The GEM-RP8LCD is a user-friendly, menu-driven digital keypad that is
compatible with the NAPCO GEM-Series GEM-P800, P801, and P400
control-panels. Refer to User Guide OI276 for operation instructions.
While the GEM-RP8 may be used to fully program any of the previous
listed panels, the GEM-RP8LCD keypad provides the optimum in ease
of keypad and panel programming. In addition, to ease installation, the
RP8LCD includes an internal Expansion Zone Module (EZM) inside the
keypad itself.
SPECIFICATIONS
Operating Voltage: 12 V DC (supplied by panel)
Current Drain: 100 mA Standby
35 mA (cut Jumpers W1, W2 and W3)
Dimensions: 4 3/8” x 5 7/8” x 1 1/8”
Subtract keypad current from combined auxiliary current of the
Note:
control panel.
MOUNTING THE KEYPAD
A keypad should be located near each exit/entry door. To open the
case, insert a screwdriver into either slot at the bottom and push up with
a slight twisting motion to release the retainer tab. Repeat for the other
slot. Pull out at the bottom and lift off the two hooks at the top.
The GEM-RP8LCD features a handy pull-up reference label. (This label
must be used in UL installations). Before mounting the keypad onto the
wall, push the sliding label plate (with label and felt backing affixed and
handle facing forward) down the guides at the rear of the keypad until it
snaps into place. Once installed, the sliding label plate cannot be
removed without first removing the keypad from the wall.
Note:
The
keypad fire and panic keys should not be considered a substitute for a
listed manual initiating device, such as a pull box.
If installing onto a double-gang box, insert mounting screws through the
two vertical elongated holes on the left side of the case and into the box.
If the box is visible when viewed from the front, adjust the keypad
vertically and tighten the screws. Then, using hardware suitable for the
mounting surface, add one or two screws at the right side of the keypad
case directly into the wall to ensure a secure installation.
Note:
Do not
over tighten the screws! Uneven walls may cause the keypad case to
distort.
WIRING
Connect the keypad wires as shown in the table below. Caution: Do not
run keypad wiring with loop wiring.
Keypad Wire Color Panel Terminals
RED Remote Bus (+) PWR
BLACK Remote Bus (–) GND
GREEN Remote Bus Green/Data
ORANGE
GRAY All Gray wi res are (–) Co mmon
BLUE
BROWN (–) PGM Output
WHITE Not Used
VIOLET Not Used
YELLOW Not Used
EOL Resistor Required
*
(+) Keypad Zone 1 *
(+) Keypad Zone 2 *
WI1115 6/02
CONFIGURING THE KEYPAD
A total of up to four (4) keypads may be connected to the panel. GEMRP8LCD keypad and the GEM-RP8 may be intermixed but require
different configuration procedures, as described in the following
paragraphs. For an overview of the GEM-RP8LCD programming
modes, see the Keypad Programming Modes section at the end of this
manual.
Each GEM-RP8LCD keypad can be configured for the following: (a)
keypad feedback beep; (b) keypad sounder; (c) entry/exit countdown
display; (d) displaying zone faults; (e) keypad PGM output; (f) dialer test;
(g) easy exit option; (h) ready message option; (i) enable keypad panic
buttons; (j) keypad address; (k) EZM Address; (l) enable EZM Zones;
(m) EZM Zone response time; (n) access control message changes; (o)
exit delay time display ; and (p) entry delay time display. Keypads to be
programmed are isolated from the control panel and information entered
is stored within the keypad itself.
After completing RP Configuration Mode, press
Descriptions and press
and U to start the LCD to LCD Transfer
P
Option to transfer zone descriptions to other keypads in your system.
See page 7 for an overview of Keypad Configuration Mode.
To enter RP Configuration Mode:
1. Disconnect green wire from Remote Bus panel terminal--or-short the green wire(s) to remote ground.
2. Press the
”.
SYSTEM
3. Enter the factory code of 11123
button and the display will read “OUT OF
C
.
R
The software version number appears briefly, then the words “RP
CONFIGURATION PROGRAM MODE” appear. The first selection is
“Feedback Beep”. Before proceeding, please make note of the following:
When in RP Configuration Mode:
Press U to change a configuration. Changing a configuration ad-
vances the system to the next selection. Press the
continue scrolling through the selections (scroll down) or press the
button to return to previous selections (scroll up). Press
B
to exit Keypad Configuration Mode. The first selection is
Upon entering the Keypad Configuration Mode (press
to exit), “Feedback Beep Presently ON” displays, indicating that the
tactile beep, which sounds when any button is pressed, is on. To turn
off the tactile feedback beep, press
. The tactile feedback beep will
U
immediately turn off, and the system will advance to the next selection
(Keypad Sounder). If feedback beep is off and you wish to turn it on
again, press
Presently OFF”. Press
(to scroll back). Display will read “Feedback Beep
B
to turn on.
U
C
any time
Keypad Sounder (Default = ON)
To turn off the keypad sounder, press U. All keypad sounds will be off,
except for the Feedback Beep. Do not program in U.L. installations.
E/E Countdown (Display) (Default = ON)
Exit delay allows time for the user to leave the premises after arming;
entry delay provides the user time to enter and disarm. To turn off (or
turn on) the display of the exit/entry delay countdown, press
Requires times to be entered. See Exit/Entry Time Display on
Note:
next page.
Entry and Exit delays, respectively.
Factory program defaults to 30 and 45 seconds for
Note:
Display Zn Fault (Default = ON)
To turn off the scrolling display of zone faults, press U. If faulted
zones exist and this setting is OFF, window will only display “Zone
Faulted” and not scroll zones.
Keypad PGM Opt (Default = OFF)
A common use of this feature is to activate a door strike for the
purposes of remotely unlocking a door. The PGM is a switched
negative output that is activated when this option is selected and by
pressing
. If this option is OFF, the Activate Access function will not
U
display in the Function Menu. Connect the device controlled by the
PGM between +PWR and the PGM terminal (maximum load of 10
mA). The PGM Output will remain ON for approximately 7 seconds.
Dialer Test Opt (Default = OFF)
Testing the dialer is initiated through the Function Menu. Turning ON
the Dialer Test Item enables the Activate Dialer Test entry to be listed
in the Function Menu. If turned OFF, the Activate Dialer Test entry is
removed from the Function Menu. The Dialer Test Option is not supported with the GEM-P800 and therefore must be turned off here if
used with this panel.
Easy Exit Option (Default = OFF)
This option allows a user to exit the premises while the system is armed. If
OFF, the Easy Exit function will not display in the Function Menu. Turn
OFF if not enabled in Panel. This feature should not be used in U.L. installations.
Ready Message Option (Default = OFF)
An alternate message can be used in place of the default “SYSTEM
READY” message when keypad is in a normal state. The alternate
message is “READY TO ARM” but can be changed to any other text
message by using the PC Quickloader software.
Keypad Panics F=4 A=2 P=1 (Default = 7)
1=Panic 2=Aux 3=Panic & Aux 4=Fire
5=Panic & Fire 6=Aux & Fire
7=Panic, Aux & Fire
Each Panic Zone is always a 24-Hour Zone, and each keypad can be
individually programmed for keypad panics. Enter the sum of the displayed numbers to activate the selected Panic Zone(s) as follows:
If “Keypad Panic” (P) is programmed for a keypad, police panic is
activated by pressing
programmed, pressing
and
9
8 G
. If “Keypad Aux.” (A) is
G
will trip an auxiliary emergency
0=None
U
alarm. If “Keypad Fire” (F) is programmed, pressing
7
will activate fire panic. These features must also be enabled in panel pro-
gramming via Dealer Mode. Press
to save your selection. U.L. Installa-
U
tions: If Keypad Fire [20-1] is enabled, the keypad must be mounted within
(3) three feet from the Control Panel with no intervening walls or barriers.
Keypad Address (Default = 0)
Each keypad must be assigned a unique keypad address (that is, no
two keypads may be numbered alike) in order for the PCD Windows
Downloader software to correctly configure the keypads. Keypads
must be numbered consecutively, and missing numbers are not
permitted. To assign the keypad number, enter the assigned keypad
number 1–4, then press
to save.
U
EZM Address (Default = 0)
The GEM-RP8LCD keypad includes an internal EZM (Expansion Zone
Module) that may be enabled to provide two additional hard wired
zones, assigned to zones 7 & 8. The system will support up to 2
EZMs, EZM1 and EZM2. If the EZM is not used, the EZM address
must be left at the default of “0”. To enable the EZM in the keypad,
.
enter an EZM address of “1” or “2”, and press
If 2 Keypad EZM zones are required from one keypad, enable EZM1 (1).
•
If only 1 Keypad EZM zone is required, enable keypad EZM1 (1).
•
If 1 Keypad EZM zone is required from one keypad and 1 zone from
•
another, enable EZM1 (1) in one keypad and EZM2 (2) in the other.
to save.
U
EZM Zones Enable (Default = 3)*
* EZM Address must be 1 or 2 for Zones to be enabled.
After the Keypad EZM has been enabled, the Zone(s) to be used on
the Keypad EZM must also be enabled as follows:
• To enable EZM zone 1, enter 1 on the display and press
To enable EZM zone 2, enter 2 on the display and press
•
• To enable both EZM zones 1 and 2, enter 3 and press
NOTE: If zones are enabled, then 2.2K EOL resistor (provided)
must be used (in parallel with N/O, in series with N/C devices).
Assigning EZM Zones in Dealer Program Mode
In addition to configuring the keypad, the panel must be programmed
for the use of keypad EZM zones. These zones must be mapped to
zones 7 & 8 in the same fashion as RF transmitters - by entering a
special RF ID and point # in blocks 77 & 78, as follows:
Keypad configured as EZM 1:
To enable
1. Enable EZM Address 1 as described above.
2. Enable EZM zone 1 as described above in “EZM Zones Enable”.
3. Go to block 77 and enter RF ID# 111111:5-1 (point 1) to map to
zone 7 (or block 78 to map to zone 8).
4. Wire zone device to the keypad Orange and Gray wires.
To enable
1. Enable EZM Address 1 as described above.
2. Enable EZM zone 2 as described above in “EZM Zones Enable”.
3. Go to block 77 and enter RF ID# 111111:5-2 (point 2) to map to
zone 7 (or block 78 to map to zone 8).
4. Wire zone device to the keypad Blue and Gray wires.
Keypad configured as EZM 2:
To enable
1. Enable EZM Address 2 as described above.
2. Enable EZM zone 1 as described above in “EZM Zones Enable”.
3. Go to block 77 and enter RF ID# 222222:b-1 (point 1) to map to
zone 7 (or block 78 to map to zone 8).
4. Wire zone device to the keypad Orange and Gray wires.
To enable
1. Enable EZM Address 2 as described above.
2. Enable EZM zone 2 as described above in “EZM Zones Enable”.
3. Go to block 77 and enter RF ID# 222222:b-2 (point 2) to map to
zone 7 (or block 78 to map to zone 8).
Zone 1
Zone 2
Zone 1
Zone 2
on Keypad
on Keypad
on Keypad
on Keypad
EZM 1
EZM 1
EZM 2
EZM 2
:
:
:
:
U
and
U
U
.
G
.
.
Page 2
Page 3
4. Wire zone device to the keypad Blue and Gray wires.
EZM Zone 50ms Response (Default = 0)
The default loop response of each keypad expansion zone is 750mS,
however the response time of any zone can be reduced to 50mS as
follows:
• To reduce zone 1 to 50mS, enter 1 on the display and press
To reduce zone 2 to 50mS, enter 2 on the display and press
•
To reduce both zone 1 and 2 to 50mS, enter 3 and press U.
•
U
U
.
.
Access Control Message (Default = 0)
The default Access-Control message is “**ENTER NOW**”. This
display may be changed to any of the following messages:
ENTRY
0
1 “Door Control”
2 “Gate Control”
3
MESSAGE
“** ENTER NOW **” (Default)
“Light Control”
Enter the number of the message you wish displayed and press U.
Exit Delay Time Display (Default = 045)
The delay time which permits exit through an Exit/Entry Zone after the
system is armed, allows a user to leave the premises without
off an immediate alarm. Exit Delay may be programmed for up to 255
seconds (4¼ minutes). Enter the number of seconds and press
Changing this configuration updates the keypad only, not the
Note:
panel. The panel delay time is updated via Dealer Mode only; to keep
the panel and keypad delay times synchronized, be certain to program
the keypad for the same time as programmed for the panel.
setting
U
.
Entry Delay Time Display (Default = 030)
Entry delay time permits entry through Exit/Entry Zone(s) after the
system is armed without setting off an immediate alarm. Entry Delay
allows the user time to enter and disarm the system. Upon entering,
the keypad sounder will sound an entry sound to remind the user to
disarm the system. Entry DelayTime may be programmed for up to
255 seconds (4¼ minutes). Enter the number of seconds and press
U
.
Changing this configuration updates the keypad only, not
Note:
the panel. The panel delay time is updated via Dealer Mode only; be
certain to program the keypad for the same time as programmed for
the panel.
Exiting Keypad Configuration Mode
Press
to loop back through selections or press
R
C
to enter
the Zone Descriptions Mode, in which you can change the zone descriptions that appear on the keypad display. If you wish to exit the
Keypad Configuration Mode, press
C
(display will read “OUT OF
SYSTEM”). Replace the green wire to the Remote Bus Panel Terminal.
Display will display panel status.
ZONE DESCRIPTIONS MODE
Zones are independent circuits that protect specific areas of the
premises. The displayed zone descriptions may be changed to suit the
particular design of the premises. To change Zone Descriptions:
1. Disconnect green wire from Remote Bus panel terminal.
2. Press
3. Enter factory code: 11123
The software version number appears briefly, then “RP CONFIGURA-
TION MODE” appears. After a few seconds, the words “Feedback
Beep Presently ON” appear.
4. Press
Scroll descriptions forward or backward using
•
To return to normal keypad operation, press
•
wire to the Remote Bus panel terminal.
After entering Zone Descriptions Mode, the keypad will automatically return
•
to “OUT OF SYSTEM” if no activity is detected for longer than 4 minutes.
Press U to save when the zone description is complete.
•
R
1
3
4
and
and
and
and
to scroll to the desired zone.
B
2
to position the cursor within the display.
6
to scroll through numbers, letters, etc.
to erase text while moving the cursor back-
5
7
8
to move the word to the right.
to move the
Quick Word List
The keypad contains pre-programmed zone descriptions, avoiding the
need to scroll through individual numbers, letters, and symbols. Press
G
followed by the two-digit number of the entry listed in the Quick
Word List table (above). For example, to enter the description “DINING
ROOM”, press
after Quick Words are entered, and entering
existing word.
LCD TO LCD TRANSFER OPTION
Zone descriptions can be transferred from the programmed keypad
(master) to the unprogrammed others (slaves) in the system.
1. Program the primary keypad (master) with the appropriate zone
descriptions, etc, as described in Zone Descriptions Mode above.
2. As a safety precaution, remove AC and DC power to the panel.
3. Wire all keypads to the panel and reapply power.
The LCD TO LCD TRANSFER OPTION is accessed through Keypad
Configuration Mode, as follows:
4. Disconnect green wire from Remote Bus panel terminal.
5. Press
C
6. Enter the factory code of 11123
The software version number appears briefly, then the words “RP CONFIGURATION MODE” appear. After a few seconds, the words
“
Feedback Beep Presently ON
7. Press
C
display. The keypad is now ready to replicate keypad data to the
other keypads in the system.
8. In order for the transfer to take place, all keypads must be physically
linked to each other and isolated from the panel. Therefore, connect all
green wires from all keypads. Do not connect green wires to panel.
9. To initiate the transfer, press
transmitting data to all slaves. The words SENDING are displayed
as the keypad cycles through the database (which is displayed on
the LCD during this process). At short intervals, the words
“SENDING STOPPED…PLEASE WAIT” will display. Similarly, the slave
keypads receiving data will display” RECEIVING”.
10. When complete, the words “OUT OF SYSTEM” will display. Reconnect all wires as described previously for normal operation.
G
1 9
G
6 1.
and the display will read “
” appear.
and
and “LCD TO LCD TRANSFER OPTION” will
P
A space is automatically set
Note:
G 0 0
OUT OF SYSTEM
.
R
. The master keypad will start
U
splits an
”.
Page 3
Page 4
BASIC OPERATION--FUNCTION MENU
This section provides an overview of system operation. For additional
information, please refer to the User's Guide furnished with the keypad
(OI276).
FUNCTION MENU
The
tions.
• To enter and scroll through the Function Menu, press
• To select and execute a function, press
• Functions may be manually scrolled forward or backward using
• To return to normal keypad operation, press
DISPLAY ZN FAULTED
Will display only if zone faults are present. The system will display a
listing of all faulted zones. After all faulted zones are displayed, the
system exits the Function Menu and returns to its normal display.
DISPLAY ZN BYPASSED
Will display only if bypassed zones exist. If an open zone cannot immediately be fixed, it can be left unprotected, or bypassed, while the rest of
the system is armed. The system will display a listing of all bypassed
zones. After all bypassed zones are displayed, the system exits the
Function Menu and returns to its normal display.
DISPLAY SYSTEM TRBL
Will display only if system troubles are present. The panel is constantly
monitoring its own components, as well as all critical services, such as
AC power, to ensure that it is always ready to provide the protection for
which it was designed. If one of these components should fail, the keypad will caution you by displaying “SYS TBL” and beeping the keypad
buzzer. Press
system troubles are displayed, the system exits the Function Menu and
returns to its normal display.
DISPLAY ZN DIRECTORY
Zones are independent circuits that protect specific areas of the
premises. The system directory will display a listing of all zones. After
all zones are displayed, the system exits the Function Menu and returns
to its normal display.
ACTIVATE BELL TEST
Enter this command to turn on the Bell, keypad sounder and keypad
LEDs for 2 seconds. The battery is tested during a Bell Test, and
automatically every 24 hours* to ensure proper battery operation under
load. The Alarm output requires a battery in order to supply the
specified output. If the battery cannot sustain the load, a low battery
indication will be displayed. A battery test is also performed on powerup after a 3 minute delay. *
when Household Fire [96-3] has been selected. A keypad shortcut of
R 1
ACTIVATE DIALER TEST
If activated in the Keypad Configuration Mode, activating the dialer test
sends a communicator dialer test to the central station. A
communication failure will be indicated at the keypad by a system
trouble “FAIL TO COMM” display. Repeat the test to attempt to correct
a communication failure, as any successful communication will clear
this display. Press
supported with the GEM-P800 and therefore must be disabled in Keypad Configuration Mode (page 2, Dialer Test Opt) if used with this
panel.
DEACTIVATE CHIME
Press
violated. The duration of the tone is panel programmable (except for
button provides access to a wide assortment of utility func-
R
.
R
.
U
R
and
B
, respectively.
. The keypad will
C
automatically return to its normal operating mode if no activity is
detected for longer than one minute.
to display a listing of all system troubles. After all
U
A battery test occurs every 4 hours
Note:
can be used to activate the Bell Test.
to initiate the test.
U
P
to sound a tone at the keypad when a Chime Zone is
This feature is not
Note:
the P800). To deactivate the Chime Mode, re-enter the Function Menu
and when “DEACTIVATE CHIME“ is displayed, press
Chime Mode is disabled while armed.
U
.
Note:
DEACTIVATE KEYPAD SOUNDER
The keypad sounder is a local warning device at each keypad. This
command turns the keypad sounder ON or OFF. When the keypad is
deactivated, all keypad sounds will be silenced except for keypad
feedback beeps. The keypad sounder may activate under the following
conditions: (a) entry delay has started; (b) an attempt was made to arm
with a zone in trouble; (c) 10 seconds exit time remaining (only if Exit/Entry with Urgency is enabled at the panel [21-2]); (d) invalid code
entered; or (e) system troubles and alarms.
ACTIVATE EASY EXIT
EASY EXIT provides one button arming for non-security critical
premises. Must be programmed in panel in order to function. Select
Easy Arming for each Keypad. Disarming still requires a valid user
code. To arm press and hold
R 0
can be used to activate this feature (program Easy Exit/
. In addition, a keypad shortcut of
Q
Easy Arm function [22-2] at panel). Do not program in UL Installations.
This feature will not appear unless Easy Exit Option is enabled in Keypad Configuration Mode.
ACTIVATE PROGRAM
Activates the USER PROGRAM MODE. Your dealer has programmed
into your system a special User Program Code. This code can be used
to not only Arm and Disarm the system, but also to enter PROGRAM
MODE, where you can program other User Codes. See USER PROGRAM MODE, below, for a full explanation of the features available
within this mode.
This feature is disabled while armed or while
Note:
reporting (unless reporting occurs within first 3 minutes of panel powerup from a cold start).
ACTIVATE ACCESS
Will display only if Keypad PGM Opt is enabled in the Keypad Configuration Mode. Pressing [ENTER] will cause the keypad (–) PGM Output
(brown wire) to enable an active low voltage output. In addition, if Ac-cess Output [23-2]* is enabled in the panel, the panel PGM will enable
an active low output. When activated, the Access Control Message will
appear on the keypad and the output will remain active low voltage for
approximately 7 seconds.
*Access Output is not available in all GEM-Series Panels.
Note:
These
systems have not been investigated by UL for compliance with UL294
(Access Control Systems).
ACTIVATE FAULT FIND
This troubleshooting aid will help the installer locate swingers. When
accessed, two things occur:
• The loop response of each zone is set for the fastest response time.
• Causing or repairing a fault activates the sounder for about 1
second.
Tapping and poking at suspect points, the installer can easily locate
swingers by listening for the beep. This eliminates the need of returning
to the keypad to visually check after each attempt. Press
C
restore normal operation. Arming the system automatically cancels the
Fault Find Mode.
Note:
will not beep if the signal strength is less than 3.
When testing wireless systems, the keypad
This feature is
Note:
disabled while armed or within first 3 minutes of panel power-up from a
cold start.
ACTIVATE DOWNLOAD
Used on-site for remote downloading of a control-panel program from
the PCD3000. Press
feature is disabled while armed or while reporting (unless reporting occurs within first 3 minutes of panel power-up from a cold start).
to initiate the data transfer.
U
Note:
The
to
This
Page 4
Page 5
PROGRAM MODE
PROGRAM MODE
!
User Program Mode
!
USER PROGRAM MODE is accessed through the Function Menu.
Zone Descriptions Mode
1. To enter the Function Menu, press
2. Skip through the functions by pressing
comprises two options:
R
.
until ACTIVATE PRO-
R
GRAM is displayed.
3. Press
U
.
4. When “USER PROG. MODE USERS=1” displays, the system is ready
for USER CODE programming.
To return to normal keypad operation, press
•
C
. The keypad
will automatically return to its normal operating mode if no activity
is detected for longer than one minute.
•
A keypad shortcut of
Note:
R 8
can be used to pro-
ceed directly to USER PROGRAM MODE without the need to
scroll through the Function Menu.
USER PROGRAM MODE
Up to 8 personal User Codes may be programmed at the keypad.
Default User Code.
The first code programmed should replace the default (User 01) code.
Each user should be assigned his own dissimilar code and should be
cautioned against divulging his code to anyone else. Thus should it
become necessary to remove a user from the system, that one code
may be cancelled without affecting other codes, and that user would
then be prevented from entry.
Programming / Reprogramming a User Code
Enter the digit of the user number to be programmed.
1.
Enter the new User Code (up to 4 digits). The new User Code is
2.
automatically saved.
Repeat steps for each User Code to be programmed. While in User
Program Mode, the Armed, Status and SYS TBL display will continue
to flash. Follow the example below to program
1923.
User 2’s
User Program Mode Example:
Press
1.
Enter
2.
times confirming a valid entry. They keypad will automatically
save the new User Code for the user number, and reset to allow
a new user number to be programmed (or reprogrammed).
A two or three digit User Code can be used by entering zeros
Note:
in the last digits. For example, “37” can be used by entering
“3700”. For another example, “373” can be used by entering
“3730”. This feature applies only to the GEM-RP8LCD, not the
GEM-RP8 keypad.
(Keypad beeps twice).
2
1 9 2 3
. The keypad will beep four
Changing or Canceling a Code
To change any User Code, merely program over the existing code.
To cancel a Code, press the number of the user to be deleted and
Q
press
deleted.
Exiting User Program Mode
To exit User Program Mode press
Notes:
While in User Program Mode, the ARMED and STATUS lights will
•
continue to flash and burglar and fire alarm functions are disabled.
In selecting your codes, do not program repetitive numbers (1111),
•
consecutive numbers (1234), your birth date, address, or other
. The User Code associated with the user will now be
.
C
code to
obvious combinations. If the keypad detects no Program Mode
activity for more than 4 minutes, a tone will sound. Press
C
to silence.
You can access
•
gram Mode by pressing
ZONE DESCRIPTIONS MODE
.
R
from User Pro-
Ambush Code
The Ambush Code is a special four-digit code entered by the user to
disarm, typically to cause a silent report to be sent to the central station.
Thus, should the user be forced to disarm by an assailant, he can
silently signal an emergency while appearing to be merely disarming the
panel.
In dealer mode, program Ambush [20-4]. If enabled, the 8th User Code
will send an Ambush report when entered to disarm the system.
Additional Programming required:
• Program User 8 Arm/Disarm Code.
• Select reporting to Telco 1 [36-2] or Telco 3 [56-2].
Page 5
Page 6
KEYPAD MESSAGES
The GEM-RP8-LCD Keypad can display the following messages.
ALARM - Alarm condition, followed by one or more zone descriptions.
ALARM MEMORY - Appears after an alarm condition and a valid code is en-
tered or when alarm condition times out. Warns of a past alarm
condition.
BELL TEST - Appears after entering this Function Menu item that initiates bell
test. Enter this command to turn on the Bell, keypad sounder and
keypad LEDs for 2 seconds.
BYPASSED ZONES - Displays one or more zones bypassed.
CAN'T ARM SYSTEM - Arming attempt made, but system condition prevents
arming.
CAN'T ARM SYSTEM...PRESS RESET - Displays when arming is attempted
with the Fire icon on or system troubles displaying. Solution is to
press the RESET button and then arm the system.
CAN'T ARM SYSTEM...SILENCING - Displays when the bell is on and a valid
code is entered.
CAN'T ARM SYSTEM...ZONE FAULTED - Displays when arming is at-
tempted with a Zone in trouble. Secure zone (or bypass) before
arming.
DEALER PROGRAM MODE - Appears after entering a valid Dealer Code and
entering Dealer Program Mode.
DIRECTORY - Displays a list of all zone descriptions.
DISARM NOW XXX SECONDS - Entry delay in progress. XXX = Entry time
remaining in 2-second decrements.
ENTER CODE FOR PROGRAM MODE - Appears after Function Menu item
is selected to Activate Program Mode. Enter your code then press
ENTER to enter Program Mode.
ENTER CODE FOR USER x - Enter the number of the user to be added or
changed, enter the 4 digit code.
ENTER DEALER CODE TO EXIT - In Dealer Program Mode, appears after
pressing [Function] [8]. You must enter the Dealer code to leave
Dealer Program Mode.
ENTER LOCATION < > - In Dealer Program Mode, enter a 2-digit location
number (see programming sheet).
FAULTED ZONES - One or more zones not secured. Status of zone descrip-
tion(s) displayed.
FIRE ALARM - Alarm condition on a Fire Zone. Enter your code then press
ENTER to silence the sounder.
FORCED RESET - Appears when pressing [1] [2] and [3] simultaneously.
INVALID ENTRY TRY AGAIN - Wrong code entered.
LCD TO LCD TRANSFER OPTION - Zone descriptions and other keypad
configuration information can be transferred from the programmed
keypad (Sending) to the unprogrammed others (Receiving) in the
system.
NONE - May appear if message "ZONE FAULTED" displays--but the zone
clears after entering the Function Menu.
OUT OF SYSTEM - Appears about 30 seconds after disconnecting (or short-
ing to ground) the green data wire. Also appears after disconnecting
the data wire and pressing RESET. This message must display in
order to access Keypad Configuration Mode.
PLEASE EXIT XXX SECONDS - Displays exit delay time in 2-second decre-
ments.
READY TO ARM - All zones operating; system can be armed. ("SYSTEM
READY" is an alternate equivalent message).
RECEIVING - Appears while receiving Keypad Configuration or Zone Descrip-
tions from a Quickloader or another RP8LCD keypad that is sending
data.
RP CONFIGURATION MODE - You are entering the RP8LCD Configuration
Refer to OI276.
Note:
mode. Changes in this mode are stored in the keypad.
RP VERSION - Software version appears when entering Keypad Configura-
SENDING - Appears while sending Zone Descriptions to another RP8LCD
SENDING STOPPED - PLEASE WAIT - When large amounts of data are
SYSTEM ARMED - Panel armed.
SYSTEM READY - All zones operating; system can be armed. ("READY TO
-->TO START PRESS THE ENTER KEY - Initiate the LCD to LCD Transfer
USER PROG. MODE USERS = 12345678 - Enter the number of the user to
ZN DESCRIPTIONS MODE - You are entering the Zone Descriptions Mode
ZONE FAULTED - One or more zones not secured.
tion Mode.
transferred, pauses may appear for a few seconds, accompanied by
this message.
ARM" is an alternate equivalent message).
Option by pressing Enter on the keypad.
be added or changed and enter the 4-digit code.
which allows you to change and update the zone descriptions which
appear on the keypad display to suit the particular design of the
protected premises
System Troubles
AC Failure - Power failure. Check power transformer. Check for blown fuse
Bell Wire Cut - Bell wire severed (open on bell circuit).
Fail to Comm - Unsuccessful communication to central station. Note: Will
Telco Line Cut - Telephone line cut or system down.
Low Battery - Battery below 11 volts. If not recharged within 48 hours after
Rcvr or Ezm Tbl - EZM module cover removed, or keypad EZM not respond-
RF Receiver Jam - Receiver not responding/jammed.
RF LB / ZnXX - Burglar Transmitter Low Battery. XX = The zone number to
RF SUP ZnXX - Supervisory Burglar Transmitter Indication--panel has not
RF Smk LB #XX - Smoke Detector Low Battery. XX = The smoke detector
RF Smk SUP #XX - Supervisory Smoke Detector Indication. Panel has not
Fire Trouble - Appears when an open in the hard-wired smoke detector exists.
Zn Trouble #XX - Appears when a zone trouble exists. The panel has one or
or circuit breaker; general power outage.
also display if panel is improperly programmed to report: i.e., Report Alarm, Report Codes, Subscriber ID Numbers, etc. Must be
programmed.
AC is restored, replace battery.
ing, or receiver not responding.
which the transmitter is mapped. Replace Battery.
received a signal from the transmitter within 12 (default) hours or
programmed time. XX = The Zone number to which the transmitter
is mapped. Replace Battery.
number as programmed in the panel. Replace Battery.
received a response from the transmitter within 4 (default) hours or
programmed time. XX = The smoke detector number as programmed in the panel. Replace Battery.
more of the following 3 troubles: Zone Short (P800 panels only),
Transmitter Tamper or Dual Tech Self Test Fail. XX = The Zone
number.
Page 6
Page 7
(“LCD TO LCD
Press P
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Presently ON/OFF
Feedback Beep
Keypad Sounder
E/E Countdown
Display Zn Fault
Keypad PGM Opt
Dialer Test Opt
Easy Exit Option
Ready Msg Option
Keypad Panics
F=4 A=2 P=1 7
Keypad Address
1
EZM Address
Disable=0 2
EZM Zones Enable
Zn1=1 Zn2=2 3
EZM Zones 50 ms
Zn1=1 Zn2=2 3
Access Control
Message 0
Exit Delay Time
Display 030
Entry Delay Time
Display 020
TRANSFER OPTION”)
green wires to panel).
Press U to begin transfer.
all keypads (Do not connect
Connect all green wires from
to Exit
R
: “OUT OF SYSTEM”)
to enter changes
U
Press
•
R to scroll to next selection •B to scroll to previous selection
•
Enter Factory Code: 11123
and Press
Software RP version number appears
RP CONFIGURATION MODE
GEM-RP8LCD Keypad
C
Remove Green wire from
“Remote Bus” Panel terminal,
(Press
Press C
(“ZN DESCRIPTIONS MODE”)
to repeat list
Press R
C
Press
Reconnect Green wire(s) to
(“SYSTEM READY”)
Remote Bus Panel Terminal
Operation
Exit to Normal
KEYPAD CONFIGURATION MODE (RP CONFIGURATION MODE)
.
to select.
U
PROGRAM MODE
Press
Keypad Commands
Enter code
PROGRAM MODE”)
(“ENTER CODE FOR
and press
U
Dealer
see Panel
(Dealers only---
documentation)
Program Mode
Operation
Exit to Normal
to Exit
”)
MODE
MODE
C
If Zone Faults?
If Zone Bypasses?
Disarmed)
Press R
FUNCTION MENU (Keypad
Repeat
FUNCTION MENU / PROGRAM MODE
KEYPAD PROGRAMMING MODES
DISPLAY ZN FAULTED
KEYPAD MESSAGE CONDITION
DISPLAY ZN BYPASSED
(“ZN DESCRIPTIONS
Always appear s
If System Trouble?
DISPLAY SYSTEM TRBL
Always appear s
ACTIVATE BELL TEST
DISPLAY ZN DIRECTORY
Always appear s
If enabled in Keypad
DEACTIVATE CHIME
ACTIVATE DIALER TEST
If enabled in Keypad
ACTIVATE EASY EXIT
DEACTIVATE KEYPAD SOUNDER
Always appear s
Configuration Mode
Configuration Mode
Always appear s
Always appear s
Configuration Mode
If enabled in Keypad
ACTIVATE ACCESS
ACTIVATE PROGRAM
Always appear s
ACTIVATE DOWNLOAD
ACTIVATE FAULT FIND
Press C to Exit at any time
Repeat
ZONE DESCRIPTIONS
(“ENTER CODE FOR
USER PROGRAM MODE
Press
USERS= 1 ”)
Program Mode
Zone Descriptions
Press R to advance to
Page 7
Page 8
NAPCO LIMITED WARRANTY
NAPCO SECURITY SYSTEMS, INC. (NAPCO)
warrants its products to be free from manufacturing
defects in materials and workmanship for
months
following the date of manufacture. NAPCO will,
thirty-six
within said period, at its option, repair or replace any
product failing to operate correctly without charge to
the original purchaser or user.
This warranty shall not apply to any equipment, or any
part thereof, which has been repaired by others,
improperly installed, improperly used, abused, altered,
damaged, subjected to acts of God, or on which any
serial numbers have been altered, defaced or
removed. Seller will not be responsible for any
dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR
IMPLIED, WHICH EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. THERE IS
NO EXPRESS OR IMPLIED WARRANTY OF
MERCHANTABILITY OR A WARRANTY OF FITNESS
FOR A PARTICULAR PURPOSE. ADDITIONALLY,
THIS WARRANTY IS IN LIEU OF ALL OTHER
OBLIGATIONS OR LIABILITIES ON THE PART OF
NAPCO.
Any action for breach of warranty, including but not
limited to any implied warranty of merchantability, must
be brought within the six months following the end of
the warranty period.
IN NO CASE SHALL NAPCO BE LIABLE TO
ANYONE FOR ANY CONSEQUENTIAL OR
INCIDENTAL DAMAGES FOR BREACH OF THIS OR
ANY OTHER WARRANTY, EXPRESS OR IMPLIED,
EVEN IF THE LOSS OR DAMAGE IS CAUSED BY
THE SELLER'S OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional who
installed and maintains your security system. In order
to exercise the warranty, the product must be returned
by the security professional, shipping costs prepaid
and insured to NAPCO. After repair or replacement,
NAPCO assumes the cost of returning products under
warranty. NAPCO shall have no obligation under this
warranty, or otherwise, if the product has been
repaired by others, improperly installed, improperly
used, abused, altered, damaged, subjected to
accident, nuisance, flood, fire or acts of God, or on
which any serial numbers have been altered, defaced
or removed. NAPCO will not be responsible for any
dismantling, reassembly or reinstallation charges.
This warranty contains the entire warranty. It is the sole
warranty and any prior agreements or representations,
whether oral or written, are either merged herein or are
expressly cancelled. NAPCO neither assumes, nor
authorizes any other person purporting to act on its
behalf to modify, to change, or to assume for it, any
other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in
excess of NAPCO's original selling price of the
product, for any loss or damage, whether direct,
indirect, incidental, consequential, or otherwise arising
out of any failure of the product. Seller's warranty, as
hereinabove set forth, shall not be enlarged,
diminished or affected by and no obligation or liability
shall arise or grow out of Seller's rendering of technical
advice or service in connection with Buyer's order of
the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE
SYSTEM BE COMPLETELY TESTED WEEKLY.
Warning:
Despite frequent testing, and due to, but not
limited to, any or all of the following; criminal
tampering, electrical or communications disruption, it is
possible for the system to fail to perform as expected.
NAPCO does not represent that the product/system
may not be compromised or circumvented; or that the
product or system will prevent any personal injury or
property loss by burglary, robbery, fire or otherwise;
nor that the product or system will in all cases provide
adequate warning or protection. A properly installed
and maintained alarm may only reduce risk of burglary,
robbery, fire or otherwise but it is not insurance or a
guarantee that these events will not occur.
CONSEQUENTLY, SELLER SHALL HAVE NO
LIABILITY FOR ANY PERSONAL INJURY,
PROPERTY DAMAGE, OR OTHER LOSS BASED ON
A CLAIM THE PRODUCT FAILED TO GIVE
WARNING. Therefore, the installer should in turn
advise the consumer to take any and all precautions
for his or her safety including, but not limited to, fleeing
the premises and calling police or fire department, in
order to mitigate the possibilities of harm and/or
damage.
NAPCO is not an insurer of either the property or
safety of the user's family or employees, and limits its
liability for any loss or damage including incidental or
consequential damages to NAPCO's original selling
price of the product regardless of the cause of such
loss or damage.
Some states do not allow limitations on how long an
implied warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, or
differentiate in their treatment of limitations of liability
for ordinary or gross negligence, so the above
limitations or exclusions may not apply to you. This
Warranty gives you specific legal rights and you may
also have other rights which vary from state to state.
Page 8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.