Robust, flexible
24V commercial fire
systems supporting
up to 255 zones/
points using all-new
fire devices in hardwire,
wireless, conventional
& addressable
technologies
:
Gem-C Firewolf Series 24V Commercial
Intelligent Addressable Fire Panel,
NFPA72-compliant, 96 outputs, 4 onboard
NACs (6.5A total), expandable to 24, built in
Sync/Strobe/Horn Module (System Sensor &
Wheelock) and dual line DACT plus optional
TCP/IP reporting. Nearly a mile., max. wire
run – any wire type –ideal for retrofits. Also
supports legacy and conventional devices,
too. Powerful battery capacity up to 32Ah
total.
Features remote smoke obscuration
reporting
4More zones/points – up to 255
4More power – 7 amps
4 More NAC’as – 4 on board
4Built in strobe/horn sync
4 More standby power
432 Amp hour battery capacity
4Regulated 24V output
24V Addressable &
Conventional Fire
255, 128 or 32 point kits
NAC Extender provides nearly 7A and
4 onboard NACs with up to 2A ea; up to
16Ah total battery capacity. Easily distributes
synched bell and strobe outputs with built
in module. Monitors AC, battery trouble,
tamper and ground fault on Napco bus or
provides universal FACP support.
Regulated Auxiliary Power Supplies
Commercial fire, 12V regulated 2A models;
or 1.75A version with plug-in transformer
Firewolf Advanced Analog Addressable
Commercial Fire Devices support auto-drift
compensation and maintenance alert function
Gemini-C New UL Commercial Wireless
Line with supervised tamper & automatic,
continuously supervised signal strength
(requires no manual test activation).
Firewolf Menu-Driven Custom Alpha
Keypads Same familiar Napco ez-
programming and usage. (Keyswitch support,
too.)
Compliances - NFPA 72, UL Commercial
Fire, UL864 9th Ed., UL985. (CSFM, FM, MEA
listings pending.)
Page 2
Napco Commercial™ Firewolf-Series Components
for 32 to 255 Point 24V Commercial Fire Systems:
SYSTEM
• Main Control board supports up to two (2) Addressable Fire SLCs
(addressable Signaling Line Circuit controllers). (Note: Only 1 SLC is
accomodated within the Medium panel enclosure.*)
• Fire 4-wire bus for keypads and non-SLC (conventional) devices,
including 12V devices
• Power Supply includes either 4A or 7A @ 24V
• RS-232 Printer Module for optional onsite parallel printer
• Supports up to 7 fire keypads, GEMC-FK1, mounted anywhere on the
bus. (As few as one keypad required on system for equipment savings.)
• Easy-to-use Gemini-style menu-driven operation with backlit custom
alphanumeric display and functionality for
Reset, Acknowledge, Silence (with disable).
• Full Keyswitch Support
• Synch module built in on each NAC (System Sensor & Wheelock
protocols)
• Dual Phone Line built in
• 2 On board serial ports - one for internet reporting; one for
high-speed local downloading
• TCP/IP Internet reporting module
• Regulated Auxiliary Power Supplies - Commercial fire, 12V regulated
2A or 1.75A version with plug in transfomer
• Addressable SLC Loop Isolator (optional use - for some fire
applications requiring increased circuit integrity, e.g., meets Class A,
Style 7 loop requirements.
• Choice of two enclosures - Between the studs enclosures, recess or
surface mount –
• Larger version supports up to 32 AH at 24V. Dimensions: 24” x
14.25” x 5.2” (H x W x D) without cover. Removable battery shelves,
accommodate pairs of 7Ah, 7.5Ah and 8Ah batteries, etc.
• Medium Enclosure – supports 16 AH at 24V. Dimensions: 16”x
14.25” x 5.2” (H x W x D) without cover. (*Note: Only 1 SLC is accomodated.) 16Ah battery backup capacity.
INPUTS
Up to 255 Zones. Zones can come from any of the following
initiating devices:
• Addressable SLC Loop – supports up to (2) 126 point loops
• Commercial RF Receiver –
• Supports Commercial Wireless Fire devices
• Wireless Smoke Detector
• Wireless Heat Detector
• Conventional 1- to 4-zone EZM Expansion modules on the 4-wire fire
bus or SLC loops
• Conventional 2-wire or 4-wire smoke detector input module
• SLC Fire Devices Supported:
• Analog Smoke Detector
• Analog Heat Detector
• Duct Detector
• Pull Station
• Conventional Zone Module
• Short Circuit Isolator
Advantages
• Easy Wire Compatibility - Addressable SLC
controller supports shielded, unshielded,
twisted and untwisted wire - ideal for retrofits
• Longer SLC loop lengths, support more
device loads each, too (see below for
distance at maximum device load in alarm/
standby each):
• 10,000 ft. #14AWG • 6,200 ft. #16AWG •
4,000 ft. #18AWG
• Support for Legacy and Existing Notification Appliances -One
NAC output configurable for 12V for compatibility for easy retrofit
compatibility
• UL Regulated NAC outputs
• Automatic drift compensation for smoke detectors
• Keypads mount anywhere on the bus and have flash-able firmware –
for updates via Quickloader command (# GEMC-FK1, shown above)
• Programmable obscuration level by smoke detector device
• Smoke Obscuration Report genererated remotely or locally or in any
of 3 ways - Quickloader device sensitivity report allows the printout of
a report for the AHJ listing the current status of all smoke detectors
in the system including the programmed obscuration level and the
actual sensitivity reading for each device. This report can be generated
remotely (uploaded) or locally through notebook PC or use optional
onsite printer.
• Full line of UL Commercial Devices for more flexibility & labor-savings
Example, Use Gemini Commercial Wireless 2-input module (GEMCWL-WD2) to convert any UL listed fire device into a UL wireless device,
ideal for sprinkler supervisories or for use with pull stations (mounts on
top of wall/conduit or in deep sngle-gang box (plastic).
• Separate 7Amp 4-NAC Extender (GEM-NAC7) 4 onboard NACs with
up to 2A ea., expandable for up to 24 per system. Up to 16Ah total
battery capacity. Regulated 24V Aux. power. Monitors AC, battery
trouble, tamper and ground fault on Napco bus - Also Provides
Universal FACP support for easy standardization in upgrades
OUTPUTS
Up to 96 outputs
• Four on board Class B or 2 Class A NAC circuits, 2 amps each, total 6.5
amps at 24V
• Built in Wheelock and System Sensor NAC sync/strobe/horn protocol
allows initial silence of audible appliances while maintaining visual
notification, without the use of additional modules.
• Addressable SLC Fire Devices: Supervised relay, unsupervised relay
• Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8 open
collector output (GEMC-OUT8)
(Shown above)
32-Point GEM-C Firewolf™ 24V Commercial Fire System
Agencies
NFPA 72, UL Commercial Fire, UL864 9th Ed., UL985. (CSFM, FM,
MEA listings pending.)
Page 3
RECEIVER
WIRELESS
(4, MAX.)
GEMC-RECV
initiating
Single Fire
N/O device
SINGLE ZONE
WITH TAMPER
GEMC-WL-SMK
SMOKE DETECTOR
HEAT DETECTOR
GEMC-WL-HEAT
TRANSMITTER
GEMC-WL-WD2
4 OR 7 AMP MAIN POWER SUPPLY
BATTERIES
8 ZONE
GEMC-EZM8
CONVENTIONAL
GEMC-F8ZCPIM
8 Fire Zone Expander
MODULE
ZONE EXPANSION
MODULE
GEMC-OUT8
REMOTE RELAY
8 ZONE OUTPUT
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
–
–
–
S
2-WIRE
2-WIRE
SMOKE
+
+
+
OUTPUT
MODULE
GEMC-RM3008
–
S
2.2K
SMOKE
EOLR
+
–
S
2.2K
SMOKE
EOLR
+
–
S
2.2K
SMOKE
EOLR
+
–
S
2.2K
SMOKE
EOLR
+
–
S
2.2K
SMOKE
EOLR
+
–
S
SMOKE
+
–
S
SMOKE
+
–
S
SMOKE
+
8 ZONES OF
2.2K
EOLR
}
2.2K
EOLR
CONVENTIONAL 2-WIRE SMOKES
2.2K
EOLR
PULL STATIONS AND/OR HEAT DETECTORS
FIRE BUS DEVICES
HORN
HORN
ALL
OR ALL
SYSTEM
MUST BE
WHEELOCK
ALL
OR ALL
SYSTEM
MUST BE
WHEELOCK
2-WIRE
FIRE SLC
GEMC-PS24V4A-R)
4 OR 7 AMP MAIN
POWER SUPPLY
(GEMC-PS24V7A-R or
FIREWOLF SYSTEM COMPONENTS
STROBE
SENSOR
STROBE
HORN
STROBE
SENSOR
STROBE
LOOP
ADDRESSABLE
FWC-FSLC-SMK
24 VOLT
GEMC-24VR
BOOSTER
HORN
STROBE
HORN
HORN
HORN
HORN
STROBE
HORN
HORN
SMOKE
ADDRESSABLE
INTERNET
REPORTING
GEMC-NL-MOD
MODULE
SUPPLY
12V AUX POWER
GEMC-12V2APS-CF
2.2K
EOLR
}
2.2K
EOLR
2.2K
EOLR
-- or --
CIRCUITS (CLASS B) (SHOWN)
CIRCUITS (CLASS A)
• 4 ON-BOARD NAC
• 2 ON-BOARD NAC
2.2K
EOLR
HORN
STROBE
STROBE
HORN
STROBE
STROBE
STROBE
DETECTOR
STROBE
HORN
STROBE
HORN
STROBE
HEAT
DETECTOR
ADDRESSABLE
FWC-FSLC-HEAT
MODULE
PRINTER
GEMC-FPRINT
HORN
HORN
HORN
HORN
STROBE
HORN
HORN
HORN
HORN
STROBE
2.2K
EOLR
2.2K
EOLR
2.2K
EOLR
}
• 4 ON-BOARD NAC
2.2K
EOLR
FWC-FSLC-PULL
BATTERIES
FIRE
(MAXIMUM 2)
SLC MODULE
GEMC-FW-SLC
(TELCO 2 SECOND REPORTING LINE)
(TELCO 1 REMOTE DOWNLOAD / REPORTING)
FIREWOLF-SERIES
LARGE ENCLOSURE (SHOWN)
MOTHERBOARD
FIRE
(MAXIMUM 2)
SLC MODULE
GEMC-FW-SLC
BATTERIES
STROBE
STROBE
STROBE
STROBE
-- or --
CIRCUITS (CLASS B)
PULL
ADDRESSABLE
MUST BE ALL
WHEELOCK OR ALL
SYSTEM SENSOR
HORN
HORN
STROBE
HORN
HORN
STROBE
(NOT SHOWN)
CIRCUITS (CLASS A)
• 2 ON-BOARD NAC
PULL STATION
FWC-FSLC-DUCT
GEMC-FK1
(5, MAX.)
GEMC-NAC7
NAC EXTENDER
FIRE KEYPAD
BATTERIES
F
L
O
W
E
R
I
STROBE
HORN
STROBE
STROBE
HORN
STROBE
F
L
O
W
E
R
I
F
DUCT DETECTOR
F
L
O
W
E
R
I
F
FWC-FSLC-EZM2
F
FWC-FSLC-RM2
F
L
O
W
E
R
I
F
FWC-FSLC-SOM1
FWC-FSLC-EZM1
DUAL INPUT
MONITOR MODULE
MODULE
DUAL RELAY
F
L
O
W
E
R
I
F
F
L
O
W
E
R
I
F
DEVICES
UP TO 126
(6" BASE ONLY)
ZONE MODULE
CONVENTIONAL
ISOLATOR
SHORT CIRCUIT
FWC-FSLC-SMK6B
SUPERVISED
OUTPUT MODULE
FWC-FSLC-CZM
FAST RESPONSE
MONITOR MODULE
FWC-FSLC-ISO
Note: The four GEMC-RECV max. is reduced by 1 for each SLC module.
2 SLC MODULES, max.
Page 4
NAPCO COMMERCIAL FIREWOLF SERIES SYSTEM ORDERING INFO.
Napco Commercial Fire Kits
GEMC-FW-255KT
GEMC-FW-128KT
GEMC-FW-32KT
255 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
• 24V Panel, 255 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A
notification power
• 7 Amp, 24V Power Supply
• Built in horn/strobe synch. module on each NAC
• Built in dual line communicator; dual onboard serial ports
• Quickloader up/downloading including remote smoke obscuration reporting
• Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32Ah battery backup.
• Menu-driven LCD Fire Keypad mounts anywhere on bus. (Also, full keyswitch support)
128 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
As above, but with
• 24V Panel, 128 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A
notification power
32 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
Similar to above, but with
• 24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NACs providing up to 4A
notification power
• Locking, Medium Red Enclosure, 16 x 17” reversible door, with 14.25” x 16” base. Houses up to 16Ah battery backup.
Conventional Fire System Peripherals
GEMC-FK1
GEMC-F8ZCPIM
GEMC-EZM8
GEMC-NL-MOD
LCD Fire Red Keypad (Menu-driven operation, functionality for Reset, Acknowledge, Silence (with disable).
Conventional 8-zone 2-wire fire input module. Plugs into motherboard, for conventional 2-wire smoke detectors or
any conventional fire detection device.
8-point expansion module
Internet Reporting Module
Wireless Firewolf Peripherals
GEMC-WL-SMK
GEMC-WL-HEAT
GEMC-WL-WD2
GEMC-REVC
Gemini Comml Wireless Smoke, Photoelectric
Gemini Comml Wireless Heat, 135º F
Gemini Comml Wireless 2-input module
Gemini Commercial Wireless255 point RF Receiver (Up to 4 per system, max.)
Addressable Firewolf Peripherals
GEMC-FW-SLC
FWC-FSLC-SMK
FWC-FSLC-HEAT
FWC-FSLC-DUCT
FWC-FSLC-EZM2
FWC-FSLC-EZM1
FWC-FSLC-CZM
FWC-FSLC-RM2
FWC-FSLC-ISO
FWC-FSLC-SOM1
FWC-FSLC-PULL
FWC-FSLC-PROG2
FWC-FSLC-SMK6B
Addressable SLC Fire Module, supports up to 128 addressable SLC fire devices, below. Up to 2 connect to Panel.
Addressable Analog SLC Smoke, photoelectric, head**
Addressable Analog SLC Heat, 135ºF, head**
Addressable SLC Duct smoke detector, photoelectric
Addressable SLC 2-zone conventional expansion module. Uses one address on SLC loop, but yields 2 indep. contact monitoring
circuits, for pull stations, water flow and other dry contact alarm initiating devices.
Addressable SLC 1-input conventional module, similar to usage above.
Addressable SLC single module, for montoring of dry contacts, ie., pull stations and conv. smokes
Addressable SLC 2-output module (requires 1 SLC address)
Addressable SLC Short Circuit Module (Optional: For special applications, meets Class A, Style 7 loop reqts.)
Addressable SLC Fire supervised output module. Application examples: elevator recall, HVAC shutdown, add’l NAC output w/
power supply
Addressable SLC Fire Pull StationTool for address-programming SLC devices
** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and –HEAT devices
Output Options
GEMC-NAC7
GEMC-12V2APS-CF
GEMC- FPRINT
GEMC-RM3008
GEMC-RS232
GEMC-OUT8
Remote 4-output NAC Extender, for 6.5A ttl, or 2A, max. on any 1 output. Red 14 x 16” can, connects to 120VAC, supports 32Ah
standby batts. Supervised, fire bus connection. System Sensor and Wheelock NAC synch. (5/system, for 20 add’l NAC circuits ttl.)
12VDC Power Supply for Fire Bus, remote supervised. Direct 120VAC connection, supports 2ea. 12V, 7Ah standby batts.
Parallel printer module
8 Form C Relay Output Module
RS232 Adapter for serial output from Panel
PGM Output Module, 8 open collector PGM outputs
NAPCO Security Technologies, Inc.
www.napcosecurity.com
1-800-645-9445 • 631-842-9400
Amityville, NY USA
August 2010, Specifications subject to change A601