as Save current settings command.
Complete "Save Current setting" command packet as follows;
SOH-'0'-'A'-'0'-'A'-'0'-'4'-STX-'0'-'C'-ETX-CHK- CR
Command code '0' 'C'
ETX
(19/139)
Hi Lo
5.5.2 Get Timing Report and Timing reply.
The controller requests the monitor to report the displayed image timing.
STX
ASCII: 01h-30h-41h-30h-41h-30h-34h-02h-30h-37h-03h-CHK-0Dh
The monitor replies status as the following format;
STX
Command code '0' '7'
Send "07"(30h, 37h) as Get Timing Report command.
Complete "Get Timing Report" command packet as follows;
SOH-'0'-'A'-'0'-'A'-'0'-'4'-STX-'0'-'7'-ETX-CHK- CR
Command SS H Freq. V Freq. ETX
'4' 'E'
SS: Timing status byte
Bit 7 = 1: Sync Frequency is out of range. Bit 6 = 1: Unstable count Bit 5-2 Rese r v e d ( Don' t c a r e ) Bit 1 1 : P o s i t ive H o r i z o ntal s y n c pola r i t y
0:Ne g a t i v e Hor i z o n t a l sync polarity.
Bit 0 1: P o s itiv e V e r t ical s y n c pola r i t y .
0:Ne g a t i v e Ver t i c a l sync polarity.
H Freq: Horizontal Frequency in unit 0.01kHz
V Freq: Vertical Frequency in unit 0.01Hz
ETX
MSB
LSB
MSB
LSB
Ex.) When H Freq is '1''2''A''9' (31h, 32h, 41h, 39h), it means 47.77kHz.
(20/139)
5.5.3 NULL Message
The NULL message returned from the monitor is used in the following cases;
01h-30h-30h-41h-42h-30h-34h-02h-42h-45h-03h-CHK-0Dh
SOH-'0'-'0'-'A'-'B'-'0'-'4'-STX-'B'-'E'-ETX-CHK- CR
STX
To tell the controller that the monitor does not have any answer to give to the host (not
read y o r n ot e x p e c t e d)
A n u l l m e s s age will be returned by the monitor if the “Start Proof of Play” command is
sent and the monitor has already started Proof of Play.
A null message will be returned by the monitor if the “Stop Proof of Play” command is sent
and the monitor has not started Proof of Play.
Complete "NULL Message" command packet as follows;
Command code
'B' 'E'
ETX
(21/139)
IV. Control Commands
6. Typical procedure example
The following is a sample of procedures to control the monitor, these are examples of "Get
parameter", "Set parameter" and "Save current settings".
6.1. How to change the “Backlight” setting.
Step 1. The controller requests the Monitor to reply with the current brightness setting and
capability to support this operation. (Get parameter)
Header Message Check code
SOH-'0'-Monitor ID-
'0'-'C'-'0'-'6'
Header
SOH (01h): Start of Header '0' (30h): Reserved Monitor ID: Specify the Monitor ID from which you want to get a value.
Ex.) If Monitor ID is '1', specify 'A'. '0' (30h): Message sender is the controller. 'C' (43h): Message type is "Get parameter command". '0'-'6' (30h, 36h): Message length is 6 bytes.
Message
STX (02h): Start of Message '0'-'0' (30h, 30h): Operation code page number is 0. '1'-'0' (31h, 30h): Operation code is 10h (in the OP code page 0). ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 2. The monitor replies with current Backlight setting and capability to support this
operation.
Header Message Check
SOH-'0'-'0'-Monitor ID-
'D'-'1'-'2'
Header
SOH (01h): Start of Header '0' (30h): Reserved '0' (30h): Message receiver is the controller.
Monitor ID: Indicate a replying Monitor ID.
Ex.) When this byte is set to 'A', the replying Monitor ID is '1'. 'D' (44h): Message Type is "Get parameter reply". '1'-'2' (31h, 32h): Message length is 18 bytes.
Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Result code. No error. '0'-'0' (30h, 30h): Operation code page number is 0. '1'-'0' (31h, 30h): Operation code is 10h (in the page 0). '0'-'0' (30h, 30h): This operation is "Set parameter" type. '0'-'0'-'6'-'4' (30h, 30h, 36h, 34h): Backlight max value is 100(0064h). '0'-'0'-'3'-'2' (30h, 30h, 33h, 32h): Current Backlight setting is 50(0032h) . ETX (03h): End of Message
Check code
STX-'0'-'0'-'1'-'0'-ETX BCC CR
STX-'0'-'0'-'0'-'0'-'1'-'0'-'0'-'0'
-'0'-'0'-'6'-'4'-'0'-'0'-'3'-'2'-ETX
Delimiter
Delimiter
code
BCC CR
(22/139)
BCC: Block Check Code R e f e r to t h e s e c ti o n 4 . 3 “ Ch e c k c o d e ” f o r a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 3. The controller request the monitor to change the Backlight setting
Header Message Check
SOH-'0'-Monitor ID-
'0'-'E'-'0'-'A'
STX-'0'-'0'-'1'-'0'-
'0'-'0'-'5'-'0'-ETX
Delimiter
code
BCC CR
Header
SOH (01h): Start of Header '0' (30h): Reserved Monitor ID: Specify the Monitor ID of which you want to change a setting.
Ex.) If Monitor ID is '1', specify 'A'. '0' (30h): Message sender is the controller. 'E' (45h): Message Type is "Set parameter command". '0'-'A' (30h, 41h): Message length is 10 bytes.
Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Operation code page number is 0. '1'-'0' (31h, 30h): Operation code is 10h (in the page 0). '0'-'0'-'5'-'0' (30h, 30h, 35h, 30h): Set Backlight setting 80(0050h). ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 4. The monitor replies with a message for confirmation.
Header Message Check
code
SOH-'0'-'0'- Monitor ID –
'F'-'1'-'2'
STX-'0'-'0'-'0'-'0'-'1'-'0'—'0'-'0'-
'0'-'0'-'6'-'4'-'0'-'0'-'5'-'0'-ETX
BCC CR
Header
SOH (01h): Start of Header '0' (30h): Reserved '0' (30h): Message receiver is the controller. Monitor ID: Indicate a replying Monitor ID.
Ex.) When this byte is set to 'A', the replying Monitor ID is '1'.
'F' (46h): Message Type is "Set parameter reply".
'1'-'2' (31h, 32h): Message length is 18 bytes.
Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Result code. No error. '0'-'0' (30h, 30h): Operation code page number is 0. '1'-'0' (31h, 30h): Operation code is 10h (in the page 0). '0'-'0' (30h, 30h): This operation is "Set parameter" type. '0'-'0'-'6'-'4' (30h, 30h, 36h, 34h): Backlight max value is 100(0064h). '0'-'0'-'5'-'0' (30h, 30h, 35h, 30h): Received a Backlight setting was 80(0050h) . ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
Delimiter
(23/139)
CR (0Dh): End of packet
Repeat Step 1 and Step 2, if you need to check the Backlight setting. (Recommended)
Step 5. Request the monitor to store the Backlight setting. (Save Current Settings Command)
Header Message Check
code
SOH-'0'-Monitor ID-
'0'-'A'-'0'-'4'
Header
SOH (01h): Start of Header '0' (30h): Reserved Monitor ID: Specify the Monitor ID which you want to store the setting.
Ex.) If Monitor ID is '1', specify 'A'. '0' (30h): Message sender is the controller. 'A' (41h): Message type is "Command". '0'-'4' (30h, 34h): Message length is 4 bytes.
Message
STX (02h): Start of Message '0'-'C' (30h, 43h): Command code is 0Ch as "Save current settings". ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
STX-'0-'C'-ETX BCC CR
Delimiter
(24/139)
6.2. How to read the measurement value of the built-in temperature sensors.
Target displays have three built-in temperature sensors. The controller can monitor inside temperatures by using those sensors with external control.
The following shows the procedure for reading the temperatures from the sensors.
Step 1. Select a temperature sensor which you want to read.
Header Message Check
code
SOH-'0'-Monitor ID-
'0'-'E'-'0'-'A'
Header
SOH (01h): Start of Header '0' (30h): Reserved Monitor ID: Specify the Monitor ID which you want to get a value.
Ex.) If Monitor ID is '1', specify 'A'. '0' (30h): Message sender is the controller. 'E' (45h): Message Type is "Set parameter command". '0'-'A' (30h, 41h): Message length is 10 bytes.
Message
STX (02h): Start of Message
'0'-'2' (30h, 32h): Operation code page number is 2. '7'-'8' (37h, 38h): Operation code is 78h (on page 2). '0'-'0'-'0'-'1' (30h, 30h, 30h, 31h): Select the temperature sensor #1 (01h).
00h: No meaning 01h: Sensor #1 02h: Sensor #2 03h: Sensor #3
ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 2. The monitor replies for confirmation.
STX-'0'-'2'-'7'-'8'-
'0'-'0'-'0'-'1'-ETX
BCC CR
Delimiter
Header Message Check
code
SOH-'0'-'0'-Monitor ID-
'F'-'1'-'2'
Header
SOH (01h): Start of Header '0' (30h): Reserved '0' (30h): Message receiver is the controller. Monitor ID: Indicates a replying Monitor ID.
Ex.) When this byte is set to 'A', the replying Monitor ID is '1'. 'F' (46h): Message Type is "Set parameter reply". '1'-'2' (31h, 32h): Message length is 18 bytes.
Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Result code. No error. '0'-'2' (30h, 32h): Operation code page number is 2. '7'-'8' (37h, 38h): Operation code is 78h (in the page 2). '0'-'0' (30h, 30h): This operation is "Set parameter" type. '0'-'0'-'0'-'3' (30h, 30h, 30h, 33h): Number of temperature sensors are 3 (0003h). '0'-'0'-'0'-'1' (30h, 30h, 30h, 31h): temperature sensor is #1. ETX (03h): End of Message
STX-'0'-'0'-'0'-'2'-'7'-'8'-'0'-'0'-
'0'-'0'-'0'-'3'-'0'-'0'-'0'-'1'-ETX
(25/139)
BCC CR
Delimiter
Check code
BCC: Block Check Code R e f e r t o t h e s e ct i o n 4 . 3 “C h e c k c o d e” f o r a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 3. The controller requests the monitor to send the temperature from the selected sensor.
Header Message Check
Delimiter
code
SOH-'0'-Monitor ID-
STX-'0'-'2'-'7'-'9'-ETX BCC CR
'0'-'C'-'0'-'6'
Header
SOH (01h): Start of Header '0' (30h): Reserved Monitor ID: Specify the Monitor ID which you want to get a value.
Ex.) If Monitor ID is '1', specify 'A'. '0' (30h): Message sender is the controller. 'C' (43h): Message Type is "Get parameter". '0'-'6' (30h, 36h): Message length is 6 bytes.
Message
STX (02h): Start of Message
'0'-'2' (30h, 32h): Operation code page number is 2. '7'-'9' (37h, 39h): Operation code is 79h (in the page 2). ETX (03h): End of Message
Check code
BCC: Block Check Code Re f e r t o the s e c t i on 4 . 3 “ C h eck c o d e ” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
Step 4. The monitor replies a temperature of selected sensor.
Header Message Check
Delimiter
code
SOH-'0'-'0'-Monitor ID-
'D'-'1'-'2'
STX-'0'-'0'-'0'-'2'-'7'-'9'-'0'-'0'
-'F'-'F'-'F'-'F'-'0'-'0'-'3'-'2'-ETX
BCC CR
Header
SOH (01h): Start of Header '0' (30h): Reserved '0' (30h): Message receiver is the controller. Monitor ID: Indicate a replying Monitor ID.
Ex.) When this byte is set to 'A', the replying Monitor ID is '1'. 'D' (44h): Message Type is "Get parameter reply". '1'-'2' (31h, 32h): Message length is 18 bytes.
Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Result code. No error. '0'-'2' (30h, 32h): Operation code page number is 2. '7'-'9' (37h, 39h): Operation code is 79h (in the page 2). '0'-'0' (30h, 30h): This operation is "Set parameter" type. 'F'-'F'-'F'-'F' (46h, 46h, 46h, 46h): Maximum value. '0'-'0'-'3'-'2' (30h, 30h, 33h, 32h): The temperature is 25 degrees Celsius.
Read o u t v a lue i s 2 ' s complement.
Temperature [Celsius]
Readout value Binary Hexadecimal
(26/139)
ETX (03h): End of Message
Check code
BCC: Block Check Code R e f e r to t h e s e c ti o n 4 . 3 “ Ch e c k c o d e ” f o r a BCC calculation.
Delimiter
CR (0Dh): End of packet
+125.0 0000 0000 1111 1010 00FAh + 25.0 0000 0000 0011 0010 0032h + 0.5 0000 0000 0000 0001 0001h 0 0000 0000 0000 0000 0000h
- 0.5 1111 1111 1111 1111 FFFFh
- 25.0 1111 1111 1100 1110 FFCEh
- 55.0 1111 1111 1001 0010 FF92h
(27/139)
OP code
to
adjust the R
6.3. Operation Code (OP code) Table
1) SPECTRAVIEW ENGINE Setting = OFF
Item
page
INPUT 00h 60h 0: No mean
INPUT
PICTURE MODE 02h 1Ah 0: No mean
BACKLIGHT 00h 10h 0: dark
BRIGHTNESS 00h 92h 0: dark
BRIGTNESS
GAMMA CORRECTION 02h 68h 0: No mean
GAMMA
PICTURE
AUTO HDE SELECT *2 11h B2h 0: No mean
COLOR 02h 1Fh 0: pale
COLOR TEMPERATURE 00h 54h 0:2600K
COLOR TEMPERATURE
00h 14h 9: 10000K
(CUSTOM)
OP code Parameter Remarks
1: VGA(RGB) *1 3: DVI *1 5: VIDEO *1 12(0Ch): YGA(YPbPr) *1 13(0Dh): OPTION 15(0Fh): DisplayPort1 16(10h): DisplayPort2 17(11h): HDMI1 18(12h): HDMI2 130(82h): HDMI3 *2 135(87h): MP 136(88h): COMPUTE MODULE
1: sRGB 3: HIGHBRIGHT 4: STANDARD 5: CINEMA 8: CUSTOM1 9: CUSTOM2
| 100(64h): bright
| 100(64h): bright
1: NATIVE 4: 2.2 5: DICOM SIM. 6: PROGRAMMABLE1 7: S GAMMA 8: 2.4 13(0Dh): PROGRAMMABLE2 14(0Eh): PROGRAMMABLE3 16(10h): HYBRID LOG *2 17(11h): ST2084(PQ) *2
1: ON 2: OFF
| 100(64h): deep
| 74(4Ah):10000K
11(0Bh): CUSTOM
OP code page 11h, OP code 06h operation is same.
sRGB: PC mode only CINEMA: A/V mode only
100K/step
Select "CUSTOM"
COLOR
R GAIN 00h 16h 0: Dark
| 255(FFh): Bright
B GAIN 00h 18h 0: Dark
| 255(FFh): Bright
G GAIN 00h 1Ah 0: Dark
| 255(FFh): Bright
(28/139)
G B gain.
OP code
Depends on a
Depends on a
Item
page
COLOR CONTROL 00h RED:
HUE 00h 90h 0: purplish
CONTRAST 00h 12h 0: low
SHARPNESS 00h 8Ch 0: dull
AUTO SETUP 00h 1Eh 0: No mean
OP code Parameter Remarks
9Bh YELLOW: 9Ch GREEN: 9Dh CYAN: 9Eh BLUE: 9Fh MAGENTA: A0h
0: | 100(64h):(center) | 200(C8h):
| 100(64h): greenish
| 100(64h): high
| 24(18h): sharp
1: Execute
Momentary
AUTO ADJUST 10h B7h 0: No mean
1: OFF 2: ON
H POSITION 00h 20h 0: Left side
| Max.: Right side
V POSITION 00h 30h 0: Bottom side
| Max.: Top side
CLOCK 00h 0Eh 0:
ADJUST *1
PHASE 00h 3Eh 0:
H RESOLUTION 02h 50h 0: Low
V RESOLUTION 02h 51h 0: Low
COLOR SYSTEM *1 02h 21h 0: No mean
| Max. :
| Max. :
| Max. : High
| Max.: High
1: NTSC 2: PAL 3: SECAM 4: AUTO 5: 4.43NTSC 6: PAL-60
display timing
display timing
(29/139)
OP code
comm a n ds can
OP code page
Item
page
INPUT RESOLUTION *1 02h DAh Input Resolution select
UHD U P S C A L ING * 2 1 1 h 09 h 0: N o m e an
ASPE C T 0 2 h 70h 0 : N o me a n
ZOOM 1 1 h 2Ch 0 - 8 9 (59h ) : N o mean
AS P E C T
OP code Parameter Remarks
0:No mean 1:Item 1(always Auto) 2:Item 2 3:Item 3 4:Item 4 5:Item 5
Ex) Item 1= AUTO Item 2= -- / 1024x768 / 1400x1050 / 800x600 / 1280x960 Item 3= -- / 1280x768 / 1680x1050 / 1024x576 / 1600x900 / Item 4= -- / 1360x768 /
-- /
-- /
-­Item 5= -- / 1366x768
-- /
-- /
--
1: O F F 2: L O W 3: M I D D O L E 4: H I G H
1: N O R M A L 2: F U L L 3: W I D E 4: Z O O M 6: D Y N A M I C 7: 1 : 1
90(5 A h ) : 9 0% 91(5 B h ) : 9 1% | 100( 6 4 h ) : 100% | 300( 1 2 C h ) : 300 %
Wide : Dyna m i c A/V mode on l y
The foll o w i n g
also be used.
02h OP code 6Fh Parameter 0: No mean 1: 100% 2: 101% | 201(C9h): 300%
(30/139)
Loading...
+ 111 hidden pages