NAPCO FREEDOM F-64TP Operating Manual

1
OPERATING GUIDE for your NAPCO FREEDOM Home Security System
© NAPCO 2006 OI318A 9/06
R
Freedom F-64TP Touchpad
2
The NAPCO Freedom F-64TP is a “smart” interac­tive menu-driven Touchpad with an integral motion sensor, integral siren, and integral speaker designed for your NAPCO control panel. It is designed for ease of use and to eliminate false alarms by using the exit door deadbolt for arming and disarming, rather than memorized Touchpad codes. Its alphanumeric screen not only displays the status of your system, the speaker also provides step-by-step instructions to guide you through all operations. In addition, alarms can be silenced by the use of a uniquely coded digital key called an "I-FOB".
All monitored door deadbolts must be engaged before arming the system. Unbolted doors will display on the Touchpad even if the doors are closed. The
Touchpad display scrolls all significant open or faulted zones (except PIR's) and when this scrolling stops, the system is ready to arm, even if the primary exit door is open or unbolted. To Arm the system, simply press either the STAY button (if staying within the premises) or the AWAY button (if leaving), and then engage the exit door deadbolt.
To disarm, simply unlock the deadbolt--no need to enter memorized entry codes that other systems re­quire, thus preventing false alarms.
This booklet contains important information about the operation of your system with this Freedom F­64TP Touchpad . Read it carefully and keep it handy for future reference. Check the Glossary for an expla­nation of terms that may be unfamiliar to you.
You'll probably find subjects mentioned in this book­let that do not apply to your system. NAPCO control panels have such a wide variety of features that few security systems, if any, will ever need them all. Your alarm professional has chosen appropriate features for your particular needs.
Regardless of how your system has been config­ured, rest assured that it has been carefully designed and engineered to the highest industry standards. To assure optimum safety and security, familiarize your­self with this equipment. Periodically check its condi­tion and state of readiness by testing it at least once a week in both the ac/battery and battery-only modes (ask your alarm professional how to make these tests).
INTRODUCTION
1 Test your sounding device and backup battery
(Perform these tests only on weekends or at a time designated by your
alarm company)
1. While disarmed, press MENU.
2. Press MENU until ACTIVATE SIREN TEST appears in the display.
3. Press YES to execute the test. The alarm will sound for about two sec-
onds.
If the alarm does not sound, call for service.
If the battery is low, LOW BATTERY E02-00 SERVICE will appear in
the display indicating a low battery condition. Allow 24 hours for the battery to recharge. If the trouble continues, call for service.
2 Test your central station communicator
(Activate Dialer Test programmed? YES NO)
1. Notify your Central Station of the impending test.
2. While disarmed, insert your Master I-FOB into the Touchpad. Press MENU.
3. Press MENU until ACTIVATE DIALER TEST appears in the display.
4. Press YES to send a test code to the central station.
If the test is not successful, COMM FAIL E03-00 SERVICE will dis-
play, indicating a communication failure. Call for service.
Note: Any subsequent successful transmission will clear a Failure to
Communicate system trouble.
IMPORTANT - TEST YOUR SYSTEM WEEKLY
From a Disarmed State
3
TABLE OF CONTENTS
TABLE OF CONTENTS
F-64TP TOUCHPAD CONTROLS & INDICATORS .................4
SYSTEM DISARMED ..............................................................6
ARMING WHEN LEAVING ......................................................7
ARMING STAY: PROTECTING YOURSELF AT HOME .........8
ARMING AND LEAVING WITH OTHERS STAYING ...............9
EXITING WITH THE SYSTEM ALREADY ARMED ..........10-11
BYPASSING ZONES (OVERVIEW) ......................................12
ARMING AND LEAVING WITH A FAULTED ZONE .............. 13
ARMING AND STAYING WITH A FAULTED ZONE ..............14
BYPASSING USING THE ZONE DIRECTORY .....................15
EMERGENCY BUTTONS ......................................................16
DISARMING THE SYSTEM ................................................... 17
SILENCING AN ALARM ........................................................18
FIRE PROTECTION ..............................................................19
TOUCHPAD MENU MODE ....................................................21
USER PROGRAM MODE ......................................................25
USER I-FOB LIST ..................................................................28
SYSTEM TROUBLE ERROR CODES ...................................29
ZONE LIST ............................................................................34
FCC PART 68 STATEMENT ..................................................35
NAPCO LIMITED WARRANTY .....................................................38
IF THE ALARM IS SOUNDING:
To silence an alarm, insert your I-FOB key into the slot on the Touchpad and remove when alarm has silenced.
Proceed with caution! (See pages 17 & 18).
ALARM TIME OUT: _________ Minutes
FOR SERVICE, CALL: ___________________________
TO CANCEL AN ALARM REPORT, CALL: _________________________
R
4
SYSTEM READY
10/15/06 12:05P
BYPASS FIRE FIRE TBL SYS TBL
F-64TP TOUCHPAD CONTROLS & INDICATORS
20
2
3
4
5
6
19
21
22
7
13 17
9
8
4
12
10
11
16
15
14
18 1
5
F-64TP TOUCHPAD CONTROLS & INDICATORS
LCD Window – 32 character LCD displays
system status messages, zone descriptions, system troubles, etc.
STATUS Light. Lights (green) to indicate
that the system is ready for arming. If a zone is not secured, the light will be off and the zone will display in the window. If a zone has been bypassed, the STATUS light will blink while armed.
ARMED Light. Lights (red) to indicate that
the system is armed. If an alarm has occurred, the ARMED LED will be flashing.
Alarm Speaker – Will sound a LOUD
steady sweep tone when intrusion is detected or a distinct pulsating tone for a fire alarm condition. Also chirps to indicate armed AWAY, and provides for audible voice prompts.
STAY Button – Press once to initiate the
arm Stay sequence. Stay Mode bypasses all interior zones simultaneously to allow free movement within the premises. Hold down for 2 seconds if all zones secure to eliminate 60-second pre-arm delay.
AWAY Button – Press to initiate arm
AWAY sequence when no one is to remain home. Exit through the door and engage the deadbolt from outside the premises. System will be fully armed with
all perimeter and interior devices activated.
BYPASS Button – Press to enter the
Bypass Menu, where system functions are displayed in the LCD window. Press
YES to select the desired function; press RESET to exit. Bypassing a zone
deactivates the zone from the system.
MENU Button – Press to enter Function
Mode, in which available system functions are displayed in the LCD window. The desired function is then selected by pressing the YES button. Press RESET to exit.
DISARM / RESET Button – Press to silence
Fire alarms, troubles and exits Function Mode (see MENU Button).
YES Button – Press to select the desired
function in menus (see MENU Button, above).
NO Button – Press to answer no to menu
questions and proceed to the next question (see MENU Button, above).
ENTER Button – Press to accept displayed
value and to move cursor to next position.
Integral PIR – Used to detect intruders and
your presence near the Touchpad during arming and disarming. Do not block.
FIRE Button – Press and hold down for 2
seconds to alert the Central Station of a fire emergency.
+ AUX Button – Press and hold down for 2
seconds to alert the Central Station of a auxiliary emergency.
Police Button – Press and hold down for
2 seconds to alert the Central Station of a police emergency.
I-FOB – The I-FOB is a uniquely coded
digital key. Insert the I-FOB into its keyhole to disarm the system and silence the siren in case of an alarm.
Slide Plate – Lift to view brief descriptions of
Touchpad buttons and procedures.
Bypass Icon – Appears as a reminder that
zones have been bypassed (by pressing the BYPASS button). If it is necessary to bypass any inoperative zones, it is important to have the zones repaired as soon as possible.
Fire Icon – Steady indicates a fire alarm
condition. Flashing indicates fire alarm sounding.
Fire TBL Icon – Indicates a problem on a
fire zone is detected.
System TBL Icon – Indicates a trouble
condition exists on the system. Press SILENCE to silence sounder and display the trouble.
1
20
2
3
4
5
6
7
8
9
10
11
12
13
14
16
15
17
18
19
21
22
6
SYSTEM DISARMED
Please note the following information when the system is disarmed:
When the system is disarmed, the premises is NOT protected from intruders--but the keypad alarm buttons FIRE, AUX, and POLICE are ALWAYS active (as are any other "24 hour" devices that the installer provided for your system). See page 16 for more information regarding these Emergency Buttons.
When all perimeter zones (except the local exit/entry door) are secure, the arming sequence can be started by pressing STAY or AWAY. The green STATUS light must be on steady and the LCD window will display "SYSTEM READY". If the local exit/entry door is open or unlocked, the second line of the LCD will scroll between the date / time display and "DOOR UNLOCKED".
When the system is NOT ready to arm, the green STATUS light will be off and the LCD window will scroll "SYSTEM NOT READY" followed by all faulted perimeter zones and open/unbolted doors, including the local exit/entry door.
To prevent confusion during arming, interior zones (such as motion sensors, trip beams, etc.), do not scroll on the Touchpad LCD window when activated. The status of all zones (including the interior zones) can be displayed in the LCD window by answering YES to the "DISPLAY OPEN
ZONES Y/N" Touchpad Menu Mode function (see Touchpad Menu Mode, page 21).
SYSTEM READY
STATUS
DISPLAY OPEN ZONES Y/N
7
ARMING WHEN LEAVING
1
Check the Touchpad indicators. The green STATUS light must be ON-STEADY, and the LCD window will read "SYSTEM READY", indicating that the system is ready to arm.
If the green STATUS light is off and zones are scrolling in the display, a perimeter zone is faulted or a monitored deadbolt (other than your primary exit door) is unlocked (if the primary exit door is unlocked, the LCD window will read "DOOR UNLOCKED"). Check the open zones listed and close the door, window, or lock the deadbolts as needed. If you cannot immediately secure the zones or lock the deadbolts, they may be bypassed (see page 12).
2
Press the AWAY button.
The Touchpad will voice prompt the correct action.
If you change your mind after pressing AWAY, press RESET to clear arming.
3
Open the door, exit and close the door. The exit delay period, during which you can safely exit the prem­ises, is 60 seconds in length by default, but can be changed by your installer if desired.
4
Lock the deadbolt from the outside to arm the system. The Touchpad will sound one chirp to indicate the system is armed.
After pressing AWAY, if the deadbolt has not been locked within the exit delay time, the system will re- vert back to a disarmed state.
After pressing AWAY, if the system detects movement inside the premises during the exit delay time, it will automatically revert to Stay mode, providing perimeter protection with the interior protection such as interior motion sensors turned off. (See ARMING STAY on page 8).
Note: If you lose your deadbolt key, see page 24 for activating a special "Lost Key Mode".
If you are leaving with no other family members remaining home:
Listen for the voice prompt, "Please exit and lock door to Arm System". The LCD window will read "EXIT
AND LOCK DOOR TO ARM-AWAY", starting the exit delay period .
SYSTEM READY
"Please exit and lock
door to arm system"
AWAY
8
ARMING STAY: PROTECTING YOURSELF AT HOME
Arming in the Stay mode allows you to remain home with the perimeter protection active but with the interior protection off, so that you may move freely within the premises.
1
Check the Touchpad indicators. The green STATUS light must be ON-STEADY, and the LCD win­dow will read "SYSTEM READY", indicating that the system is ready to arm.
If the green STATUS light is off and zones are scrolling in the display, a perimeter zone is faulted or a monitored deadbolt (other than your exit door) is unlocked (if the primary exit door is unlocked, the LCD window will read "DOOR UNLOCKED"). Check the open zones listed and close the door, window, or lock the deadbolts as needed. If you cannot immediately secure the zones or lock the deadbolts, they may be bypassed (see page 12).
2
Press the STAY button.
The Touchpad will voice prompt the correct action.
If you change your mind after pressing STAY, press RESET to clear arming.
3
The LCD window will read "ARMING STAY MODE" during the exit delay time period.
4
After the exit delay time period, the system will arm in Stay mode.
Note: To avoid the exit delay time period and arm Stay immediately,
press and hold STAY for 2 seconds.
To disarm, see page 17.
SYSTEM READY
"System is arming
in Stay mode"
STAY
"System armed
Stay"
9
ARMING AND LEAVING WITH OTHERS STAYING
1
Check the Touchpad indicators. The green STATUS light must be ON-STEADY, and the LCD win­dow will read "SYSTEM READY", indicating that the system is ready to arm.
If the green STATUS light is off and zones are scrolling in the display, a perimeter zone is faulted or a moni- tored deadbolt (other than your exit door) is unlocked (if the primary exit door is unlocked, the LCD window will read "DOOR UNLOCKED"). Check the open zones listed and close the door, window, or lock the dead­bolts as needed. If you cannot immediately secure the zones or lock the deadbolts, they may be bypassed (see page 12).
2
Press the STAY button.
The Touchpad will voice prompt the correct action.
If you change your mind after pressing STAY, press RESET to clear arming.
3
Open the door, exit and close the door, with others remaining
home. The LCD window will read "EXIT AND LOCK DOOR TO ARM-STAY".
4
Lock the deadbolt to arm the system.
If the deadbolt has not been locked within the exit delay
time (usually 60 seconds of pressing STAY), the system will revert back to a disarmed state.
The deadbolt can be locked from the inside by those
remaining home.
Note: If you lose your deadbolt key, see page 24 for activating a special "Lost Key Mode".
If you are arming and leaving with other family members remaining home:
The LCD window will read "ARMING STAY MODE" during the exit delay time period.
SYSTEM READY
"Please lock door to
arm in Stay mode"
"System armed
Stay"
STAY
"System is arming
in Stay mode"
10
EXITING WITH THE SYSTEM ALREADY ARMED
With the system armed in Stay mode, the Touchpad will read "ARMED STAY".
The LCD window will read "EXIT AND LOCK DOOR TO ARM-STAY" during the exit delay time period.
2
Unlock the deadbolt from the inside.
3
Open the door, exit and close the door.
If the system is Armed STAY and you are leaving with other family members remaining home: (If NO other family members are remaining home, see next page).
4
Lock the deadbolt from the outside (or have someone lock the deadbolt from the inside) to arm the system.
If the deadbolt has not been locked within the exit
delay time period (usually 60 seconds), the system will revert back to a disarmed state.
Note: If you lose your deadbolt key, see page 24 for activating a special "Lost Key Mode".
1
Press the STAY button.
The Touchpad will voice prompt the correct action.
"Please lock door to
arm in Stay mode"
STAY
ARMED STAY
"System is arming
in Stay mode"
"System armed
Stay"
11
EXITING WITH THE SYSTEM ALREADY ARMED
1
Press the AWAY button.
The Touchpad will voice prompt the correct action.
If you change your mind after pressing AWAY, press RESET to clear arming.
The LCD window will read "EXIT AND LOCK DOOR TO ARM-AWAY".
2
Unlock the deadbolt from the inside. The Touchpad will voice prompt the correct action.
3
Open the door, exit and close the door.
If the system is Armed STAY and you are leaving with NO other family members remaining home: (If other family members are remaining home, see previous page).
With the system armed in Stay mode, the Touchpad will read "ARMED STAY".
4
Lock the deadbolt from the outside to arm the system. The Touchpad will sound one chirp to indicate the system is armed.
If the deadbolt has not been locked within the exit delay time period (usually 60 seconds), the system
will revert back to a disarmed state.
If the system detects movement inside the premises the exit delay time period (usually 60 seconds), it
will automatically revert to Stay mode, providing perimeter protection with the interior protection such as interior motion sensors turned off. (See ARMING STAY: PROTECTING YOURSELF AT HOME- page 8).
Note: If you lose your deadbolt key, see page 24 for activating a special "Lost Key Mode".
"Please exit and lock
door to arm system"
AWAY
"Please exit and lock
door to arm system"
12
BYPASSING ZONES (OVERVIEW)
You want to arm the system, but a zone cannot be secured, or you wish to intentionally leave a perimeter door open. These "faulted" or open zone(s), may be temporarily removed from the system or "bypassed". Warning: Bypassed zones are unpro- tected--always have the system checked and repaired as soon as possible. The following is a bypassing overview.
With the window or door perimeter zone open or "faulted" (excluding the primary exit/entry door--see warning on page 14), the zone description of this open zone will appear in the Touchpad LCD window.
1
Press the BYPASS button to enter a special Bypass Menu. The first Menu item is "DISPLAY ZN DIRECTORY
Y/N".
2
Press YES to list all zones in your system. Follow the voice prompts. The Bypass icon will ap-
pear for each bypassed zone listed. Go to step 3.
Press NO or MENU to scroll to the next Bypass Menu selection "BYPASS ALL OPEN ZONES Y/
N", allowing you to bypass all zones currently open (excluding the primary exit/entry door). Press NO or MENU and the Bypass Menu repeats.
3
With "DISPLAY ZN DIRECTORY Y/N" in the LCD window, press YES to list all zones in your sys­tem. Scroll forward or backward through the zone list using the YES × and NO Ø buttons (the menu repeats or "loops"). As you scroll through each zone, the Bypass or Trouble icons will ap­pear (or not appear) depending on the status of each zone. When the zone that you wish to by­pass appears on the Touchpad LCD window, press BYPASS. The Bypass icon will appear. Press RESET to continue.
4
With the selected perimeter zone now bypassed, you can now proceed with either arming Stay or Away, as desired. Press STAY or AWAY, then lock the deadbolt to arm the system with the faulted zone(s) bypassed.
05-BACK DOOR
(example)
01-BACK DOOR
BYPASS
SYSTEM READY
"Display Zone Directory?"
Press YES to select or
MENU to skip"
BYPASS
NO Ø
YES×
13
ARMING AND LEAVING WITH A FAULTED ZONE
You want to arm and leave the premises, but wish to intentionally leave a window open. Or perhaps a door deadbolt is bro­ken and is unable to be quickly repaired and locked. These "faulted" zone(s), may be temporarily removed from the system ("bypassed"). Warning: Bypassed zones are unprotected--have the system checked and repaired as soon as possible.
1
Press the BYPASS button. The LCD window will read "DISPLAY ZN DIRECTORY Y/N".
2
Press NO and the next menu selection "BYPASS ALL OPEN ZONES Y/N" appears. Press YES to bypass all open perimeter zones (excluding the primary exit/entry door).
3
Press AWAY, open the door and exit.
4
Lock the deadbolt to arm the system with the faulted zone(s) bypassed.
The Touchpad will sound one chirp to
indicate the system is armed.
Warning: Bypassed zones are unprotected--have the system checked and repaired as soon as possible.
Note: If you lose your deadbolt key, see page 24 for activating a special "Lost Key Mode".
SYSTEM READY
BYPASS
"Exit and lock door
to arm system"
"Display Zone Directory?"
Press YES to select or
MENU to skip"
BYPASS
NOØ
YES
×
14
ARMING AND STAYING WITH A FAULTED ZONE
Perhaps you want to arm the system and stay within the premises, but wish to intentionally leave a door open with all other perimeter protection secure. These open "faulted" zone(s), may be temporarily removed from the system ("bypassed"). Remember, all bypassed zones--doors, windows, etc.--are unprotected.
1
Press the BYPASS button. The LCD window will read "DISPLAY ZN DIRECTORY Y/N".
2
Press NO and the next menu selection "BYPASS ALL OPEN ZONES Y/N" appears. Press YES to bypass all open perimeter zones (excluding the primary exit/entry door).
3
Press STAY--or--press and hold STAY for 2 seconds to arm instantly.
4
Close and lock the primary exit/entry door deadbolt to arm the system with the faulted zone(s) bypassed.
WARNING: When bypassing a monitored door, be aware that the bypassed door is temporarily removed from the system and will not send a disarm signal to the Touchpad when unlocked, and false alarms may result. Therefore, an I-FOB MUST be used to disarm when entering through a bypassed monitored door.
"Display Zone Directory?"
Press YES to select or
MENU to skip"
STAY
BYPASS
NOØ
YES
×
15
BYPASSING USING THE ZONE DIRECTORY
Bypassing using the Zone Directory allows you to scroll through a list of all zones in your system and manually select which zone to bypass. These "faulted" zone(s), may be temporarily removed from the system ("bypassed"). Warning: Bypassed zones are unprotected--have the system checked and repaired as soon as possible.
1
Press the BYPASS button. The LCD window will read "DISPLAY ZN DIRECTORY Y/N".
2
Press YES. The Zone Directory will display, starting with zone 1. Press YES to scroll up and press NO to scroll down through the list of zones. When the zone you wish to bypass appears on the LCD win-
dow, press BYPASS and the Bypass icon will appear for each bypassed zone listed.
3
With the selected perimeter zone now bypassed, you can now proceed with either arming Stay or Away, as desired. Press RESET, allowing the LCD window to read "SYSTEM READY". Then press
STAY or AWAY and lock the deadbolt to arm the system with the faulted zone(s) bypassed.
WARNING: When bypassing a monitored door, be aware that the bypassed door is temporarily removed from the system
and will not send a disarm signal to the Touchpad when unlocked, and false alarms may result. Therefore, an I-FOB MUST be used to disarm when entering through a bypassed monitored door.
BYPASS
"Display Zone Directory?"
Press YES to select or
MENU to skip"
YES
16
EMERGENCY BUTTONS
Emergency Buttons (Only available if programmed).
Fire Emergency Hold down the Fire button to alert the central station of a fire emer-
gency. *
(Fire Emergency programmed? YES NO)
Auxiliary Emergency Hold down this button to alert the central station of an auxiliary
emergency. *
(Auxiliary Emergency programmed? YES NO)
Auxiliary Emergency: _______________________________________
Police Emergency Hold down the Police Emergency button to alert the central station of
a police emergency. *
(Police Emergency programmed? YES NO)
The Emergency Buttons, if programmed, are always active, whether the system is armed or disarmed. The Emergency But­ton must be Held Down for 2 seconds to activate the emergency alarm and transmit the signals to central station.
17
DISARMING THE SYSTEM
Disarming when returning home:
When returning home, simply unlocking your deadbolt from the outside will automatically disarm the sys­tem. The red ARMED light will go out and, if there are no previously bypassed perimeter open zones, the green STATUS light will turn on.
If an alarm has occurred while you were away, opening the deadbolt will initiate an entry delay sequence. The I-FOB must be used to disarm the system or an alarm will be initiated within a short interval. If the de­lay is completed without the I-FOB used to disarm the system, the alarm will sound and the I-FOB must be inserted to silence the alarm.
Proceed with caution! If you suspect that an intruder may still be in the premises, leave immediately and call authorities from a neighbor's telephone. If system in alarm, insert I-FOB to silence.
Disarming when home (Armed Stay):
When home with the system armed in the Stay mode, unlocking the deadbolt from the inside will disarm the system. The red ARMED light will go out and the green STATUS light will come on.
The system may also be disarmed with the I-FOB. To disarm the system, insert your I-FOB key into the I­FOB slot on the Touchpad and remove when the system is disarmed.
Ambush Feature (Optional):
If an intruder forces you to disarm your system upon entry, you can silently signal an emergency while ap­pearing to be merely disarming the Touchpad. Send a silent "ambush" alarm to the central station by pressing the RESET button for 2 seconds (within 15 seconds* of disarming the system). There will be no indication that a silent alarm has been sent. Note: Consult your installer to determine if the Ambush fea­ture is enabled in your system. *
15 seconds by default; this time can be changed by your installer.
ALARM
18
If an alarm occurs while you are at home:
The Touchpad siren will sound and the red AR MED light will flash. The LCD window will read "ALARM". Proceed with caution! If you suspect that an intruder may still be in the premises, leave immediately and call authorities from a neighbor's telephone. The Touchpad will prompt you to insert the I-FOB.
To silence the alarm, insert your I-FOB key into the I-FOB slot on the face of the Touchpad and re­move when alarm has silenced.
The LCD window will continue to display the names of the zone(s) on which the alarm occurred. De­termine which zone caused the alarm and then press
RESET to clear the alarm memory.
If an alarm occurs while you are away:
When you unlock the deadbolt to enter, the Touchpad sounder will activate and the red ARMED light will be flashing to warn you that an alarm had occurred while you were away.
Proceed with caution! If you suspect that an intruder may still be on the premises, leave immedi­ately and call authorities from a neighbor's phone.
To disarm the system, you must insert your I-FOB key into the I-FOB slot on the Touchpad. If the system is not disarmed in 30 seconds, the alarm will sound.
The LCD window will continue to display the names of the zone(s) on which the alarm occurred. De­termine which zone caused the alarm and then press
RESET to clear the alarm memory.
SILENCING AN ALARM
ARMED
RESET
RESET
ALARM
19
If a fire is detected, the siren will sound a distinct pulsating tone and the LCD window will flash the word FIRE. If a Fire Alarm does occur:
1
If a fire is in progress, evacuate the premises immediately! Call the Fire Department from an outside phone.
2
If there is no evidence of a fire, press RESET or insert your I-FOB key into the Touchpad.** The siren will silence, and the word FIRE in the Touchpad LCD window will stop flashing.
3
Determine which device went into alarm. If you are protected by smoke detectors, the light on the active detector will be lit. Once it is determined which smoke detector is in alarm, press
RESET to
reset the smoke detector.
4
If the Fire Zone has reset properly, the words SYSTEM READY should appear in approximately 30 seconds. If the words SYSTEM READY do not appear, press RESET again in a few minutes. If the words SYSTEM READY still do not appear, call for service.
Fire-Zone Trouble
The system is constantly monitoring the Fire Zone to insure the connections to the protective devices are in good working order.
If a problem on a Fire Zone is detected, a System Trouble will display. The sounder will activate and LCD window will display the name of the zone in trouble.
Press the RESET button to silence the sounder. Call for service immediately.
*Consult your installer to determine if your system includes fire protection. **Check if only I-FOB can silence fire alarm: YES NO
FIRE PROTECTION*
FIRE
RESET
RESET
20
FIRE PROTECTION
Preparing a Fire Escape Plan
Even with the most advanced fire alarm system, adequate protection requires an escape plan.
To prepare your plan, draw floor plans of your building. Show two ex­its - a front or back door and a window from each room. (Make sure the win­dow works. You may need a special fire-escape ladder if the window is high up). Write down your outside meeting place.
Family Rehearsal
Rehearse each of the following activities:
1. Everyone in his room with the doors closed.
2. One person sounds the alarm.
3. Each person tests his door.
4. Pretend the door is hot and use the alternate escape exit.
5. Everyone meets outdoors at the assigned location.
Important! - Read Carefully
Discuss these escape procedures
with all those who use the building:
1. In a residence, sleep with the bed­room door closed. A closed door will hold back deadly smoke while you escape.
2. When the fire alarm signals, es­cape quickly. Do not stop to pack.
3. Test the door. If it is hot, use your alternate route through the win­dow. If the door is cool, brace your shoulder against it and open it cautiously. Be ready to slam the door if smoke or heat rushes in.
Crawl through smoke, holding your breath. Close the doors again on leaving to help prevent the fire from spreading.
4. Go to your specific outdoor meet­ing place so you can see that eve­ryone is safe.
5. Assign someone to make sure no­body returns to the burning build­ing.
6. Call the Fire Department from a neighbor's telephone.
Would You Like More Safety Information?
For more information on home fire detection, burn safety, and home fire safety, write to the National Fire Protection Association, Public Affairs Dept. 05A, Batterymarch Plaza, Quincy, MA 02269.
21
TOUCHPAD MENU MODE
The Touchpad can provide access to a wide assortment of utility functions, each displayed on the Touchpad LCD window in a prompting “YES/NO” format.
1 To enter Touchpad Menu Mode, press MENU. 2 To skip a function, press NO. 3 To select and execute a function, answer YES.
Press RESET to return to normal Touchpad operation. The Touchpad will automatically return to its normal operating mode if no activity is detected for longer than one minute.
When the last function in the menu appears, press MENU again to repeat the menu.
Note: All functions in the menu appear if the Master I-FOB is inserted into the Touchpad before pressing MENU; if a User I-FOB is
inserted or if an I-FOB is NOT inserted, only a limited number of functions will be displayed. Limited functions are noted below.
ENTER BYPASS MENU Y/N
ACTIVATE CHIME Y/N
ENTER BYPASS MENU - The Bypass Menu provides a list of items to bypass. The
first Menu item is "BYPASS ALL OPEN ZONES" allows you to bypass all open perimeter zones (excluding the primary exit/entry door). The Bypass icon will ap­pear for each bypassed zone listed. The next Bypass Menu selection "DISPLAY ZN BYPASSED " appears only if zones are bypassed and allows you to display those bypassed zones. The next Bypass Menu selection "DISPLAY ZN DIREC- TORY" allows you to display a listing of all zones in the Area. Press YES and NO to scroll through each of these lists.
ACTIVATE CHIME - The Chime Mode will sound a tone at the Touchpad when the
programmed zone is faulted while disarmed. To deactivate the Chime Mode, re­enter Touchpad Menu Mode and when “DEACTIVATE CHIME“ is displayed, press
YES. Note: The Chime Mode is disabled while armed. Chime is disabled for Pro­tected zones while armed, Never Armed zones (such as a driveway sensor) will
22
continue to chime when system is armed.
CHANGE KEYPAD BEEP VOLUME - When the Touchpad buttons are pressed or
when an entry warning activates, the Touchpad beeper sounds. This function allows the Touchpad beeper volume to be adjusted. Press YES to increase, press NO to de­crease. Selections are HIGH, MED-HIGH, MED, LOW and OFF.
CHANGE VOICE VOLUME - All Touchpad functions are displayed in the LCD window
and are accompanied by a voice prompt. This function allows the Touchpad voice prompt volume to be adjusted. Press YES to increase, press NO to decrease. Selec­tions are HIGH, MED-HIGH, MED, LOW and OFF.
ACTIVATE SIREN TEST - Activates the alarm (while disarmed) for about 2 seconds and
performs a battery test. If the alarm does not sound, call for service. Note: If the bat­tery is low, a “LOW BATTERY E02-00 SERVICE” will appear in the display indicating a low battery condition. First allow 24 hours for the battery to recharge. If the trouble continues, call for service.
DISPLAY FIRE ALARM - Displays alarms that have occurred on the Fire Zone(s). Press
the YES and NO buttons to scroll zones. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
DISPLAY FIRE TROUBLE - Displays trouble conditions that have been detected on the
Fire Zone(s). Press the YES and NO buttons to scroll zones. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
TOUCHPAD MENU MODE
ACTIVATE SIREN TEST Y/N
DISPLAY FIRE ALARM Y/N
DISPLAY FIRE TROUBLE Y/N
CHANGE KEYPAD BEEP VOLUME Y/N
CHANGE VOICE VOLUME Y/N
23
ACTIVATE FAULT FIND Y/N
RESET SYSTEM TBL Y/N
ACTIVATE FAULT FIND - Activates a multiple diagnostic test report. For installer's use
only. If accidentally enabled, press RESET to exit. Note: This selection only appears
with a Master I-FOB inserted in the Touchpad.
RESET SYSTEM TBL - System troubles display and sound at the Touchpad. Correct-
ing the trouble will clear most indications, however the following error codes will require manual reset: E13; E19; E20 and E22. (See SYSTEM TROUBLE ERROR CODES for a description of error codes). Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
ACTIVATE DIALER TEST – Allows a central station communication test to be initiated,
transmitting a Test Timer signal. For installer's use only. If accidentally enabled, press RESET to exit. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
ENTER LOG MENU – The Log Menu provides a list of logged events. DISPLAY
ALARM LOG displays the most recent alarm events. DISPLAY TOTAL LOG dis-
plays the most recent events of all types. DISPLAY FIRE LOG displays the most re­cent fire events. DISPLAY OP/CL LOG displays the most recent openings and clos­ings and DISPLAY SYSTEM LOG displays the most recent system events. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
ACTIVATE PROGRAM - Activates the User Program Mode. See page 25 for more infor-
mation. Note: This feature is disabled while armed. Note: This selection only ap­pears with a Master I-FOB inserted in the Touchpad.
TOUCHPAD MENU MODE
ACTIVATE DIALER TEST Y/N
ENTER LOG MENU Y/N
ACTIVATE PROGRAM Y/N
24
ACTIVATE DOWNLOAD Y/N
ACTIVATE DOWNLOAD - For installer's use only. If accidentally enabled, press RESET
to exit. Note: This feature is disabled while armed. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
ACTIVATE LOST KEY MODE - In the event that the keys to your deadbolt are lost or sto-
len, the system may still be used by arming in the Lost Key Mode. In Lost Key Mode, the system may be armed as usual, however unlocking the deadbolt will not disarm the system. The system may only be disarmed with the I-FOB digital key. When Lost Key Mode is active and you wish to deactivate, this menu item changes to DEACTIVATE LOST KEY MODE. NOTE: If your deadbolt key is lost, it is important that you have your locksmith re-key the deadbolt, or have the deadbolt replaced as soon as possi­ble. In addition, we strongly recommend keeping your I-FOB on a different key ring as your deadbolt key. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
ACTIVATE PIR TEST - Allows a passive infrared / motion detector test to be initiated
within the system. For installer's use only. If accidentally enabled, press RESET to exit. Note: This selection only appears with a Master I-FOB inserted in the Touchpad.
TOUCHPAD MENU MODE
ACTIVATE LOST KEY MODE Y/N
ACTIVATE PIR TEST Y/N
25
USER PROGRAM MODE
User Program Mode
Your Installer has programmed into your system a uniquely coded digital Master I-FOB that can be used to not only disarm the system and silence the siren, but also allows access to the User Program Mode. User Program Mode allows you to program various options, such as adding other User Codes, setting the system Time and Date, enrolling new I-FOB's, etc. The following explains how you can enter User Program Mode and to program these additional options:
Enter the User Program Mode
1. Insert your Master I-FOB into the Touchpad. Press MENU to enter the Touchpad Menu Mode, then remove the I-FOB from the Touchpad.
2. Press MENU until “ACTIVATE PROGRAM Y/N” is displayed, then press YES. “CHANGE DATE Y/N” will display indicating that the system is ready to update the first option, the
current date. Press YES to change the date.
Enter Date
1. With “ENTER DATE (MM/DD/YY)” displayed in the LCD window, of the two digits repre­senting the month, the cursor is located under the left digit. Press the YES or NO but- tons to increment (or decrement) this left digit as needed. Press ENTER move the cur­sor to the right.
2. To edit the date, press the YES or NO buttons to increment (or decrement) the digits as needed. Press ENTER move the cursor to the right, then repeat this process for the year. When finished, press MENU to save, and the next option, "CHANGE TIME Y/N" will display. Press YES to change the time.
Enter Time
1. With “ENTER TIME (HH:MM)” displayed in the LCD window, of the two digits represent­ing the hour, the cursor is located under the left digit. Press the YES or NO buttons to increment (or decrement) the hour digits as needed. Press ENTER to move the cursor to the right.
ENTER DATE (00/00/00)
ACTIVATE PROGRAM Y/N
ENTER TIME (00:00A)
26
2. Repeat this process to increment (or decrement) the minute as needed. Press ENTER move the cursor to the right and press the YES or NO buttons to toggle between "A" and "P" (for AM and PM). When finished, press MENU to save and proceed to the next op­tion, "ENROLL MASTER I-FOB Y/N".
Create Master I-FOB
The I-FOB is a uniquely coded digital key that performs the following functions when in­serted into the Touchpad I-FOB slot:
Disarm an armed system
Silence an active alarm
Reset a fire alarm
The Master I-FOB supplied with your system also allows access to additional features within the Touchpad Menu Mode (see page 21), including access to this User Program Mode. Note: Only one Master I-FOB can exist within the system. Because the Master I-FOB must be used to enter this User Program Mode menu, this option "Create Master I-FOB" is in­cluded in case your existing Master I-FOB--although still working--is perhaps physically dam­aged in some way and you wish to physically replace it with a new I-FOB (contact your secu­rity professional and order part F-IFOB). If you press YES to this selection, the Touchpad will prompt you to insert a new I-FOB, thus replacing the existing Master I-FOB. (In theory, you can insert the existing Master I-FOB, but this redundant operation will only overwrite the exist­ing valid Master I-FOB code, thus "re-creating" a Master I-FOB). Note: The Master I-FOB allows access to all system security features and thus should be kept in a secure location.
Create User I-FOB
In addition to allowing the disarming of the system and silencing the siren, User I-FOB's al­low limited access to system features. You can add up to 5 additional "User" I-FOB's to the system. Create a User I-FOB as follows:
1. Obtain a new I-FOB from your security professional (order part F-IFOB).
USER PROGRAM MODE
ENROLL MASTER I-FOB Y/N
ENROLL USER I-FOB Y/N
27
2. With “CREATE USER I-FOB Y/N” displayed in the LCD window, press "Y" and the LCD window will request to insert the new I-FOB into the Touchpad.
3. After 5 seconds, the I-FOB will be programmed, and you will be prompted to remove the I-FOB from the Touchpad.
It is recommended that you record the name of each person in possession of each User I­FOB in the list shown on the next page so that you will know which I-FOB user number to delete from the system, as described in the next section.
Remove I-FOB's From The System
In the event that a User I-FOB is lost, use the following procedure to remove I-FOB's from the system, except the Master I-FOB*:
On a disarmed system:
1. Enter the User Program Mode as described above.
2. Press MENU until “DELETE I-FOB Y/N” displays in the LCD window. Press YES and "DELETE ENTRY USER I-FOB U02" will appear in the LCD window.
3. Press ENTER and the confirmation message "U02 DELETE ENTRY Y/N" will appear.
4. Press YES and after a short processing interval, the Touchpad will read "U02 DELETED DELETE AGAIN Y/N". Press YES to remove another I-FOB user number from the sys- tem, or press NO to return to the User Program Mode.
Exit the User Program Mode
When you have completed programming or erasing User Codes, press RESET to exit the
User Program Mode.
USER PROGRAM MODE
* In the event that the Master I-FOB is lost, contact the alarm company to arrange a replacement.
DELETE I-FOB Y/N
28
USER I-FOB LIST
The space below is for recording the names of those in possession of User I-FOB's in your system. If an I-FOB is lost, be sure to delete its I-FOB number from the system (using the procedure on the previous page) as soon as possible.
I-FOB Number Area Name
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
I-FOB Number Area Name
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
U __ __
29
SYSTEM TROUBLE ERROR CODES
Your control panel is capable of detecting a variety of troubles that may affect system performance. In the unlikely event that a problem should occur, the SYS TBL (system trouble) icon will display on the left side of LCD window along with one or more of the following error codes. If the problem is related to a specific zone or device, the corresponding number will also be indicated. Below is a list of the most common troubles along with the necessary corrective action, if any. If a message appears that is not listed below, call your security professional for service. When a system trouble occurs, the Touchpad can be silenced and the display can be cleared by pressing RESET. The system can then be armed and disarmed as usual. Note: If you cannot
clear a system trouble yourself, call installing company for service as soon as possible.
Trouble
Indication
System Trouble
Condition
Action
E01-00
AC Power Failure
This trouble will occur if AC power is not present. Make sure system transformer is plugged into AC receptacle and check the circuit breaker, otherwise call installing company for service.
E02-00
Low Battery
If there has been a recent power failure, the battery may be partially depleted and must be re­charged by the control panel. The control panel performs an automatic daily test of the battery, at which time the trouble will clear if the battery has been recharged.
If the trouble does not clear in 24 hours, call installing company for service.
E03-00
Communication
Failure
The system was not able to report to central station. If this is due to a temporary interruption in the telephone service, the trouble can be cleared when the service is restored by performing a Communication Test:
1) Press MENU while disarmed and insert I-FOB.
2) Answer NO until “ACTIVATE DIALER TEST” appears in the window.
3) Press YES to send a test signal to the central station. If the trouble continues, call installing company for service.
30
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E04-NN
Wireless Transmitter Supervisory Failure
A problem has been detected with a wireless transmitter. Call installing company for service
E05-NN
Wireless Transmitter Low Battery
The battery in a wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding to the number NN. The replacement battery for the F-LTRANS transmitter, GEM-PIR motion detector and GEM-GB glass break detector is the Duracell DL123A 3 volt lith­ium (2 required for the GEM-PIR and GEM-GB). The replacement battery for the GEM-SMK is the Duracell MN1604 9 Volt Alkaline (2 required). The GEM-DT Dual Technology Sensor re­quires 4 C-cell alkaline batteries.
Warning: Replace batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery, or dispose of in fire.
E06-NN
Receiver Response Failure
Call installing company for service.
E07-00
Download Failure Call installing company for service.
E08-00
Telephone Line Cut The telephone line has failed. If telephone service has been temporarily interrupted, the trouble
will clear automatically when it is restored. Otherwise, call installing company for service.
E09-00
System Cold Start Call installing company for service.
31
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E10-NN
Touchpad Response Failure Call installing company for service.
E11-NN
Touchpad Tamper A Touchpad has been removed from the wall. Call installing company for service if
problem cannot be repaired.
E12-NN
Expansion Zone Module Response Failure
Call installing company for service.
E13-NN
Expansion Module Tamper The cover has been removed from a zone expansion module. A problem has been de-
tected with an Expansion Module. Call installing company for service.
E14-NN
Relay Board Response Failure
NN= Relay Board Number. Call installing company for service.
E15-NN
RF Transmitter Tamper Wireless Transmitter Tamper Cover removed. NN=Transmitter Number. Call installing
company for service.
E16-NN
Wireless Receiver Jam A problem has been detected with the wireless receiver. Call installing company for
service.
E17-NN
Receiver Tamper Condition Call installing company for service.
E18-NN
KeyFob Transmitter Low Battery
The batteries (2) in the wireless KeyFob transmitter indicated are low and should be replaced. The replacement battery is the #386 watch battery.
Warning: Replace batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery, or dispose of in fire.
32
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E19-00
User Program Memory Error
Call installing company for service.
E20-00
Dealer Program Memory Error
Call installing company for service.
E21-00
System Shutdown Call installing company for service.
E22-NN
Sensor Watch Activity Failure
A Motion Sensor on the zone indicated has failed the programmed Sensor Watch activity test. Insure that the sensor is able to detect activity in the area; clear any obstacles which may be blocking the sensor from detecting activity. Press RESET to clear the display, and then use the Touchpad Menu Mode to Reset System TBL (see page 23). If you cannot correct the problem yourself, call installing company for service.
E23-00
Burglary Bus Failure Call installing company for service.
E24-00
Service Message The system is in need of a preventive maintenance service call. Call installing company for ser-
vice.
E27-00
Printer Failure Call installing company for service.
E39-00
Receiver Capacity Error
Call installing company for service.
33
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E40-00
RF Self Test Failure A wireless motion sensor on the zone indicated has failed its automatic self test routine.
Call installing company for service.
E41-NN
Fire Trouble A problem has been detected on the Fire zone indicated. Call installing company for service.
E51-00
Bell/Siren Trouble There is a problem with the Bell or Siren. Call installing company for service.
E58-00
Telemetry Trouble Call installing company for service.
E59-00
Telemetry Failure Call installing company for service.
34
The space below is for recording the descriptions of the zones in your system.
If the system has a faulted zone, the zone description will appear on the LCD window. Refer to the list below to see
which zone is open and secure it (close the door or window, etc.).
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE LIST
35
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENT
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
This equipment uses the following jacks: An RJ31 X is used to connect this equipment to the telephone network. The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive IRENs on the
telephone line may result in the devices not ringing in response to an incoming call, in most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discon­tinuance of service may be required. If advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe necessary.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice in order for you to make the necessary modifi­cations in order to maintain uninterrupted service.
If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If the trouble is causing harm to the telephone network, the telephone company may request you remove the equipment from the network until the problem is resolved.
There are no user serviceable components in this product, and all necessary repairs must be made by the manufacturer. Other repair methods may invalidate the FCC registration on this product. This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service is subject to state
tariffs. This equipment is hearing-aid compatible. When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for the call. Perform
such activities in the off-peak hours; such as early morning or late evening.
36
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of rea­sons. For example:
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without
power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
A user may not be able to reach a panic or emergency button quickly enough.
Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation
manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their de­tection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease.
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices sound on a different level of the premises, then they are less likely to alert all people. Persons may not hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
Telephone lines needed to transmit alarm signals from a premises to an alarm monitoring center may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
- Continued
37
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM (Continued)
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect them-
selves from the situation. In the case of a monitored alarm system, authorities may not respond appropriately.
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last
as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Wireless transmitters (used with some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all re­duce the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insur­ance. Business owners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their employ­ees to learn about these developments.
38
NAPCO LIMITED WARRANTY
NAPCO SECURITY SYSTEMS, INC. (NAPCO) warrants its products to be free from manufacturing defects in materials and work­manship for thirty-six months following the date of manufacture. NAPCO will, within said period, at its option, repair or replace any product failing to operate correctly without charge to the original purchaser or user.
This warranty shall not apply to any equipment, or any part thereof, which has been repaired by others, improperly installed, improp­erly used, abused, altered, damaged, subjected to acts of God, or on which any serial numbers have been altered, defaced or re­moved. Seller will not be responsible for any dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. THERE IS NO EXPRESS OR IMPLIED WARRANTY OF MERCHANTABILITY OR A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. ADDITIONALLY, THIS WARRANTY IS IN LIEU OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF NAPCO.
Any action for breach of warranty, including but not limited to any implied warranty of merchantability, must be brought within the six months following the end of the warranty period.
IN NO CASE SHALL NAPCO BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional who installed and maintains your security system. In order to exercise the war­ranty, the product must be returned by the security professional, shipping costs prepaid and insured to NAPCO. After repair or re­placement, NAPCO assumes the cost of returning products under warranty. NAPCO shall have no obligation under this warranty, or otherwise, if the product has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to accident, nuisance, flood, fire or acts of God, or on which any serial numbers have been altered, defaced or removed. NAPCO will not be responsible for any dismantling, reassembly or reinstallation charges.
This warranty contains the entire warranty. It is the sole warranty and any prior agreements or representations, whether oral or writ-
39
ten, are either merged herein or are expressly cancelled. NAPCO neither assumes, nor authorizes any other person purporting to act on its behalf to modify, to change, or to assume for it, any other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in excess of NAPCO's original selling price of the product, for any loss or damage, whether direct, indirect, incidental, consequential, or otherwise arising out of any failure of the product. Seller's warranty, as herein­above set forth, shall not be enlarged, diminished or affected by and no obligation or liability shall arise or grow out of Seller's ren­dering of technical advice or service in connection with Buyer's order of the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM BE COMPLETELY TESTED WEEKLY.
Warning: Despite frequent testing, and due to, but not limited to, any or all of the following; criminal tampering, electrical or commu­nications disruption, it is possible for the system to fail to perform as expected. NAPCO does not represent that the product/system may not be compromised or circumvented; or that the product or system will prevent any personal injury or property loss by bur­glary, robbery, fire or otherwise; nor that the product or system will in all cases provide adequate warning or protection. A properly installed and maintained alarm may only reduce risk of burglary, robbery, fire or otherwise but it is not insurance or a guarantee that these events will not occur. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP­ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. Therefore, the installer should in turn advise the consumer to take any and all precautions for his or her safety including, but not limited to, fleeing the prem­ises and calling police or fire department, in order to mitigate the possibilities of harm and/or damage.
NAPCO is not an insurer of either the property or safety of the user's family or employees, and limits its liability for any loss or dam­age including incidental or consequential damages to NAPCO's original selling price of the product regardless of the cause of such loss or damage.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, or differentiate in their treatment of limitations of liability for ordinary or gross negligence, so the above limi­tations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may also have other rights which vary from state to state.
40
THE FOLLOWING STATEMENT IS REQUIRED BY THE FCC
RADIO AND TELEVISION INTERFERENCE
This equipment has been tested and found to comply with the limits for a Class-B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio-frequency energy and, if not installed and used in accordance with the instruc­tions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following meas­ures:
Reorient or relocate the receiving antenna;
Increase the separation between the equipment and the receiver;
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected;
Consult the dealer or an experienced radio/TV technician for help.
You may also find the helpful the following booklet, prepared by the FCC: “How to Identify and Resolve Radio-TV Interference Problems”. This booklet is available from the U.S. Government Printing Office, Washington, DC 20402.
Changes and Modifications not expressly approved by the manufacturer or registrant of this equipment can void your authority to operate this equipment under Federal Communications Commissions rules.
This device complies with part 15 of FCC Rules. Operation is subject to the following two conditions; (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause unde­sired operation.
This Class B digital apparatus complies with Canadian ICES-003 Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
41
NOTES
42
NOTES
43
NOTES
44
333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440
Publicly traded on NASDAQ Symbol: NSSC
www.napcosecurity.com
R
Loading...